ArticlePDF Available

Energy Losses or Savings Due to Air Infiltration and Envelope Sealing Costs in the Passivhaus Standard: A Review on the Mediterranean Coast

MDPI
Buildings
Authors:

Abstract and Figures

To obtain the Passivhaus Certificate or Passivhaus Standard (PHS), requirements regarding building envelope air tightness must be met: according to the n50 parameter, at a pressure of 50 Pa, air leakage must be below 0.6 air changes per hour (ACH). This condition is verified by following the blower door test protocol and is regulated by the ISO 9972 standard, or UNE-EN-13829. Some construction techniques make it easier to comply with these regulations, and in most cases, construction joints and material joints must be sealed in a complex way, both on façades and roofs and at ground contact points. Performing rigorous quality control of these processes during the construction phase allows achieving a value below 0.6 ACH and obtaining the PHS certification. Yet, the value can increase substantially with the passage of time: as windows and doors are used, opened, or closed; as envelope materials expand; with humidity; etc. This could result in significant energy consumption increases and losing the PHS when selling the house at a later point in time. It is therefore important to carefully supervise the quality of the construction and its execution. In this study, we focused on a house located in Sitges (Barcelona). The envelope air tightness quality was measured during four construction phases, together with the sealing of the joints and service ducts. The blower door test was performed in each phase, and the n50 value obtained decreased each time. The execution costs of each phase were also determined, as were the investment amortisation rates based on the consequent annual energy demand reductions. Air infiltration dropped by 43.81%, with the final n50 value resulting in 0.59 ACH. However, the execution costs—EUR 3827—were high compared to the energy savings made, and the investment amortisation period rose to a 15- to 30-year range. To conclude, these airtightness improvements are necessary in cold continental climates but are not applicable on the Spanish Mediterranean coast.
This content is subject to copyright.
Citation: Echarri-Iribarren, V.;
Gómez-Val, R.; Ugalde-Blázquez, I.
Energy Losses or Savings Due to Air
Infiltration and Envelope Sealing
Costs in the Passivhaus Standard: A
Review on the Mediterranean Coast.
Buildings 2024,14, 2158. https://
doi.org/10.3390/buildings14072158
Academic Editors: Alberto Meiss
and Irene Poza Casado
Received: 18 May 2024
Revised: 15 June 2024
Accepted: 18 June 2024
Published: 13 July 2024
Copyright: © 2024 by the authors.
Licensee MDPI, Basel, Switzerland.
This article is an open access article
distributed under the terms and
conditions of the Creative Commons
Attribution (CC BY) license (https://
creativecommons.org/licenses/by/
4.0/).
buildings
Article
Energy Losses or Savings Due to Air Infiltration and Envelope
Sealing Costs in the Passivhaus Standard: A Review on the
Mediterranean Coast
Víctor Echarri-Iribarren 1, 2, * , Ricardo Gómez-Val 1and Iñigo Ugalde-Blázquez 1
1
Department of Architecture, International University of Catalunya, Carrer Iradier 22, 08017 Barcelona, Spain;
rjgomez@uic.es (R.G.-V.); iugalde@uic.es (I.U.-B.)
2Department of Building Construction, University of Alicante, Carretera de San Vicente s/n, San Vicente del
Raspeig, 03690 Alicante, Spain
*Correspondence: vecharri@uic.es; Tel.: +34-93-254-18-00
Abstract: To obtain the Passivhaus Certificate or Passivhaus Standard (PHS), requirements regarding
building envelope air tightness must be met: according to the n
50
parameter, at a pressure of
50 Pa, air leakage must be below 0.6 air changes per hour (ACH). This condition is verified by
following the blower door test protocol and is regulated by the ISO 9972 standard, or UNE-EN-13829.
Some construction techniques make it easier to comply with these regulations, and in most cases,
construction joints and material joints must be sealed in a complex way, both on façades and roofs
and at ground contact points. Performing rigorous quality control of these processes during the
construction phase allows achieving a value below 0.6 ACH and obtaining the PHS certification.
Yet, the value can increase substantially with the passage of time: as windows and doors are used,
opened, or closed; as envelope materials expand; with humidity; etc. This could result in significant
energy consumption increases and losing the PHS when selling the house at a later point in time.
It is therefore important to carefully supervise the quality of the construction and its execution. In
this study, we focused on a house located in Sitges (Barcelona). The envelope air tightness quality
was measured during four construction phases, together with the sealing of the joints and service
ducts. The blower door test was performed in each phase, and the n
50
value obtained decreased each
time. The execution costs of each phase were also determined, as were the investment amortisation
rates based on the consequent annual energy demand reductions. Air infiltration dropped by 43.81%,
with the final n
50
value resulting in 0.59 ACH. However, the execution costs—EUR 3827—were high
compared to the energy savings made, and the investment amortisation period rose to a 15- to 30-year
range. To conclude, these airtightness improvements are necessary in cold continental climates but
are not applicable on the Spanish Mediterranean coast.
Keywords: Passivhaus Standard; airtightness; energy efficiency; building overheating; construction
quality; investment amortization; air infiltration; blower door test; envelope sealing;
Mediterranean climate
1. Introduction
According to EUROSTAT’s latest available publication, the real estate sector, especially
the residential sector, is responsible for 27.9% of energy consumption. This is why it is nec-
essary to reduce the energy consumption of buildings. It is also a regulatory obligation [
1
].
In recent years, the European Commission has issued a number of directives to reduce
energy consumption in housing construction [
2
,
3
]. These directives have been transposed
into various member countries’ regulatory frameworks, including in southern Europe.
However, in southern European countries, a shift of mindset needs to occur towards de-
signing more energy-efficient homes [
4
]. These changes have already been introduced in
Spain at the regulatory level in the country’s Technical Building Code (CTE), which encom-
passes all applicable construction regulations and includes energy consumption reduction
Buildings 2024,14, 2158. https://doi.org/10.3390/buildings14072158 https://www.mdpi.com/journal/buildings
Buildings 2024,14, 2158 2 of 20
as an essential parameter [
5
7
]. Passivhaus certification (PHS) is set to gain ground as
a housing
construction option, owing mainly to the low operational energy consumption
of Passivhaus buildings [
8
]. The certification requires that newly built homes follow an
envelope airtightness standard below 0.6 ACH at 50 pascals (Pa) of pressure (n
50
). This
requirement entails additional efforts for construction companies and property developers,
as they need to implement a series of controls and repairs until the n
50
requirement is
fulfilled, making it possible to obtain PHS certification.
In recent years, several studies have been conducted on the performance of these
buildings in terms of comfort [
9
] and energy efficiency. A substantial number of detailed
analyses have been conducted on the functioning of these homes in cold climates, both
in public buildings [
10
] and in private ones [
11
]. These analyses have demonstrated
that energy consumption related to heating uses represents more than 50% in several
Western countries. Optimal results have been obtained regarding the climatic behaviour
of the houses studied. For example, the geometry of the façades helps to minimise the
overheating of housing, such as the 115
inclination of the south façades in London [
12
].
The cost of incorporating the Passivhaus standard into buildings varies between 8% and
15% [
13
]. There have also been related studies in Mediterranean climate conditions showing
that comfort requirements account for 72% of the total energy use [
14
], as is the case in
other warm climates [
15
]. In this case, no unanimous results or conclusions have been
reached, generating debates in the scientific community about the suitability of the PH
Standard and the need to adapt it [
16
]. This aspect depends very much on the location.
For example, in Ireland, the simulation estimated an overheating rate of 0%. The main
problem detected in the research is the risk of overheating in buildings [
17
,
18
]. To this
end, building shapes have been examined, as well as sun protection features and the
dimensions of the openings [
19
], leading to an optimal window-to-façade ratio of 30%.
Building shapes and distribution plans are also directly related to climatic behaviour, with
an ideal ratio of 1:1.44 [
20
]. Analyses have even been conducted on the types of rooms in
which the greatest overheating occurs, with bedrooms presenting the highest risks [
21
].
For all these reasons, the human factor has proven to have a direct impact on the risk of
overheating in these homes, with confirmation from more than 20% of the inhabitants [
22
].
To improve this aspect in Passivhaus buildings, it is necessary to adopt solutions that
incorporate passive natural ventilation and sunlight systems [
23
]. These conditions are
especially suitable for warm or temperate climates, in which the architectural characteristics
of the building directly influence how these buildings will function climatically in the most
adverse summer months [24].
Another interesting dimension of analysis and improvement regarding Passivhaus
houses is the increase in air infiltration through envelopes. It is important to observe how
this latter parameter evolves by taking measurements in Passivhaus homes that have been
in use for a long period of time. In this regard, it is notable that, due to the increase in
recent years in the size of building openings, infiltration studies of existing buildings have
detected lower air infiltration rates in older and less insulated buildings than in more
modern buildings. With respect to the measurements conducted through case studies over
a long period of time, such as a full year, optimistic estimates of previous energy demand
simulations have been compared with actual consumption [
25
,
26
]. The real data obtained
after the Passivhaus building is in operation has been shown to present higher values than
those estimated through simulation.
To date, studies have focused on indoor air quality [
27
] and on how to improve indoor
air quality and performance [
28
]. The ventilation demand also influences thermal comfort,
resulting in an optimal relationship between a mix of natural and mechanical ventilation
during 82% of the annual occupancy [
29
]. The interior comfort parameter is regarded as key,
given that it is among the objectives of a range of current regulations. It has been found that
this objective is not always met and that the measures implemented to improve comfort
and indoor air quality are in fact doing the opposite. Despite comfort improvements
observed in most modern buildings, which have even obtained a Passivhaus (PHS)-type
Buildings 2024,14, 2158 3 of 20
certification, it is necessary to ask whether the required efforts of Passivhaus compliance
do have
an effective
impact on the parameters [
30
]. Studies have concluded that nZEBs are
more likely to overheat than older and conventional buildings. These different kinds of
buildings even maintain similar CO2concentrations.
In relation to air infiltration through windows, various analyses have been conducted
to improve airtightness [
31
,
32
]. However, it has been shown that studies are lacking on
how to homogenise the controls that allow for evaluating Passivhaus house behaviour and
their operation over time [
33
,
34
]. It is particularly important to evaluate the extra cost of
obtaining the PHS in hot and temperate climates, although it has been shown to perform
well regarding energy demands and CO2emissions [11].
Yet, no studies have been found on both the technical and financial costs of the leak
checks that must be performed in succession using the blower door test until fulfilling the
Passivhaus standard requirement. For its part, the financial effort required to obtain PHS
certification has been evaluated. Taking into account the various current administrative
subsidies [
35
] and construction cost increases, it has been found to amount to approximately
30%. This extra cost is amortised over an average period of around 10 years, so the extra
effort is generally considered acceptable. However, if such solutions and certifications are
to be globally implemented within the country—and not restricted to luxury housing—the
focus must be on low-cost or social housing scenarios [
36
]. Affordable social housing
construction costs can be reduced by up to 22% of the build cost, even while maintaining
the PHS. No studies have been performed on the additional costs and time required to
achieve an n
50
parameter below 0.6 ACH once optimal climate conditioning solutions have
been applied. It is worth noting that to comply with the certification procedure, the leak
detection procedure and sealing need to be performed repeatedly until fulfilling the PHS
certification requirement. The punctual air infiltrations detected have a major impact on the
building’s overall tightness and, therefore, on its climatic conditioning and energy demands.
These infiltrations usually occur through the window joinery [
37
]. In Passivhaus homes,
these leaks are reduced to a minimum, unlike in traditional construction [
38
]. In the case of
existing buildings, the PHS requirement of n
50
is not as demanding as it is below 1 ACH.
Despite this, the difficulty of achieving this parameter in these constructions makes such
renovations even more costly, and it is not certain that the outcome
will be successful [39]
.
Regarding home construction systems, few studies have applied modular prefabri-
cated systems. In theory, these systems are ideal for building Passivhaus homes, but they
must be optimised to ensure adequate climatic operation as well as easy and effective joint
sealing produced by the system [
40
]. In this study, just four connection details fulfil the
PHS requirements.
The Passivhaus certification requires the commitment of all agents involved, including
in the design phase, the project technical drafting process, all construction phases, and sub-
sequent use and maintenance. Insufficient production and management of these measures,
commitment, and system knowledge would seriously jeopardise the expected beneficial
results or lead to unforeseen negative outcomes [
41
]. The present work is
an in-depth
study of the latest requirements necessary to obtain the Passivhaus certification for a home.
It highlights the measurements and work evaluation necessary to guarantee adequate
envelope airtightness and the obtention of the certification, as well as the investment amor-
tisation periods within the framework of the Mediterranean climate. A comparison with
cold Central European climates is also provided.
This study’s objective was to quantify the energy savings achieved during the var-
ious phases of the Passivhaus home envelope sealing and analyse the subsequent cost-
effectiveness. The aim was to analyse the standard’s applicability to homes located on
the Spanish Mediterranean coast and to conduct a comparison with the Central European
continental climate. To do this, we performed a case study analysis.
Buildings 2024,14, 2158 4 of 20
2. Description of the Case Study
The property under study was a newly built detached single-family house located in
the municipality of Sitges (on street 30–32 Camídel Coll) in the province of Barcelona. The
house has a basement, a ground floor, and a first floor (Figure 1). The basement was built
with a perimeter wall and a reinforced concrete slab. The upper floors were constructed
using a system of prefabricated panels made by the Evowall company. Their system of
massive panels with a metal lattice was approved by the European Technical Assessment.
The panels are made of a metal framework of S275 hot-rolled steel, with 5 cm of EPS thermal
insulation, 8 cm of PIR thermal insulation, a mortar coating using a mixture of cement and
EPS insulation, and gypsum on the inner face. The outer face consists of a mortar coating
applied with a cement and insulation mix, finished with a lime mortar layer (Figure 2).
The windows are made of PVC with rolling shutters. According to tests conducted by the
Technological Institute of Construction (ITEC), the U of the façade panels is
0.214 W/(m2K)
,
and that of the roof panels is 0.475 W/(m
2
K). The exterior carpentry—profiles, tracks, and
shutters—was made by the Weru group.
Buildings 2024, 14, 2158 4 of 20
Spanish Mediterranean coast and to conduct a comparison with the Central European
continental climate. To do this, we performed a case study analysis.
2. Description of the Case Study
The property under study was a newly built detached single-family house located in
the municipality of Sitges (on street 3032 Camí del Coll) in the province of Barcelona. The
house has a basement, a ground oor, and a rst oor (Figure 1). The basement was built
with a perimeter wall and a reinforced concrete slab. The upper oors were constructed
using a system of prefabricated panels made by the Evowall company. Their system of
massive panels with a metal laice was approved by the European Technical Assessment.
The panels are made of a metal framework of S275 hot-rolled steel, with 5 cm of EPS ther-
mal insulation, 8 cm of PIR thermal insulation, a mortar coating using a mixture of cement
and EPS insulation, and gypsum on the inner face. The outer face consists of a mortar
coating applied with a cement and insulation mix, nished with a lime mortar layer (Fig-
ure 2). The windows are made of PVC with rolling shuers. According to tests conducted
by the Technological Institute of Construction (ITEC), the U of the façade panels is 0.214
W/(m2 K), and that of the roof panels is 0.475 W/(m2 K). The exterior carpentryproles,
tracks, and shuers—was made by the Weru group.
(a) (b)
Figure 1. (a) Floor plan with dimensions; (b) Exterior view of south façade.
This house was built in view of achieving the Passivhaus certication, which sets an
n50 < 0.6 ACH for newly-built single-family homes. The building section for which the PHS
certication studies were conducted was the housing area itself, located on the ground
oor and the rst oor (Figure 3). The garage and the machine room in the basement were,
therefore, not built according to Passivhaus standards.
Figure 1. (a) Floor plan with dimensions; (b) Exterior view of south façade.
Buildings 2024, 14, 2158 5 of 20
Figure 2. Construction details of the typical envelopes.
Figure 2. Cont.
Buildings 2024,14, 2158 5 of 20
Buildings 2024, 14, 2158 5 of 20
Figure 2. Construction details of the typical envelopes.
Figure 2. Construction details of the typical envelopes.
This house was built in view of achieving the Passivhaus certification, which sets
an n50 < 0.6
ACH for newly-built single-family homes. The building section for which the
PHS certification studies were conducted was the housing area itself, located on the ground
floor and the first floor (Figure 3). The garage and the machine room in the basement were,
therefore, not built according to Passivhaus standards.
The layout is shown in Figure 4. To ensure appropriate sealing and to comply with the
PHS requirements, different measurements were taken by the construction company using
the blower door test. Measurements were taken by the construction company on several
occasions, specifically on 3 October 2023 and 21 November 2023. On 5 December 2023,
the Praxis company, specialising in Passivhaus certification, was required to perform the
blower door test. Measurements were also made using a digital anemometer and smoke
machine to detect air leaks during these tests.
Buildings 2024, 14, 2158 5 of 20
Figure 2. Construction details of the typical envelopes.
Figure 3. Cont.
Buildings 2024,14, 2158 6 of 20
Buildings 2024, 14, 2158 6 of 20
Figure 3. Furnished and delimited ground oor and rst oor.
The layout is shown in Figure 4. To ensure appropriate sealing and to comply with
the PHS requirements, dierent measurements were taken by the construction company
using the blower door test. Measurements were taken by the construction company on
several occasions, specically on 3 October 2023 and 21 November 2023. On 5 December
2023, the Praxis company, specialising in Passivhaus certication, was required to perform
the blower door test. Measurements were also made using a digital anemometer and
smoke machine to detect air leaks during these tests.
Figure 4. Cross-section of the kitchen and rst-oor master bedroom.
The conducted tests led the construction company to carry out a series of additional
seals, especially in the service ducts, which presented the greatest number of detected air
leaks (Figure 5). Plastic tape and elastic amorphous seals were used for the sealing.
Figure 3. Furnished and delimited ground floor and first floor.
Buildings 2024, 14, 2158 6 of 20
Figure 3. Furnished and delimited ground oor and rst oor.
The layout is shown in Figure 4. To ensure appropriate sealing and to comply with
the PHS requirements, dierent measurements were taken by the construction company
using the blower door test. Measurements were taken by the construction company on
several occasions, specically on 3 October 2023 and 21 November 2023. On 5 December
2023, the Praxis company, specialising in Passivhaus certication, was required to perform
the blower door test. Measurements were also made using a digital anemometer and
smoke machine to detect air leaks during these tests.
Figure 4. Cross-section of the kitchen and rst-oor master bedroom.
The conducted tests led the construction company to carry out a series of additional
seals, especially in the service ducts, which presented the greatest number of detected air
leaks (Figure 5). Plastic tape and elastic amorphous seals were used for the sealing.
Figure 4. Cross-section of the kitchen and first-floor master bedroom.
The conducted tests led the construction company to carry out a series of additional
seals, especially in the service ducts, which presented the greatest number of detected air
leaks (Figure 5). Plastic tape and elastic amorphous seals were used for the sealing.
Buildings 2024,14, 2158 7 of 20
Buildings 2024, 14, 2158 7 of 20
(a) (b)
Figure 5. (a) Detection of air inltration after phase P1; (b) Details of sealing using adhesive tape.
3. Materials and Methods
A building’s annual energy demand depends on various factors, some of which are
highly complex, such as the orientation, local climate, materials used, and the technical
characteristics of the envelopes [42]. Assessing the actual heat ow through envelopes
over the cycle of a week, a month, or a full year is a truly complex task [43]. It requires
simulation tools that consider the envelope thermal inertia and ground contact, the ther-
mal bridges of the construction systems used, as well as the solar radiation on the exterior
surfaces or the air conditioning systems used. In addition, factors relating to the construc-
tion’s inherent deciencies must be considered, such as contacts between dierent mate-
rials, joineries, intrinsic humidity variations, expansion eects during the material execu-
tion of the project, etc. Envelope airtightness varies according to climatic conditions, out-
side air pressure at any given time, and the maintenance and usage by the homes users
of mobile elements such as carpentry, adjustable slats, or grids [44]. This makes it dicult
to estimate or quantify the real energy impact of air inltration, which is also subject to
unforeseen events and imbalances. Constant variations in outdoor air pressure make it
even harder, although this point can be solved by obtaining annual statistical averages per
season or at specic times of the year [45]. Despite the above, designing a suitable meth-
odology and strategy to extract data from methodology-adapted parameters allows for
approaching the problem with the necessary level of quality assurance.
3.1. Envelope Airtightness
The main study objective was to quantify the energy impacts of envelope airtightness
under various scenarios and to estimate the corresponding investment amortisation. To
this end, we present below the case study of a house whose envelope airtightness value
was expected to be low owing to the quality of the construction company and the prefab-
rication system used, as well as the applied sealing, carpentry quality, and air tightness.
The execution of the envelope sealing took place over four phases at four- and six-
week intervals. We performed the blower door test four times, immediately after each
phase. This allowed for making on-site decisions regarding the technique to be used in
Figure 5. (a) Detection of air infiltration after phase P1; (b) Details of sealing using adhesive tape.
3. Materials and Methods
A building’s annual energy demand depends on various factors, some of which are
highly complex, such as the orientation, local climate, materials used, and the technical
characteristics of the envelopes [
42
]. Assessing the actual heat flow through envelopes over
the cycle of a week, a month, or a full year is a truly complex task [
43
]. It requires simulation
tools that consider the envelope thermal inertia and ground contact, the thermal bridges
of the construction systems used, as well as the solar radiation on the exterior surfaces
or the air conditioning systems used. In addition, factors relating to the construction’s
inherent deficiencies must be considered, such as contacts between different materials,
joineries, intrinsic humidity variations, expansion effects during the material execution of
the project, etc. Envelope airtightness varies according to climatic conditions, outside air
pressure at any given time, and the maintenance and usage by the home’s users of mobile
elements such as carpentry, adjustable slats, or grids [
44
]. This makes it difficult to estimate
or quantify the real energy impact of air infiltration, which is also subject to unforeseen
events and imbalances. Constant variations in outdoor air pressure make it even harder,
although this point can be solved by obtaining annual statistical averages per season or at
specific times of the year [
45
]. Despite the above, designing a suitable methodology and
strategy to extract data from methodology-adapted parameters allows for approaching the
problem with the necessary level of quality assurance.
3.1. Envelope Airtightness
The main study objective was to quantify the energy impacts of envelope airtightness
under various scenarios and to estimate the corresponding investment amortisation. To this
end, we present below the case study of a house whose envelope airtightness value was
Buildings 2024,14, 2158 8 of 20
expected to be low owing to the quality of the construction company and the prefabrication
system used, as well as the applied sealing, carpentry quality, and air tightness.
The execution of the envelope sealing took place over four phases at four- and six-week
intervals. We performed the blower door test four times, immediately after each phase.
This allowed for making on-site decisions regarding the technique to be used in phases P2,
P3, and P4, and whether or not to carry them out. This was performed according to the n
50
value obtained, the expected execution costs for each phase, and the amortisation of these
seals according to the energy savings made.
Phase P1
Sealing of construction joints using a hermetic liquid membrane. Application of
expanding polyurethane foam in joinery together with the façade envelope manufacturers.
Plastic adhesive tape and amorphous seals. Completed in September 2023.
Phase P2
Detection of critical points. Sealing of joints of materials and plane contacts using
polyurethane expanding foam. Contact between carpentry and shutter units with ISO3
polyurethane-based adhesive plastic tapes. Amorphous seals.
Phase P3
Sealing of joints between plane contacts and materials using polyurethane expand-
ing foam. Seals in installation passageways, mainly electrical ones, are based on ISO3
polyurethane-based adhesive plastic tapes and elastic amorphous ISO-TOP seals.
Phase P4
Detection of insufficiently airtight spots. Joints are sealed using techniques similar to
those in P3.
To evaluate the envelope airtightness value, the blower door test was conducted in the
various construction phases. It was executed in accordance with European
Standard EN 13829
(
Thermal performance of buildings—Determination of air permeability of buildings—Fan
pressurization method
) using the blower door GMBH MessSysteme für Luftdichtheit
equipment. Corresponding graphs were obtained for pressurisation and depressurisation
at 10–70 pascals (Pa) of air pressure and an n
50
airtightness value of 50 Pa. A specific sheet
developed for the research group “Architecture & Energy” of the University of Valladolid
was used to characterise the resulting information [
46
]. This tool was developed specifically
to characterise 140 parameters that can intervene in infiltration [
46
]. The parameters were
collected in a database, which was then used for the overall result evaluation.
To obtain the average building envelope airtightness value—a parameter that is always
difficult to quantify—we followed the protocol established in the UNE-EN-ISO 13790:2008
standard. This method allows for converting the n
50
value to a rate of changes/hour
under normal pressure conditions and as an average value over a time interval via the
following expression:
nwinter = 2·n50·ei·εi, (1)
n50—air changes/hour at 50 Pascals;
ei—wind protection coefficient = 0.05;
εi—height correction factor = 1.
In this way, using the DesignBuilder version 7 tool and the mathematical corpus
described in Section 3.2.1, it was possible to simulate the energy impact. We obtained
global annual energy demand values and partial ones exclusively due to the envelope
airtightness value.
We used the blower door test tool to detect thermal bridges through images from
Flyr’s ThermaCam P25 thermal imaging camera. The quantification was conducted using
the AnTherm programme, and we estimated a thermal bridge gain or loss of pressure of
3.5% of the total thermal loads due to the envelope thermal transmittance U-values, which
were close to those obtained in previous studies [47,48].
Buildings 2024,14, 2158 9 of 20
3.2. Assessment of the Energy Impact of Air Infiltration
Estimating the energy impact of air infiltration is an arduous task. It cannot be entirely
accurate, as it depends not only on the airtightness of the building envelope but also on
weather conditions, which are usually difficult to predict [
49
]. No common criterion exists
regarding which model is suitable to assess the energy impact of air infiltration through
the envelope [
50
]. So far, different calculation models have been developed to varying
degrees of complexity and reliability [
51
]. The simplest models are based on a uniform
distribution of leak pathways and constant average leaks over time. In this study, the
impact was evaluated using two different tools and methodologies: a simplified calculation
model (Equations (1)–(8)), and DesignBuilder simulation software.
3.2.1. Application of the Simplified Calculation Model
The first simplified calculation model used applies the degree-day concept, which
links the average temperature outside the tested home to the indoor comfort temperature
(21
C for heating and 24
C for cooling) [
7
]. This estimate is theoretical: real energy
consumption depends on each household’s specific indoor air temperature T
i
setpoint
conditions. This calculation procedure makes it possible to assess the Q
inf
energy impact
considering specific climatic data of the house location. The calculation considers the air
infiltration flow obtained through the blower door test n
50
, the specific capacity of the V
inf
air in the area under study, and the temperature differences between the home’s indoor air
Tiand outdoor air Te[52].
Qinf =Cp·Gt·Vinf, (2)
Here,
Q
inf
is the annual energy loss (kWh/year) due to air infiltration. Q
inf-H
is considered
for heating and Q
inf-C
for cooling. Annual energy losses are expressed per surface area unit.
Cpis the specific air heat capacity, which is 0,34 Wh/m3K.
G
t
is the number of annual degree-days (kKh/year), both for heating (G
t-C
), with
a basic
comfort temperature of 21
C, and for cooling (G
t-R
), with a basic comfort tempera-
ture of 25 C.
V
inf
is the air leakage rate (m
3
/h). V
inf
must be obtained from the values obtained
in the test, which are expressed with a pressure difference of 50 Pa and do not reflect the
actual filtration process to which the house is subjected.
The Persily–Kronvall estimation (Equation (3)) is a simple and widespread model in
the scientific community, and it was adopted in this first model [
53
]. It assumes a linear
relationship between permeability at 50 Pa and the average annual infiltration:
qinf =q50/20, (3)
where
qinf is the air permeability (m3/(h m2)].
q50 is the air permeability at 50 Pa (m3/(h m2)).
This linear relationship between tightness and infiltration was subsequently evolved [
53
],
incorporating some parameters and coefficients based on the house location characteristics
according to Equations (4) and (5):
qinf =q50/N, (4)
N=C·cf 1·cf 2·cf 3,(5)
where
N is a constant.
C is the climate factor, calculated in the model using hourly climate data for over
200 points in the U.S. and Canada. The value ranges from 15 to 30.
cf
1
is the building height correction factor, applicable to buildings in which the tested
spaces are on one floor (cf 1= 1) up to three floors (cf 1= 0.7).
Buildings 2024,14, 2158 10 of 20
cf
2
is the site shielding correction factor, for well-shielded cases (cf
2
= 1,2), (cf
2
= 1) or
exposed houses (cf 2= 1), (cf 2= 0.9).
cf
3
is the leak correction factor, which depends on the value of the leakage exponent
n. Buildings with small cracks receive a correction factor cf
3
= 1.4 while leaking buildings
with large cracks or holes have a correction factor cf3= 0.7.
This extended simplified model was adopted to calculate the average infiltration
flow in the Spanish Mediterranean region, obtaining the climatic factor C value through
assimilation with US climates as a function of the average temperature and wind speed. For
the coefficients cf
1
,cf
2,
and cf
3
, a value equal to 1 was adopted in all three cases, since the
small cracks detected in the envelope of the dwelling reached an average value. The type
of infiltration opening was obtained from the mean value of the flow exponent,
n = 0.59
.
The V
inf
, or air leakage rate, required to determine the energy impact was calculated based
on the air permeability rate and the envelope surface area (Equation (6):
Vinf =qinf AE, (6)
where
AEis the envelope area (m2).
Once we obtained the value of the envelope air infiltration volume or air leak-
age rate V
inf
to calculate the energy impact according to the annual average corrected
through Equations (1)–(6), we quantified the sensible heat Q
s
and latent heat Q
l
using the
following equations:
Qs=Vinf·Ce·ρ·(TeTi), (7)
Here,
Q
s
is the value of the energy impact of the sensible heat of the air leakage rate V
inf
(W).
Vinf is the air leakage rate (m3/h).
Ceis the specific air heat under normal conditions (0.349 Wh/kgK).
ρis the air density (kg/m3).
T
e
is the outside air temperature in degrees Kelvin (K), taken as an annual
average value
.
Tiis the inside air temperature (21 K in winter and 24 K in summer).
Ql=Vinf·Cv·ρ·(WeWi), (8)
Here,
Qlis the energy impact value of the latent heat of the air leakage rate Vinf (W).
Vinf is the air leakage rate (m3/h).
Cvis the water vaporisation heat (0.628 W/gvapour).
ρis the specific air volume (kg/m3).
W
e
is the specific outside air humidity taken as the annual average value (g
vapour
/kg).
Wiis the specific indoor air humidity (gvapour/kg).
3.2.2. Obtaining Annual Energy Demand Using DesignBuilder
The second quantitative approximation method was executed through DesignBuilder.
To quantify the energy impact, the U-value transmittance values of all envelopes [
54
]
obtained in
situ using the TESTO 635-2 [
55
,
56
] equipment were entered into the Design-
Builder model. To simulate the building’s behaviour in terms of energy demand and
interior comfort parameters, the data and parameter values described next were intro-
duced into the tool. The winter period ran from 1 December to 30 April, and the summer
period from 1 May to 30 November. This decision was based on the results obtained in
previous studies and according to the various model calibrations performed in the same
geographical location. The indoor air temperatures were set at 21
C in winter and
24 C
in summer. Maintenance temperatures of 17
C in winter and 27
C in summer were
selected for night-time. For the regulatory calculation of air renewal, the occupancy was
5 people. To comply with regulations, a value of 0.63 ACH was established according to
Buildings 2024,14, 2158 11 of 20
Spain’s current Technical Building Code (CTE). The model was applied by eliminating the
existing basement of the dwelling, considering a very airtight access door, and calculating
the energy loss values with the U-value, as if the ground floor were in contact with the
ground. The air infiltration values entered in the tool were those obtained by the blower
door test. All parameters related to the outdoor climate, including the solar radiation
values, setpoint temperatures, air change rate according to the CTE regulations, etc., were
entered into the DesignBuilder tool. The calculation model used in DesignBuilder was that
of the total demand for all energy necessary to establish the set temperature conditions.
Therefore, the energy efficiency of the heat recovery unit was not taken into account. The
infiltration values obtained in the n
50
were applied in the four construction phases P1, P2,
P3, and P4, with the calculated air infiltration value average of the building envelope being
transformed according to expression (1).
A thermoflowmetric study of the opaque envelopes was conducted for the two south
façade rooms (kitchen at a height of 0.70 m and living room), the north façade (multipurpose
room), and the north and south façade first-floor bedrooms. The ground contact U-value
transmittance was also calculated in accordance with ISO 9869-1:2014 [
57
]. The tests
lasted at least one week for each U-value transmittance measurement. The data were
analysed using AMR WinControl software (https://www.ahlborn.com/en/products/amr-
win-control-software-for-data-acquisition-and-measured-data-processing) developed by
Ahlborn for ALMEMO measuring equipment. The method used was the “average method”,
i.e., the thermal transmittance was calculated by dividing the thermal flow average density
by the difference in average temperature [58,59].
3.3. Air Infiltration and Its Energy Impact: Investment Amortisation Approach
Having established a method to quantify the air infiltration energy impact and com-
pare it using DesignBuilder, it was possible to pursue the study objectives. To this end, four
phases of the construction and sealing process, P1, P2, P3, and P4, were technically defined,
and the execution cost of each was quantified. The investment amortisation period was
estimated according to the methodology shown in Figure 6.
Figure 6. Methodology to assess energy and investment amortisation in the 4 scenarios under study.
The n
50
value and the actual building envelope airtightness over the entire one-year
cycle were progressively analysed over the 4 phases, together with the energy impact due to
these air infiltrations. Finally, the home’s life cycle cost (LCC) was applied in the 4 scenarios
or designed phases. To this end, the UNE-EN 15459-1:2018 [
60
] standard was applied to
Buildings 2024,14, 2158 12 of 20
the house CCL in the 4 scenarios, P1, P2, P3, and P4. The overall cost was calculated using
the following expressions:
Cg(t) = Cl+jht
i=1(Ca,i(j)·Rdisc (i)) ValF,t(j)i, (9)
RR=Rint Ri
1+Ri/100 , (10)
Rdisc (i) = 1
1+RR/100 i
, (11)
where
Cg—overall cost.
Cl—initial investment costs.
Ca—recurring costs.
Rdisc—discount rate.
i—years.
Valf—residual value (EUR).
RR—real interest rate.
Ri—inflation rate.
Rint—interest rate.
The investment costs, recurring costs, and maintenance costs for a period of
30 years
were obtained from various databases of companies in the sector in Barcelona. The
costs of the energy consumed over 30 years were determined using expressions (7) and
(8), adjusted to the DesignBuilder simulation estimates, and an electricity mix cost of
0.242 EUR/kWh [61].
This quantification of overall execution costs and the savings achieved by reducing the
actual envelope airtightness in each phase allowed us to address the study hypothesis. By
subsequently determining the market value of the Passivhaus certification and comparing
it with non-certified housing values, we could establish whether it would be advisable
or not to adopt the sealing requirements of phases P2, P3, and P4 to reduce the n
50
value
below 0.6 ACH.
4. Results
Table 1shows the n
50
results obtained from the blower door test in each of the
4 phases
,
as well as the estimation of the energy loss calculation due to air infiltration according to
expression (1). As can be observed, the initial value was above 0.6 ACH, and a substantial
reduction was achieved in phases P2 (Figure 7), P3, and P4, dropping below the maximum
value allowed by the Passivhaus standard. The techniques for detecting the largest infil-
tration points, in addition to those applied for sealing, were satisfactory, and the desired
objective was met. Since similar results have been obtained in previous publications, we
were able to conclude that the work was technically valid [32,37].
Table 1. Results of n50 and average winter and summer infiltration in the three phases.
Envelope Air Infiltration eiεiP1 P2 P3 P4 % Reduction
n50 (blower door test) ACH 1.05 0.95 0.75 0.59 43.81
nwinter and nsummer 0.05 1 ACH 0.105 0.095 0.075 0.059 43.81
Buildings 2024,14, 2158 13 of 20
Buildings 2024, 14, 2158 13 of 20
Figure 7. Results from n
50
and the blower door test in phase P2.
Table 2. Calculation of annual energy demands due to air inltration in the four phases.
Parameter Material Execution and Sealing Phases
Phase P1 P2 P3 P4
q
inf
m
3
/hm
2
0.289 0.262 0.207 0.164
V
inf
m
3
/h 73.87 66.97 52.79 41.92
Q
s
kWh/y 319.15 288.75 227.96 179.33
Ql kWh/y 2632.28 2381.58 1880.20 1479.09
Annual energy demand due to infiltration kWh/m
2
y 6.55 5.74 4.46 3.73
Annual energy demand (expressions (1) to (8)) kWh/y 10,203.60 9989.37 9560.18 9191.32
Percentage % 100.00 97.79 93.69 90.08
As illustrated in Table 3, the results of the DesignBuilder simulations (Figure 8) are
visibly close to those obtained through the mathematical expressions (1 to 8), with a max-
imum deviation of 2.2%. They were both conducted to obtain the annual energy demand.
For the ideal load method to achieve annual energy consumption, a recuperator eciency
(Siber DF Excellen 400 Plus) value of 0.85 was taken into account in terms of air renewal.
Table 3. Calculation of energy loads and demands of the four phases, using DesignBuilder.
Parameter P1 P2 P3 P4
Total surface area 255.62 m
2
Total volume 703.8 m
3
Envelope airtightness (n
50
)
ACH 1.05 0.95 0.75 0.59
Lighting load kWh 1693.14 1693.14 1693.14 1693.14
Ventilation load (0.63 ACH) kWh 982.85 984.18 985.79 988.86
Envelope infiltration load kWh 1632.65 1435.93 1137.92 932.57
Occupancy load kWh 1618.82 1616.98 1613.21 1610.34
Envelope U load kWh 5103.92 5111.30 5126.22 5137.67
Windows U load kWh 2302.07 2266.72 2315.77 2282.63
Annual energy demand due to infiltration kWh/m
2
y 6.38 5.62 4.36 3.64
Total winter demand kWh/y 5546.4 5433.30 5221.12 5040.88
Total winter energy demand kWh/m
2
y 21.197 20.830 20.115 19.506
Figure 7. Results from n50 and the blower door test in phase P2.
Regarding the translation of these values into energy consumption quantifications, Ta-
ble 2breaks down the methodological process in Section 3.2.1., in which C = 18,
cf
1
= 1, cf
2
= 0.9, and cf
3
= 1.4. This air infiltration energy demand is also given with
respect to the energy demand of air changes of 0.63 ACH and the annual energy demand
due to air conditioning. These values are similar to those obtained in previous publica-
tions [
30
]. The energy demand due to envelope air infiltration accounted for 16.41% of
the annual energy demand in P1 and dropped to 11.93% in P3. These values are high
for conventional homes but not for Passivhaus Certificate housing, where thermal load
reduction and the heat recovery system substantially reduce annual energy demands [
62
].
Table 2. Calculation of annual energy demands due to air infiltration in the four phases.
Parameter Material Execution and Sealing Phases
Phase P1 P2 P3 P4
qinf m3/hm20.289 0.262 0.207 0.164
Vinf m3/h 73.87 66.97 52.79 41.92
QskWh/y 319.15 288.75 227.96 179.33
Ql kWh/y 2632.28 2381.58 1880.20 1479.09
Annual energy demand due to infiltration kWh/m2y6.55 5.74 4.46 3.73
Annual energy demand (expressions (1) to (8))
kWh/y 10,203.60 9989.37 9560.18 9191.32
Percentage % 100.00 97.79 93.69 90.08
As illustrated in Table 3, the results of the DesignBuilder simulations (Figure 8) are vis-
ibly close to those obtained through the mathematical expressions (1 to 8), with
a maximum
deviation of 2.2%. They were both conducted to obtain the annual energy demand. For the
ideal load method to achieve annual energy consumption, a recuperator efficiency (Siber
DF Excellen 400 Plus) value of 0.85 was taken into account in terms of air renewal.
Buildings 2024,14, 2158 14 of 20
Table 3. Calculation of energy loads and demands of the four phases, using DesignBuilder.
Parameter P1 P2 P3 P4
Total surface area 255.62 m2
Total volume 703.8 m3
Envelope airtightness (n50) ACH 1.05 0.95 0.75 0.59
Lighting load kWh 1693.14 1693.14 1693.14 1693.14
Ventilation load (0.63 ACH) kWh 982.85 984.18 985.79 988.86
Envelope infiltration load kWh 1632.65 1435.93 1137.92 932.57
Occupancy load kWh 1618.82 1616.98 1613.21 1610.34
Envelope Uload kWh 5103.92 5111.30 5126.22 5137.67
Windows Uload kWh 2302.07 2266.72 2315.77 2282.63
Annual energy demand due to infiltration kWh/m2y6.38 5.62 4.36 3.64
Total winter demand kWh/y 5546.4 5433.30 5221.12 5040.88
Total winter energy demand kWh/m2y21.197 20.830 20.115 19.506
Total summer demand kWh/y 4661.40 4555.62 4338.97 4150.43
Total summer energy demand kWh/m2y17.739 17.404 16.665 16.016
Solar gains through the glass in winter kWh 2701.90 2701.90 2701.90 2701.90
Annual energy demand (DesignBuilder) kWh/y 9983.60 9772.09 9401.70 9081.41
Total annual energy demand kWh/m2y28.367 27.659 26.210 24.957
Buildings 2024, 14, 2158 14 of 20
Total summer demand kWh/y 4661.40 4555.62 4338.97 4150.43
Total summer energy demand kWh/m2y 17.739 17.404 16.665 16.016
Solar gains through the glass in winter kWh 2701.90 2701.90 2701.90 2701.90
Annual energy demand (DesignBuilder) kWh/y 9983.60 9772.09 9401.70 9081.41
Total annual energy demand kWh/m2y 28.367 27.659 26.210 24.957
Figure 8. DesignBuilder simulation model.
As can be observed, glazing solar gains lead to signicant heating savings in winter,
with a free gain of 10.57 kWh/m2 y. This can occur thanks to the automated regulation
system of opening and closing blinds or shuers depending on the solar radiation condi-
tions and the Ti, if allowed. In this way, the winter energy demand is 10.63 kWh/m2 y in
Phase 1 and 8936 kWh/m2 y in Phase 4.
Table 4 shows the results obtained for the execution costs, maintenance costs, overall
costs, annual energy savings due to inltration reduction, and construction investment
amortisation periods. These amortisation periods were estimated based on experiences
reported in other studies [63,64]. The databases of companies in the sector were used to
calculate the installation costs. The cost of plastic adhesive jointing tape was based on a
ratio of 30.59 EUR/mL, including the costs of the operating technicians. Elastic amorphous
seals were valued according to previous experience and average construction company
costs. The total considered cost, including labour, was 16.59 EUR/mL.
Table 4. Calculation of the investment amortisation period of the four phases.
Sealing Type Cost
(EUR/mL)
Measurement
(mL)
Total Cost
(EUR/m) P1 (EUR) P2 (EUR) P3 (EUR) P4 (EUR)
Hermetic liquid membrane 44.38 192.5 8542.80 8.542.81
Expanding polyurethane foam 22.75 127.8 2907.45 2049.60 563.22 294.77
Plastic adhesive joint tape 30.59 127.8 3909.36 2189.63 657.16 901.6 160.44
Elastic amorphous seals 16.59 111.7 1853.25 584.08 421.61 297.92 549.64
Initial investment costs EUR 17,193.40 13,365.90 1641.99 1494.29 691.18
Maintenance costs (30 years) EUR 2096 1437.0 325.0 237.0 97.2
Overall Cost (Cg) EUR 19,289.4 14,802.9 1966.99 1731,29 788.38
Annual energy consumption kWh/year 9983.60 9772.09 9401.70 9081.41
Annual savings (0.242 EUR/kWh) EUR 51.74 155.61 244.90
Amortisation Period Years 31.73 20.15 15.63
Figure 8. DesignBuilder simulation model.
As can be observed, glazing solar gains lead to significant heating savings in winter,
with a free gain of 10.57 kWh/m
2
y. This can occur thanks to the automated regulation sys-
tem of opening and closing blinds or shutters depending on the solar radiation conditions
and the Ti, if allowed. In this way, the winter energy demand is 10.63 kWh/m
2
y in Phase 1
and 8936 kWh/m2y in Phase 4.
Table 4shows the results obtained for the execution costs, maintenance costs, overall
costs, annual energy savings due to infiltration reduction, and construction investment
amortisation periods. These amortisation periods were estimated based on experiences
Buildings 2024,14, 2158 15 of 20
reported in other studies [
63
,
64
]. The databases of companies in the sector were used
to calculate the installation costs. The cost of plastic adhesive jointing tape was based
on
a ratio
of 30.59 EUR/mL, including the costs of the operating technicians. Elastic
amorphous seals were valued according to previous experience and average construction
company costs. The total considered cost, including labour, was 16.59 EUR/mL.
Table 4. Calculation of the investment amortisation period of the four phases.
Sealing Type Cost
(EUR/mL)
Measurement
(mL) Total Cost
(EUR/m)
P1
(EUR)
P2
(EUR)
P3
(EUR)
P4
(EUR)
Hermetic liquid membrane 44.38 192.5 8542.80 8.542.81
Expanding polyurethane foam 22.75 127.8 2907.45 2049.60 563.22 294.77
Plastic adhesive joint tape 30.59 127.8 3909.36 2189.63 657.16 901.6 160.44
Elastic amorphous seals 16.59 111.7 1853.25 584.08 421.61 297.92 549.64
Initial investment costs EUR 17,193.40
13,365.90
1641.99 1494.29 691.18
Maintenance costs (30 years) EUR 2096 1437.0 325.0 237.0 97.2
Overall Cost (Cg)EUR 19,289.4 14,802.9 1966.99 1731,29 788.38
Annual energy consumption kWh/year 9983.60 9772.09 9401.70 9081.41
Annual savings (0.242 EUR/kWh)
EUR 51.74 155.61 244.90
Amortisation Period Years 31.73 20.15 15.63
As can be observed, the amortisation periods of investments in the detection work
and subsequent joinery sealing in the various phases were too long; they amounted to
over
30 years
for P2 and more than 15 years for P4. These values are well above those
required for an adequate operation, which would be around 5–10 years. In addition, the
electricity mix cost was higher in those years than in 2020, which would have led to even
less favourable rates. A comparison of the four scenarios is shown in Figure 9.
Buildings 2024, 14, 2158 15 of 20
As can be observed, the amortisation periods of investments in the detection work
and subsequent joinery sealing in the various phases were too long; they amounted to
over 30 years for P2 and more than 15 years for P4. These values are well above those
required for an adequate operation, which would be around 5–10 years. In addition, the
electricity mix cost was higher in those years than in 2020, which would have led to even
less favourable rates. A comparison of the four scenarios is shown in Figure 9.
Figure 9. Results of the global cost for 30 years, energy due to inltration, annual energy demand,
and investment amortisation period in the four scenarios under study.
Lastly, we analysed the inltration energy impact and investment amortisation in
colder climate zones, in this case, in Central Europe [36,65], and compared the data with
those of the Spanish Mediterranean region. To do this, we used the same case study, the
house in Sitges, and simulated its location in Prague using DesignBuilder. The conditions
of construction culture, execution costs, and per capita income, which do not dier sub-
stantially from those of Spain, support the validity of the comparison. The most notable
dierence was the electricity mix cost per kWh: it was EUR 0.3212 in Prague and EUR
0.242 in Sitges (Barcelona).
Table 5 and Figure 10 show the results obtained. One can see that the energy impact
due to inltration was around 217–228% higher than that of Sitges. The annual energy
demand was 51,981 kWh/m
2
compared to 28,367 kWh/m
2
in Sitges, i.e., 183.25% higher.
The PHS requirements would not be met in that case. On the other hand, the amortisation
periods of the investments made to seal the envelopes, in all their phases, would be highly
recommended, as they reduce the annual energy demand to a value of 46,087 kWh/m
2
y,
allowing for amortisation of the investments in less than 5 years.
Table 5. Calculation of energy demand and investment amortisation period in Prague.
PRAGUE
Parameter P1 P2 P3 P4
Overall cost (C
g
) 94.1% per capita EUR 13,929.5 1850.93 1629,14 741.87
Annual energy demand due to infiltration kWh/y 1153.89 1045.44 587.83 651.70
Annual energy demand due to infiltration kWh/m
2
y 13.84 12.72 10.93 8.33
Total winter energy demand kWh/y 7035.30 6963.39 6813.58 6707.65
Total winter energy demand kWh/m
2
y 46.43 44.99 43.27 40.82
Total summer energy demand kWh/y 913.15 924.89 941.16 962.38
Total summer energy demand kWh/m
2
y 5.555 5.430 5.339 5.270
Total annual energy demand kWh/y 13,287.38 12,890.15 12,425.68 10,433.64
Total annual energy demand kWh/m
2
y 51,981 50,427 48,610 46,087
Annual savings (0.3212 EUR/kWh) EUR 127.56 276.72 916.44
Amortisation Period Years 14.51 12.58 4.61
Figure 9. Results of the global cost for 30 years, energy due to infiltration, annual energy demand,
and investment amortisation period in the four scenarios under study.
Lastly, we analysed the infiltration energy impact and investment amortisation in
colder climate zones, in this case, in Central Europe [
36
,
65
], and compared the data with
those of the Spanish Mediterranean region. To do this, we used the same case study, the
house in Sitges, and simulated its location in Prague using DesignBuilder. The conditions
of construction culture, execution costs, and per capita income, which do not differ sub-
stantially from those of Spain, support the validity of the comparison. The most notable
difference was the electricity mix cost per kWh: it was EUR 0.3212 in Prague and EUR 0.242
in Sitges (Barcelona).
Buildings 2024,14, 2158 16 of 20
Table 5and Figure 10 show the results obtained. One can see that the energy impact
due to infiltration was around 217–228% higher than that of Sitges. The annual energy
demand was 51,981 kWh/m
2
compared to 28,367 kWh/m
2
in Sitges, i.e., 183.25% higher.
The PHS requirements would not be met in that case. On the other hand, the amortisation
periods of the investments made to seal the envelopes, in all their phases, would be highly
recommended, as they reduce the annual energy demand to a value of 46,087 kWh/m
2
y,
allowing for amortisation of the investments in less than 5 years.
Table 5. Calculation of energy demand and investment amortisation period in Prague.
PRAGUE
Parameter P1 P2 P3 P4
Overall cost (Cg) 94.1% per capita EUR 13,929.5 1850.93 1629,14 741.87
Annual energy demand due to infiltration kWh/y 1153.89 1045.44 587.83 651.70
Annual energy demand due to infiltration kWh/m2y13.84 12.72 10.93 8.33
Total winter energy demand kWh/y 7035.30 6963.39 6813.58 6707.65
Total winter energy demand kWh/m2y46.43 44.99 43.27 40.82
Total summer energy demand kWh/y 913.15 924.89 941.16 962.38
Total summer energy demand kWh/m2y5.555 5.430 5.339 5.270
Total annual energy demand kWh/y 13,287.38 12,890.15 12,425.68 10,433.64
Total annual energy demand kWh/m2y51,981 50,427 48,610 46,087
Annual savings (0.3212 EUR/kWh) EUR 127.56 276.72 916.44
Amortisation Period Years 14.51 12.58 4.61
Buildings 2024, 14, 2158 16 of 20
Figure 10. Comparative results of the global cost for 30 years, energy due to inltration, annual
energy demand, and investment amortisation period between P1 and P4 in Sitges and Prague.
5. Discussion
The application of the Passivhaus standard to housing on the Mediterranean coast
has been the subject of ongoing debate. The most controversial factor is the overheating
of the air and interior walls in summer, which leads to signicant comfort loss and high
air conditioning energy consumption.
Yet, to date, there has been lile discussion on the need to build an envelope that
would be as airtight as that required in Central Europe. As established by Wolfgang Feist,
the current director of the Darmstadt Passivhaus Institut, and by Bo Adamson in the late
1980s, achieving an n
50
value below 0.6 ACH seems to be an obvious condition to full in
that area. However, this requirement is not so justiable on the Mediterranean coast,
where the outside air rarely drops below 0 °C. It would therefore be relevant to conduct
further research and establish reasonable n
50
value parameters taking into account con-
struction execution costs and an amortisation period of less than 5 years for construction
and sealing cost overruns. Another decisive factor in this issue is the market value that
Passivhaus certication would give to the property in terms of capital gains. This variable
would undoubtedly make it advisable to adopt n
50
values below 0.6 ACH since the addi-
tional construction and sealing costs are usually much lower than the market value in-
crease of the property.
It is also necessary to incorporate the variable of overall material implementation
costs, which dier greatly from one country to another in the Mediterranean region and
Central Europe. In Germany, they account for approximately 1600–2800 EUR/m
2
, while in
Spain, they are in the range of 1400–2200 EUR/m
2
. Currently, the Passivhaus standard
involves an additional cost that ranges from 3% to 8% of the total construction budget,
with the average additional cost in Germany being 6%, though there have been cases
where the extra cost is nil. In the Spanish Mediterranean area, the average cost overrun is
around 27%, due to overall lower carpentry quality, poor airtightness, and the absence of
heat recovery systems in conventional construction.
6. Conclusions
The requirement to apply a maximum value of n
50
of 0.6 ACH in Passivhaus homes
on the Spanish Mediterranean coast is subject to debate. Given the values found in this
study for a PH house located in Sitges (Barcelona), it would seem more reasonable to ap-
ply the construction and sealing techniques of the Phase 1 envelope only. If successive
phases of seal improvement were applied—P2, P3, and P4—to reduce the n
50
value to 0.6
ACH with a higher material execution cost, the investment amortisation period would be
too long, as it would range from 15 to 30 years. The resulting n
50
value in P1 is 1.05, which
is far above the PHS limit. However, the energy losses due to this value increase annual
energy demand by only 13.66%, that is, 3.41 kWh/m
2
y, accounting for an annual energy
cost increase of EUR 244.90. Compared to the execution costs of EUR 3827 for the three
phases—the total costs applied in P4—the investment amortisation period would be over
Figure 10. Comparative results of the global cost for 30 years, energy due to infiltration, annual
energy demand, and investment amortisation period between P1 and P4 in Sitges and Prague.
5. Discussion
The application of the Passivhaus standard to housing on the Mediterranean coast
has been the subject of ongoing debate. The most controversial factor is the overheating of
the air and interior walls in summer, which leads to significant comfort loss and high air
conditioning energy consumption.
Yet, to date, there has been little discussion on the need to build an envelope that
would be as airtight as that required in Central Europe. As established by Wolfgang Feist,
the current director of the Darmstadt Passivhaus Institut, and by Bo Adamson in the late
1980s, achieving an n
50
value below 0.6 ACH seems to be an obvious condition to fulfil in
that area. However, this requirement is not so justifiable on the Mediterranean coast, where
the outside air rarely drops below 0
C. It would therefore be relevant to conduct further
Buildings 2024,14, 2158 17 of 20
research and establish reasonable n
50
value parameters taking into account construction
execution costs and an amortisation period of less than 5 years for construction and sealing
cost overruns. Another decisive factor in this issue is the market value that Passivhaus
certification would give to the property in terms of capital gains. This variable would
undoubtedly make it advisable to adopt n
50
values below 0.6 ACH since the additional
construction and sealing costs are usually much lower than the market value increase
of the property.
It is also necessary to incorporate the variable of overall material implementation costs,
which differ greatly from one country to another in the Mediterranean region and Central
Europe. In Germany, they account for approximately 1600–2800 EUR/m
2
, while in Spain,
they are in the range of 1400–2200 EUR/m
2
. Currently, the Passivhaus standard involves
an additional cost that ranges from 3% to 8% of the total construction budget, with the
average additional cost in Germany being 6%, though there have been cases where the
extra cost is nil. In the Spanish Mediterranean area, the average cost overrun is around 27%,
due to overall lower carpentry quality, poor airtightness, and the absence of heat recovery
systems in conventional construction.
6. Conclusions
The requirement to apply a maximum value of n
50
of 0.6 ACH in Passivhaus homes on
the Spanish Mediterranean coast is subject to debate. Given the values found in this study
for a PH house located in Sitges (Barcelona), it would seem more reasonable to apply the
construction and sealing techniques of the Phase 1 envelope only. If successive phases of
seal improvement were applied—P2, P3, and P4—to reduce the n
50
value to 0.6 ACH with
a higher material execution cost, the investment amortisation period would be too long, as
it would range from 15 to 30 years. The resulting n
50
value in P1 is 1.05, which is far above
the PHS limit. However, the energy losses due to this value increase annual energy demand
by only 13.66%, that is, 3.41 kWh/m
2
y, accounting for an annual energy cost increase
of EUR 244.90. Compared to the execution costs of EUR 3827 for the three phases—the
total costs applied in P4—the investment amortisation period would be over 15 years. The
same would be true for phases F2 and F3, where the implementation costs would be EUR
1641.99 and EUR 3136.28, respectively, and the amortisation periods would be 31 years
and
20 years
. It would therefore be advisable not to undertake phases P2, P3, and P4. The
property could not obtain the PHS with an n
50
value of 1.05 ACH, but given that the PHS
does not contribute to market value in the Spanish real estate valuation system, there is no
need to continue improving envelope tightness with phases P2, P3, and P4.
When the same house is subjected to a DesignBuilder simulation in Prague, i.e.,
in
a colder
Central European climate, the scenario is entirely different. Severe winter
conditions imply that reducing the air infiltration through the envelope to the n
50
value of
0.59 ACH entails significant annual energy savings of 2853.74 kWh/y. The electricity mix
costs EUR 0.324/kWh, and a substantial annual saving of EUR 916.44 is achieved. In this
case, the amortisation period of the investments required to improve the construction is
less than 5 years. We can thus conclude, in this specific case study, that the execution of
phases P2, P3, and P4 would be feasible in cold continental climates, but in mild conditions,
such as the Mediterranean climate, it would be more appropriate, in terms of energy and
investments, to maintain the initial building construction solution of phase P1. To draw
any concrete conclusions from an environmental perspective, it would first be necessary to
conduct the arduous task of completing a whole life cycle assessment (LCA), including the
P2, P3, and P4 sealing techniques.
To summarise, we are facing a complex problem that requires successive examinations
and a detailed analysis of case studies in order to determine an n
50
infiltration value ad-
justed to the climatic conditions and the energy and execution cost requirements according
to each region or geographical area.
Buildings 2024,14, 2158 18 of 20
Author Contributions: Conceptualization, V.E.-I. and R.G.-V.; methodology, V.E.-I.; software, I.U.-B.;
validation, V.E.-I., I.U.-B. and R.G.-V.; investigation, V.E.-I., I.U.-B. and R.G.-V.; resources, R.G.-V. and
I.U.-B.; data curation, V.E.-I. and I.U.-B.; writing—original draft preparation, V.E.-I.; writing—review
and editing, V.E.-I.; funding acquisition, R.G.-V. All authors have read and agreed to the published
version of the manuscript.
Funding: This research received no external funding.
Data Availability Statement: There is not data available publicly.
Acknowledgments: The authors gratefully acknowledge the technical help provided by EVOWALL
TECHNOLOGY S.L. and the RV4 architect’s office in order to carry out the different tests needed for
this paper.
Conflicts of Interest: The authors declare no conflicts of interest. The company and the architect’s
office had no role in the design of the study; in the collection, analyses, or interpretation of data; in
the writing of the manuscript; or in the decision to publish the results.
References
1.
European Commission. Directive 2002/91/EC of the European Parliament and of the Council of 16 December 2002 on the energy
performance of buildings. Off. J. Eur. Commun. 2003,L1, 65–70.
2.
European Commission. Directive 2010/31/EU of European Parliament and of the Council of 19 May 2010 on the energy
performance of buildings (recast). Off. J. Eur. Union 2010,L153, 13–35.
3.
European Commission. Directive 2012/27/EU of European Parliament and of the Council of 25 October 2012 on energy efficiency,
amending Directive 2009/125/EC and 2010/30/EU and repealing Directives 2004/8/EC and 2006/32/EC. Off. J. Eur. Union 2012,
L315, 1–56.
4.
Attia, S.; Eleftheriou, P.; Xeni, F.; Morlot, R.; Ménézo, C.; Kostopoulos, V.; Betsi, M.; Kalaitzoglou, I.; Pagliano, L.; Cellura, M.;
et al. Overview and future challenges of nearly zero energy buildings (nZEB) design in Southern Europe. Energy Build. 2017,155,
439–458. [CrossRef]
5.
Technical Building Code CTE. Basic Document on Energy Savings DB-HE; Spanish Ministry of Housing: Madrid, Spain, 2006. (In Spanish)
6.
Spanish Ministry of Housing. Orden VIV/984/2009, de 15 de Abril, Por la Que se Modifican Determinados Documentos Básicos del
Código Técnico de la Edificación Aprobados por el Real Decreto 314/2006, de 17 de Marzo, y el Real Decreto 1371/2007, de 19 de Octubre;
Spanish Ministry of Housing: Madrid, Spain, 2009. (In Spanish)
7.
Spanish Ministry of Public Works and Transport. Orden FOM/1635/2013, de 10 de Septiembre, por la Que se Actualiza el Documento
Básico DB-HE Ahorro de Energía, del Código Técnico de la Edificación, Aprobado por Real Decreto 314/2006, de 17 de Marzo; (Publicado en:
«BOE» núm. 219, de 12 de Septiembre de 2013, Páginas 67137–67209); Spanish Ministry of Public Works and Transport: Madrid,
Spain, 2013. (In Spanish)
8.
Passive House—Passivhaus Institut (PHI). Available online: https://passivehouse.com/02_informations/01_whatisapassivehouse/
01_whatisapassivehouse.htm (accessed on 9 April 2019).
9.
Blázquez, T.; Suárez, R.; Ferrari, S.; Sendra, J. Improving winter thermal comfort in Mediterranean buildings upgrading the
envelope: An adaptive assessment based on a real survey. Energy Build. 2023,278, 112615. [CrossRef]
10.
Reguis, A.; Tunzi, M.; Vand, B.; Tuohy, P.; Currie, J. Energy performance of Scottish public buildings and its impact on the ability
to use low-temperature heat. Energy Build. 2023,290, 113064. [CrossRef]
11.
Liu, C.; Mohammadpourkarbasi, H.; Sharples, S. Evaluating the potential energy savings of retrofitting low-rise suburban
dwellings towards the Passivhaus EnerPHit standard in a hot summer/cold winter region of China. Energy Build. 2021,
231, 110555. [CrossRef]
12.
Lavafpour, Y.; Sharples, S.; Gething, B. The impact of building form on overheating control: A case study of Larch House. Archit.
Sci. Rev. 2020,63, 467–480. [CrossRef]
13.
Bravo-Orlandini, C.; Gomez-Soberon, J.M.; Valderrama-Ulloa, C.; Sanhueza-Duran, F. Energy, Economic, and Environmental
Performance of a Single-Family House in Chile Built to Passivhaus Standard. Sustainability 2021,13, 1199. [CrossRef]
14.
Causone, F.; Tatti, A.; Pietrobon, M.; Zanghirella, F.; Pagliano, L. Yearly operational performance of a nZEB in the Mediterranean
climate. Energy Build. 2019,198, 243–260. [CrossRef]
15.
Strang, M.; Leardini, P.; Brambilla, A.; Gasparri, E. Mass Timber Envelopes in Passivhaus Buildings: Designing for Moisture
Safety in Hot and Humid Australian Climates. Buildings 2021,11, 478. [CrossRef]
16.
Finegan, E.; Kelly, G.; O’Sullivan, G. Comparative analysis of Passivhaus simulated and measured overheating frequency in
a typical dwelling in Ireland. Build. Res. Inf. 2020,48, 681–699. [CrossRef]
17.
Figueroa-Lopez, A.; Arias, A.; Oregi, X.; Rodriguez, I. Evaluation of passive strategies, natural ventilation and shading systems,
to reduce overheating risk in a passive house tower in the north of Spain during the warm season. J. Build. Eng. 2021,43, 102607.
[CrossRef]
18.
Jang, J.; Natarajan, S.; Lee, J.; Leigh, S.-B. Comparative Analysis of Overheating Risk for Typical Dwellings and Passivhaus in the
UK. Energies 2022,15, 3829. [CrossRef]
Buildings 2024,14, 2158 19 of 20
19.
Chiesa, G.; Acquaviva, A.; Grosso, M.; Bottaccioli, L.; Floridia, M.; Pristeri, E.; Sanna, E.M. Parametric Optimization of Window-
to-Wall Ratio for Passive Buildings Adopting A Scripting Methodology to Dynamic-Energy Simulation. Sustainability 2019,11,
3078. [CrossRef]
20.
Hong, Y.; Ezeh, C.I.; Deng, W.; Lu, J.; Ma, Y.; Jin, Y. Climate adaptation of design scheme for energy-conserving high-rise
buildings-Comparative study of achieving building sustainability in different climate scenarios. Energy Rep. 2022,8, 13735–13752.
[CrossRef]
21.
Brembilla, E.; Hopfe, C.J.; Mardaljevic, J.; Mylona, A.; Mantesi, E. Balancing daylight and overheating in low-energy design using
CIBSE improved weather files. Build. Serv. Eng. Res. Technol. 2020,41, 210–224. [CrossRef]
22.
Rodriguez Vidal, I.; Otaegi, J.; Oregi, X. Thermal Comfort in NZEB Collective Housing in Northern Spain. Sustainability 2020,
12, 9630. [CrossRef]
23.
Zune, M.; Tubelo, R.; Rodrigues, L.; Gillott, M. Improving building thermal performance through an integration of Passivhaus
envelope and shading in a tropical climate. Energy Build. 2021,253, 111521. [CrossRef]
24.
Campo Ruano, P.; de Lapuerta Montoya, J.M.; Garcia-German, J.; Menendez Amigo, J.; Mendoza Alonso, V.; Camara Ruiz,
I. Technical and constructive energy strategies of the first Passivhaus Plus school in Spain. Inf. De La Constr. 2023,75, e492.
[CrossRef]
25.
Kang, Y.; Chang, V.W.-C.; Chen, D.; Graham, V.; Zhou, J. Performance gap in a multi-storey student accommodation complex
built to Passivhaus standard. Build. Environ. 2021,194, 107704. [CrossRef]
26.
Escandón, R.; Calama-González, C.M.; Alonso, A.; Suárez, R.; León-Rodríguez, Á.L. How Do Different Methods for Generating
Future Weather Data Affect Building Performance Simulations? A Comparative Analysis of Southern Europe. Buildings 2023,
13, 2385. [CrossRef]
27.
Moreno-Rangel, A.; Sharpe, T.; McGill, G.; Musau, F. Indoor Air Quality and Thermal Environment Assessment of Scottish
Homes with Different Building Fabrics. Buildings 2023,13, 1518. [CrossRef]
28.
Santin, O.G.; Grave, A.; Jiang, S.; Tweed, C.; Mohammadi, M. Monitoring the performance of a Passivhaus care home: Lessons for
user-centric design. J. Build. Eng. 2021,43, 102565. [CrossRef]
29.
Mustafa, M.; Cook, M.J.; McLeod, R.S. Enhancing non-domestic Passivhaus auditoria ventilation design for improved indoor
environmental quality. Build. Environ. 2023,234, 110202. [CrossRef]
30.
Otaegi, J.; Hernandez, R.J.; Oregi, X.; Martin-Garin, A.; Rodriguez-Vidal, I. Comparative Analysis of the Effect of the Evolution of
Energy Saving Regulations on the Indoor Summer Comfort of Five Homes on the Coast of the Basque Country. Buildings 2022,
12, 1047. [CrossRef]
31.
Liu, C.; Sharples, S.; Mohammadpourkarbasi, H. Evaluating Insulation, Glazing and Airtightness Options for Passivhaus
EnerPHit Retrofitting of a Dwelling in China’s Hot Summer-Cold Winter Climate Region. Energies 2021,14, 6950. [CrossRef]
32.
Echarri-Iribarren, V.; Sotos-Solano, C.; Espinosa-Fernandez, A.; Prado-Govea, R. The Passivhaus Standard in the Spanish
Mediterranean: Evaluation of a House’s Thermal Behaviour of Enclosures and Airtightness. Sustainability 2019,11, 3732.
[CrossRef]
33.
Moreno-Rangel, A.; Sharpe, T.; McGill, G.; Musau, F. Indoor Air Quality in Passivhaus Dwellings: A Literature Review.
International. J. Environ. Res. Public Health 2020,17, 4749. [CrossRef]
34.
Korsavi, S.S.; Jones, V.R.; Bilverstone, P.A.; Fuertes, A. A longitudinal assessment of the energy and carbon performance of
a Passivhaus university building in the UK. J. Build. Eng. 2021,44, 103353. [CrossRef]
35.
Martinez-Soto, A.; Saldias-Lagos, Y.; Marincioni, V.; Nix, E. Affordable, Energy-Efficient Housing Design for Chile: Achieving
Passivhaus Standard with the Chilean State Housing Subsidy. Appl. Sci. 2020,10, 7390. [CrossRef]
36.
Forde, J.; Hopfe, C.J.; McLeod, R.S.; Evins, R. Temporal optimization for affordable and resilient Passivhaus dwellings in the
social housing sector. Appl. Energy 2020,261, 114383. [CrossRef]
37.
Feijó-Muñoz, J.; Poza-Casado, I.; González-Lezcano, R.; Pardal, C.; Echarri, V.; Fernández-Agüera, J.; Assiego de Larriva, R.;
Fernández-Agüera, J.; Dios-Viéitez, M.J.; del Campo-Díaz, V.J.; et al. Methodology for the Study of the Envelope Airtightness of
Residential Buildings in Spain: A Case Study. Energies 2018,11, 704. [CrossRef]
38. Mitchell, R.; Natarajan, S. UK Passivhaus and the energy performance gap. Energy Build. 2020,224, 110240. [CrossRef]
39.
Rose, J.; Kragh, J.; Nielsen, K.F. Passive house renovation of a block of flats—Measured performance and energy signature
analysis. Energy Build. 2022,256, 111679. [CrossRef]
40.
Yakimchuk, T.; Linhares, P.; Hermo, V. Evaluation of a modular construction system in accordance with the Passivhaus standard
for components. J. Build. Eng. 2023,76, 107234. [CrossRef]
41.
Zhao, J.; Carter, K. Do passive houses need passive people? Evaluating the active occupancy of Passivhaus homes in the United
Kingdom. Energy Res. Soc. Sci. 2020,64, 101448. [CrossRef]
42.
Echarri, V.; Espinosa, A.; Rizo, C. Thermal Transmission through Existing Building Enclosures: Destructive Monitoring in
Intermediate Layers versus Non-Destructive Monitoring with Sensors on Surfaces. Sensors 2017,17, 2848. [CrossRef] [PubMed]
43.
Bienvenido-Huertas, D.; Moyano, J.; Rodríguez-Jiménez, C.E.; Marín, D. Applying an artificial neural network to assess thermal
transmittance in walls by means of the thermometric method. Appl. Energy 2019,233–234, 1–14. [CrossRef]
44.
Xu, C.; Nielsen, P.V.; Liu, L.; Jensen, R.L.; Gong, G. Impacts of airflow interactions with termal boundary layer on performance of
personalized ventilation. Build. Environ. 2018,135, 31–41. [CrossRef]
Buildings 2024,14, 2158 20 of 20
45.
Poza-Casado, I.; Cardoso, V.E.; Almeida, R.M.; Meiss, A.; Ramos, N.M.; Padilla-Marcos, M. Residential buildings airtightness
frameworks: A review on the main databases and setups in Europe and North America. Build. Environ. 2020,183, 107221.
[CrossRef]
46.
Feijó-Muñoz, J.; Pardal, C.; Echarri, V.; Fernández-Agüera, J.; Assiego de Larriva, R.; Montesdeoca Calderín, M.; Poza-Casado, I.;
Padilla-Marcos, M.A.; Meiss, A. Energy impact of the air infiltration in residential buildings in the Mediterranean area of Spain
and the Canary Islands. Energy Build. 2019,188–189, 226–238. [CrossRef]
47.
Bienvenido-Huertas, D.; Fernández Quiñones, J.A.; Moyano, J.; Rodríguez-Jiménez, C.E. Patents Analysis of Thermal Bridges in
Slab Fronts and Their Efect on Energy Demand. Energies 2018,11, 2222. [CrossRef]
48. Echarri-Iribarren, V.; Rizo-Maestre, C.; Echarri-Iribarren, F. Healthy Climate and Energy Savings: Using Termal Ceramic Panels
and Solar Thermal Panels in Mediterranean Housing Blocks. Energies 2018,11, 2707. [CrossRef]
49.
Wang, Y.; Shi, S.; Zhou, Z.; Guo, S.; Zhao, B. Air infiltration rate distribution across Chinese five climate zones: A modelling study
for rural residences. Build. Environ. 2024,252, 111284. [CrossRef]
50.
Porsani, G.B.; Casquero-Modreg, N.; Trueba, J.B.E.; Bandera, C.F. Empirical evaluation of EnergyPlus infiltration model for a case
study in a high-rise residential building. Energy Build. 2023,296, 113322. [CrossRef]
51.
Poza-Casado, I.; Rodríguez-Del-Tío, P.; Fernández-Temprano, M.; Padilla-Marcos, M.; Meiss, A. An envelope airtightness
predictive model for residential buildings in Spain. Build. Environ. 2022,223, 109435. [CrossRef]
52.
Younes, C.; Shdid, C.A.; Bitsuamlak, G. Air infiltration through building envelopes: A review. J. Build. Phys. 2012,35, 267–302.
[CrossRef]
53. Sherman, M.H. Estimation of infiltration from leakage and climate indicators. Energy Build. 1987,10, 81–86. [CrossRef]
54.
Benaddi, F.Z.; Boukhattem, L.; Tabares-Velasco, P.C. Multi-objective optimization of building envelope components based on
economic, environmental, and thermal comfort criteria. Energy Build. 2024,305, 113909. [CrossRef]
55.
Aznar, F.; Echarri, V.; Rizo, C.; Rizo, R. Modelling the Thermal Behaviour of a Building Facade Using Deep Learning. PLoS ONE
2018,13, e0207616. [CrossRef] [PubMed]
56.
Liu, Z.; Zhou, X.; Tian, W.; Liu, X.; Yan, D. Impacts of uncertainty in building envelope thermal transmittance on heating/cooling
demand in the urban context. Energy Build. 2022,273, 112363. [CrossRef]
57.
ISO 9869-1:2014; Thermal Insulation-Building Elements-In Situ Measurement of Thermal Resistance and Thermal Transmittance.
Part 1: Heat Flow Meter Method. ISO: Geneva, Switzerland, 2014. Available online: https://www.iso.org/standard/59697.html
(accessed on 13 April 2019).
58.
Onatayo, D.; Aggarwal, R.; Srinivasan, R.S.; Shah, B. A data-driven approach to thermal transmittance (U-factor) calculation of
double-glazed windows with or without inert gases between the panes. Energy Build. 2024,305, 113907. [CrossRef]
59.
Bucklin, O.; Müller, T.; Amtsberg, F.; Leistner, P.; Menges, A. Analysis of thermal Transmittance, air Permeability, and hygrothermal
behavior of a solid timber building envelope. Energy Build. 2023,299, 113629. [CrossRef]
60.
UNE-EN 15459-1:2017; Energy Performance of Buildings—Economic Evaluation Procedure for Energy Systems in Buildings—Part
1: Calculation Procedures, Module M1-14. CEN. European Committee for Standardization: Brussels, Belgium, 2017. Available
online: https://standards.cen.eu/dyn/www/f?p=204:110:0::::FSP_PROJECT,FSP_ORG_ID:40932, 6209&cs=%20110690DD8F9
BE238B61D722D035C11CAE (accessed on 11 June 2019).
61.
IDAE. Informe de Precios Energéticos Regulados. April 2024. Available online: https://www.idae.es/sites/default/files/
estudios_informes_y_estadisticas/Tarifas_Reguladas_abril_2024.pdf (accessed on 7 May 2024).
62.
Mihai, M.; Tanasiev, V.; Dinca, C.; Badea, A.; Vidu, R. Passive house analysis in terms of energy performance. Energy Build. 2017,
144, 74–86. [CrossRef]
63.
Gainza-Barrencua, J.; Odriozola-Maritorena, M.; Hernandez_Minguillon, R.; Gomez-Arriaran, I. Energy savings using sunspaces
to preheat ventilation intake air: Experimental and simulation study. J. Build. Eng. 2021,40, 102343. [CrossRef]
64.
Echarri-Iribarren, V.; Rizo-Maestre, C.; Sanjuan-Palermo, J.L. Underfloor Heating Using Ceramic Thermal Panels and Solar
Thermal Panels in Public Buildings in the Mediterranean: Energy Savings and Healthy Indoor Environment. Appl. Sci. 2019,
9, 2089. [CrossRef]
65.
Dan, D.; Tanasa, C.; Stoian, V.; Brata, S.; Stoian, D.; Nagy Gyorgy, T.; Florut, S.C. Passive house design—An efficient solution for
residential buildings in Romania. Energy Sustain. Dev. 2016,32, 99–109. [CrossRef]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual
author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to
people or property resulting from any ideas, methods, instructions or products referred to in the content.
... Before proceeding to the return-on-investment calculation, in the second phase of the research we quantified the Passivhaus envelope air leakage energy. To this end, the same methodology applied in a previous study [76] was followed based on Formulas (12)- (16). According to Formula (12), the n winter value was 0.154 n 50 , i.e., a 15.4% leakage air flow compared to the Blower Door test at 50 Pa (in Formula (12), e i wind protection coefficient = 0.07; ε i or corrective factor height = 1.1). ...
... As can also be observed, this low impact on the annual energy demand of the leakage air in Passivhaus homes on the Spanish Mediterranean coast represents a small saving in annual energy costs in euros. In other words, measures to reduce the n 50 value in PH homes are not beneficial in financial terms, but they are in terms of environmental impact reduction, as demonstrated in recent research [76]. ...
Article
Full-text available
Regulatory demands for indoor air renewal in buildings entail high levels of energy consumption. This is the only way to provide minimum indoor air quality (IAQ) and avoid some common lesions and pathologies. In Passivhaus standard (PHS) houses, a heat recovery system is required between the indoor–outdoor air masses of the air renewal system. This configuration substantially reduces energy consumption. In addition, the obligation to reduce envelope air leakage below the n50 value of 0.60 ACH usually allows for a decrease in the energy consumed to less than 15 kWh/m²y in winter, as required by the PHS. It is complex, however, to quantify the energy demands of a building, whether in the project phase or in the operational or use phase. The present study focuses on the application of the PHS in Spanish Mediterranean housing. The aim was to assess whether it is suitable to use heat recovery systems by quantifying the energy savings obtained, execution costs, infiltration air flow, ventilator power usage, and maintenance. To this end, we performed a study on an existing PHS house in Abrera (Barcelona, Spain). It was found that heat recovery systems are always cost-effective in cold climates such as that of Central Europe but are only profitable in Spanish Mediterranean houses when the system costs less than approximately EUR 2500. In this case, the investment is covered over a period of 9.4–12.8 years and over 14–18 years when the equipment costs more than EUR 3000. Annual savings range from EUR 184.44 to 254.33 in Abrera compared to EUR 904.99 to 934.82 in a city like Berlin, that is, a 400–500% increase in savings. Moreover, leakage air energy accounted for 13% to 15% of that of renewal air, −1.348 kWh/m²y and 2.276 kWh/m²y compared to 8.55 kWh/m²y and 17.31 kWh/m²y, respectively. Lastly, recovery system average efficiency or ηt performance—which is usually between 82% and 95%—did not play a relevant role in deciding whether the system should be installed or not.
Article
Full-text available
Climate change will have a great impact on the hottest climates of southern Europe and the existing residential stock will be extremely vulnerable to these future climatic conditions. Therefore, there is an urgent need to update this building stock considering imminent global warming by applying climatic files that predict future conditions in building performance simulations. This research makes use of the two most applied tools (Meteonorm and CCWorldWeatherGen) for generating future climate hourly datasets for 2050 and 2080 in southern Spain. The results predicted for outdoor and indoor thermal conditions and cooling and heating demands are evaluated for two different scale simulation models: a test cell and a multi-family building located in southern Spain. The main aim of this work is the development of a comparative analysis of the results to highlight their potential differences and raise awareness of the influence of the climate data projection method on the simulation outcome. The results show that the projection method selected for producing future climatic files has relevant effects on the analysis of thermal comfort and energy demand, but it is considerably reduced when an annual evaluation is developed.
Article
Full-text available
The European Council has proposed reducing buildings' energy consumption as one way to decarbonization by 2050. Currently, digital twins are used for real-time energy management, but there are discrepancies between predicted and measured energy performance due to uncertainties in building energy models (BEMs). Air leakage is a key parameter that is difficult to obtain and EnergyPlus users often employ a constant value or apply air leakage equations with pre-determined coefficients. This research is a preliminary step in reducing this uncertainty in the author's methodology of BEMs calibration, using EnergyPlus and measured data. The study empirically verifies the ability of the EnergyPlus model's design flow rate to accurately replicate dynamic infiltration values within a zone of a high-rise residential building, where a tracer gas test using and a blower door test were conducted. Three new methods for calculating were developed and evaluated. The results were assessed based on the American Society for Testing Material D5157 (Standard Guide for Statistical Evaluation of Indoor Air Quality Models). The models generated with ad-hoc coefficients were compared to those from the literature (EnergyPlus, DOE-2, and BLAST). Among the models with off-the-shelf coefficients, the one with calculated with in situ data and DOE-2 coefficients demonstrates an accuracy that is only 26% lower than the best model with regression coefficients, which has an R2 value of 0.94 and an NMSE value of 0.02 in the training period.
Article
Full-text available
Passivhaus is an energy performance standard for buildings that has been deeply analyzed in the current scientific literature. However, the study of the Passivhaus standard for components and the use of certified components in the construction of new nearly-zero energy buildings have not been thoroughly discussed. Additionally, hygrothermal performance evaluations of components in accordance with this standard have not been fully presented to the scientific community. This paper addresses this topic and aims to evaluate the hygrothermal performance of a Spanish modular construction system of extruded aluminum, in accordance with the criteria for Passivhaus components, suitable for warm temperate climate. A three-part methodology was implemented, including hygrothermal performance simulations on fourteen connection details comprising wall, roof, window, and floor solutions. The initial outcomes reveal that only four connection details fully meet the Passivhaus criteria for components. Therefore, an optimization of the connection details is proposed to validate the Passivhaus suitability of the construction system. The connection details are redesigned to reduce thermal energy losses in the junctions and to eliminate the risk of interstitial condensation. Several simulation processes are then conducted and the new results are compared against the criteria for components, validating the Passivhaus suitability. The evaluation presented in this paper provided valuable data that enabled to later optimize and submit the construction system to the Passivhaus Institut to become the first lightweight metallic construction system for walls and roofs manufactured in Spain with a Passivhaus certification for warm temperate climate.
Article
Full-text available
The ongoing climate change and policies around it are changing how we design and build homes to meet national carbon emission targets. Some countries such as Scotland are adopting higher-energy-efficient buildings as minimum requirements in the building regulations. While net zero homes might be more energy-efficient and emit fewer operational carbon emissions, we have yet to fully understand the influence on the indoor environment, particularly on indoor air quality (IAQ) and thermal comfort. This study compares the IAQ of three homes in Scotland with equal internal layouts and designs but different building fabrics. The homes represent the minimum Scottish building regulations (2015), the Passivhaus standard and the Scottish 'Gold Standard'. Temperature, relative humidity, PM 2.5 and total volatile organic compounds (tVOC) were measured at five-minute intervals for seven months and compared to occupants' subjective responses to the IAQ. All three homes had temperatures above the recommended thresholds for overheating. Measured hygrothermal conditions were within the ideal range 66.4% of the time in the Passivhaus, 56.4% in the Gold Standard home and 62.7% in the control home. Measured IAQ was better in homes with higher energy efficiency, particularly tVOC. For instance, indoor PM 2.5 in the Passivhaus were 78.0% of the time below the threshold, while in the standard home the figure was 51.5%, with a weak correlation with outdoor PM 2.5 (Passivhaus: B r s = 0.167, K r s = 0.306 and L r s = 0.163 (p < 0.001); Gold: B r s = −0.157, K r s = 0.322 and L r s = 0.340 (p < 0.001); Control: B r s = −0.111, K r s = 0.235 and L r s = 0.235 (p < 0.001)). TVOCs in the Passivhaus were 81.3%, while in the control home they were 55.0%. While the results cannot be generalised, due to the small sample, this study has significant policy implications, particularly in Scotland, exhibiting the importance of IAQ in current building legislation and sustainable assessment methods.
Article
Full-text available
Enhanced energy conservation strategies often involve tightly controlled ventilation flow rates. However, strategies that don't carefully consider ventilation rates can, in certain contexts, result in inadequate ventilation, with increased risks of poor indoor environmental quality and user acceptance. These design challenges are often exacerbated in non-domestic buildings with highly dynamic occupancy patterns. This study used computational fluid dynamics, supported by field measurements, to investigate the relationship between zonal supply air strategies and thermal comfort in the George Davies Centre, Leicester University, which is the largest non-domestic certified Passivhaus building in the UK. Ventilation strategies involving mechanical ventilation operating with heat recovery turned on and off, and natural ventilation systems were investigated in relation to their ability to maintain thermal comfort in an auditorium space characterised by high internal heat gains and tiered seating. The results show that, depending on the selected thermal comfort criterion, a thermally comfortable environment could be achieved when incoming air is in the range of 9–26 °C for mechanical ventilation with heat recovery and 17–29 °C for natural ventilation. These temperatures are referred to as ‘limiting operating temperatures’ in the paper. The work showed that in a temperate climate, thermal comfort could be maintained, for up to 80% of the year, using mixed mode ventilation, without space conditioning, in combination with intelligent design and control strategies. Operating in natural ventilation mode also provided increased fresh air supply capacity, a finding which is particularly relevant in the context of mitigating airborne viral transmission.
Article
Air infiltration rate is one of the fundamental parameters in the design and analysis of building environment, which is the fundamental mode of air exchange between indoor and outdoor in non-mechanically ventilated residences when doors and windows are closed. Most Chinese residential buildings have no mechanical ventilation equipment installed. Previous researches on Chinese housing have primarily focused on urban residences. However, the number of both urban households and rural households accounts for almost half of Chinese households. Considering the significant urban-rural differences in Chinese housing, there is an urgent need for researching the air infiltration rate in rural area. This study employed a multi-zone network airflow model approach to simulate the air infiltration rate of 111 rural residential samples in 13 Chinese provinces, obtaining the hour-by-hour results for a whole typical weather year of each sample. Thus, the distributions of air infiltration rate for each rural region were finally summarized. Additionally, we performed field measurements in 23 samples to validate the simulation results. According to the results, the mean value of air infiltration rate is larger than that of urban residences, and its distribution in each climatic zone generally follows a log-normal distribution. The results are expected to be applied for indoor air quality studies, building energy consumption analysis, and other frontiers related to architectural environmental design and analysis.
Article
The process of determining the appropriate systems to be replaced as part of a building renovation can pose significant challenges in the decision-making phase. These challenges often include financial restrictions, thermal comfort maintenance, and environmental mitigation. Forecasting these factors will therefore enable the design of more efficient and sustainable buildings. This study proposes a simulation-based multi-objective optimization methodology to explore the optimal building envelope design according to economic, environmental, and thermal comfort criteria. The retrofit evaluation and optimization approach developed is applied to a classroom building, and the investigation is carried out in six different climates corresponding to six locations in Morocco. The considered design features are the decision variables related to the building envelope components and are derived from a preliminary analysis conducted using a bioclimatic chart implemented in the Climate Consultant 6.0 environmental program for six locations. The selected design variables include walls and roof compositions, window glazing type, windows-to-wall ratio (WWR), and window shading. Three objective functions are considered to be minimized in this work, including life cycle cost (LCC), life cycle CO2 (LCCO2), and thermal discomfort hours (Tdh). The dynamic building simulation software TRNSYS and the free generic optimization tool GENOPT are coupled to accomplish the multi-objective optimization approach. Simulation results revealed that there is a unique set of values of optimal solutions for each climate zone. Based on the evaluated trade-offs between different criteria, optimum solutions lead to potential reductions of 18–14 % in life cycle cost saving index (LCCSI), 20–26 % in life cycle CO2 saving index (LCCO2 SI), and 21–11 % in thermal discomfort hours saving index (TdhSI) according to the climate type. Moreover, implementing the optimum solutions leads to a payback period ranging from 6 to 8.5 years depending on climate type.
Article
Understanding the thermal performance of window units is of utmost importance for the advancement of energy-efficient building design. Thermal transmittance (U-factor) is one of the most important indicators of a window system's efficiency, especially in colder climates. Presently, the Window U-factor is typically calculated using one of two standard approaches: experimental methods and computational modeling both having significant limitations. This makes it crucial to develop methods that can calculate the thermal performance of windows in the field and more on already installed windows. This research introduces a data-driven approach to calculating the U-factor of double-glazed windows filled with and without inert gases. The study is confined to double-glazed windows containing either air or a defined percentage of inert gases (75 % Argon, 85 % Argon, and 95 % Argon). The study reveals that the center of glazing, due to its prominence in window construction, plays a significant role in determining the window's thermal attributes. It also establishes a correlation between glass emissivity and center of glass U-factor (thermal transmittance). Furthermore, our developed data-driven approach exhibits considerable reliability in calculating the thermal transmittance of double-glazed windows, as validated by comparison with industry-standard NFRC 100-certified U-factor values. The insights garnered from this research contribute significantly to the understanding of double-glazed window design and the development of more energy-efficient fenestration products. It provides a robust foundation for industry professionals aiming to reduce energy consumption and work towards a sustainable future.