MERV 13 Filtration for Office Buildings During COVID-19 Pandemic

Authors:

Abstract and Figures

The COVID-19 pandemic increased the need for buildings to protect occupants from infection due to airborne pathogens. This paper investigates the use of filtration to remove viral particles in the air handling system, specifically studying trade-offs between filter quality and operational cost. While high-efficiency filters remove viral particles more effectively, they also tend to increase the pressure drop and energy use in the air handling system. Two HVAC filters are compared: (1) moderately rated MERV 10 filter and (2) more efficient MERV 13 filter. These filters are evaluated for a five-zone medium office building in a cold and dry climate, modeled using the Modelica Buildings library. New models for the HVAC filters and virus behavior are developed to support this study. The results show MERV 13 filtration reduces the average virus concentration by about 10% compared to MERV 10 filtration, but increases the annual energy consumption by about 3%.
Content may be subject to copyright.
Proceedings of the 12
nd
International Symposium
on Heating, Ventilation and Air Conditioning (ISHVAC 2021)
Seoul, Korea, 24-26 November 2021
1
MERV 13 Filtration for Office Buildings During COVID-19 Pandemic
Cary A. Faulkner
1
, John E. Castellini Jr.
1
, Wangda Zuo
1,2,*
, David M. Lorenzetti
3
, Michael D.
Sohn
3
1
University of Colorado Boulder, Boulder, CO, U.S.A.
2
National Renewable Energy National Laboratory, Golden, CO, U.S.A.
3
Lawrence Berkeley National Laboratory, Berkeley, CA, U.S.A.
*
Corresponding email: Wangda.Zuo@colorado.edu
ABSTRACT
The COVID-19 pandemic increased the need for buildings to protect occupants from infection due
to airborne pathogens. This paper investigates the use of filtration to remove viral particles in the air
handling system, specifically studying trade-offs between filter quality and operational cost. While high-
efficiency filters remove viral particles more effectively, they also tend to increase the pressure drop and
energy use in the air handling system. Two HVAC filters are compared: (1) moderately rated MERV 10
filter and (2) more efficient MERV 13 filter. These filters are evaluated for a five-zone medium office
building in a cold and dry climate, modeled using the Modelica Buildings library. New models for the
HVAC filters and virus behavior are developed to support this study. The results show MERV 13 filtration
reduces the average virus concentration by about 10% compared to MERV 10 filtration, but increases the
annual energy consumption by about 3%.
KEYWORDS: COVID-19, Indoor Air Quality, HVAC Filtration, Modelica.
1 INTRODUCTION
Improving indoor air quality in buildings is important to reduce the risk of infection from airborne
transmission during the COVID-19 pandemic. It is well known that the risk of COVID-19 infection is
significant indoors. For example, one recent study (Qian et al., 2021) identified 318 outbreaks of three or
more COVID-19 cases in China and found all occurred in indoor environments. Consequently,
organizations like ASHRAE issued guidelines (ASHRAE, 2021) to improve indoor air quality in buildings
to reduce the risk of infection. These guidelines included recommendations for operating the heating,
ventilation, and air-conditioning (HVAC) system, such as achieving at least Minimum Efficiency Reporting
Value (MERV) 13 level filtration for recirculating air. More efficient filters are beneficial to removing
recirculating viral particles in the air handling system, but have potential negative impacts as well.
Particularly, more efficient filters may be more expensive or increase the pressure drop through the air
handling system with a higher fan energy consumption (Zaatari et al., 2014). Some HVAC systems may
not even be sized to overcome the increased pressure drop of high efficiency filters. In this paper, we discuss
the research required to quantify the trade-offs when increasing filter efficiency.
Previous literature tried to study trade-offs of HVAC filter efficiency. Azimi and Stephens (2013)
compared the trade-offs of risk reduction of influenza virus and annual cost for different HVAC filters.
2
They found that increasing filtration efficiency is beneficial to reducing risk of infection, but reaches a level
of diminishing returns for risk reduction with more significant increases in annual cost for the most efficient
HVAC filters. Pease et al. (2021) investigated the effect of filtration efficiency on indoor virus
concentration and probability of infection for COVID-19 virus. They also found that increasing filtration
reduces risk of infection, but the risk reduction becomes relatively smaller beyond MERV 8 level filtration.
Although notable progress has been made in the literature to quantify the impacts of increased
filtration efficiency, further scientific advancement can be achieved. Some of the above studies may have
benefitted from the use of detailed modeling to fully account for the dynamics of the HVAC system. For
example, the supply flow rates and outdoor air fractions are often assumed to be constant for a given
scenario. Some also often assume steady-state virus concentrations when evaluating risk of infection.
However, these values are dynamic in practice and affect the predicted risk of infection and operational
cost.
This paper aims to address these considerations through detailed dynamic modeling of an HVAC
system. We develop a dynamic system model based on the Modelica Buildings library (Wetter et al., 2014)
to compare moderate MERV 10 level filtration and more efficient MERV 13 level filtration. Detailed
HVAC system modeling with the Modelica language has been used to perform dynamic analyses for
various applications, such as data center cooling energy efficiency (Fu et al., 2019) and chiller plant control
performance (Fan et al., 2021). Additionally, new models for HVAC filters and indoor virus behavior are
developed to support this study.
In Section 2 we describe the development and implementation of new models for HVAC filtration
and indoor virus behavior into an existing HVAC system model for a medium office building located in a
cold and dry climate. The results for indoor virus concentration and energy consumption are then
summarized in Section 3. Finally, conclusions are drawn in Section 4.
2 MODEL IMPLEMENTATION
We developed an HVAC system model for a medium office building that incorporates new models
to support this study. First, we describe the prototype medium office building. We then describe the new
models for HVAC filtration and indoor virus behavior.
2.1 Description of Building System
The building model is based on the DOE commercial reference medium office building (Field et al.,
2010; DOE), with a focus on expressing the bottom floor. This floor contains five zones as shown in Figure
1, which are assumed to be well-mixed in the model. The Core zone has a volume of 2,698 m3, the North
and South zones have volumes of 569 m3, and the East and West zones have volumes of 360 m3. The HVAC
system consists of a central air handling unit with heating and cooling coils that serve this floor. Each zone
has variable-air-volume (VAV) terminal boxes with reheat coils, as well. The HVAC system is sized for
the studied climate of Denver, Colorado, USA, which is a cold and dry climate. Cooling is provided using
a chilled water system and heating is provided via a hot water system. The system is controlled based on
the VAV 2A2-21232 control sequence from the Sequences of Operation for Common HVAC Systems as
described in (Wetter et al., 2018).
3
Figure 1. Floor layout of medium office building.
2.2 HVAC Filter Model
An HVAC filter model was developed to support this study. This model incorporates two key features:
1) the filtration of viral particles based on a defined efficiency value and 2) the added system pressure drop
due to the filter. First, the removal of viral particles from the airflow through the filter is described as:
ܿ௢௨௧ =1−ߟ௙௜௟௧௘௥ܿ௜௡, (1)
where cout is the virus concentration in the airflow leaving the filter, ηfilter is the defined filter efficiency, and
cin is the virus concentration in the airflow entering the filter.
Next, the static pressure drop across the filter is calculated as:
Δ݌௙௜௟௧௘௥ =݇௙௜௟௧௘௥ ݉௙௜௟௧௘௥
, (2)
where Δpfilter is the static pressure drop caused by the filter, ݉
݂݈݅ݐ݁ݎ is the mass flow rate of airflow through
the filter, and the constant kfilter is determined as:
݇௙௜௟௧௘௥ =୼௣೙೚೘
೙೚೘
, (3)
where Δpnom is the nominal pressure drop for the nominal mass flow rate, ݉௡௢௠ . As the inputs to the filter
model, these values depend on the filter rating and are shown in Table 1. The filter efficiency values come
from ASHRAE Standard 52 (ASHRAE, 2017) assuming viral particle diameters in the range of 1-3 μm.
The values of the nominal pressure drop come from data for MERV 10 (Dwyer, a) and MERV 13 (Dwyer,
b) filters. The nominal pressure drop settings are chosen based on the average initial resistance and final
resistance for the nominal flow rate. A summary of the filter simulation settings is shown in Table 1.
Table 1. HVAC filter model values.
Filter Nominal Pressure Drop (Pa) Efficiency
MERV 10 143 50%
MERV 13 162 85%
2.3 Virus Transport Modeling
In addition, we develop new models to represent virus behavior indoors. First, we model a single
“sick” person in each zone working from 9:00 AM to 5:00 PM, Monday through Friday throughout the
year. These sick people generate viral particles based on a constant quanta generation rate of 100 quanta/hr,
where a quantum is the dose of viral droplet nuclei that is expected to cause infection in 63% of susceptible
people (Buonanno, 2020). The viral particles were generated in the well-mixed zones when the sick people
were present.
Viral decay due to death of airborne virus was also modeled in this study. The viral decay is described
as:
4
ܿሶௗ௘௖௔௬,௭௢௡௘ =݇ௗ௘௖௔௬ܿ௭௢௡௘ , (4)
where ܿሶௗ௘௖௔௬,௭௢௡௘ is the rate of viral decay in the zone, kdecay is the constant rate of viral decay, and czone is
the virus concentration in the zone. This equation has been used to model viral decay in well-mixed zones
in the literature (Pease, 2021).
Finally, risk of infection based on the virus concentration is calculated using the Wells-Riley
approach (Riley et al., 1978) as:
ܴݐ=1−exp (ܫܴ ׬ܿݐ݀ݐ
), (5)
where R(t) is the risk of infection in terms of percentage, IR is the volumetric inhalation rate of air for an
occupant, and ׬ܿݐ݀ݐ
is the integral of virus concentration in the room since time t0. The predicted
number of infections in a zone can be calculated based on the risk as:
ܴݐ=ܴܵ(ݐ), (6)
where R0(t) is the predicted number of infections over time and S is the number of susceptible occupants in
the zone.
3 RESULTS
The heat maps in Figure 2 show the magnitude of normalized concentration during different times
of the day throughout the entire year. The normalized concentration, c0, is the annual average concentration
for MERV 10 level filtration and is used throughout this study. The heat maps show MERV 13 level
filtration reduces the magnitude of virus concentration compared to MERV 10 level filtration, as seen by
the overall darker magnitudes of concentration for the MERV 10 heat map. Both heat maps follow similar
trends, where the concentration increases quickly at 9:00 AM when the sick people arrive, reaches its peak
during the day, then falls when the sick people leave and the virus decays and is flushed out of the building.
Additionally, a higher concentration can be seen during the middle of the year, especially for MERV 10
level filtration. This is because during the summer the system tends to supply the minimum outdoor air to
save on cooling energy. Since these filters do not remove 100% of viral particles, the amount of fresh
outdoor air supplied also affects the virus concentration, and more so for the less efficient MERV 10 filter.
Overall, MERV 13 level filtration reduces the average virus concentration throughout the year by about 10%
compared to MERV 10 level filtration.
Figure 2. Heat maps showing normalized virus concentration throughout the year for MERV 10
(left) and MERV 13 (right) filtration.
Next, sample concentration results for a hot summer day in the North zone are shown. This day was
chosen to show the results when the ventilation system supplies the minimum outdoor airflow, and thus
relies more on the filter to remove viral particles from the building air. Figure 3 shows the results for
normalized concentration and predicted number of infections for this day. The virus concentration results
show MERV 13 level filtration reduces the peak concentration by about 17% compared to MERV 10 level
5
filtration for this day. Additionally, MERV 13 level filtration reduces the predicted number of infections
on this day by about 0.31 compared to MERV 10 level filtration. This means that at least one infection is
predicted in the zone for both filtration strategies, but the probability of a second infection is reduced by
about 30% using MERV 13 level filtration.
Figure 3. Normalized concentration (left) and predicted number of infections (right) for the two
filters during a hot summer day.
Next, the annual energy consumption results are shown in Table 2. For this system, the fan energy is
dominant, followed by the heating energy, then cooling energy. The resistance of the filters is significant
to the fan energy consumption and the increased resistance of the MERV 13 filter shows about a 12%
increase in fan energy usage. Interestingly, the system with the MERV 13 filter uses more cooling energy
and less heating energy. This is due to the fan which dissipates heat from the motor. As the fan works harder,
the amount of dissipated heat increases, which is why the MERV 13 case sees a reduction in heating energy
but an increase in cooling energy. The total energy consumption increased by about 3% using MERV 13
level filtration compared to MERV 10.
Table 2. Annual Energy Consumption.
Filter Fan Energy
(MWhr)
Cooling Energy
(MWhr)
Heating Energy
(MWhr)
Total Energy
(MWhr)
MERV 10 32.8 13.2 26.3 72.3
MERV 13 36.7 13.5 24.3 74.5
4 CONCLUSION
Use of MERV 10 and MERV 13 level filtrations during the COVID-19 pandemic were investigated
for a medium office building in a cold and dry climate. The results showed MERV 13 level filtration
provided better indoor air quality compared to MERV 10 level filtration and could reduce the predicted
number of infections. However, use of MERV 13 level filtration increased the annual energy consumption
by about 3% due to the increase in fan energy caused by the higher resistance of the MERV 13 filter. The
provided models can be used to evaluate the trade-offs of strategies to improve indoor air quality during
the COVID-19 pandemic, including different levels of filtration or ventilation. Furthermore, these models
can be used to analyze strategies to improve indoor air quality for other virus scenarios.
5 ACKNOWLEDGEMENTS
This research was supported in part by the U.S. Defense Threat Reduction Agency and performed
under U.S. Department of Energy Contract No. DE-AC02-05CH11231. This work emerged from the
IBPSA Project 1, an international project conducted under the umbrella of the International Building
6
Performance Simulation Association (IBPSA). Project 1 will develop and demonstrate a BIM/GIS and
Modelica Framework for building and community energy system design and operation.
REFERENCES
Azimi, P., & Stephens, B. (2013). HVAC filtration for controlling infectious airborne disease transmission
in indoor environments: predicting risk reductions and operational costs. Building and environment, 70,
150-160.
Buonanno, G., Stabile, L., & Morawska, L. (2020). Estimation of airborne viral emission: Quanta emission
rate of SARS-CoV-2 for infection risk assessment. Environment international, 141, 105794.
Fan, C., Hinkelman, K., Fu, Y., Zuo, W., Huang, S., Shi, C., Mamaghani, N., Faulkner, C., & Zhou, X.
(2021). Open-source Modelica models for the control performance simulation of chiller plants with
water-side economizer. Applied Energy, 299, 117337.
Field, K., Deru, M., & Studer, D. (2010). Using DOE commercial reference buildings for simulation studies.
Fu, Y., Zuo, W., Wetter, M., VanGilder, J. W., Han, X., & Plamondon, D. (2019). Equation-based object-
oriented modeling and simulation for data center cooling: A case study. Energy and Buildings, 186,
108-125.
Pease, L. F., Wang, N., Salsbury, T. I., Underhill, R. M., Flaherty, J. E., Vlachokostas, A., Kulkarni, G., &
James, D. P. (2021). Investigation of potential aerosol transmission and infectivity of SARS-CoV-2
through central ventilation systems. Building and Environment, 197, 107633.
Qian, H., Miao, T., Liu, L., Zheng, X., Luo, D., & Li, Y. (2021). Indoor transmission of SARS‐CoV‐2.
Indoor Air, 31(3), 639-645.
Riley, E. C., Murphy, G., & Riley, R. L. (1978). Airborne spread of measles in a suburban elementary
school. American journal of epidemiology, 107(5), 421-432.
Wetter, M., Zuo, W., Nouidui, T. S., & Pang, X. (2014). Modelica buildings library. Journal of Building
Performance Simulation, 7(4), 253-270.
Wetter, M., Hu, J., Grahovac, M., Eubanks, B., & Haves, P. (2018, September). OpenBuildingControl:
Modeling feedback control as a step towards formal design, specification, deployment and verification
of building control sequences. In Building Performance Modeling Conference and SimBuild.
Zaatari, M., Novoselac, A., & Siegel, J. (2014). The relationship between filter pressure drop, indoor air
quality, and energy consumption in rooftop HVAC units. Building and Environment, 73, 151-161.
ASHRAE. (2017). Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency
by Particle Size. Retrieved from
https://www.ashrae.org/File%20Library/Technical%20Resources/COVID-19/52_2_2017_COVID-
19_20200401.pdf.
ASHRAE. (2021). Core Recommendations for Reducing Airborne Infectious Aerosol Exposure. Retrieved
from https://www.ashrae.org/file%20library/technical%20resources/covid-19/core-recommendations-
for-reducing-airborne-infectious-aerosol-exposure.pdf.
DOE. Commercial Reference Buildings. Retrieved from
https://www.energy.gov/eere/buildings/commercial-reference-buildings.
Dwyer (a). MERV 10 Pleated Filters. Retrieved from https://www.dwyer-
inst.com/PDF_files/Priced/DF10_cat.pdf
Dwyer (b). MERV 13 Pleated Filters. Retrieved from https://www.dwyer-
inst.com/PDF_files/Priced/DF13_cat.pdf.
ResearchGate has not been able to resolve any citations for this publication.
Article
Full-text available
Data center cooling accounts for about 1% of electricity usage in the United States. Computer models are pivotal in designing and operating energy-efficient cooling systems. Compared to conventional building performance simulation programs, the equation-based object-oriented modeling language Modelica is an emerging approach that can enable fast prototyping and dynamic simulation of cooling systems. In this case study, we first modeled the cooling and control systems of an actual data center located in Massachusetts using the open-source Modelica Buildings library, and then calibrated a baseline model based on measurement data. The simulation of the baseline model identified several operation-related issues in the cooling and control systems, such as degraded cooling coils, improper dead band in control settings, and simultaneous cooling and heating in air handlers. Afterwards, we used a sequential search technique as well as an optimization scheme to investigate the energy saving potentials for different energy efficiency measures aiming to address the abovementioned issues. Simulation results show potential energy savings up to 24% by resolving identified control-related issues and optimizing the supply air temperature.
Article
Full-text available
This article describes the Buildings library, a free open-source library that is implemented in Modelica, an equation-based object-oriented modelling language. The library supports rapid prototyping, as well as design and operation of building energy and control systems. First, we describe the scope of the library, which covers heating, ventilation and air-conditioning systems, multi-zone heat transfer and multi-zone airflow and contaminant transport. Next, we describe differentiability requirements and address how we implemented them. We describe the class hierarchy that allows implementing component models by extending partial implementations of base models of heat and mass exchangers, and by instantiating basic models for conservation equations and flow resistances. We also describe associated tools for pre- and post-processing, regression tests, co-simulation and real-time data exchange with building automation systems. The article closes with an example of a chilled water plant, with and without water-side economizer, in which we analysed the system-level efficiency for different control setpoints.
Article
Full-text available
The U.S. Department of Energy developed 256 EnergyPlus models for use in studies that aim to characterize about 70% of the U.S. commercial building stock. Sixteen building types - including restaurants, health care, schools, offices, supermarkets, retail, lodging, and warehouses - are modeled across 16 cities to represent the diversity of U.S. climate zones. Weighting factors have been developed to combine the models in proportions similar to those of the McGraw-Hill Construction Projects Starts Database for 2003-2007. This paper reviews the development and contents of these models and their applications in simulation studies.
Article
The COVID-19 pandemic has raised concern of viral spread within buildings. Although the near-field transmission and the infectious spread within individual rooms are well studied, the impact of aerosolized spread of SARS-CoV-2 via air handling systems within buildings remains unexplored. This study evaluates the concentrations and probabilities of infection for both building interior and exterior exposure sources using a well-mixed model in a multi-room building served by a central air handling system (without packaged terminal air conditioning). In particular, we compare the influence of filtration, air change rates, and the fraction of outdoor air. When the air supplied to the rooms comprises both outdoor air and recirculated air, we find filtration lowers the concentration and probability of infection the most in both source and connected rooms. We find that increasing the air change rate removes virus from the source room faster but also increases the rate of exposure in connected rooms. Therefore, slower air change rates reduce infectivity in connected rooms at shorter durations. We further find that increasing the fraction of virus-free outdoor air is helpful, unless outdoor air is infective in which case pathogen exposure inside persists for hours after a short-term release. Increasing the outdoor air to 33% or the filter to MERV-13 decreases the infectivity in the connected rooms by 19% or 93% respectively, relative to a MERV-8 filter with 9% outdoor air based on 100 quanta/h of 5 μm droplets, a breathing rate of 0.48 m³/h, and the building dimensions and air handling system considered.
Article
It is essential to understand where and howsevere acute respiratory syndrome coronavirus 2 (SARS‐CoV‐2)is transmitted.Case reports were extracted from the local Municipal Health Commissions of 320prefecturalmunicipalities in China (not including Hubei province). We identified alloutbreaks involving three or more cases and reviewed the major characteristics of the enclosed spaces in which the outbreakswere reported and their associated indoor environmental aspects.Three hundred and eighteen outbreaks with three or more cases were identified,comprising a total of 1245 confirmed cases in 120prefectural cities. Amongst the identified outbreaks, 53.8% involved three cases, 26.4%involved four cases, and only 1.6%involved ten or more cases. Home‐based outbreakswere the dominant category (254 of 318 outbreaks;79.9%), followed by transport‐based outbreaks (108;34.0%), and many outbreaks occurred in more than one categoryof venue. All identified outbreaksof three or more cases occurred in indoor environments, which confirmsthat sharing indoor spaceswith one or more infected persons isa major SARS‐CoV‐2 infection risk.
Article
A measles epidemic in a modern suburban elementary school in upstate New York in spring, 1974, is analyzed in terms of a model which provides a basis for apportioning the chance of infection from classmates sharing the same home room, from airborne organisms recirculated by the ventilating system, and from exposure in school buses. The epidemic was notable because of its explosive nature and its occurrence in a school where 97% of the children had been vaccinated. Many had been vaccinated at less than one year of age. The index case was a girl in second grade who produced 28 secondary cases in 14 different classrooms. Organisms recirculated by the ventilating system were strongly implicated. After two subsequent generations, 60 children had been infected, and the epidemic subsided. From estimates of major physical and biologic factors, it was possible to calculate that the index case produced approximately 93 units of airborne infection (quanta) per minute. The epidemic pattern suggested that the secondaries were less infectious by an order of magnitude. The exceptional infectiousness of the index case, inadequate immunization of many of the children, and the high percentage of air recirculated throughout the school, are believed to account for the extent and sharpness of the outbreak.