G. L. Maatman’s scientific contributions

What is this page?


This page lists works of an author who doesn't have a ResearchGate profile or hasn't added the works to their profile yet. It is automatically generated from public (personal) data to further our legitimate goal of comprehensive and accurate scientific recordkeeping. If you are this author and want this page removed, please let us know.

Publications (1)


Minimum water requirements for suppression of room fires
  • Article

February 1970

·

15 Reads

·

13 Citations

Fire Technology

F. Salzberg

·

F. J. Vodvarka

·

G. L. Maatman

In many areas, it is essential that no water be wasted in fighting fire. How much water is needed to extinguish typical room fires? This is the question the authors sought to answer in the experiments reported here.

Citations (1)


... I ett mångårigt arbete sammanfattas forskningen som skedde ungefär under perioden 1950 -1970 med avseende på erforderligt släckvattenflöde. Sammanställningen baseras på forskning utförd av bland andra Lloyd-Layman (1950), Thomas & Smart (1954), Thomas & Smart (1954), Thomas (1959), Rasbash (1962), Fry & Lustig (1963) samt Salzberg, Vodvarka & Maatman (1970). Denna tidiga forskning bygger i stor utsträckning på statistiska undersökningar och pekar på att -2 l/min/m 2 är den kritiska påföringshastigheten för att få kontroll av rumsbränder -3.7 l/min/m 2 kan anses vara den minsta effektiva påföringshastigheten -5 l/min/m 2 kan anses vara den generellt optimala påföringshastigheten -Vid verkliga bränder kan 4 l/min/m 2 anses vara optimalt för ett rum -Vid verkliga bränder kan 6 l/min/m 2 anses vara optimalt för två rum -För kommersiella byggnader (affärer, kontor, mm) om 50 -100 m 2 , kan 6.5 l/min/m 2 anses vara optimal påföringshastighet. ...

Reference:

Räddningsinsatser vid brand i byggnad, en forskningsöversikt
Minimum water requirements for suppression of room fires
  • Citing Article
  • February 1970

Fire Technology