Fire Tests of Load-Bearing, Light-Steel-Framed Wall Systems Insulated with Polyurethane Foam

MDPI
Applied Sciences
Authors:
  • University of Zagreb Faculty of Civil Engineering
  • University of Zagreb Faculty of Civil Engineering

Abstract and Figures

This paper presents the details of three fire tests conducted on light-steel-framed (LSF), load-bearing wall systems, which consist of polyurethane insulation injected into the cavities of the steel frame between two or three layers of gypsum fibreboard. To investigate the thermal and structural performance limits under standard fire conditions, observations were made during the tests, and temperatures and vertical displacements were recorded. Although combustible insulation was used, the results obtained are promising for the application of studied LSF wall systems in buildings, where fire resistance of more than 60 min is required.
This content is subject to copyright.
Citation: Jelˇci´c Rukavina, M.; Skeji´c,
D.; Milovanovi´c, B.; Ўcapec, T. Fire
Tests of Load-Bearing, Light-Steel-
Framed Wall Systems Insulated with
Polyurethane Foam. Appl. Sci. 2024,
14, 637. https://doi.org/10.3390/
app14020637
Academic Editor: Asterios Bakolas
Received: 26 November 2023
Revised: 4 January 2024
Accepted: 9 January 2024
Published: 11 January 2024
Copyright: © 2024 by the authors.
Licensee MDPI, Basel, Switzerland.
This article is an open access article
distributed under the terms and
conditions of the Creative Commons
Attribution (CC BY) license (https://
creativecommons.org/licenses/by/
4.0/).
applied
sciences
Article
Fire Tests of Load-Bearing, Light-Steel-Framed Wall Systems
Insulated with Polyurethane Foam
Marija Jelˇci´c Rukavina 1,* , Davor Skeji´c 2, Bojan Milovanovi´c 1and Tomislav Ўcapec 3
1Department of Materials, Faculty of Civil Engineering, University of Zagreb, Fra Andrije Kaˇci´ca Mioši´ca 26,
10 000 Zagreb, Croatia; bojan.milovanovic@grad.unizg.hr
2
Department for Structures, Faculty of Civil Engineering, University of Zagreb, Fra Andrije Kaˇci´ca Mioši´ca 26,
10 000 Zagreb, Croatia; davor.skejic@grad.unizg.hr
3Laboratory for Thermal Measurements, Stubiˇcka Slatina 26, 49 243 Oroslavje, Croatia; tscapec95@gmail.com
*Correspondence: marija.jelcic.rukavina@grad.unizg.hr
Abstract: This paper presents the details of three fire tests conducted on light-steel-framed (LSF),
load-bearing wall systems, which consist of polyurethane insulation injected into the cavities of
the steel frame between two or three layers of gypsum fibreboard. To investigate the thermal and
structural performance limits under standard fire conditions, observations were made during the
tests, and temperatures and vertical displacements were recorded. Although combustible insulation
was used, the results obtained are promising for the application of studied LSF wall systems in
buildings, where fire resistance of more than 60 min is required.
Keywords: light-steel-frame walls; fire tests; polyurethane thermal insulation; gypsum fibre boards;
high temperatures; fire resistance ratings
1. Introduction
Light-steel framing (LSF) is a drywall system that offers high architectural flexibility,
lower construction and transportation costs, reduced weights, the possibility of recycling
and reuse, and at the same time high mechanical strength and stability [
1
,
2
]. LSF systems
are manufactured as both load-bearing and non-load-bearing construction elements and
are available in a wide range of compositions. The disadvantages of these systems are
the lack of adaptability in situations where on-site adaptation is required, the low thermal
mass, the higher maintenance costs, the limited number of storeys, the risk of corrosion
of the metal elements due to condensation and possible air and water infiltration, the
high thermal conductivity of the steel parts and fire behaviour [
3
]. The system consists of
three main components: cold-formed steel structure (studs and tracks), sheathing boards
(wallboards) and thermal insulation, each of which has its own function as an integral
part of the system [
1
]. Other materials are necessary, such as screws, membranes for
waterproofing and air tightness, and finishing layers. The cold-formed steel structure
forms the skeleton of the system and provides stability and rigidity, which is protected
by the sheathing. The thermal insulation serves to prevent heat loss and provide the
necessary thermal comfort. The fire resistance of LSF wall systems is an important factor
in preventing the spread of fire and eventually the collapse of the building in case of fire
occurrence. Although it can be determined by fire testing or modelling, in most cases, it is
determined by fire tests in which a specimen is subjected to a standardized fire load, usually
represented by the ISO standard curve [
4
]. According to the test results, the specimen is
assigned a fire resistance rating (FRR) based on the failure time evaluated according to
the three criteria of structural stability, insulation and integrity [
5
,
6
]. Structural failure of
load-bearing LSF systems under fire conditions is primarily due to the reduction in the
mechanical properties of the steel frame, where at a temperature of 550
C, only about 60%
of the original yield strength of the steel is maintained [
7
]. The FRR of LSF wall systems is
Appl. Sci. 2024,14, 637. https://doi.org/10.3390/app14020637 https://www.mdpi.com/journal/applsci
Appl. Sci. 2024,14, 637 2 of 18
affected by many factors, such as configuration (number and type of applied wallboards,
type and position of insulation material), geometry (stud spacing) and load ratio [
8
,
9
].
Of the factors mentioned, the type of wallboards and the type and position of insulation
play a decisive role [
10
]. The wallboards protect the steel frame from direct fire exposure
and delay temperature development [
5
]. Elevated thermal properties of various wallboards
that can be used in LSF structures have been studied as an indication of their behaviour
under fire exposure. As an example, Steau and Mahendran [
11
] studied gypsum boards
(GBs), calcium silicate boards (CaSiBs), magnesium oxide boards (MgOBs), perlite boards
(PBs), and structural plywood (PW), while Gnanachelvam et al. [
12
] investigated GBs,
PCM-gypsum boards (PCMBs), magnesium sulphate boards (MgSO4Bs) and fibre cement
boards (FBs). The results revealed that GBs exhibited the least mass loss when exposed
to elevated fire temperatures, which has the potential to maintain a higher FRR of LSF
structures than those with other type of wallboards. Furthermore, the addition of fibres in
GBs could potentially lead to better FRR by preventing cracking during fire exposure [
13
].
Other benefits of GBs are ease of fabrication and the widespread availability of the primary
material for its production [
14
]. Kodur and Sultan [
9
] determined that a layer of 15.9 mm
thick GB on an uninsulated load-bearing wall gives an FRR of 35 min, while two layers of
12.5 mm thick GB give an FRR of 100 min. This means that the FRR of LSF constructions
can be significantly increased by adding multiple layers of wallboards rather than just
increasing the thickness of the wallboard, due to the staggered positions of the wallboard
joints of the two applied layers which are often the weak point on wallboards. When the
first joint on the exposed layer opens, underneath is usually a continuous layer which
offers protection for a certain period of time. Due to the current trend in the construction
industry to improve the energy efficiency of new and existing buildings, the use of thermal
insulation in LSF structures is mandatory. Depending on the location of the insulation,
LSF structures are defined as: (a) cold-framed structures, where the insulation is located
in the cavity, (b) warm-framed structures, where the insulation is located entirely on the
exterior and (c) hybrid structures, which are a combination of cold- and warm-framed
structures [
1
,
15
]. Thermal insulation positioned in the cavity of load-bearing LSF structures
tends to lower FRR, as shown in the studies of Kodur and Sultan [
9
], Ariyanayagam and
Mahendran [16,17] and Alfawakhiri and Sultan [18]. Due to the low thermal conductivity
of the insulation, a thermal barrier is formed, which leads to non-uniform heating of the
LSF members [
19
]. This creates a high temperature gradient between the exposed and
unexposed sides of the LSF structure. Since one side of the steel structure is heated much
more than the other, structural failure of the load-bearing structure occurs. Studies on this
topic have shown that externally insulated load-bearing LSF assemblies have better fire
performance [
8
,
20
], but the disadvantage of such structures is the more complicated assem-
bly process and the greater thickness of the element which makes the net floor area of such
buildings smaller. A literature review revealed that most studies focused on the FRR of LSF
constructions insulated with non-combustible (glasswool, rockwool and cellulose fibres
in most cases [
1
,
15
]) thermal insulation, because organic polymeric insulation materials
tend to increase fire intensity. However, the use of these materials is problematic where
there is a risk of condensation and increased exposure to moisture. If water penetrates
the system, these materials absorb the moisture, which increases the thermal conductiv-
ity of the material, reduces its insulating properties and potentially increases the risk of
corrosion of metal elements in LSF systems. With respect to organic combustible thermal
insulation, Gnanachelvam et al. [
21
] investigated LSF walls with PCM-mat in the cavity
and concluded that such materials lined with fire-rated wallboards do not contribute to
the fire load. LSF system with other combustible insulation materials, especially polymers,
are scarcely studied for their FRR although because the low thermal resistance value they
could provide good thermal properties at ambient temperatures. In recent decades, rigid
polyurethane foam (PUR) in particular has been used together with other materials to
obtain composites with low weight, good heat resistance, high toughness and ductility,
high impact resistance, efficient sound insulation and excellent mechanical properties [
22
].
Appl. Sci. 2024,14, 637 3 of 18
On the other hand, when used in high temperature environments, PUR foams are very
combustible polymers with rapidly spreading flames, high thermal emissions and smoke
generation [
23
25
]. When PUR foam is exposed to elevated heat, the chemical bonds
generally break down, producing volatile gases that ignite when combined with oxygen.
During this process, the PUR first softens and then decomposes, which manifests itself
as charring. Due to the increased heat during combustion, the chemical links are further
broken down and ignite until only char remains. The ignition and decomposition of PUR
foam has been intensively studied and well described in the relevant literature [
23
26
].
Depending on the test method used, the heating rate of the sample, the air flow and the
weight loss, the ignition and decomposition temperatures for polyurethane foams are
between 260
C and 500
C and between 400 and 650
C, respectively [
24
]. The combustion
of PUR produces large quantities of smoke that obstruct visibility, with carbon monoxide
and hydrogen cyanide being the most important toxic combustion products. The addition
of flame retardants causes PUR to form a small protective layer of charcoal on the mate-
rial [
27
,
28
], which can have a positive effect on fire behaviour for a certain period of time.
Flame retardants have an influence on the smoke and toxicity development of PUR.
There are some contradictions in the literature regarding the effect of flame retardants
on the overall toxicity of PUR foams [
25
]. A literature search revealed only one study that
addressed the fire performance of assemblies with PUR foam and gypsum fibreboards in
the form of structurally insulated panels (SIPs) [
29
], which showed that that such assemblies
can only withstand 30 min of fire exposure. In the scientific project “Composite Light Steel
Framed Panel with an Integrated Load-bearing Structure”, led by the University of Zagreb,
Faculty of Civil Engineering, and industry partners, an innovative load-bearing LSF system
has been developed to improve construction speed and energy efficiency. In addition
to lightweight steel members, the LSF system consists of gypsum fibreboards (GFBs) as
sheathing and PUR foam as thermal cavity insulation. Furthermore, spacers are added to
physically separate the wallboards from the steel members and, consequently, reduce the
thermal bridging effect. The idea behind the development of such an LSF system with the
chosen components is described in our previous paper [
30
]. In the current paper, the details
of the experimental study on the fire resistance of the aforementioned LSF wall systems
exposed to the standard ISO 834 are presented. For this purpose, three test specimens were
made from the same components differing only in the number (double and triple) and type
of gypsum fibreboards (regular—A2 board, and with improved fire properties—A1 board).
2. Experimental Study
2.1. Test Specimen Components and Construction
The experimental study was conducted on three load-bearing LSF wall panel spec-
imens consisting of a steel frame, PUR foam as cavity thermal insulation and GFBs as
sheathing wallboards. The dimensions of the specimens were 1.5 m wide and 3.0 m high.
The members of the steel frame steel (studs, tracks and noggings), consisted of 0.95 mm
thick C-sections with dimensions of 89
×
42
×
10 mm. The C-sections were made of S550
GD steel sheets. A total of four studs (labelled S1, S2, S3 and S4) with a length of 2995 mm,
two tracks (labelled T1 and T2), and two noggings (labelled N1 and N2) with a length of
1500 mm were used to construct the steel frame, as shown in Figure 1b.
The studs were located at 486 mm from the centre axis off-centre, while the noggings
were located 984 mm off-centre from the top and bottom tracks. A total of 16 nodes (numbered
1–16 in Figure 1a) were formed. The members of the steel frame were fixed with self-tapping
flat-head screws with dimensions 6
×
19 mm and a diameter of 3.5 mm. To ensure the physical
distance between the inner sheathing wallboards and the steel frame, 6 steel Z shaped spacers
(Figure 1b) were placed on both sides of the specimen at certain positions along the length of
studs S2 and S3 and noggings N1 and N2. The spacers were made of the same type of steel as
all other steel members.
Appl. Sci. 2024,14, 637 4 of 18
Appl. Sci. 2024, 14, x FOR PEER REVIEW 4 of 19
Figure 1. Layout of the LSF wall frame and characteristic connection details: (a) steel frame; (b) Z-
shaped spacers near the node, (c) cut-out of the steel frame. Red circles numbered 1–16 indicate the
16 nodes formed in the steel frame.
The studs were located at 486 mm from the centre axis o-centre, while the noggings
were located 984 mm o-centre from the top and boom tracks. A total of 16 nodes (num-
bered 1–16 in Figure 1a) were formed. The members of the steel frame were xed with
self-tapping at-head screws with dimensions 6 × 19 mm and a diameter of 3.5 mm. To
ensure the physical distance between the inner sheathing wallboards and the steel frame,
6 steel Z shaped spacers (Figure 1b) were placed on both sides of the specimen at certain
positions along the length of studs S2 and S3 and noggings N1 and N2. The spacers were
made of the same type of steel as all other steel members.
The steel frame was lined on both sides with two or three layers of GFBs, respectively.
Two types of 12.5 mm GFBs were used from the same manufacturer (James Hardie Europe
GmbH, Düsseldorf, Germany), GFB with density 1150 ± 50 kg/m
3
and reaction to re A2,
s1-d0 [31], A2 GFB onwards, and GFB with improved re properties (density 1250 ± 50
and reaction to re A1 [32]), A1 GFB onwards. Two of the specimens (designated as Spec-
imen P1 and Specimen P2, Figure 2a) were of the same composition, double-lined on both
sides with A1 GFB, while one specimen (designated as Specimen 3, Figure 2b) was triple-
lined with an outer layer of A1 GFB and two inner layers of A2 GFB. A2 GFBs are shown
in green, while the A1 GFBs are shown in light orange.
(a)
(b)
Figure 1. Layout of the LSF wall frame and characteristic connection details: (a) steel frame;
(b) Z-shaped spacers near the node, (c) cut-out of the steel frame. Red circles numbered 1–16
indicate the 16 nodes formed in the steel frame.
The steel frame was lined on both sides with two or three layers of GFBs, respectively.
Two types of 12.5 mm GFBs were used from the same manufacturer (James Hardie Europe
GmbH, sseldorf, Germany), GFB with density 1150
±
50 kg/m
3
and reaction to fire A2,
s1-d0 [
31
], A2 GFB onwards, and GFB with improved fire properties (density 1250
±
50 and
reaction to fire A1 [
32
]), A1 GFB onwards. Two of the specimens (designated as Specimen P1
and Specimen P2, Figure 2a) were of the same composition, double-lined on both sides with
A1 GFB, while one specimen (designated as Specimen 3, Figure 2b) was triple-lined with an
outer layer of A1 GFB and two inner layers of A2 GFB. A2 GFBs are shown in green, while
the A1 GFBs are shown in light orange.
Appl. Sci. 2024, 14, x FOR PEER REVIEW 4 of 19
Figure 1. Layout of the LSF wall frame and characteristic connection details: (a) steel frame; (b) Z-
shaped spacers near the node, (c) cut-out of the steel frame. Red circles numbered 1–16 indicate the
16 nodes formed in the steel frame.
The studs were located at 486 mm from the centre axis o-centre, while the noggings
were located 984 mm o-centre from the top and boom tracks. A total of 16 nodes (num-
bered 1–16 in Figure 1a) were formed. The members of the steel frame were xed with
self-tapping at-head screws with dimensions 6 × 19 mm and a diameter of 3.5 mm. To
ensure the physical distance between the inner sheathing wallboards and the steel frame,
6 steel Z shaped spacers (Figure 1b) were placed on both sides of the specimen at certain
positions along the length of studs S2 and S3 and noggings N1 and N2. The spacers were
made of the same type of steel as all other steel members.
The steel frame was lined on both sides with two or three layers of GFBs, respectively.
Two types of 12.5 mm GFBs were used from the same manufacturer (James Hardie Europe
GmbH, Düsseldorf, Germany), GFB with density 1150 ± 50 kg/m
3
and reaction to re A2,
s1-d0 [31], A2 GFB onwards, and GFB with improved re properties (density 1250 ± 50
and reaction to re A1 [32]), A1 GFB onwards. Two of the specimens (designated as Spec-
imen P1 and Specimen P2, Figure 2a) were of the same composition, double-lined on both
sides with A1 GFB, while one specimen (designated as Specimen 3, Figure 2b) was triple-
lined with an outer layer of A1 GFB and two inner layers of A2 GFB. A2 GFBs are shown
in green, while the A1 GFBs are shown in light orange.
(a)
(b)
Figure 2. Wall configurations used in the fire tests: (a) Cross section of the double lined specimens
(P1 and P2); (b) cross section of triple lined specimen (P3).
Three differently cut pieces with approximate dimensions of 500
×
1990 mm,
1000
×
1990 mm and 1005
×
1500 mm were used for each layer of the sheathing, as
shown in Figure 3.
Appl. Sci. 2024,14, 637 5 of 18
Appl. Sci. 2024, 14, x FOR PEER REVIEW 5 of 19
Figure 2. Wal l co ngurations used in the re tests: (a) Cross section of the double lined specimens
(P1 and P2); (b) cross section of triple lined specimen (P3).
Three dierently cut pieces with approximate dimensions of 500 × 1990 mm, 1000 ×
1990 mm and 1005 × 1500 mm were used for each layer of the sheathing, as shown in
Figure 3.
Figure 3. GFB wallboard lining conguration. The red box indicates the wallboard conguration
for double-lined, while blue box for triple-lied LSF walls.
The layout of the ambient side wallboard is a mirror image of the re-side wall-
boards. The joints of the base layer boards (GFB2, GFB3 for double-lined specimens and
GFB3 and GFB4 for triple-lined specimens) were secured with mesh and paper tape and
lled with the reproof joint ller. In addition, joints, screw holes and the wallboard strips
on S1, S4, N1 and N2 were coated with a thin layer of reproof joint ller. After lining the
steel structure, the cavity of the panel was lled with a two-component PUR foam with
the following properties: density 45 kg/m3 with a tolerance of ±5%, thermal conductivity
in the range of 0.020–0.023 W/mK and reaction to re class E according to the manufac-
turers specications. Injection of PUR into the test specimens was performed with a low-
pressure injector at a pressure of 510 bar and was completed within an hour for each
specimen.
2.2. Thermocouple Arrangement
K-type thermocouples (NiCr-Ni) were installed on the ambient side of the wall pan-
els in accordance with EN 1365-1 [33]. Additional thermocouples of the same type were
installed, before lling the cavity with PUR foam, for monitoring the temperature devel-
opment throughout the test panel—horizontally at three positions (A, B and C) at two
heights, 1600–1650 mm (low, LT) and 2500–2550 mm (high, HT) from the boom track, as
shown in Figure 4a. Through the cross sections of the tested panels, the thermocouples
were placed as follows (Figure 4b,c):
1. Between wallboard layers on both sides (ambient and re side)labelled 1, 2, 6 and
7 for double-lined specimens and 1, 2, 3, 7, 8 and 9 for triple-lined specimens.
2. On the hot and cold anges and on the web of the lipped channel, C-shaped steel
studs—marked 3, 4 and 5 for double-lined specimens and 4, 5 and 6 for triple-lined
specimens.
Figure 3. GFB wallboard lining configuration. The red box indicates the wallboard configuration for
double-lined, while blue box for triple-lied LSF walls.
The layout of the ambient side wallboard is a mirror image of the fire-side wallboards.
The joints of the base layer boards (GFB2, GFB3 for double-lined specimens and GFB3
and GFB4 for triple-lined specimens) were secured with mesh and paper tape and filled
with the fireproof joint filler. In addition, joints, screw holes and the wallboard strips on
S1, S4, N1 and N2 were coated with a thin layer of fireproof joint filler. After lining the
steel structure, the cavity of the panel was filled with a two-component PUR foam with the
following properties: density 45 kg/m
3
with a tolerance of
±
5%, thermal conductivity in
the range of 0.020–0.023 W/mK and reaction to fire class E according to the manufacturer’s
specifications. Injection of PUR into the test specimens was performed with a low-pressure
injector at a pressure of 5–10 bar and was completed within an hour for each specimen.
2.2. Thermocouple Arrangement
K-type thermocouples (NiCr-Ni) were installed on the ambient side of the wall pan-
els in accordance with EN 1365-1 [
33
]. Additional thermocouples of the same type were
installed, before filling the cavity with PUR foam, for monitoring the temperature develop-
ment throughout the test panel—horizontally at three positions (A, B and C) at two heights,
1600–1650 mm (low, LT) and 2500–2550 mm (high, HT) from the bottom track, as shown in
Figure 4a. Through the cross sections of the tested panels, the thermocouples were placed
as follows (Figure 4b,c):
1.
Between wallboard layers on both sides (ambient and fire side)—labelled 1, 2, 6 and 7
for double-lined specimens and 1, 2, 3, 7, 8 and 9 for triple-lined specimens.
2.
On the hot and cold flanges and on the web of the lipped channel, C-shaped steel studs
marked 3, 4 and 5 for double-lined specimens and 4, 5 and 6 for triple-lined specimens.
A total of 42 thermocouples were installed in double-lined specimens and 54 in the
triple-lined specimen. The thermocouples were welded to copper disks with a diameter
of 12.0 mm and a thickness of 0.2 mm. The furnace temperature was measured using six
K-type plate thermocouples symmetrically placed inside the furnace chamber at about
100 mm from the exposed surface of the specimen in accordance with EN 1363-1 [34].
Appl. Sci. 2024,14, 637 6 of 18
Appl. Sci. 2024, 14, x FOR PEER REVIEW 6 of 19
(a)
(b)
(c)
Figure 4. Thermocouple positions through the cross-sections of the specimens: (a) Front side of the
test specimens; (b) cross-sections of specimens P1 and P2; (c) cross-section of specimen P3.
A total of 42 thermocouples were installed in double-lined specimens and 54 in the
triple-lined specimen. The thermocouples were welded to copper disks with a diameter
of 12.0 mm and a thickness of 0.2 mm. The furnace temperature was measured using six
K-type plate thermocouples symmetrically placed inside the furnace chamber at about 100
mm from the exposed surface of the specimen in accordance with EN 1363-1 [34].
2.3. Test Set-Up and Fire Test Methodology
The opening of the furnace was 3.0 m wide and 3.0 m high and the additional width
of the furnace opening was lled with non-combustible autoclaved aerated concrete
(AAC) blocks and ceramic wool (with a density of 130 kg/m3 and a thickness of 25.4 mm)
on both sides of the test specimen. Figure 5 shows the specimen test set-up.
Figure 4. Thermocouple positions through the cross-sections of the specimens: (a) Front side of the
test specimens; (b) cross-sections of specimens P1 and P2; (c) cross-section of specimen P3.
2.3. Test Set-Up and Fire Test Methodology
The opening of the furnace was 3.0 m wide and 3.0 m high and the additional width
of the furnace opening was filled with non-combustible autoclaved aerated concrete (AAC)
blocks and ceramic wool (with a density of 130 kg/m
3
and a thickness of 25.4 mm) on both
sides of the test specimen. Figure 5shows the specimen test set-up.
Appl. Sci. 2024,14, 637 7 of 18
The specimen was loaded with a specially designed beam providing a total load of 22.5 kN,
i.e., a uniform load of 15 kN/m on the top of the specimen. The load was applied to the beam
20 min before the start of the test using hydraulic jacks and maintained throughout the test. The
bottom of the specimen was secured with bolts that connected the specimen to a reinforced
concrete slab. The specimen was unloaded when a steep increase in displacement was observed,
and the structure tended to collapse. As combustible thermal insulation was used in specimens,
the complete collapse of the specimen could damage the test equipment and endanger the safety
of the laboratory personnel. The burners of the furnace were turned off with the delay after
unloading when the rapid increase in temperatures of steel members was observed. The vertical
deformations of the specimens were measured using displacement transducers placed at the top
of the specimen, between the load beam and the fixed frame, recoding the distances between
the load beam and the fixed frame. The changes in this distance correspond to the measured
verticaldisplacements of the specimen. In addition, thermographic measurements were taken
with an imaging camera during the fire test of specimen P1 to record the heat evolution on the
whole unexposed side, which allowed a better understanding of the failure mode. The target fire
curve was set in accordance with EN 1363-1 [
34
] using 6 radiant burners. The air temperature
in the test area was maintained at 20 (
±
5)
C for 24 h prior to the fire test. The temperature
readings of the thermocouples and the vertical displacements of the specimens were taken at
1 min intervals.
Appl. Sci. 2024, 14, x FOR PEER REVIEW 7 of 19
Figure 5. Specimen set-up in the testing furnace.
The specimen was loaded with a specially designed beam providing a total load of
22.5 kN, i.e., a uniform load of 15 kN/m on the top of the specimen. The load was applied
to the beam 20 min before the start of the test using hydraulic jacks and maintained
throughout the test. The boom of the specimen was secured with bolts that connected
the specimen to a reinforced concrete slab. The specimen was unloaded when a steep in-
crease in displacement was observed, and the structure tended to collapse. As combustible
thermal insulation was used in specimens, the complete collapse of the specimen could
damage the test equipment and endanger the safety of the laboratory personnel. The burn-
ers of the furnace were turned o with the delay after unloading when the rapid increase
in temperatures of steel members was observed. The vertical deformations of the speci-
mens were measured using displacement transducers placed at the top of the specimen,
between the load beam and the xed frame, recoding the distances between the load beam
and the xed frame. The changes in this distance correspond to the measured vertical dis-
placements of the specimen. In addition, thermographic measurements were taken with
an imaging camera during the re test of specimen P1 to record the heat evolution on the
whole unexposed side, which allowed a beer understanding of the failure mode. The
target re curve was set in accordance with EN 1363-1 [34] using 6 radiant burners. The
air temperature in the test area was maintained at 20 5) °C for 24 h prior to the re test.
The temperature readings of the thermocouples and the vertical displacements of the
specimens were taken at 1 min intervals.
3. Test Observations and Results
The obtained results, which are composed of the observations during the tests as well
as of the timetemperature and vertical displacement proles, are presented separately
for each tested specimen in the next Sections 3.1–3.3. Since all tested specimens showed a
similar appearance at the end of the test, the observations for all three specimens are pre-
sented in Section 3.4.
3.1. Specimen P1
Specimen P1 consisted of double A1 gypsum bre-boards on both sides. It was un-
loaded at the 67th minute because, as will be shown later, there was a threat of possible
structural collapse. No smoke, ames, discolouration or cracks were observed on the am-
bient side of the specimen by the end of the test, indicating that the integrity failure crite-
rion in accordance with EN 13501-2 [6] for FRR was not achieved. The temperature–time
prole obtained in the furnace can be seen in Figure 6a,b and agrees well with the standard
re curve within the limits prescribed by EN 1363-1 [34]. Temperatures through the cross-
section are presented as average values measured on thermocouples placed at the same
Figure 5. Specimen set-up in the testing furnace.
3. Test Observations and Results
The obtained results, which are composed of the observations during the tests as well
as of the time–temperature and vertical displacement profiles, are presented separately
for each tested specimen in the next Sections 3.13.3. Since all tested specimens showed
a similar appearance at the end of the test, the observations for all three specimens are
presented in Section 3.4.
3.1. Specimen P1
Specimen P1 consisted of double A1 gypsum fibre-boards on both sides. It was unloaded
at the 67th minute because, as will be shown later, there was a threat of possible structural
collapse. No smoke, flames, discolouration or cracks were observed on the ambient side of
the specimen by the end of the test, indicating that the integrity failure criterion in accordance
with EN 13501-2 [
6
] for FRR was not achieved. The temperature–time profile obtained in the
furnace can be seen in Figure 6a,b and agrees well with the standard fire curve within the limits
prescribed by EN 1363-1 [
34
]. Temperatures through the cross-section are presented as average
values measured on thermocouples placed at the same height: upper (2500–2550 mm, HT) in
Figure 6a and lower (1600–1650 mm, LT) in Figure 6b. As shown in Figure 6a, the temperature
between the two wallboards (thermocouple P1-HT1) remained below 100
C (temperature
Appl. Sci. 2024,14, 637 8 of 18
plateau) for a period of about 20 min after the start of the test when the temperature in the
furnace had already reached about 800
C. This delay in the temperature rise was due to
the dehydration process of free and bound water in the GFBs [
35
,
36
]. After 20 min of fire
exposure, the temperature recorded at thermocouple P1-HT1 increased significantly and
reached maximum value of 746
C in the 80th minute (the burners had already been turned
off). At the position between the second wallboard and the PUR foam (thermocouple P1-
HT2), the delay in the temperature rise extended to around 48 min of fire exposure, when
the temperature started to continuously increase up to the end of the test. Temperatures at
the steel sections (thermocouples P1-HT3, P1-HT4 and P1-HT5) began to rise steeply about
60 min after the start of the test, reaching 117
C, 80
C and 63
C at the time of specimen
unloading, and 665
C, 442
C and 302
C in the 90th minute at the hot flange, web and cold
flange, respectively. Compared to the temperature profiles obtained at the upper position,
the average temperatures recorded at the lower positions (LTs—see Figure 6b) are similar up
to the 50th minute of fire exposure when the steeper temperature rise at all thermocouple
positions was observed. When the specimen was unloaded (67th min), temperatures of 722
C,
539
C and 115
C were recorded at the hot flange, web and cold flange, respectively, while
the maximum temperatures were recorded after the burners were turned off and were 818
C,
842
C and 724
C respectively. These temperatures indicate that the recrystallization point
of the steel was reached, which would result in significant deformation and loss of (local)
structural stability of the steel members.
Appl. Sci. 2024, 14, x FOR PEER REVIEW 8 of 19
height: upper (2500–2550 mm, HT) in Figure 6a and lower (1600–1650 mm, LT) in Figure
6b. As shown in Figure 6a, the temperature between the two wallboards (thermocouple
P1-HT1) remained below 100 °C (temperature plateau) for a period of about 20 min after
the start of the test when the temperature in the furnace had already reached about 800
°C. This delay in the temperature rise was due to the dehydration process of free and
bound water in the GFBs [35,36]. After 20 min of re exposure, the temperature recorded
at thermocouple P1-HT1 increased signicantly and reached maximum value of 746 °C in
the 80th minute (the burners had already been turned o). At the position between the
second wallboard and the PUR foam (thermocouple P1-HT2), the delay in the temperature
rise extended to around 48 min of re exposure, when the temperature started to contin-
uously increase up to the end of the test. Temperatures at the steel sections (thermocouples
P1-HT3, P1-HT4 and P1-HT5) began to rise steeply about 60 min after the start of the test,
reaching 117 °C, 80 °C and 63 °C at the time of specimen unloading, and 665 °C, 442 °C
and 302 °C in the 90th minute at the hot ange, web and cold ange, respectively. Com-
pared to the temperature proles obtained at the upper position, the average temperatures
recorded at the lower positions (LTssee Figure 6b) are similar up to the 50th minute of
re exposure when the steeper temperature rise at all thermocouple positions was ob-
served. When the specimen was unloaded (67th min), temperatures of 722 °C, 539 °C and
115 °C were recorded at the hot ange, web and cold ange, respectively, while the max-
imum temperatures were recorded after the burners were turned o and were 818 °C, 842
°C and 724 °C respectively. These temperatures indicate that the recrystallization point of
the steel was reached, which would result in signicant deformation and loss of (local)
structural stability of the steel members.
(a) (b)
(c) (d)
Figure 6. Fire test results for specimen P1: (a) average temperatures at high position (HTs); (b) aver-
age temperatures at low position (LTs); (c) temperature proles at the unexposed side of the speci-
men; (d) average vertical displacement and displacement rate.
Figure 6. Fire test results for specimen P1: (a) average temperatures at high position (HTs);
(b) average temperatures at low position (LTs); (c) temperature profiles at the unexposed side of the
specimen; (d) average vertical displacement and displacement rate.
Figure 6c presents the individual and the average temperatures on the unexposed side
of the tested wall indicating that the insulation failure criterion (average temperature rise of
140
C and 180
C on individual thermocouples, respectively) according to EN 13501-2 [
6
]
Appl. Sci. 2024,14, 637 9 of 18
was not reached. The highest average temperature was 61
C and the highest individual
temperature was 86
C observed after the burners were turned off. As Figure 6d shows, the
specimen deformed continuously from the 15th minute until the unloading. From the 15th
to the 25th minute, there was a sudden increase in deformations, followed by a stable phase.
During this period, the temperatures at the exposed specimen side (P1-HT1 and P1-LT1)
were increasing from a stable stage (100
C), as shown in Figure 6a,b. A sudden increase
in the vertical displacement can also be seen at the 45th minute (vertical displacement
rate of 0.4 mm/min), which can be attributed to the recorded board falling off, followed
by a further increase in the 60th minute. This increase could be attributed to the rising
temperatures at the steel frame members (P1-LT3, Figure 6b).
3.2. Specimen P2
Specimen P2 was of the same composition as specimen P1 and was tested to check
uniformity of the test results. However, the specimen had to be unloaded earlier, at the
50th minute of the fire exposure while the furnace burners were shut down at the 67th
minute. As with specimen P1, no smoke, water vapour or cracking was observed on the
ambient side during the entire test period, indicating that the integrity failure criterion was
not reached. The temperature–time profile obtained in the furnace (Figure 7a,b) agrees well
with the standard fire curve within the limits prescribed. Monitored average temperatures
for the upper positions are shown in Figure 7a up to 90 min. As shown in the figure, the
temperature between the two wallboards (thermocouple P2-HT1) remained below 100
C
(temperature plateau), for a period of about 20 min of fire exposure and then began to rise
until the end of the test. The delay in the temperature rise between the second wallboard and
the PUR foam (thermocouple P2-HT2) extended to 46 min after the start of the test, when
the temperature rise followed that of thermocouple between the two wallboards (P2-HT1).
At the time of unloading, the temperatures at the hot flange (P2-HT3), web (P2-HT4) and cold
flange (P2-HT5) were 64
C, 55
C and 50
C, respectively, and reached maximum values
of 577
C, 573
C and 336
C, respectively, when the burners were turned off during the
90 min temperature-monitoring period. Compared to the temperature profiles shown for the
upper position (Figure 7a), the average thermocouple temperatures recorded at the lower
position (Figure 7b) are similar up to the 40th minute of fire exposure. However, it can be
seen that after the dehydration period, the temperatures between the two wallboards (P2-LT1)
increase rapidly. The same trend in temperature rise was observed at the position between
base wallboard and PUR foam (P2-LT2) with later start of temperature rise. At the 50th min of
exposure time (unloading), temperatures of 76
C, 62
C and 53
C were recorded at the hot
flange (P2-LT3), web (P2-LT4) and cold flange (P2-LT5), respectively, and reached maximum
values of 783 C, 734 C and 681 C, respectively, after turning off the radiant burners.
As for specimen P1, the individual and average temperature recorded on the unex-
posed wallboards shown in Figure 7c indicate that the insulation failure criteria were not
reached. Figure 7d presents the vertical deformations that occurred during the 50 min fire
test. Until the 15th minute, the specimen expanded due to the increasing heat, then there
was a sudden increase in the opposite direction, i.e., the direction of the applied load. From
the 20th minute, the temperatures at the exposed specimen side (P1-HT1 and P1-LT1—see
Figure 7a,b) started to increase from stable stage (100
C). Until the 35th minute, the speci-
men remained stable with no significant deformation observed. From this point on, the
specimen deformed continuously with high displacement rate (from 0.4 mm/min to almost
0.8 mm/min), indicating a possible collapse of the structure. Consequently, the specimen
was unloaded at the 50th minute.
Appl. Sci. 2024,14, 637 10 of 18
Appl. Sci. 2024, 14, x FOR PEER REVIEW 10 of 19
(a) (b)
(c) (d)
Figure 7. Fire test results for specimen P2: (a) average temperatures at high positions (HTs); (b)
average temperatures at low positions (LTs); (c) temperatures recorded at the unexposed side of the
specimen; (d) average vertical displacement and displacement rate.
As for specimen P1, the individual and average temperature recorded on the unex-
posed wallboards shown in Figure 7c indicate that the insulation failure criteria were not
reached. Figure 7d presents the vertical deformations that occurred during the 50 min re
test. Until the 15th minute, the specimen expanded due to the increasing heat, then there
was a sudden increase in the opposite direction, i.e., the direction of the applied load.
From the 20th minute, the temperatures at the exposed specimen side (P1-HT1 and P1-
LT1—see Figure 7a,b) started to increase from stable stage (100 °C). Until the 35th minute,
the specimen remained stable with no signicant deformation observed. From this point
on, the specimen deformed continuously with high displacement rate (from 0.4 mm/min
to almost 0.8 mm/min), indicating a possible collapse of the structure. Consequently, the
specimen was unloaded at the 50th minute.
3.3. Specimen P3
Specimen 3 was tested to observe the benet of an additional layer of wallboard on
the FRR The specimen consisted of triple gypsum breboards on both sides (two A2 GFBs
and one A1 GFB). Specimen 3 was unloaded at the 108th minute and the burners were
turned o in the 111th minute. No smoke, water vapour, ames or cracks were observed
on the ambient side of the specimen throughout the test, indicating that the integrity fail-
ure criterion was not reached. Monitored average temperatures for the upper positions up
to 130 min after the start of the test are shown in Figure 8a.
Figure 7. Fire test results for specimen P2: (a) average temperatures at high positions (HTs);
(b) average temperatures at low positions (LTs); (c) temperatures recorded at the unexposed side of
the specimen; (d) average vertical displacement and displacement rate.
3.3. Specimen P3
Specimen 3 was tested to observe the benefit of an additional layer of wallboard on
the FRR The specimen consisted of triple gypsum fibreboards on both sides (two A2 GFBs
and one A1 GFB). Specimen 3 was unloaded at the 108th minute and the burners were
turned off in the 111th minute. No smoke, water vapour, flames or cracks were observed
on the ambient side of the specimen throughout the test, indicating that the integrity failure
criterion was not reached. Monitored average temperatures for the upper positions up to
130 min after the start of the test are shown in Figure 8a.
From the figure, it can be seen that the temperature between the two wallboards
(thermocouple P3-HT1) remained below 100
C for a period of about 20 min after the start
of the test (temperature plateau) and then began to rise steeply. The temperature at the
boundary between the base layer (GFB3) and the insulation (P3-HT3) remained below
100
C until 60 min of fire exposure. After the initial delay, the temperature increased very
slowly until the 90th minute and then increased rapidly to 814
C at the 110th minute.
Temperatures at the steel sections (thermocouples P3-HT4, P3-HT5 and P3-HT6) began to
rise rapidly about 95 min after the test had started reaching maximum values of 819
C
at the hot flange and web of steel profile, and 785
C at the cold flange. The average
temperatures recorded on the lower positions of P3 (see Figure 8b) are similar to those
recorded at upper positions up to the 50th minute of fire exposure, with some differences
thereafter. Very similar temperature profiles were obtained at the position between the
exposed and middle (i.e., PL3-LT2) and between the middle and base layers (i.e., PL3-LT3)
of the gypsum fibreboards. The temperatures recorded on the steel studs (P3-LT4, P3-LT5
and P3-LT6) started to increase almost at the same time (95th minute) as those recorded at
high position (P3-HT4, P3-HT5 and P3-HT6) and maximum values of 845
C, 867
C and
Appl. Sci. 2024,14, 637 11 of 18
768
C, respectively, were reached. From the aforementioned figures, temperature–time
curves for positions 1–6 follow the same pattern after the specimens were unloaded and
burners were shut down. The stagnation in temperature rise was then observed, which was
followed by a temperature increase in the last 10 min, although there was no heat output
from the furnace. Fast temperature rises at each position throughout the cross-section of the
specimen were obviously a consequence of PUR burning. At the ambient side (Figure 8c),
the obtained maximum individual and average temperatures were around 45
C, which
was below the insulation criteria for FRR.
Figure 8. Fire test results for specimen P3: (a) average temperatures at high positions (HTs),
(b) average temperatures at low positions (LTs); (c) temperatures recorded at the unexposed side of
the specimen; (d) average vertical displacement and displacement rate.
As Figure 8d shows, the specimen vertically expanded due to the increased heat from the
12th to the 33rd minute. After the initial expansion, the measured vertical displacementsshow a
steady increase in the direction of the applied load (vertical displacement rate of 0.6 mm/min).
At the 33rd minute, the temperatures between GFB1 and GFB2 were 220–240
C. After the
initial propagation, the vertical displacements remained stable with only small fluctuations until
the 99th minute. At the 99th minute, a sharp increase in the measured vertical displacements
(vertical displacement rate from 0.5 mm/min to 0.7 mm/min) occurred, possibly leading to
collapse of the structure.
3.4. Post-Test Observations
Post-test observations of all tested specimens indicate that all wallboards on the exposed
side collapsed completely, and the PUR foam was almost completely charred. The steel
members exhibited localised buckling around relatively rigid nodes 6 and 7. Global buckling
of top diagonal members (under the load application position) was also recorded. For an
example, Figure 9presents the exposed side of test specimen P2.
Appl. Sci. 2024,14, 637 12 of 18
Appl. Sci. 2024, 14, x FOR PEER REVIEW 12 of 19
As Figure 8d shows, the specimen vertically expanded due to the increased heat from
the 12th to the 33rd minute. After the initial expansion, the measured vertical displace-
ments show a steady increase in the direction of the applied load (vertical displacement
rate of 0.6 mm/min). At the 33rd minute, the temperatures between GFB1 and GFB2 were
220240 °C. After the initial propagation, the vertical displacements remained stable with
only small uctuations until the 99th minute. At the 99th minute, a sharp increase in the
measured vertical displacements (vertical displacement rate from 0.5 mm/min to 0.7
mm/min) occurred, possibly leading to collapse of the structure.
3.4. Post-Test Observations
Post-test observations of all tested specimens indicate that all wallboards on the ex-
posed side collapsed completely, and the PUR foam was almost completely charred. The
steel members exhibited localised buckling around relatively rigid nodes 6 and 7. Global
buckling of top diagonal members (under the load application position) was also rec-
orded. For an example, Figure 9 presents the exposed side of test specimen P2.
Figure 9. Post test observations for specimen P2: (a) exposed side of upper part of test specimen; (b)
exposed side of lower part of test specimen; (c) node 6; (d) node 7.
4.
Discussion
4.1. Overall Behaviour of Tested Specimens
The results presented separately for each LSF specimen show similar behaviour and
mode of failure during standard re exposure. At the beginning of the test, the gypsum
breboards protected the steel frame from a temperature rise for some time. In addition,
the low thermal conductivity of the PUR foam contributed to low heat transfer through
the specimen before it began to decompose. Once the free and physically bound water
evaporated from the GFBs, they became susceptible to cracking, and parts of boards fell
o, allowing heat to penetrate the combustible cavity insulation and steel members. For
the specimens with double GFBs (specimens P1 and P2), the sudden temperature rise on
the steel members started after about 5060 min (Figures 6a,b and 7a,b), while the addi-
tional board on the specimen with triple GFBs prolonged the steep temperature rise for
an additional 30 min (Figure 8a,b). When the ignition temperature for the PUR insulation
Figure 9. Post test observations for specimen P2: (a) exposed side of upper part of test specimen;
(b) exposed side of lower part of test specimen; (c) node 6; (d) node 7.
4. Discussion
4.1. Overall Behaviour of Tested Specimens
The results presented separately for each LSF specimen show similar behaviour and
mode of failure during standard fire exposure. At the beginning of the test, the gypsum
fibreboards protected the steel frame from a temperature rise for some time. In addition,
the low thermal conductivity of the PUR foam contributed to low heat transfer through
the specimen before it began to decompose. Once the free and physically bound water
evaporated from the GFBs, they became susceptible to cracking, and parts of boards
fell off, allowing heat to penetrate the combustible cavity insulation and steel members.
For the specimens with double GFBs (specimens P1 and P2), the sudden temperature
rise on the steel members started after about 50–60 min (Figures 6a,b and 7a,b), while
the additional board on the specimen with triple GFBs prolonged the steep temperature
rise for an additional 30 min (Figure 8a,b). When the ignition temperature for the PUR
insulation was reached (between 200
C and 300
C), the additional heat generated by
combustion contributed to the temperature rise on the steel sections and maintained the
high temperatures even after the burners in the furnace were turned off. Nevertheless, the
heat generated by the PUR combustion was not sufficient to raise the furnace temperature
(Figures 6a,b–8a,b). Throughout the test period, all tested specimens showed no signs of
integrity and insulation failure. As mentioned earlier, according to previous studies on
the load-bearing cavity insulated LSF wall exposed to fire test [
16
18
], structural failure is
usually the predominant failure mode due to the non-uniform heating of the steel members.
In accordance with EN 1365-1 [
33
], structural failure occurs when the displacement reaches
the value h/100 mm (height/100) or when the displacement rate reaches a value of 3
h/1000 mm/min. This means that a displacement of 30 mm or a displacement rate of
6 mm/min must be achieved. Figure 10a shows the comparison between the average
measured displacements for all tested specimens, while Figure 10b shows the comparison
of the average displacement rates. During the time of unloading, the two structural failure
criteria were not reached but a trend of steep increase can be observed. Since the specimens
were manufactured with non-standard dimensions and unloaded earlier than the above
criteria were reached, it is not possible to give an official FRR. However, the results shown
Appl. Sci. 2024,14, 637 13 of 18
in Figure 10a,b suggest that specimens P1 and P2 could achieve a minimum FRR of 60
min and specimen P3 of minimum 90 min, which is sufficient for use in residential and
commercial buildings.
Appl. Sci. 2024, 14, x FOR PEER REVIEW 13 of 19
was reached (between 200 °C and 300 °C), the additional heat generated by combustion
contributed to the temperature rise on the steel sections and maintained the high temper-
atures even after the burners in the furnace were turned o. Nevertheless, the heat gener-
ated by the PUR combustion was not sucient to raise the furnace temperature (Figures
6a,b–8a,b). Throughout the test period, all tested specimens showed no signs of integrity
and insulation failure. As mentioned earlier, according to previous studies on the load-
bearing cavity insulated LSF wall exposed to re test [16–18], structural failure is usually
the predominant failure mode due to the non-uniform heating of the steel members. In
accordance with EN 1365-1 [33], structural failure occurs when the displacement reaches
the value h/100 mm (height/100) or when the displacement rate reaches a value of 3 h/1000
mm/min. This means that a displacement of 30 mm or a displacement rate of 6 mm/min
must be achieved. Figure 10a shows the comparison between the average measured dis-
placements for all tested specimens, while Figure 10b shows the comparison of the aver-
age displacement rates. During the time of unloading, the two structural failure criteria
were not reached but a trend of steep increase can be observed. Since the specimens were
manufactured with non-standard dimensions and unloaded earlier than the above criteria
were reached, it is not possible to give an ocial FRR. However, the results shown in
Figure 10a,b suggest that specimens P1 and P2 could achieve a minimum FRR of 60 min
and specimen P3 of minimum 90 min, which is sucient for use in residential and com-
mercial buildings.
(a) (b)
Figure 10. Comparison between the measured (a) displacements and (b) displacement rates.
Post-test inspection of the tested specimens revealed that the cavity insulation was
completely burned, leaving only layers of charcoal (Figure 9), while the steel members
around nodes in central studs (N6 and N7 according to Figure 1) were deformed in all
three specimens (Figure 9c,d). It was also noted that the GBFs were still aached to the
steel structure at the top and near the boom of the specimen. This led to the conclusion
that the failure of the exposed GBF was localized and probably occurred about 1 m from
the boom of the specimen. At this location, the re from the furnace entered the cavity,
resulting in decomposition of insulation. This is conrmed by the results of the infrared
thermography monitoring and thermograms taken on specimen P1 at the 67th and 76th
minutes of testing, Figure 11.
Figure 10. Comparison between the measured (a) displacements and (b) displacement rates.
Post-test inspection of the tested specimens revealed that the cavity insulation was
completely burned, leaving only layers of charcoal (Figure 9), while the steel members
around nodes in central studs (N6 and N7 according to Figure 1) were deformed in all
three specimens (Figure 9c,d). It was also noted that the GBFs were still attached to the
steel structure at the top and near the bottom of the specimen. This led to the conclusion
that the failure of the exposed GBF was localized and probably occurred about 1 m from
the bottom of the specimen. At this location, the fire from the furnace entered the cavity,
resulting in decomposition of insulation. This is confirmed by the results of the infrared
thermography monitoring and thermograms taken on specimen P1 at the 67th and 76th
minutes of testing, Figure 11.
Appl. Sci. 2024, 14, x FOR PEER REVIEW 14 of 19
(a) (b)
Figure 11. Thermograms for specimen P1: (a) in the 67th minute; (b) in the 76th minute.
Thermographic measurements showed that the predominant heat transfer occurred
in the lower third of the specimen, which is consistent with the temperature–time curves
shown in Figure 6a,b. As can be seen from the gures, a signicant temperature increase
(maximum temperature above 100 °C was achieved) was observed at the nodes positioned
at the lower part of the specimens (around nodes N6 and N7). This higher temperature is
directly correlated with the position of joints (as shown in Figure 3) implying that the
joints failed rst and the PUR insulation degraded around this location rst. This resulted
with heat being transmied through the boards and consequently to the non-exposed sur-
face of the specimen. Additionally, higher temperatures than the surroundings are ob-
served in the areas where spacers and screws are positioned.
4.2. Comparison between Nominally Identical Specimens (P1 and P2)
Since re tests are expensive and time-consuming, the results are usually analysed,
and conclusions are drawn from individual measurements. On the other hand, studies
dealing with repeated re tests with the same specimens have shown that re tests are
dicult to reproduce in terms of their physical quantities even though they were designed
to be repeated under the same conditions [37]. Therefore, two nominally identical LSF
panels (P1 and P2) are tested for comparison. Figure 12a,b show the comparison of the
time–temperature curves recorded between the two GBFs (positions HT1 and LT1) and
between the GFB base layer and the PUR insulation (positions HT2 and LT2) for specimens
P1 and P2, while Figure 12c,d show the comparison of the time–temperature curves ob-
tained at the steel studs at both thermocouple positions.
Figure 11. Thermograms for specimen P1: (a) in the 67th minute; (b) in the 76th minute.
Thermographic measurements showed that the predominant heat transfer occurred
in the lower third of the specimen, which is consistent with the temperature–time curves
shown in Figure 6a,b. As can be seen from the figures, a significant temperature increase
(maximum temperature above 100
C was achieved) was observed at the nodes positioned
at the lower part of the specimens (around nodes N6 and N7). This higher temperature is
directly correlated with the position of joints (as shown in Figure 3) implying that the joints
failed first and the PUR insulation degraded around this location first. This resulted with
heat being transmitted through the boards and consequently to the non-exposed surface of
the specimen. Additionally, higher temperatures than the surroundings are observed in the
areas where spacers and screws are positioned.
Appl. Sci. 2024,14, 637 14 of 18
4.2. Comparison between Nominally Identical Specimens (P1 and P2)
Since fire tests are expensive and time-consuming, the results are usually analysed,
and conclusions are drawn from individual measurements. On the other hand, studies
dealing with repeated fire tests with the same specimens have shown that fire tests are
difficult to reproduce in terms of their physical quantities even though they were designed
to be repeated under the same conditions [
37
]. Therefore, two nominally identical LSF
panels (P1 and P2) are tested for comparison. Figure 12a,b show the comparison of the time–
temperature curves recorded between the two GBFs (positions HT1 and LT1) and between
the GFB base layer and the PUR insulation (positions HT2 and LT2) for specimens P1 and
P2, while Figure 12c,d show the comparison of the time–temperature curves obtained at
the steel studs at both thermocouple positions.
Appl. Sci. 2024, 14, x FOR PEER REVIEW 15 of 19
(a) (b)
(c) (d)
Figure 12. Comparisons of time–temperature curves for specimens P1 and P2: (a) average time–
temperature curves recorded at GBFs (higher positions—HTs); (b) average time–temperature curves
recorded at GBFs (lower positions—LTs); (c) average time–temperature curves recorded on steel
studs at higher positions (HTs); (d) average–time-temperature curves recorded on steel studs at
lower positions (LTs).
Although specimens P1 and P2 were made from the same components, tested under
the same conditions and exhibited similar failure modes, the degradation of specimen P2
began earlier. In general, the timetemperature curves recorded at GBFs at the lower po-
sitions for both specimens (Figure 12b) show greater dierences compared to the analo-
gous results recorded at the upper positions (Figure 12a). The location where the cracks
are believed to have formed comes from the observations made from the thermograms
(Figure 11) and it is located directly above nodes N6 and N7, where local buckling was
observed during the post-test inspection. About 40 min after the start of the test, severe
horizontal cracking and opening of the joints were observed on both specimens. The dif-
ferences between the time–temperature curves in the steel members of specimens P1 and
P2 are also high (Figure 12c,d), especially at lower position from the 50th minute onwards
(Figure 12d). Consequently, the observed vertical deection was more pronounced for
specimen P2 (Figure 10). These discrepancies in the obtained results indicate the need to
repeat the re tests to draw strong conclusions and provide a broader basis for the results
if modelling is used. Thus, the results obtained do not allow clear conclusions to be drawn
regarding the uniformity of the results obtained and the subsequent FRR. If FRR is con-
cerned, since the load was removed before the structural failure criteria were reached, it
is hard to predict the behaviour of panels from test end onward. However, the results
obtained on both specimens suggest that an FRR of at least 60 min can be achieved for LSF
with combustible cavity insulation protected with two layers of GBF with reaction to re
A1.
Figure 12. Comparisons of time–temperature curves for specimens P1 and P2: (a) average time–
temperature curves recorded at GBFs (higher positions—HTs); (b) average time–temperature curves
recorded at GBFs (lower positions—LTs); (c) average time–temperature curves recorded on steel
studs at higher positions (HTs); (d) average–time-temperature curves recorded on steel studs at lower
positions (LTs).
Although specimens P1 and P2 were made from the same components, tested under
the same conditions and exhibited similar failure modes, the degradation of specimen P2 be-
gan earlier. In general, the time–temperature curves recorded at GBFs at the lower positions
for both specimens (Figure 12b) show greater differences compared to the analogous results
recorded at the upper positions (Figure 12a). The location where the cracks are believed to
have formed comes from the observations made from the thermograms (Figure 11) and
it is located directly above nodes N6 and N7, where local buckling was observed during
the post-test inspection. About 40 min after the start of the test, severe horizontal cracking
and opening of the joints were observed on both specimens. The differences between
the time–temperature curves in the steel members of specimens P1 and P2 are also high
(Figure 12c,d), especially at lower position from the 50th minute onwards (Figure 12d).
Consequently, the observed vertical deflection was more pronounced for specimen P2
Appl. Sci. 2024,14, 637 15 of 18
(Figure 10). These discrepancies in the obtained results indicate the need to repeat the fire
tests to draw strong conclusions and provide a broader basis for the results if modelling is
used. Thus, the results obtained do not allow clear conclusions to be drawn regarding the
uniformity of the results obtained and the subsequent FRR. If FRR is concerned, since the
load was removed before the structural failure criteria were reached, it is hard to predict
the behaviour of panels from test end onward. However, the results obtained on both
specimens suggest that an FRR of at least 60 min can be achieved for LSF with combustible
cavity insulation protected with two layers of GBF with reaction to fire A1.
4.3. Comparison between Specimens with Different Wallboard Layers (P1 and P3)
The comparison between specimens P1 and P3 was made with the aim of determin-
ing the effect of different arrangement, type and number of wallboard layers on the fire
behaviour of studied LSF panels. Although specimen P3 did not fail up to the 108th
minute, the purpose of this comparison is to evaluate the fire behaviour in the first 90 min.
Since specimen P2 failed earlier than P1, specimen P1 was taken as more appropriate
to determine the behavioural differences in a longer time frame. Comparing the time-
temperature curves shown in Figure 13a,b, it can be seen that the addition of one layer of
GBF in specimen P3, even if inner ones are of A2 GFB, significantly affected the temperature
development at the interface between the base layer and the insulation (P1-(H/L)T2 vs.
P3-(H/L)T3). The temperatures for both specimens between the two exposed wallboards
at positions HT1 and LT1 were similar until the 20th minute. After the 20th minute, the
temperatures between the exposed wallboards in specimen P3 began to be significantly
higher than the analogous temperatures in specimen P1. This difference is much more
pronounced at the higher positions, P3-HT1 vs. P1-HT1, see Figure 13a. This significant
temperature increase could be attributed to the formation of cracks in specimen P3.
Appl. Sci. 2024, 14, x FOR PEER REVIEW 16 of 19
4.3. Comparison between Specimens with Dierent Wallboard Layers (P1 and P3)
The comparison between specimens P1 and P3 was made with the aim of determin-
ing the eect of dierent arrangement, type and number of wallboard layers on the re
behaviour of studied LSF panels. Although specimen P3 did not fail up to the 108th mi-
nute, the purpose of this comparison is to evaluate the re behaviour in the rst 90 min.
Since specimen P2 failed earlier than P1, specimen P1 was taken as more appropriate to
determine the behavioural dierences in a longer time frame. Comparing the time-tem-
perature curves shown in Figure 13a,b, it can be seen that the addition of one layer of GBF
in specimen P3, even if inner ones are of A2 GFB, signicantly aected the temperature
development at the interface between the base layer and the insulation (P1-(H/L)T2 vs. P3-
(H/L)T3). The temperatures for both specimens between the two exposed wallboards at
positions HT1 and LT1 were similar until the 20th minute. After the 20th minute, the tem-
peratures between the exposed wallboards in specimen P3 began to be signicantly higher
than the analogous temperatures in specimen P1. This dierence is much more pro-
nounced at the higher positions, P3-HT1 vs. P1-HT1, see Figure 13a. This signicant tem-
perature increase could be aributed to the formation of cracks in specimen P3.
At the time of unloading specimen P1 (67th minute), the temperatures at the interface
between the inner wallboards and the insulation were signicantly lower. The tempera-
ture dierence between the interface of the wallboards and insulation at the higher ther-
mocouple position (P1-HT2 and P3-HT3, Figure 13a) was 321 °C. The temperature dier-
ence at the lower thermocouple positions (P1-LT2 and P3-LT3, Figure 13b) was even
higher—467 °C. Comparing the temperatures recorded at the steel studs for the whole test
period, it can be seen that the temperatures in specimen P3 remained below 100 °C at both
the lower and higher positions (see Figure 13c,d). Comparing the hot ange temperatures
at lower positions, the dierence is 656 °C (Figure 13d) at the 67th minute of the test.
(a) (b)
(c) (d)
Figure 13. Time–temperature curves comparisons for specimen P1 and P3: (a) average time–tem-
perature curves for higher positions (HTs); (b) average time–temperature curves for lower positions
Figure 13. Time–temperature curves comparisons for specimen P1 and P3: (a) average time–
temperature curves for higher positions (HTs); (b) average time–temperature curves for lower
positions (LTs); (c) average time–temperature curves measured on the steel studs (HTs); (d) average
time–temperature curves measured on steel studs (LTs).
Appl. Sci. 2024,14, 637 16 of 18
At the time of unloading specimen P1 (67th minute), the temperatures at the interface
between the inner wallboards and the insulation were significantly lower. The temperature
difference between the interface of the wallboards and insulation at the higher thermocou-
ple position (P1-HT2 and P3-HT3, Figure 13a) was 321
C. The temperature difference at the
lower thermocouple positions (P1-LT2 and P3-LT3, Figure 13b) was even higher—467
C.
Comparing the temperatures recorded at the steel studs for the whole test period, it can
be seen that the temperatures in specimen P3 remained below 100
C at both the lower
and higher positions (see Figure 13c,d). Comparing the hot flange temperatures at lower
positions, the difference is 656 C (Figure 13d) at the 67th minute of the test.
5. Conclusions
This paper presents the details of three fire tests conducted on a newly proposed
composition for LSF wall systems using PUR foam in the cavities, with spacers separating
the GFBs from the steel structure. Two specimens were identically sheathed with two A1
GFBs, while the third specimen were sheathed with two A2 GBFs and one outer A1 GFB.
Based on the experimental results and discussion, the following conclusions can be drawn:
1.
During testing, the integrity and insulating properties of the tested LSF panels were
undisputed, and all test specimens showed indications of structural collapse. Nev-
ertheless, a reliable mode of failure (governing the FRR criteria) cannot be specified
because the insulation used is combustible and the tests were terminated before the
failure criteria were reached.
2.
Two 12.5 mm thick layers of A1 GBFs delayed the temperature rise in the steel bars by
about 50 min (observed at lower positions of thermocouples) to 60 min (observed at
higher position of thermocouples), while the configuration with two A2 GBFs and an
outer A1 GFB caused an additional delay of 30 min.
3.
Post-fire test observations showed that all three test specimens exhibited similar local
buckling of the steel members in the lower segment near the rigid nodes.
4.
The results obtained on two identical specimens under the same conditions demon-
strate the need to perform a larger number of nominally identical tests, especially to
broaden the basis for verification when fire behaviour modelling is used.
Since there are no data in the existing literature on the behaviour of LSF walls with
combustible cavity insulation materials, the results presented in this study are valuable
for future studies. Although combustible PUR insulation was used, the study showed
promising results for the application of developed LSF panels in prefabricated and modular
structures in both residential and commercial buildings where an FRR of more than 60 min
is required. To comprehend the behaviour of LSF panels with PUR insulation in a fire
situation, particularly with regard to their potential application in specific building types, it
is crucial to investigate the potential release of toxic gases from the used PUR foam on the
side exposed to the fire. Cost-optimal configuration of the wallboards should be established
by further research, which could lead to testing of different types of wallboards with their
different position in the cross section of the system, even introducing the possibility of
an installation layer, which could enable reduction in penetrations through the system,
easier airtightness barrier installation and easier detailing (regarding the fire resistance) of
multiple panel connections—especially if the installation layer is filled with mineral wool
or similar non-combustible insulation material.
Author Contributions: Conceptualization, M.J.R., D.S. and T.Š.; methodology, M.J.R., D.S. and T.Š.;
formal analysis, M.J.R., D.S., B.M. and T.Š.; investigation, M.J.R., D.S., B.M. and T.Š.; writing—original
draft preparation, D.S. and T.Š.; writing—review and editing, M.J.R., D.S. and B.M.; visualization,
M.J.R., D.S. and B.M.; project administration, M.J.R.; funding acquisition, M.J.R. All authors have
read and agreed to the published version of the manuscript.
Funding: This research was funded by the European Union through the European Regional Develop-
ment Fund’s Competitiveness and Cohesion Operational Program, grant number KK.01.1.1.07.0060,
project “Composite lightweight panel with integrated load-bearing structure (KLIK-PANEL)”.
Appl. Sci. 2024,14, 637 17 of 18
Institutional Review Board Statement: Not applicable.
Informed Consent Statement: Not applicable.
Data Availability Statement: The data presented in this study are available on request from the
corresponding author. The data are not publicly available due to privacy.
Conflicts of Interest: The authors declare no conflict of interest.
References
1.
Soares, N.; Santos, P.; Gervásio, H.; Costa, J.J.; da Silva, L.S. Energy efficiency and thermal performance of lightweight steel-framed
(LSF) construction: A review. Renew. Sustain. Energy Rev. 2017,78, 194–209. [CrossRef]
2.
Rodrigues, E.; Soares, N.; Fernandes, M.S.; Gaspar, A.R.; Gomes, Á.; Costa, J.J. An integrated energy performance-driven
generative design methodology to foster modular lightweight steel framed dwellings in hot climates. Energy Sustain. Dev. 2018,
44, 21–36. [CrossRef]
3.
Jerónimo, R.; Gonçalves, M.; Furtado, C.; Rodrigues, K.; Ferreira, C.; Simões, N. Experimental Assessment and Validation of the
Hygrothermal Behaviour of an Innovative Light Steel Frame (LSF) Wall Incorporating a Monitoring System. Buildings 2023,13, 2509.
[CrossRef]
4.
Ariyanayagam, A.D.; Mahendran, M. Experimental study of load-bearing cold-formed steel walls exposed to realistic design fires.
J. Struct. Fire Eng. 2014,5, 291–329. [CrossRef]
5.
Ariyanayagam, A.D.; Mahendran, M. Fire tests of non-load bearing light gauge steel frame walls lined with calcium silicate
boards and gypsum plasterboards. Thin-Walled Struct. 2017,115, 86–99. [CrossRef]
6.
EN 13501-2; Fire Classification of Construction Products and Building Elements—Part 2: Classification Using Data from Fire
Resistance Tests, Excluding Ventilation Services. CEN The European Committee for Standardization: Brussels, Belgium, 2016.
7. Wang, Y.; Burgess, I.; Wald, F.; Gillie, M. Performance-Based Fire Engineering of Structures; CRC Press: Boca Raton, FL, USA, 2012.
8.
Gunalan, S.; Kolarkar, P.; Mahendran, M. Experimental study of load bearing cold-formed steel wall systems under fire conditions.
Thin-Walled Struct. 2013,65, 72–92. [CrossRef]
9. Kodur, V.K.R.; Sultan, M.A. Factors influencing fire resistance of load-bearing steel stud walls. Fire Technol. 2006,42, 5–26. [CrossRef]
10.
Alves, M.H.; Constantini, G.; Ianni, A.; Kimura, E.F.A.; Meda, A.; Piloto, P.A.G. Fire performance of non-load-bearing double-stud
light steel frame walls: Experimental tests, numerical simulation, and simplified method. Fire Mater. 2022,46, 227–250. [CrossRef]
11.
Steau, E.; Mahendran, M. Elevated temperature thermal properties of fire protective boards and insulation materials for light
steel frame systems. J. Build. Eng. 2021,43, 102571. [CrossRef]
12.
Gnanachelvam, S.; Mahendran, M.; Ariyanayagam, A. Elevated temperature thermal properties of advanced materials used in
LSF systems. Fire Mater. 2022,46, 12–28. [CrossRef]
13.
Just, A.; Schmid, J.; König, J. Gypsum Plasterboards Used as Fire Protection—Analysis of a Database; SP Technical Research Institute of
Sweden: Stockholm, Sweden, 2010; p. 30.
14.
Keerthan, P.; Mahendran, M. Thermal Performance of Composite Panels Under Fire Conditions Using Numerical Studies:
Plasterboards, Rockwool, Glass Fibre and Cellulose Insulations. Fire Technol. 2013,49, 329–356. [CrossRef]
15.
Santos, P.; Martins, C.; Simões da Silva, L. Thermal performance of lightweight steel- framed construction systems. Metall. Res.
Technol. 2014,111, 329–338. [CrossRef]
16.
Ariyanayagam, A.D.; Mahendran, M. Influence of cavity insulation on the fire resistance of light gauge steel framed walls.
Constr. Build. Mater. 2019,203, 687–710. [CrossRef]
17.
Ariyanayagam, A.D.; Mahendran, M. Fire performance of load bearing LSF wall systems made of low strength steel studs.
Thin-Walled Struct. 2018,130, 487–504. [CrossRef]
18.
Alfawakhiri, F.; Sultan, M.A. Fire Resistance of Loadbearing LSF Assemblies. In Proceedings of the International Specialty
Conference on Cold-Formed Steel Structures: Recent Research and Developments in Cold-Formed Steel Design and Construction,
St. Louis, MO, USA, 19–20 October 2000; University of Missouri—Rolla: Rolla, MO, USA, 2000; pp. 545–561.
19.
Tao, Y.; Mahendran, M. Fire tests and thermal analyses of LSF walls insulated with silica aerogel fibreglass blanket. Fire Saf. J.
2021,122, 103352. [CrossRef]
20.
Perera, D.; Poologanathan, K.; Gillie, M.; Gatheeshgar, P.; Sherlock, P.; Nanayakkara SM, A.; Konthesingha, K.M. C Fire
performance of cold, warm and hybrid LSF wall panels using numerical studies. Thin-Walled Struct. 2020,157, 107109. [CrossRef]
21.
Gnanachelvam, S.; Ariyanayagam, A.; Mahendran, M. Fire resistance of LSF wall systems lined with different wallboards
including bio-PCM mat. J. Build. Eng. 2020,32, 101628. [CrossRef]
22.
Somarathna, H.M.C.C.; Raman, S.N.; Mohotti, D.; Mutalib, A.A.; Badri, K.H. The use of polyurethane for structural and
infrastructural engineering applications: A state-of-the-art review. Constr. Build. Mater. 2018,190, 995–1014. [CrossRef]
23.
Liu, X.; Hao, J.; Gaan, S. Recent studies on the decomposition and strategies of smoke and toxicity suppression for polyurethane
based materials. RSC Adv. 2016,6, 74742–74756. [CrossRef]
24.
Singh, H.; Jain, A.K. Ignition; combustion; toxicity, and fire retardancy of polyurethane foams: A comprehensive review. J. Appl.
Polym. Sci. 2009,111, 1115–1143. [CrossRef]
25. Thomas McKenna, S.; Hull, T.R. The fire toxicity of polyurethane foams. Fire Sci. Rev. 2016,5, 3. [CrossRef]
Appl. Sci. 2024,14, 637 18 of 18
26.
Paabo, M.; Levin, B.C. A review of the literature on the gaseous products and toxicity generated from the pyrolysis and combustion
of rigid polyurethane foams. Fire Mater. 1987,11, 1–29. [CrossRef]
27.
Amado, J.C.Q. Thermal Resistance Properties of Polyurethanes and its Composites: A Short Review. J. Res. Updat. Polym. Sci.
2019, 66–84. [CrossRef]
28.
Günther, M.; Lorenzetti, A.; Schartel, B. From Cells to Residues: Flame-Retarded Rigid Polyurethane Foams. Combust. Sci. Technol.
2020,192, 2209–2237. [CrossRef]
29.
Le Dréau, J.; Jensen, R.L.; Kolding, K. Thermal behaviour of a gypsum fibre board associated with rigid polyurethane foam under
standard fire conditions. Energy Procedia 2015,78, 2736–2741. [CrossRef]
30.
Rukavina, M.J.; Skeji´c, D.; Kralj, A.; Ўcapec, T.; Milovanovi´c, B. Development of Lightweight Steel Framed Construction Systems
for Nearly-Zero Energy Buildings. Buildings 2022,12, 929. [CrossRef]
31.
Fermacell ®. “Fermacell ®Gypsum Fibreboards Product Data Sheet, no. 5–6 October 2019. Available online: https://www.
fermacell.co.uk/fermacellapi/downloads/file/en-GB/0690J000004BxHIQA0 (accessed on 20 September 2023).
32.
Fermacell ®. “Fermmacell Firepanel A1 Product Data Sheet. October 2019. Available online: https://www.fermacell.co.uk/
fermacellapi/downloads/file/en-GB/0690J000004BxFgQAK (accessed on 20 September 2023).
33.
EN 1365-1; Fire Resistance Tests for Loadbearing Elements—Part 1: Walls. CEN The European Committee for Standardization:
Brussels, Belgium, 2012; p. 25.
34.
EN 1363-1; Fire Resistance Tests—Part 1: General Requirements. CEN The European Committee for Standardization: Brussels,
Belgium, 2020.
35. Thomas, G. Thermal properties of gypsum plasterboard at high temperatures. Fire Mater. 2002,26, 37–45. [CrossRef]
36.
Ang, C.N.; Wang, Y.C. Effect of moisture transfer on specific heat of gypsum plasterboard at high temperatures. Constr. Build.
Mater. 2009,23, 675–686. [CrossRef]
37.
Melcher, T.; Zinke, R.; Trott, M.; Krause, U. Experimental investigations on the repeatability of real scale fire tests. Fire Saf. J. 2016,
82, 101–114. [CrossRef]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual
author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to
people or property resulting from any ideas, methods, instructions or products referred to in the content.
... Joining CFS profiles into panels, such as LSF walls, floors and light truss-girders [35], results in increased in-plane stiffness, and therefore, larger free spans and improved lateral stability, while the utilization of sheathing (often woodbased) and/or cross-bracing can further enhance the performance under lateral loading [7,[35][36][37]. Moreover, novel panels being investigated show promise in improving the inherent fire resistance limitations and overall performance of LSF systems for NZEB application, without compromising its structural behaviour [38,39]. However, even so, purely LSF based construction systems are rarely used outside of low-rise structures, as the problems of insufficient lateral stiffness and strength for mid-to high-rise application persist [40]. ...
Article
Full-text available
Currently, the construction sector is witnessing a growing demand for lightweight solutions, which can be justified by the need to adopt high-performance solutions and the fact that the industry is struggling with a shortage of skilled labour. In this sense, this study focuses on a novel and flexible building wall system, constructed using an innovative extensible LSF profile. To enhance its functionality, a monitoring system comprising printed sensors was integrated into the wall. These sensors underwent a thorough verification process. To evaluate the hygrothermal performance of the complete LSF wall solution and validate the novel monitoring system, an extensive ageing test focused on heat/rain, freeze/thaw cycles was conducted on a large-scale wall prototype. Additionally, this research introduces a novel approach by simulating exceptional solar radiation conditions, surpassing the standard cycles outlined in EAD 040083-00-0404, for the first time in this kind of solution. The results cover the measurements taken inside the building system using the incorporated monitoring system. Additionally, supplementary external temperature and heat flow sensors were used to determine the thermal transmittance. Visual and thermography inspections were also carried out. The findings reveal no instances of failures or defects that could potentially impact the hygrothermal behaviour of the system. The hybrid LSF constructive solution leads to more stable temperatures on the inner surface. The presence of direct solar radiation can raise surface temperatures by up to 5 • C compared to surfaces not exposed to such radiation, even when a light-coloured surface is used. The monitoring system worked correctly. In conclusion, the innovative profile proved to be resistant to hygrothermal cycles and the monitoring system developed is efficient.
Article
Full-text available
Light steel frame (LSF) building systems offer high structural resilience, lower costs due to fast prefabrication, and high ability to recycle and reuse. The main goal of this paper was to provide state-of-the-art main components for such systems with the intention to be implemented for use in nearly-zero energy buildings (NZEBs). A brief historical outline of the development of LSF systems was given, and the key parameters affecting the design and use of LSF systems were discussed. The influence of the individual components of the LSF system (steel studs, sheathing boards, and insulation materials) was then thoroughly discussed in light of relevant research on energy efficiency and other important properties (such as sound protection and fire resistance). Web of Science and Scopus databases were used for this purpose, using relevant key words: LSF, energy efficiency, sheathing boards, steel studs, insulation, etc. Several research gaps were identified that could be used for development and future research on new LSF systems. Finally, based on the analysis of each component, an innovative LSF composite wall panel was proposed which will be the subject of the authors’ future research. Conducted preliminary analysis showed low thermal transmittance of the system and indicates the path of its further research.
Article
Full-text available
The nature of starting materials and the condition of polyurethane (PU) preparation are regarded as the main general parameters that determine PU thermal resistance. The effect of structure and presence of additives were identified as the major specific factors on this regard. Structural factors include phase microstructure, i.e. nature and proportion and segregation of soft and hard segments); polyol type (petrochemical or natural oil-based); isocyanate and chain extender type and thermoplasticity of PU. Respect to the effect of additives,the incorporation of fillers is the direct strategy to increase PU heat resistance. With respect to fibers, in general a positive effect is found on improving thermal resistance, although this generalization could not apply overall considering the large number of different polyurethanes.
Article
Load-bearing light gauge steel framed (LSF) wall is one of the main structural elements in cold-formed steel (CFS) buildings. When cavity insulation is used to enhance the energy performance of LSF walls, their structural adequacy based fire resistance levels (FRL) decrease considerably. Hence, new insulation materials and/or different wall configurations are considered. This research study investigated the use of silica aerogel fibreglass blanket as external insulation to enhance the FRL of LSF walls. Three fire tests were conducted to determine the time-temperature profiles of different wall components and the FRL of aerogel blanket insulated LSF walls. Suitable finite element (FE) models were then developed, validated and used to further optimise the LSF wall configuration. This study shows that silica aerogel fibreglass blanket, when used as a form of external insulation, enhances the fire resistance by delaying the stud temperature development by about 20 min and reducing the stud flange temperature difference by up to 200 °C when compared with cavity insulated LSF walls. However, the aerogel blanket accelerates the temperature development of fire protective gypsum boards, which leads to an early failure of these boards. This paper presents the details of the fire tests, finite element study and their findings.
Article
New materials are increasingly used in the construction of cold-formed Light gauge Steel Frame (LSF) systems to achieve lightweight, more durable and fire resistant building systems. However, these materials are being used without good knowledge and understanding of their elevated temperature thermal properties. Hence a thorough investigation of the elevated temperature thermal properties was conducted for a range of building materials used in the LSF systems of Australia, New Zealand and Europe. Thermal property tests were conducted on gypsum plasterboards, calcium silicate boards, magnesium oxide boards, perlite boards, insulation materials and structural plywoods, totalling 21 potential LSF components. The thermal properties of specific heat at constant pressure, relative density, thermal conductivity and thermal diffusivity were determined using differential scanning calorimetry, thermogravimetric analysis and laser flash analysis and the guidelines of ASTM standard test methods. This paper presents the results of the elevated temperature thermal properties of a range of building materials used in the LSF systems. This advanced knowledge and understanding of the elevated temperature thermal properties will allow accurate predictions of the fire resistance of LSF systems using appropriate numerical and fire design methods and facilitate the development of improved LSF systems with enhanced fire resistance levels. Several materials such as gypsum plasterboards, calcium silicate boards, perlite board and rockwool fibre insulation have been identified to be suitable for use in LSF systems because of their high specific heat, low thermal conductivity, reduced mass loss and low bulk density.
Article
Double‐stud light steel frame (LSF) walls provide an enhanced insulation performance when exposed to fire conditions. However, the behavior of different configurations of such assemblies under fire is not well understood. Thus, this study aimed to assess the fire resistance of non‐load‐bearing double‐stud LSF walls subjected to ISO834 standard fire. The walls were lined with one or two type F gypsum plasterboards on each side, using cavity uninsulated or insulated with ceramic fiber. The experimental tests revealed that a wider cavity slows the heat transfer through the cross‐section, delaying the temperature rise on the unexposed surfaces. The use of ceramic fiber insulation substantially increases the fire resistance of the wall and when the cavity is partially filled with this material, if the blanket is placed towards the exposed side, enhanced insulation fire resistance is achieved. Based on the finite element method, a numerical validation was conducted using a special hybrid approach that used experimental temperature values inside the cavities or insulation blankets. This approximation was essential to improve the numerical results. Also, the employment of an air layer, located at specific regions of the models, helped to improve the numerical results, introducing an extra thermal resistance. A new simplified approach was proposed based on the improved design model available in the literature, and the results obtained are consistent with the experimental results. The predicted insulation fire resistance of the numerical and simplified methods agreed well with the experimental results and useful information is supplied to support further numerical and experimental studies.
Article
Lightweight cold‐formed steel (CFS) construction solutions are increasingly adopted in low and mid‐rise buildings. Many different materials are used to construct CFS wall systems, without a full understanding of their thermal properties. For many of these materials, only ambient temperature thermal properties are available from their manufacturers. This creates difficulty in classifying the materials for use at elevated temperatures. In this study, a series of elevated temperature thermal property tests to measure specific heat, thermal conductivity, and mass loss was conducted for a range building materials from wallboards, insulation, and phase‐change materials (PCMs), used in Australia and several other countries. Simultaneous Thermal Analyser and Laser Flash Apparatus were used to determine the elevated temperature thermal properties of the selected materials, gypsum plasterboard, PCM incorporated gypsum plasterboard, magnesium sulphate board, fibre cement board, cellulose insulation, vacuum insulation panel, microencapsulated paraffin PCM, and bio‐based PCM. Their elevated temperature thermal properties are presented in this article, which also includes analyses of their chemical composition and associated chemical reactions at elevated temperatures. These results can be used in the selection of suitable energy‐efficient and fire‐resistive materials, and in heat transfer modeling to identify wall configurations with increased fire resistance and energy efficiency.
Article
Robust and pre-fabrication construction techniques are the cutting edge practice in the building industry. Cold-frame, warm-frame and hybrid-frame are three common Light-gauge Steel Frame (LSF) wall constructions applied for better energy performance. Still, the applications of the aforementioned wall configurations are restricted due to limited fire safety studies. This paper presents the fire performance investigations and results of cold-frame, warm-frame, and hybrid frame LSF walls together with three novel configurations maintaining the same material quantities. Successfully validated 3D heat transfer finite element models were extended to six wall configurations. Time variant temperature profiles from Finite Element Analyses were evaluated against the established Load Ratio (LR)-Hot-Flange (HF) temperature curve to determine the structural fire resistance. Modified warm-frame construction showed the best performance where the Fire Resistance Level (FRL) is approximately twice that of conventional LSF wall configurations. Hence, the novel LSF wall configurations obtained by shifting the insulation material toward the fireside of the wall make efficient fire-resistant wall solutions and the new designs are proposed to be incorporated in modular constructions for enhanced fire performance. Keywords: Fire Performance, Cold-Frame, Warm-Frame, Hybrid-Frame, LSF Wall Configurations, Modular Walls, Standard Fire, FRL
Article
Light gauge steel framed (LSF) wall systems made of cold-formed steel studs and lined with different types of wallboards are increasingly used for various purposes. Gypsum plasterboards are commonly used for fire protection purposes, while recently other types of wallboards are being used based on their improved thermal and physical performance but without an understanding of their fire resistance. To increase the thermal mass of LSF wall systems, phase change materials (PCMs) with high thermal storage capacity can be used, but since some organic PCMs increase the fuel load in fire, bio-based PCMs are preferred as they are less flammable than paraffin based PCMs. However, the fire resistance of LSF wall systems incorporated with bio-based PCM has not been investigated. Therefore, this research study investigated the thermal properties of selected wallboards first and then the fire resistance of non-load bearing LSF wall systems lined with different types of wallboards such as gypsum plasterboard, magnesium sulphate board, vermiculux board and fibre cement board using standard fire tests including a thermal mass improved LSF wall system using bio-based PCM mat. Findings revealed that gypsum plasterboard gives the highest fire resistance, whereas the fibre cement board gives the lowest. Importantly, the thermal mass improved LSF wall system did not exhibit any reduction to its fire resistance due to the use of bio-based PCM mat. This paper presents the details of the standard fire tests of LSF wall systems and the results.
Article
Rigid polyurethane foams (RPUFs) exhibit short times to ignition as well as rapid flame spread and are therefore considered to be hazardous materials. This paper focuses on the fire phenomena of RPUFs, which were investigated through a multimethodological approach. Water-blown polyurethane (PUR) foams without flame retardants (FRs) as well as water-blown PUR foams containing triethyl phosphate as a gas phase-active FR were examined. The aim of this study is to clarify the influence of the FR on the fire phenomena during combustion of the foams. Additionally, materials’ densities were varied to range from 30 to 100 kg/m³. Thermophysical properties were studied by means of thermogravimetry; fire behavior and flammability were investigated via cone calorimeter and limiting oxygen index, respectively. During the cone calorimeter test, the temperature development inside the burning specimens was monitored with thermocouples, and cross sections of quenched specimens were examined visually, giving insight into the morphological changes during combustion. The present paper delivers a comprehensive study, illuminating phenomena occurring during foam combustion and the influence of a FR active in the gas phase. The superior fire performance of flame-retarded PUR foams was found to be based on flame inhibition, and on increased char yield leading to a more effective protective layer. It was proven that in-depth absorption of radiation is a significant factor for estimation of time to ignition. Cross sections investigated with the electron scanning microscope exhibited a pyrolysis front with an intact foam structure underneath. The measurement of temperature development inside burning specimens implied a shift of burning behavior towards that of non-cellular materials with rising foam density.