3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
Indoor relative humidity: relevance for health,
comfort, and choice of ventilation system
Maria Coral Albelda-Estellés Ness1
1Norwegian University of Science and Technology, Trondheim, Norway
ABSTRACT: It is generally recommended to keep the values of relative humidity (RH) indoors between
40 and 60% for comfort and health. However, the environment in our homes and offices is a lot dryer in
the winter, going down to 20% or less in cold climates. We can be in such dry environments for short
periods, but in the long term we might get physiological impairments such as dry or irritated eyes, nose,
throat and skin, and even an increase on headaches and respiratory or skin diseases and allergies. On
the other hand, too high values of relative humidity can promote growth of fungi and mites, and create
moisture problems in building materials. Those problems could be solved by finding a balance between
ventilation rate and indoor humidity production, in combination with moisture absorbing materials.
However, these strategies work better with lower air speed and ventilation rate, which may in turn conflict
with the need for fresh air to compensate for the production of CO2 and other pollutants. Typically,
mechanically ventilated spaces tend to have a lower RH than those with natural ventilation, independently
of the season and indoor temperature, since their main focus is providing enough fresh air to keep CO2
levels below 1000ppm. Recently, it has gained acceptance to monitor temperature, humidity and CO2 for
indoor air quality and health, which has the potential to show their interactions and help find an optimal
balance between them. We carried a building performance simulation (BPS)analysis of an office building
with an optimized design for passive strategies and automation in cold climate. Instead of focusing on
high air changes, this building uses extra high floors for stratification of temperature and pollutants, to
reduce the need for ventilation in winter. Then we compared indoor RH under natural and mechanical
ventilation, to reflect on the effect of the ventilation system.
KEYWORDS: relative humidity; thermal comfort; indoor air quality; building performance simulation
1. INTRODUCTION
The indoor environment in our homes and offices tends to be too dry in the cold and intermediate seasons.
With a relative humidity as low as 20% or even less, we may experience dry or irritated skin, eyes, nose
and throat, more frequent headaches or even respiratory or skin diseases and allergies (Wolkoff 2018).
That happens because when we warm up the incoming air from a colder environment, it gets dryer. Its
water content does not change, but its relative humidity decreases since the air can contain more humidity
as it gets warmer. In cold climates, the warmer indoor air can host up to 10 times more humidity than the
colder outdoor air. This means that as we ventilate a room, we are actually removing water vapour from
it. So, the room air gets dryer unless we balance the ventilation rate with the production of humidity indoors
(occupants, plants, cooking, bathing), use moisture absorbing materials that help buffering the changes
in relative humidity, and/or lower the temperature (Woloszyn et al. 2009).
We can be in such dry environments for short periods, but if prolonged in time, we might get certain
physiological impairments, especially in our skin, eyes, nose and throat, with dryness and irritation, more
frequent headaches or even respiratory or skin diseases and allergies. Therefore, it is generally
recommended to keep the values of relative humidity indoors between 40 and 60% for comfort and health.
(Arundel et al. 1986)
With a relative humidity of less than 40%, we become more vulnerable to viral respiratory infections,
because of the drying of our mucous membranes. In addition, low humidity levels activate the evaporation
of water in cough droplets, so that they shrink and get a prolonged suspension in the air and ability to
travel faster and longer thanks to their smaller size. (Ahlawat, Wiedensohler, and Mishra 2020)
3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
On the other hand, too high levels of humidity can promote growth of fungi and mites, and create moisture
problems in building materials (mould, decay, condensation, corrosion), which in turn can also affect your
health. (Baughman and Arens 1996)
Keeping optimal indoor humidity levels in the winter might be challenging because of our competing
demands for thermal comfort and air quality. As indoor air gets polluted over time by the users (CO2,
odours) and by the materials inside our buildings (emissions, odours), we need to ventilate the rooms to
get more fresh air. On the other hand, new research about comfortable conditions and air quality in
commercial aircrafts suggest that the current limits for CO2 concentration used in buildings may be
overestimated (Giaconia, Orioli, and Di Gangi 2013). The current maximum levels of 1000-1200ppm have
been calculated as a function of the acceptable outdoor CO2 concentration (350 to 500ppm) and
ventilation rates of 7.5 L/s per person. Relatively high values of CO2 concentration are not toxic “per se”,
but they are usually correlated to stuffy air and odours from bio-effluents. Following new findings, the limit
of carbon dioxide in workplaces may be safely set to 2000ppm for comfort and 5000ppm for safety
(EuropeanStandard 2009).
In addition, we have gotten used to warmer indoor temperatures in our buildings, which in turn produce
lower air moisture levels.
However, the biggest challenge when attempting to assess the impact of too dry environments on us is
that we do not have dedicated moisture sensors in our bodies (Pfluger et al. 2013). As we cannot directly
perceive water vapour, the perception of “dry air” can occur as a side effect of increasing temperature,
pollution (CO2, odours) or dust levels, which makes it difficult to isolate and measure.
In addition, we are much more sensitive to the effect of respiratory cooling, where the nose acts as a
regenerative heat and moisture exchanger (Pfluger et al. 2013). This means that the air we breathe in is
effectively helping us to cool down by convection and evaporation inside the nose. Therefore, lower
temperature and humidity levels will create a pleasant, cool and “fresh” sensation, despite constant
“pollution” of the air. In contrast, higher temperatures and relative humidity can give an impression of
“stuffy” air (Fang, Clausen, and Fanger 1998).
Besides, the moisture absorption/desorption by the materials is a very slow process that may take up to
one year or more, which makes it more complex to simulate and test.
Since relative humidity is inversely related to temperature, a very easy way to improve the environment
in a building could be to lower the indoor temperature. If you keep it down to 21°C instead of 25°C, you
can obtain a 10% increase in the moisture level, which can significantly help improving comfort and health.
However, the combined need to balance out ventilation against moisture production and allow enough
time for the building materials to react with ambient humidity, might still make it necessary to lower air
speed and ventilation rate inside the building. That is why mechanically ventilated spaces tend to provide
a dryer environment than those with natural ventilation, independently of the season and indoor
temperature (Alsmo and Alsmo 2016). Mechanical systems generally focus on higher ventilation rates to
give a sensation of “fresh air” and compensate for pollutants production. In the past, they tried to humidify
the incoming air to get a moister environment, but this created sometimes problems with bacterial growth
(legionella) inside the conditioning equipment.
More recently, it has gained more acceptance to monitor both temperature, humidity and CO2 in office
buildings, to improve indoor air quality perception and fight/reduce sick building syndrome (SBS) (Redlich,
Sparer, and Cullen 1997). This can allow us to see more clearly their interactions and find a better balance
between their competing strategies.
In order to better appreciate the correlation between ventilation rate, relative humidity and CO2
concentration, we have carried out a building performance simulation (BPS) analysis of an office building
with two different ventilation solutions, but with similar temperature curves. In this way, we tried to limit
the variables of the systems so that we could appreciate the changes in relative humidity and CO2
concentration, depending mainly on the ventilation rate.
3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
2. METHODS
The case analysed in this study is Baumschlager-Eberle 22/26, an office building in Lustenau (Austria)
with automated natural ventilation, instead of a conventional mechanical ventilation system. It was chosen
because of being a rather extreme example of passive design optimization for cold climate resulting
in very stable indoor conditions throughout the year. The most interesting quality of the indoor environment
in this building is actually the near-optimal range for relative humidity, which is within 35-60% even in the
cold and intermediate seasons (Hugentobler et al. 2016). These values are in contrast with the much
lower humidity levels (down to 10-30%) that are so common in energy efficient buildings, for similar
outdoor conditions (Frei, Reichmuth, and Huber 2004; FGK 2015).
Within the building, we focused on the second floor, where the local office for the architectural firm
Baumschlager-Eberle is located. Being an intermediate floor, it is not affected by border conditions just
below the roof or right above the ground, limiting its interaction with the outdoor climate just through the
façade. Then, we chose the office on the north-west corner because of being the most critical orientation
for the cold season, with least amount of solar radiation during working hours.
Figure 1. We modelled the whole building in DesignBuilder but focused on the North-west office on the second floor,
for the simulations. Images from DesignBuilder.
The energy concept of the building is referred to as “Concept 22/26” (Eberle, Aicher, and Hueber 2016).
Its objective is to keep the room temperatures throughout the year between 22 and 26°C, to keep a
comfortable indoor environment while minimising the use of resources (materials, space, energy). In order
to do so, the building envelope must have a very low heat transfer and a high thermal capacity. Moreover,
the mechanical HVAC system has been replaced here by a building automation system that operates
window opening for natural ventilation (fresh air and cooling), and lighting system for backup heating.
Indoor temperature, relative humidity and CO2 concentration are measured by sensors in every office, to
ensure user comfort and energy efficiency (Junghans and Widerin 2017).
The extensive use of passive strategies include:
− compact shape, as a cube of around 24 x 24 x 24 m3, to minimize heat loss
− exposed thermal mass indoors, to flatten temperature fluctuations
− high levels of insulation (average wall U-value=0.138)
− very airtight envelope (n50=0.51 on blower door test)
− window-to-wall ratio around 20%
− near-floor-height windows, for good daylight distribution
− triple glazing (U-value=0.7, SHGC-value=0.55)
− narrow vertical vents (VIP) by each window, for natural ventilation (cooling / fresh air)
− window position by inner surface of external walls, for shading
− high ceilings (3.4m) to allow for temperature and CO2 stratification, thus limiting the need for
natural ventilation in the heating season
NW
3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
wall
U-value (W/m2 K)
0.138
Internal heat capacity (KJ/m2 K)
85.76
Infiltration rate (ac/h)
0.037
window
U-value (W/m2 K)
0.7
Solar transmittance factor (SHGC)
0.55
Table 1. Main characteristics of the building envelope (Junghans and Widerin 2017).
The high-performance building envelope allows the use of the internal gains to cover most of the heating
demand in the cold seasons. The automated natural ventilation is then limited to providing fresh air to
meet indoor air quality requirements. A downside of having natural ventilation directly from the façade is
the reduction in the occupancy density. In order to protect the users from draft, they have to seat at a
distance from the windows. In this case, this is resolved by placing the circulation by the façade, instead
of by the core.
Then the lighting system functions also as backup heating, which is possible thanks to the high-
performance envelope, that minimizes heating needs. Yet, it had to be resolved with low efficiency
luminaries (fluorescent tubes), in order to provide enough heat. This use of the lighting system as a backup
heating is needed mainly in the heating season, when very low temperatures are expected in the early
hours of the working day. Even though this could be considered as some sort of electric heating, it has
the advantage of using an already existing system for two different functions (lighting and heating), instead
of installing two different systems. The equipment considered for the internal gains corresponds to one
computer and two screens per user.
Occupancy density (people/m2)
0.05
Equipment (W/m2)
11.50
Lighting (W/m2)
5.0
Table 2. Internal gains (Junghans and Widerin 2017).
We used Meteonorm (Remund 2008) to create the typical meteorological year (TMY) weather file for
the BPS analysis in Lustenau, by interpolation from the nearest weather stations (latitude 47.25°N,
longitude 9.39°E, altitude 405m). This file was obtained as the average from 10 years of temperature
measurements (2000-2009) and 20 years of solar radiation (1991-2010).
Figure 2. Psychrometric chart for the outdoor climate in Lustenau, Voralberg, Austria.
With a mean temperature of the warmest month 19.6°C and 0.6°C for the coldest, it corresponds to a
Köppen climate type Cfb (temperate, with warm summer and no dry season). Also, with 2980 HDD18 and
1277 CDD10, it gives an ASHRAE type 4A (mixed and humid). In this temperate (borderline with cold)
climate, only 8.6% of the hours fall inside the comfort zone, prior the application of any passive strategies
for climate adaptation.
8.6% comfortable hours
3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
Next, we performed the BPS analysis of the building in EnergyPlus with DesignBuilder as graphical user
interface (GUI). These tools were chosen because of their capability for simulating the behaviour of
thermal mass and moisture buffering of the materials in use, as well as the possibility for extensive tailoring
in the operation of building components and systems with EMS coding (energy management systems).
(Crawley et al. 2001; Ellis, Torcellini, and Crawley 2008)
We considered two cases in our simulations, one with natural ventilation and one with mechanical
ventilation, where we included a whole year warm up period with internal gains, to allow the full thermal
and moisture load of the materials. Then, the moisture buffering properties of the different construction
elements were introduced, so that we could use the EMPD (effective moisture penetration depth)
calculation method for heat and mass transfer. This was necessary in order to produce a more accurate
approximation to the indoor relative humidity. We chose the EMPD method over the more detailed HAMT,
because it produces very close results to those from HAMT but with much shorter simulation time and
fewer errors (Woods, Winkler, and Christensen 2013).
For the case with natural ventilation, we designed the vents to resemble the original ones in BE2226 as
much as possible (narrow VIP panels on north side of each window, along their whole height, with an
opening of 45° to the outside). These vents are controlled by the EMS to maintain optimal values of indoor
air temperature and CO2 concentration. Then, the lighting system responds to the need for adequate light
levels (500 lux) in the occupied hours, acting as well as backup heating if needed (but off during the night,
in consideration to the neighbours). This system is also controlled by EMS coding.
For the mechanical ventilation, we used a heating, ventilation and air conditioning system (HVAC) with
heat recovery and without setback schedule (always on). We used the HVAC settings for best practice in
Austria (DesignBuilder) with default horizontal vents auto created under the windows, to allow enough air
circulation in such an airtight building. In reality, this could have been solved more neatly by having a
balanced ventilation system, but this option was not available in the software. Also, it is common practice
to introduce a setback schedule for the unoccupied hours, but then we obtained higher indoor
temperatures, so we opted for keeping the system always on to obtain a temperature curve as similar as
possible to the one from the natural ventilation case, for comparability.
3. RESULTS & DISCUSSION
As mentioned earlier, we wanted to study the results from the natural ventilation and automated controls,
in contrast with a comparable HVAC system (similar thermal behaviour but higher ventilation rate).
Figure 2. Annual air temperature comparison between automated natural ventilation and HVAC system
We tried to match the temperature curves from the two systems, so that we could see more clearly the
effect of the ventilation rate on the relative humidity and CO2 concentration. The automated natural
ventilation allowed for a somewhat higher variability and was not so capable to control the summer peaks.
At the same time, this system was also providing slightly higher winter temperatures. Still, they pose a
reasonable match, given how different the two systems are, both in principle and operation.
-10
0
10
20
30
J F M A M J J A S O N D
Temperature (°C)
TC-winter TC-summer NatVent HVAC-alwaysON To
3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
Figure 3. Relative humidity comparison from the two systems under study.
We allowed for a whole year warm up period with internal gains (bi-annual simulation run period).
Compared to the conventional annual simulation, only the relative humidity with natural ventilation offered
a significant difference, for the first months before the summer. When compared with the relative humidity
from the HVAC system, we can appreciate an important increase in the winter months, getting much
closer to the recommended 40%. In the summer months, we get slightly more stable values with natural
ventilation, though both systems give similar curves. It seems like the lower ventilation rate of the
automated natural ventilation allows the moisture buffering properties of the materials to soften the curve
and increase the average values for the relative humidity.
Figure 4. Air CO2 concentration comparison for the natural and mechanical ventilation systems.
In contrast, the HVAC system provides a better indoor air quality with respect to CO2 concentration,
keeping it within the optimal range. The natural ventilation system, by prioritising a low ventilation rate that
activates the moisture buffering of the materials, allows the CO2 concentration in the winter to raise to the
higher limits of what is acceptable, yet it does not allow it to increase over 1200 ppm. In the summer, on
the other hand, the levels of CO2 are even lower with natural ventilation, though both of them produce
values far below the limits.
In the graphical comparison between the two systems, it becomes apparent the difference in ventilation
rates, where the HVAC system usually produces more than double the air changes per hour even in the
summer.
0
20
40
60
80
100
J F M A M J J A S O N D
Relative humidity (%)
optimal RH HVAC-alwaysON NatVent
0
200
400
600
800
1000
1200
1400
J F M A M J J A S O N D
CO2concentration (ppm)
best acceptable max NatVent HVAC-alwaysON
3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
Figure 5. Comparison between ventilation rates for the natural and mechanical ventilation.
Even though the annual curves for the air temperature are a reasonably close match, the differences in
relative humidity result in a very different indoor climate for the natural ventilation and the HVAC system.
While the first is mainly grouped between 30% and 60% relative humidity curves, most of the latter spreads
between 15% and 55%. Still, they both have a very high number of hours inside the comfort zones for
winter (left) and summer (right), though slightly higher for the natural ventilation (89h vs. 84h).
Figure 6. Psychrometric charts with the indoor climates created by the two systems. To the left is the natural ventilation,
and the HVAC to the right. (Climate Consultant)
We can observe some overheating in the summer months, occurring for both systems, but more significant
for the natural ventilation. This could be greatly reduced by adding solar shading to the windows, not
present in the original building.
This paper studies the effect that the choice of ventilation system can have on the indoor relative humidity
(RH) and CO2 concentration. The aim was to provide similar thermal behaviour with different ventilation
rates, so that the resulting RH and CO2 could be compared. Then again, HVAC systems are rather
complex and could be fine-tuned to provide a similar environment to that from the automated natural
ventilation. The question in this exercise was not whether to use natural or mechanical ventilation, but to
become aware of the need to adjust the ventilation rates to achieve a better balance between our
competing needs for RH and CO2. Traditionally, the main objective was to achieve low CO2
concentrations, even at the expense of creating too dry environments. Nowadays though, we know more
about the possible adverse effects of too low RH for our health in the long term (Pfluger et al. 2013), so
we ought to consider both parameters when designing the ventilation system of our choice.
0
5
10
15
20
J F M A M J J A S O N D
Ventilation rate (ach)
NatVent HVAC-alwaysON
83.9% in Thermal Comfort
89.1% in Thermal Comfort
3rd Valencia International Biennial of Research in Architecture
November, 9-11,2022 | Valencia
4. CONCLUSION
As a general recommendation, we should try to keep air humidity levels within the optimal values of 40-
60% for human health in indoor spaces. This can be best achieved by balancing ventilation rate with
moisture production, combined with moisture absorbing materials and lower indoor air temperature. An
important step for finding this balance while ensuring a good indoor air quality is to monitor both RH,
temperature and CO2 concentration, so that we can adjust the ventilation rates according to our needs.
A revision of the current limits for CO2 concentration indoors to include the latest findings from the research
community would be of great help for finding a more reasonable balance between the competing interests
for CO2 and RH, for indoor air quality, health and comfort.
Then, further research is needed in order to update the Building Bioclimatic Chart and thermal comfort
standards to include more reasonable limits of RH for health and comfort.
5. REFERENCES
Ahlawat, Ajit, Alfred Wiedensohler, and Sumit Kumar Mishra. 2020. "An overview on the role of relative humidity
in airborne transmission of SARS-CoV-2 in indoor environments." Aerosol and Air Quality Research
20 (9):1856-1861.
Alsmo, Thomas, and Catharina Alsmo. 2016. "A Comparison of Relative Humidity between Two Swedish
Buildings with Different Ventilation Solutions." Journal of Environmental Protection 7 (6):855-873.
Arundel, Anthony V, Elia M Sterling, Judith H Biggin, and Theodor D Sterling. 1986. "Indirect health effects of
relative humidity in indoor environments." Environmental health perspectives 65:351-361.
Baughman, Anne, and Edward A Arens. 1996. "Indoor humidity and human health--Part I: Literature review of
health effects of humidity-influenced indoor pollutants."
Crawley, Drury B, Linda K Lawrie, Frederick C Winkelmann, and Curtis O Pedersen. 2001. "EnergyPlus: new
capabilities in a whole-building energy simulation program." Proceedings of building simulation.
Eberle, Dietmar, Florian Aicher, and Eduard Hueber. 2016. be 2226 Die Temperatur der Architektur/The
Temperature of Architecture: Portrait eines energieoptimierten Hauses/Portrait of an Energy-
Optimized House: Birkhäuser.
Ellis, Peter G, Paul A Torcellini, and D Crawley. 2008. Simulation of energy management systems in EnergyPlus.
National Renewable Energy Lab.(NREL), Golden, CO (United States).
EuropeanStandard. 2009. CSN EN 4618: Aerospace series - Aircraft internal air quality standards, criteria and
determination methods.
Fang, Lei, Geo Clausen, and Povl Ole Fanger. 1998. "Impact of temperature and humidity on the perception of
indoor air quality." Indoor air 8 (2):80-90.
FGK. 2015. Fragen und Antworten zur Raumluftfeuchte, Report 8. Fachverband Gebäude-Klima e.V.
Frei, B, F Reichmuth, and H Huber. 2004. "Comparative evaluation of Swiss' passive'houses; Vergleichende
Auswertung schweizerischer Passivhaeuser."
Giaconia, Carlo, Aldo Orioli, and Alessandra Di Gangi. 2013. "Air quality and relative humidity in commercial
aircrafts: An experimental investigation on short-haul domestic flights." Building and Environment
67:69-81. doi: 10.1016/j.buildenv.2013.05.006.
Hugentobler, Walter, Peter Widerin, Lars Junghans, and Willem Bruijn. 2016. "DO HEALTHY BUILDINGS NEED
TECHNOLOGY?" Indoor Air 2016 - 14th International Conference of Indoor Air Quality and Climate,
Ghent, 3-8 July 2016.
Junghans, L., and P. Widerin. 2017. "Thermal comfort and indoor air quality of the “Concept 22/26”, a new high
performance building standard." Energy and Buildings 149:114-122. doi:
10.1016/j.enbuild.2017.05.020.
Pfluger, Rainer, Wolfgang Feist, Andreas Tietjen, and Andreas Neher. 2013. "Physiological impairments of
individuals at low indoor air humidity." Gefahrstoffe Reinhaltung der Luft 73 (3):107-108.
Redlich, Carrie A, Judy Sparer, and Mark R Cullen. 1997. "Sick-building syndrome." The Lancet 349
(9057):1013-1016.
Remund, Jan. 2008. "Quality of meteonorm version 6.0." Europe 6 (1.1):389.
Wolkoff, Peder. 2018. "Indoor air humidity, air quality, and health – An overview." International Journal of
Hygiene and Environmental Health 221 (3):376-390. doi: https://doi.org/10.1016/j.ijheh.2018.01.015.
Woloszyn, Monika, Targo Kalamees, Marc Olivier Abadie, Marijke Steeman, and Angela Sasic Kalagasidis.
2009. "The effect of combining a relative-humidity-sensitive ventilation system with the moisture-
buffering capacity of materials on indoor climate and energy efficiency of buildings." Building and
Environment 44 (3):515-524. doi: https://doi.org/10.1016/j.buildenv.2008.04.017.
Woods, J, J Winkler, and Dane Christensen. 2013. Evaluation of the effective moisture penetration depth model
for estimating moisture buffering in buildings. National Renewable Energy Lab.(NREL), Golden, CO
(United States).