ArticlePDF Available

Analysis of Long‐Term GIC Measurements in Transformers in Austria

Authors:
  • OMICRON electronics GmbH

Abstract and Figures

Geomagnetically induced currents (GICs), a result of solar wind interaction with the Earth’s magnetic field and the resistive ground, are known to flow in power transmission grids, where they can lead to transformer damage and grid operation problems. In this study we present an analysis of five years of continuous GIC measurements in transformer neutral points in Austria. Seven self-designed stand-alone measurement systems are currently installed in the Austrian 220 kV and 380 kV transmission levels, measuring currents up to 25 A. We identify recurrent geomagnetic activity in the measurements, and also find man-made sources of low frequency currents using frequency analysis. In order to support the transmission grid operators, two GIC simulation approaches are used to simulate GICs in the power grid. The first model uses measurements to derive the sensitivity of the location to northward and eastward geoelectric field components (which requires no detailed grid data), and the second model uses the detailed grid model to compute GICs from a geoelectric field. We evaluate two geomagnetic storms from September 2017 and May 2021 to discuss the effects of GICs on the power transmission grid and its assets.
This content is subject to copyright. Terms and conditions apply.
1. Introduction
For as long as there have been conductive networks on our planet's surface, there have been geomagnetically
induced currents (GICs) (Boteler & Pirjola,1998). These currents, which are caused by variations in the Earth's
magnetic field, flow through grounded conductive systems such as power grids, moving between the conductive
power lines and the earth via transformers (Price,2002). Due to the damage and disruption GICs can cause within
power grid infrastructure (Molinski,2002) such as that seen in Quebec during the March 1989 geomagnetic storm
(Bolduc,2002), modeling and measuring of potential currents is seeing increased interest due to grid operation
safety concerns (Kelbert,2020; Oughton etal.,2017).
Research into GICs in Austria began in 2014 in a study initiated by the Austrian Power Grid AG (APG) and
summarized in Halbedl etal.(2014). The aim of this first attempt was to investigate possible DC currents in the
Austrian high voltage power transmission network. For APG, measurements of DC are important to study the
nature of the currents and possible effects on transformers, as well as the impact of DC on different equipment
such as instrument transformers and protection devices. The data are also used as a planning basis for the design
criteria of new transformers.
The section of the Austrian power grid under investigation in the 220 and 380kV levels has 56 interconnected
substations with a total length of 6,965km of power lines and 87 transformers, spanning an area of 84,000km2.
After the initial test measurements in 2014, more DC measurement devices were installed with the aim of a
long-term measurement campaign, and the first data analysis was carried out in Halbedl etal.(2016) at the
Institute of Electrical Power Systems at Graz University of Technology (IEAN, TU Graz) and later in Bailey
etal.(2017,2018) at the Conrad Observatory for geomagnetic field measurements (ZAMG). The studies at each
Abstract Geomagnetically induced currents (GICs), a result of solar wind interaction with the Earth's
magnetic field and the resistive ground, are known to flow in power transmission grids, where they can
lead to transformer damage and grid operation problems. In this study we present an analysis of five years
of continuous GIC measurements in transformer neutral points in Austria. Seven self-designed stand-alone
measurement systems are currently installed in the Austrian 220 and 380kV transmission levels, measuring
currents up to 25A. We identify recurrent geomagnetic activity in the measurements, and also find man-
made sources of low frequency currents using frequency analysis. In order to support the transmission grid
operators, two GIC simulation approaches are used to simulate GICs in the power grid. The first model uses
measurements to derive the sensitivity of the location to northward and eastward geoelectric field components
(which requires no detailed grid data), and the second model uses the detailed grid model to compute GICs
from a geoelectric field. We evaluate two geomagnetic storms from September 2017 and May 2021 to discuss
the effects of GICs on the power transmission grid and its assets.
Plain Language Summary During geomagnetic storms, rapid changes in the Earth's magnetic field
induce an electric field in the ground, may drive currents in the power grid. These are called geomagnetically
induced currents (GICs) and they can lead to power grid operation problems and even transformer damage. In
this study we present learning's from five years of GIC measurements in Austria, which have been carried out
in seven different transformers in the grid. Some power grid transformers show larger susceptibility than other
transformers to magnetic field variations accompanied by larger GICs. We also identify some of the sources of
noise in the data such as a city subway system, and investigate two geomagnetic storms from September 2017
and May 2021 in more detail.
ALBERT ET AL.
© 2021. The Authors.
This is an open access article under
the terms of the Creative Commons
Attribution License, which permits use,
distribution and reproduction in any
medium, provided the original work is
properly cited.
Analysis of Long-Term GIC Measurements in Transformers in
Austria
D. Albert1 , P. Schachinger1 , R. L. Bailey2 , H. Renner1 , and G. Achleitner3
1Institute of Electrical Power Systems, Graz University of Technology, Graz, Austria, 2Conrad Observatory, Zentralanstalt für
Meteorologie und Geodynamik, Vienna, Austria, 3Austrian Power Grid AG, Vienna, Austria
Key Points:
Measurements of geomagnetically
induced currents (GICs) in power grid
substation transformers have been
carried out since September 2016 in
Austria
We summarize the measurements
until now and discuss data quality and
sources of noise
A statistical analysis of GIC
measurements, a comparison of
simulation models for two storms
and an attempt to a risk assessment is
performed
Correspondence to:
D. Albert,
dennis.albert@tugraz.at
Citation:
Albert, D., Schachinger, P., Bailey, R.
L., Renner, H., & Achleitner, G. (2022).
Analysis of long-term GIC measurements
in transformers in Austria. Space
Weather, 20, e2021SW002912. https://
doi.org/10.1029/2021SW002912
Received 14 SEP 2021
Accepted 22 DEC 2021
Author Contributions:
Conceptualization: D. Albert
Formal analysis: D. Albert
Investigation: D. Albert
Software: D. Albert
10.1029/2021SW002912
Special Section:
Space Weather Impacts on
Electrically Grounded Systems
at Earth's Surface
RESEARCH ARTICLE
1 of 16
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
2 of 16
institute had different focus areas: the TU Graz looked in detail at the different sources of DC in the power grid
and the effects on transformers, while the ZAMG focused on geomagnetic variations and the scales of possible
GICs both past and future. This work continues in Albert etal.(2019,2020).
There are now five years of measurements of DC in transformers at various locations in Austria. Worldwide, there
are still few countries with GIC measurements spanning long time periods and multiple locations, with some ex-
amples being New Zealand (Rodger etal.,2017), China (Zhang etal.,2015), more recently the USA (Kellerman
etal.,2021) and Finland (Pirjola,1989).
In addition to the measurements, two GIC simulation models for the Austrian power grid have been developed
based on two different geoelectric field modeling approaches.
The first model, from the IEAN, is based on the plane-wave method in combination with the power grid model.
The simulation can be interfaced with a graphical user interface (GUI) and is publically available with sample
data at https://github.com/P-Schachinger/LFC_simulator. The second method is also based on the plane-wave
method, but operates without the detailed power grid data. Instead of the power grid data, factors for the sensi-
tivity of each substation are derived from past transformer neutral current measurements. A third model from the
ZAMG developed in the past, which is not presented here, is based on calculation of the geoelectric field on a
surface with a surface conductive thin-sheet, and can be found at https://github.com/bairaelyn/GEOMAGICA. A
comparison of different models with different degrees of detail was performed in Bailey etal.(2018) and sum-
marized in Table 2 in the same publication. The results reveal only slight improvements with increasing degree
of detail of the Earth model with the thin-sheet approach. Therefore, a higher degree of detail do not justify the
effort for the ground modeling. However, due to the presence of the Alps, these effects could be larger in the
western part of Austria, where there have been fewer measurements to date. The absence of any highly conductive
coastlines makes Austria a far simpler case than for example, the UK or Sweden.
In this paper the results of an analysis of the entire data set of DC measurements and summarize the lessons
learned in the five years since the measurements started.
2. Data
2.1. DC Measurement System
The IEAN transformer neutral point current (NPC) measurement system (version 3) is a self-engineered stand-
alone and remote-controllable data acquisition system. The measurement system uses an active low pass filter
with a cut-off frequency of 0.7Hz to damp for example the 50Hz power system frequency, meaning the sampling
rate of the data acquisition can be reduced to 1Hz. An active second order low pass filter in Sallen-Key design
is preferred over a passive filter in order to reduce the filter components. This low sampling frequency allows to
use a low-cost single-board computer, such as a Raspberry Pi.
The measurements of currents are done with a Hall effect closed-loop zero flux current transducer. A shunt
resistor in series to the transformer neutral would change the impedance and therefore the GIC amplitude. The
shunt would also be large in size because it would need to carry a high short-circuit current in the case of a line-
to-ground fault. The measurement system has a guaranteed accuracy of 2%±1mA for DC in the range of ±0.1A
to ±25A. The actual measurement accuracy for DC in the range of 1–25A is below 0.2%±1mA. A technical
description of the second version of the measurement system can be found in Halbedl(2019).
The measurement data is sent to an external server at the TU Graz. Before use, the data is cleaned and missing
data or absolute values above 25A are automatically flagged. The missing values are interpolated with the
"Piecewise Cubic Hermite Interpolation" (PCHIP) method (Fritsch & Carlson,1980), which results in lower
amounts of overshooting in comparison to other interpolation methods. Considering the effect of interpolation in
the frequency domain, the PCHIP method provides the least change in the frequency spectrum of the measured
current.
2.2. GIC Measurements
At the time of writing (September 2021), seven transformer neutral points in the 220 and 380kV transmission
levels across Austria are equipped with our GIC measurement system, as depicted in Figure1. The measurement
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
3 of 16
locations are named according to order of setup going from #01 to #08 (where #06 is not in use). Measurements
started in September 2016 with one measurement system near Vienna in a 380kV transformer neutral. Figure2
gives an overview of the runtimes of all measurement systems. Client #02 was first situated in a 380kV neutral
point in eastern Austria, before it was moved to a 220kV transformer neutral point in central Austria. All follow-
ing descriptions of #02 refer to data measured at its second location.
In much of the data up until 2021 there was a cut-off point in the measurements in the negative direction of 3.5A
(but not in the positive direction). The saturated measurement periods/days are excluded in the data statistics and
further analysis. This is due the electronic design of the former transformer neutral point current measurement
system. The systems were installed in such a way that they were able to meas-
ure up to 25A in one direction and up to 3.5A in the other direction of the
transformer neutral point current. With a new electronic design, established
at all measurement locations from mid-2020 to mid-2021, the systems are
now able to measure positive and negative currents up to an amplitude of
25A.
The GIC events are detected with an automated algorithm. This is required
because short-duration peaks, caused by switching events and faults in the
power grid are also recorded. A GIC event is defined as a current with a
peak prominence of at least the mean value plus the standard deviation of the
analysis time span. The half width duration of the prominence needs to be at
least 100s. An automated algorithm for the detection of geomagnetic storms
based on the analysis of magnetic field variations was presented in Bailey
and Leonhardt(2016).
Figure 1. Substations in the Austrian transmission grid equipped with geomagnetically induced current measurement systems; DCC: Direct Current Compensation
System installed and measured; colored blocks with black numbers indicate the EURHOM earth layer model; WIC is the International Association of Geomagnetism
and Aeronomy (IAGA) code for the Conrad Observatory.
Figure 2. Measured current in A over the run times of installed measurement
systems from #01 to #08. (The #06 is not in use.) The measurement device #02
moved location in 2018, hence the two different colors.
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
4 of 16
2.3. Geomagnetic Field Data
All measurements of the local geomagnetic field in Austria refer to those car-
ried out at the Conrad Observatory, a subterranean tunnel system located near
Muggendorf in Lower Austria. The observatory is an INTERMAGNET-qual-
ity (1 sample/sec) geomagnetic observatory (see https://intermagnet.org/ for
more details) with measurements starting in 2014. Only the x- and y-compo-
nents of the field (corresponding to the northward and eastward geomagnetic
field directions, respectively) are used in the analysis. Vertical (z) field varia-
tions, which generally do not contribute to geomagnetically induced currents
at the surface, are ignored (Boteler & Pirjola,2017). The individual horizon-
tal components are also combined into the horizontal magnetic field strength
component B that describes only the intensity in the 2D surface plane (where

=
2
x+
2
y
). The geomagnetic variations dB/dt are expressed in change
in field strength per time-step, that is nT/min.
2.4. GIC Simulation
The geomagnetic storms that drive GICs lead to changes in the Earth magnet-
ic field (dB/dt) ranging from tens of nano Tesla (nT) up to several thousand
of nT per minute depending on the geomagnetic storm and the geographi-
cal location. As depicted in Figure3, the magnetic field propagates into the
electrically resistive subsurface, where it induces an electric field that can
be described by Faraday's Law of Induction. Under the assumption that the
field propagation can be treated as a plane-wave going into the Earth (Boteler
& Pirjola,2017), solving the differential Maxwell equation with the Euler
approach results in the following equations for the electric field in the north-
ward direction (Ex) and in the eastward direction (Ey):
j
 x

=−
2

2= −jyy=−0
(1−j)
(1)
−j


y

=
2
x

2=jxx=0
(1−j)
(2)
where
=()∕2
. The variables ω, μ, σ, H, E j, and z are the angular frequency, the Earth permeability, the
electric conductivity, the magnetic field, the electric field, the imaginary unit, and the downward direction into
the Earth, respectively. Equations1 and2 imply that the electric field decreases with increasing penetration depth
z. Therefore, integrating the electric field along a closed loop, for example in the y- and z-direction (Figure3)
results in an electromotive force (emf) unequal to zero. This emf drives GICs in the loop formed by the power
grid connected to ground and the ground itself. The work done by emf on the electric charge can be measured as
a virtual electric potential around the loop. Further information on the electromagnetic field calculations can be
found in Simonyi(1971) and in Simpson(2005).
Two different approaches for GIC calculations are compared to measurements: the first uses the low frequency
current (LFC) simulator tool from Schachinger and Albert(2021), and the second approach is computed with a
fit of the geoelectric field components (Ex and Ey) to the GIC measurements (Equation3).
The LFC simulator uses the plane-wave method from Pirjola(1982) to calculate an electric field in the Earth's
surface. The plane-wave method is sufficient approximation for mid-latitude countries such as Austria, because
the magnetic field variations are usually dominated by distant magnetospheric currents and spatially smooth
mid-latitude ionospheric currents. The resistive Earth itself is model with 1D layers from the European Rho
Model (EURHOM, Ádám etal.,2012). Most of Austria can be described by two different resistivity models, one
for the alps in the west (EURHOM #55) and one for the flat lands in the east (EURHOM #39, Bailey etal.,2018).
A comparison of the different models, including the EURHOM models can be found in Bailey etal.(2018). In
contrast to the Lehtinen-Pirjola method (Lehtinen & Pirjola,1985), we use the nodal admittance matrix method,
Figure 3. Depiction of geomagnetic induction and geomagnetically induced
currents (GICs) in the power grid. ∂Hx/∂t are horizontal geomagnetic
variations in the northward direction, and Ey is the corresponding geoelectric
field induced in the eastward direction. The “GIC” loop shows the loop
formed between the ground and power lines, through which the GICs flow via
transformers. Layers of resistive material going into the Earth show how the
geoelectric field tends to lose intensity with increasing depth z.
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
5 of 16
which is more common to use in the field of electrical engineering (Halbedl,2019). However, the two methods
are considered mathematically equivalent (Boteler etal.,2014). The power grid is modeled as a DC network with
voltage sources between the substation grounding and the resistive earth. The potential of all other earth refer-
ence points are changed relative to one overall reference point. This is only valid for uniform electric fields over
a certain area, however, it simplifies GIC calculation without losing much quality of the calculated GICs (Boteler
& Pirjola,1998; Halbedl,2019).
The second GIC modeling approach is based on the method described in Pulkkinen etal.(2007) and applied for
example in Torta etal.(2012). The geoelectric field is calculated using the plane-wave method using EURHOM
model #39, because, regardless of where the GIC measurements were made, the geoelectric field modeled using
#39 results in GICs that match the measurements well and better than any of the other models used, implying
this is a good approximation for most of the region. We expect that small-scale deviations do exist, although we
have yet to find any such locations. The GICs at different substations are calculated from the geoelectric field
components by applying a fit to the following equation:
j=jx+jy
(3)
where j is a specific substation measurement point in the power grid, and aj and bj are substation-specific co-
efficients that describe the contribution from each geoelectric field component and have the units Akm/V. The
substation coefficients need to be recalculated if the configuration of the power grid changes. The fit (Equa-
tion3) is applied to recent DC measurements—specifically a period in May 2021 with larger measured DC that
undoubtedly has geomagnetic sources to reduce input from other sources - and aj and bj can be determined using
the equations in Pulkkinen etal.(2007) or by carrying out a least-squares fit. Applying the method described
in Pulkkinen etal.(2007), the substation coefficients aj and bj incorporate uncertainties from the electric field
calculations, for example due to the limited Earth layer modeling.
3. Analysis
An analysis is carried out of the entire DC measurement data set by first providing an overview of each meas-
urement station statistically and then by evaluating the different sources of DC both geomagnetic and man-made
source are identified.
3.1. Overview of Data
Table1 lists the transformer neutral point current data statistics. For the calculation of the statistics, outages and
measurement errors are removed. Switching events, which can exceed the measurement limit of ±25A, are not
removed. The maximum current refers to GIC events and not to switching events. These events are checked both
manually and with a peak detection algorithm.
Client# ndays raw ndays clean μ in A σ in A | GICmean |in A DCmax in A Date of DCmax UTC Sensitivity to Ex/Ey (% from Ex/% from Ey)
01 1,671 1,651 +0.13 0.33 0.26 −8.41 2021-05-12 12:21 49/51 (r=0.86)
02 479 427 −0.12 0.02 0.14 +0.83 2021-05-12 12:20 44/56 (r=0.84)
03 1,583 1,522 −0.20 0.03 0.21 −2.42 2017-09-08 23:02 45/55 (r=0.72)
04 1,564 1,512 +0.06 0.23 0.17 −4.57 2021-05-12 12:20 36/64 (r=0.85)
05 1,383 1,330 −0.07 0.21 0.14 −13.83 2021-05-12 12:20 06/94 (r=0.89)
07 579 492 −0.48 0.14 0.47 −2.72 2020-09-04 14:18 50/50 (r=0.85)
08 159 105 +0.24 0.76 0.56 +9.31 2021-05-12 12:48 76/24 (r=0.57)
Note. μ is the mean, σ the standard variation, and DCmax the maximum current measured to date caused by a geomagnetic event (i.e., not a data spike or transformer
switching events). The column "Sensitivity to Ex/Ey" provides the contribution of each geoelectric field component (in percentage) to the measured GICs according to
the GIC fit of modeled E to recent DC measurements. In brackets, r denotes the Pearson's correlation coefficient between the GIC fit and measurements (clean days).
Table 1
Summary of the Data Properties (1-Sec Data) at Each Client
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
6 of 16
We see that the stations experience very different levels of DC, with some having experienced GICs around 10A
and greater (DCmax in #01, #05 and #08) and others not even exceeding a maximum of 1A such as #02 during a
geomagnetic storm. Almost all of the peak GICs occurred during the May 2021 storm (which will be looked at
in more detail later in this work). There are also very different levels of noise (σ) ranging from extremely quiet in
#02 and #03, and very high levels in #01 and #08.
One question we can ask is how much of the measurements can be explained by geomagnetic sources? Included
in the last column is an estimate of the contribution of each geoelectric field component to the GICs measured
at each location. This was computed from a fit of the GIC measurements (interpolated to a sampling rate of one
minute) to the geoelectric field components modeled from geomagnetic field variations according to Equation3.
The values are for data from the week of 9th–16th May 2021, which included a geomagnetic storm and some of
the largest DC measurements to date. The r value in brackets gives the Pearson's correlation coefficient achieved
by the fit (For the stormy section alone on 12th May 2021, r ranges from 0.90 to 0.97 at all stations except for
#07 and #08, where it is 0.85 and 0.82, respectively). As the correlation is generally very high, we can deduce
that the signals seen in the stations can be explained by the geoelectric field variations for the most part. Some
are modeled better from E than others, often those with greater levels of measured DC (e.g., #01 and #05). The
lower r values for #08 are likely due to the very large noise level measured at that particular substation. In general,
the signal-to-noise ratio (SNR) and the GIC amplitude is related to the power grid topology (line orientation and
center/end node/substation). In addition to geomagnetic field variations, other transformer neutral point current
sources should be considered, in order to judge the actual GICs in the context of a risk analysis for the power grid
and its assets.
In the last column in Table1, most stations are somewhat balanced in contribution from both field directions, but
#05 stands out by having roughly 94% of the currents induced by the eastward geoelectric field component alone.
Client #05 is located at a transformer at the end of a long east-to-west 380kV transmission line and therefore
highly sensitive to eastward electric fields (Ey), which result from changes in the geomagnetic field in the x-di-
rection (dBx/dt), dominated by the magnetospheric ring currents, due to the location of Austria in the mid-latitude
region. The lines from the substation of #05 to Germany are 220kV lines. In addition, no auto-transformer is
used in the substation of #05.
Among the many signals seen in the DC measurements, there is a typical daily pattern, similar to the geomag-
netic field solar quiet variation. This quiet time variability in transformer DC measurements has recently been
investigated in detail in Kellerman etal.(2021). Figures4a–4d show the calculated mean values for each minute
of a day for magnetic field measurements and GIC measurement clients #01 and #05. For clients #01 and #05,
1,650days and 1,330days, respectively, were superimposed and the mean value of every minute was calculated.
The magnetic field measurements have fewer data gaps, therefore about 1,740days were used for the mean value
calculation. This reveals that there are recurring neutral point currents with different time periods at different
measurement points that are not caused by variations in the Earth's magnetic field. The excerpt of the fast Fourier
transform (FFT) analysis of the mean values of #01 and #05 in Figure4e shows the dominant frequency shares,
produced by other sources than geomagnetic field variations. For #01 these are sources with periods of 15min
and faster. These shares are also present in the frequency spectrum of #05, however, the main fast components
have duration times of 30min. For comparison purposes, #01 and #05 were normalized to their peak value before
performing the FFT.
The alleged time shift between the two curves in Figures4c and4d likely has two main causes: first, the measure-
ment systems are set to UTC time, but there is a difference in local time between the two clients of about 9min as
they are 250km apart. Second, the sensitivities to changes in the different components of the geomagnetic field
(resulting E-fields Ex and Ey have their maxima at different times) of the transformers in the two substations is
quite different, as one is more sensitive to variations in the x-direction than the other. Another interesting effect
that can be seen in Figures4c and4d is the small offset in both measurement clients. Although the measurement
systems were calibrated during installation, the overall mean value is not zero. This is likely caused by constant
DC currents unrelated to geomagnetic variations. For low frequencies the measurements from client #05 fit the
Bx field qualitatively very well.
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
7 of 16
3.2. Noise Sources
As can be seen from Table1, there are varying levels of noise in the different measurements (mean μ and standard
deviation σ). Some of this can be explained by the location. Client #01 is located at the edge of the city of Vien-
na, where it is more likely that the noise is caused by earth-leakage currents from technical/man-made systems.
Client #05 is located 115km east of the city Munich and 50km east of a north-south railway transit corridor.
The increased noise could be caused by earth-leakage currents from the city of Munich, where there is also a DC
powered subway system operating, and by stray currents from the railway transit corridor/system.
Apart from these general noise sources, other sources of DC have been found in the measurements over the years.
So far we have been able to identify the Vienna DC powered subway system as one contributor to the transformer
neutral point currents. Another source of DC transformer neutral point currents are cathodic corrosion protection
systems of power plants and pipelines (Beltle etal.,2017). In addition, the galvanic coupling of the cathodic pro-
tection system and the transmission grid, hybrid AC/DC transmission lines are coupled through DC ion currents
(Pfeiffer etal.,2015). We are also currently investigating the effects of power electronics, such as the converters
from renewable energy resources (e.g., wind and photovoltaic, [Gertmar etal.,2005]), and the effects of trading
at the electrical energy market. Solar radiation can be excluded as a source (Albert etal.,2020).
Figure 4. Mean minute values of geomagnetic field measurements (a) Bx and (b) By, and DC measurement clients (c) #01
and (d) #05; (e) shows an excerpt from the normalized fast Fourier transform of the mean from #01 and #05.
2.1
2.1005
2.101
x
10
Mean value of Bx
1570
1580
1590
1600
By in nT
b)
Mean value of By
-0.5
0
0.5
1
I in A
c)
Mean value of Client #01
00:00:00 04:00:00 08:00:00 12:00:00 16:00:00 20:00:00
Time of day in UTC
-1
0
1
I in A
d)
Mean value of Client #05
10-4 10-3 10-2
0
0.05
0.1
|I| in pu
e)
normalized FFT of mean #01
normalized FFT of mean #05
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
8 of 16
3.2.1. Vienna DC Subway System
As first described in Halbedl(2019), leakage currents of public transporta-
tion systems are measured in several measurement systems in Austria. This
was identified by analyzing the frequency spectrum of the currents, as well as
by comparing the operating hours of the Vienna subway with patterns in the
neutral point currents. During the nights from Sunday to Thursday, the sub-
way operation stops for a few hours (from roughly 00:30 a.m. till 05:00 a.m.),
and on the nights of Friday and Saturday, the subway stays in operation
through the night. The operating times can be seen clearly in Figure5a, which
shows the root-mean-square in the DC measurements over 8-day periods.
The currents clearly stay at a higher level during weekend nights rather than
dropping to around 0A, as they do on weekdays. As can be seen in the plot,
these stray currents contribute roughly 0.2A to the measurements during the
day.
Due to the COVID-19 restrictions in public transportation, the Vienna sub-
way stopped its weekend nightly operations and also reduced the number of
trains in operation. This change in operating hours can be seen in Figure5b,
in which there are also lower neutral point currents during the weekend
nights. Lowes(2009) also identified unintended earth-leakage currents from
DC railways systems, which caused interference during geophysical surveys.
3.3. Recurrent Geomagnetic Activity
Having identified some sources of noise in the data, we now look more closely at the geomagnetic signals pres-
ent in the measurements, among which are recurrent geomagnetic activity. Geomagnetic activity has long been
known to recur roughly every 27days (Richardson etal.,2000; Tsurutani etal.,2006) due to the persistence of
high speed streams and corotating interactions regions (Alves etal.,2006) over more than one solar rotation or
Carrington rotation. This is evidenced by recurrent mild geomagnetic storms. A recent study by Gil etal.(2021)
has shown that this is also observable in power grid observations.
Figure6 shows the DC measurements across each Carrington rotation (roughly 27days long). To produce this
plot, each Carrington rotation was split into 100 time windows (each window one pixel), and the maximum abso-
lute DC or dH/dt (variation in the horizontal magnetic field strength) was found for each window, while the solar
wind speed, which clearly show corotating interaction regions in the solar wind, is plotted beneath. The recurrent
geomagnetic activity can be seen in both upper plots, although in the DC measurements it is not as pronounced as
in geomagnetic variations partly because there is a constant level of noise in the DC measurements, which some
of the geomagnetically induced currents can get lost in. Plot Figure6d shows the cross-correlations between each
time series at different time shifts. The highest correlations are between dH/dt and the solar wind, likely because
there is a better SNR. The 27-day recurrence from solar wind structures is clearly visible in the secondary peaks
at time shifts of 27 and 54days. The coherence between daily variations in dH/dt and measured GICs are also
visible.
3.4. Events During the Observation Period
Throughout the duration of the measurements and the progress of solar cycle 24 into cycle 25, we have observed
some minor and moderate geomagnetic storms. Here we present the measurements and a brief analysis of two
storms. For each storm, we also consider the cumulative GICs that would have been seen during that period by
calculating an additional parameter, GICsum.
3.4.1. Calculation of GIC-Sum
In the Austrian power grid, transformers in the 220 and 380kV levels are generally solidly grounded, without
any resistance between the transformer neutral point and the substation grounding. GICs can enter and exit the
transmission grid via the transformer neutral points. The transformers are designed to handle alternating mag-
netic flux in the magnetic transformer core, and direct magnetic flux can cause saturation of this magnetic core
Figure 5. Influence of Vienna DC subway leakage currents on transformer
neutral point currents as seen in: (a) normal operation, including over weekend
nights, where the subways stays in operation, and (b) during COVID-19
lockdown restrictions, when the subway stopped extended operation during
weekends nights.
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
9 of 16
material. Operating with a saturated transformer core has short-term and long-term effects on the transformer.
Short-term effects (scales of minutes) are half-cycle saturation leading to current and voltage distortion, which
are the reasons for the increased non-active power demand of the transformer. The increased non-active power
demand can cause undesired voltage drops and power system instabilities. If saturation in the transformer core
lasts over multiple hours or even days, the voltage and current distortion also causes transformer heating, which
can be considered as a long-term (scales of hours) effect. Short- and long-term effects of GICs on transformer
are also discussed in Gaunt etal.(2020). The transformer heating is due to the increased current and stray flux in
the metallic tank and transformer reinforcements. GICs with comparable short duration and high amplitudes as
well as GICs with comparable low amplitude and long duration can cause the transformer hot spot temperature
to increase above the acceptable design limits. A further increase in temperature causes a loss of insulation and
internal transformer failures.
Figure 6. Influence of recurrent geomagnetic activity from high speed streams and corotating interaction regions. (a) Measurements of geomagnetically induced
currents (GICs) at station #01 (from which we have the longest time series), (b) horizontal magnetic field variations (from the Conrad Observatory in Lower Austria),
(c) the measured solar wind speed showing corotating interaction regions, and (d) the cross-correlation between the time series for different shifts in time. Each variable
is plotted for each 27-day Carrington Rotation (x-axis) across all Carrington rotations from September 2016 till May 2021 (y-axis, time increasing from top to bottom).
Examples of recurring activity visible in both GIC and magnetic data that last longer than one rotation are marked with red circles in both plots. White spaces in both
plots are data gaps. The recurrent activity can be seen in the secondary cross correlation peaks at time shifts of 27 and 54days.
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
10 of 16
In order to quantify and consider the afore-mentioned long-term effects, the GICsum value is calculated according
to Equation4. The GICsum value is the accumulated absolute current amplitude over a fixed time period with a
fixed sample rate, which in this case is a time period of one hour and a sampling rate of one second.

 =
2
1|
GIC()
|
d
(4)
The data presented in Figures8 and 11 are a first attempt to quantify and take into accumulated GIC load on
transformer. For a further risk analysis, a guidance containing a threshold level where GICs starts to contribute
to an accumulated exposure and different alert levels should be provided. This guidance would be needed to be
adapted for different transformer designs.
3.4.2. 12 May 2021 Event
On 9th May 2021, a CME associated with a filament eruption was detected. This reached the Earth and became
geomagnetically effective on 12th May 2021. During this event, a maximum Kp value of 7 (GFZ German Re-
search Centre for Geoscience,2021) was reached between 12:00 and 15:00 UTC. At 14:00 UTC the Dst value
reached the minimum of −61nT (World Data Center for Geomagnetism, Kyoto, Japan, 2021). The maximum
amplitudes of currents measured in the Austrian transmission grid were 13.83 and 9.31A in clients #05 and client
#08, respectively. Figure7 shows the measured currents of three transformers and the corresponding results of
the LFC simulator tool and a fit of the geoelectric field to the data (GIC fit). For the clients #01 and #05 in a) and
b), the simulated currents fit the measured currents very well (Pearsons correlation coefficient r equals 0.84 and
0.96, respectively), however the results from the LFC simulator for client #08 in c) do not match well (r=0.22)
despite the fit matching the current well (r=0.81). This is probably caused by inaccurate grid data or uncertain-
ties in the Earth layer model.
In Figures8a, 8c and8e the 1hr GICsum value for the disturbed day May 12th is plotted, in b), d) and f) the 1hr
GICsum value for a comparable quiet period is plotted alongside. During the quiet period, the maximum Kp value
was 1-. Although the highest current amplitude was measured at client #05 (13.83A), the highest GICsum value
Figure 7. Measured currents during the May 2021 event, related simulation results of two calculation approaches and
corresponding Pearson correlation coefficients r on 12 May 2021. The selected transformers show the highest currents: (a)
client #01, (b) client #05 and (c) client #08 (the deviation of the results from the low frequency current simulator are probably
due to inaccurate grid data of this region).
-10
0
10
Client #01 Measured
LFC Simulator r = 0.84
GIC fit r = 0.9
-10
0
10
Client #05 Measured
LFC Simulator r = 0.96
GIC fit r = 0.95
11:3011:45 12:00 12:15 12:30 12:45
-10
0
10
Client #08 Measured
LFC Simulator r = 0.22
GIC fit r = 0.81
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
11 of 16
was reached at client #08. Clients #01 and #05 show a similar GICsum pattern
during both the geomagnetic disturbance and the quiet period. Both trans-
formers were exposed to comparable GICsum currents during a 1hr period.
Similar to the correlations done by Choi etal.(2015), Figure9 shows the cor-
relation between changes in the magnetic field and resulting GICs. As mag-
netic field measurements in nT/min are calculated for the x- and y-directions.
The related changes in measured currents at three measurement systems are
given in A/min. This reveals the sensitivity directions of these stations: client
#01 shows in a) and b) high correlations between changes in neutral point
current and changes of the geomagnetic field. Panels c) and d) show a higher
sensitivity of client #05 to changes in x-direction, which matches with cal-
culations in Halbedl(2019). The currents at client #08 are in general higher
than at #05, however, the changes caused by geomagnetic variations during
this event were smaller and a clustering can be seen in f), which also indicates
a lower sensitivity on changes in y-direction. The visual determined sensi-
tivities to geomagnetic fields in Figure9 also match with the sensitivities to
geoelectric fields in Table1.
3.4.3. 8-9 September 2017 Event
The September 2017 event was associated with a X9.3 flare from solar active
region (AR) 12673, which is regarded as the largest in solar cycle 24. A max-
imum Kp value of 8+ (GFZ German Research Centre for Geoscience,2021)
was reached between 12:00 and 15:00 UTC, although the maximum current
amplitude only reached 5.11A at client #01. During the September 2017 event, three measurement systems (#01,
#03, #04) were active. The current amplitude at client #03 is less than half the amplitude at client #01, therefore
only GICsum value of client #01 and #04 are plotted in Figure10. This is a particularly interesting comparison
because the two are located in the same substation in the 220 and 380kV
voltage levels.
Again, the measured currents are compared with the two calculation ap-
proaches of LFC Simulator and GIC fit. Unfortunately, the September event
was measured with the first version of the measurement system, therefore
some of the peak values are cut off because of the −3.5A limit in the meas-
urement device, and saturated GIC measurements imply that the actual GICs
were larger. As the Dst value during the September 2017 event (−122nT)
was exactly twice the Dst value during the May 2021 event (−61nT), the
GIC during the September 2017 event is expected to be in the range of 25A.
In Figures11a and11c, the 1hr GICsum value for the most disturbed period
in September 2017 is plotted, and in b) and d) the 1hr GICsum value for a
comparable quiet period is plotted. During the quiet period the maximum
Kp value was 2+. Note that client #01 is a 380kV transformer neutral meas-
urement and #04 a 220kV measurement in the same power grid substation.
Due to the increased circuit resistance in the 220kV level, the transformer
neutral currents are usually lower than those in the 380kV transformer neu-
tral, and we see they are roughly half as large in #04 as they are in #01. In
Austria, the common practice is to have one transformer neutral per voltage
level and substation grounded. This is required to reliably detect faults in the
grid and to limit line-to-ground fault currents. Usually multiple transformers
are connected in parallel to ensure 1-n security and to increase the transmis-
sion capacity. In our case in the substation of #01 and #04, three 380/220kV
transformers are connected in parallel, where the 380kV neutral point of
transformer 1 is solidly ground and the 220kV neutral point of transformer 3
is solidly grounded. Therefore, the two measurement points are at 2 different
transformers. The other neutrals of the other transformers are not grounded.
Figure 8. Cumulative 1h GICsum of client #01 for May 2021 storm (a, c, e)
and quiet (b, d, f) period during May 2021.
a) active period; #01
May 12, 00:00 May 13, 00:00
2021
0
2
4
GIC
sum,1 h
in Ah
b) quiet period; #01
May 05, 00:00May 06, 00:0
0
2021
0
2
4
c) active period; #05
May 12, 00:00 May 13, 00:00
2021
0
2
4
GIC
sum,1 h
in Ah
d) quiet period; #05
May 05, 00:00May 06, 00:0
0
2021
0
2
4
e) active period; #08
May 12, 00:00 May 13, 00:00
2021
0
2
4
GIC
sum,1 h
in Ah
f) quiet period; #08
May 05, 00:00May 06, 00:0
0
2021
0
2
4
Figure 9. Correlation of dB/dt and the resulting change in neutral point
currents dI/dt during the 12th May 2021 event: (a and b) client #01, dI/dt
standard deviation σ=0.297 A/min, (c and d): client #05 σ=0.645 A/min, (e
and f): client #08 σ=0.461 A/min. The slope k of the black least squares fit
line is also shown.
-20 020
dBx/dt in nT/min
-5
0
5
#01 dI/dt in A/min
a)
-20
02
0
dBy/dt in nT/min
-5
0
5
#01 dI/dt in A/min
b)
-20 020
dBx/dt in nT/min
-5
0
5
#05 dI/dt in A/min
c)
-20
02
0
dBy/dt in nT/min
-5
0
5
#05 dI/dt in A/min
d)
-20 020
dBx/dt in nT/min
-5
0
5
#08 dI/dt in A/min
e)
-20
02
0
dBy/dt in nT/min
-5
0
5
#08 dI/dt in A/min
f)
k: -0.080
k: -0.122
k: 0.062 k: -0.138
k: 0.119
k: 0.131
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
12 of 16
The highest current amplitude during the September 2017 event was measured at client #01 (5.11A), the highest
GICsum value was also reached at client #01 (1.9Ah). The transformer at client #04 in the same substation as
client #01 was exposed to a 1.1Ah during the same time period. During the quiet period with no geomagnetic
activity (Kp 0o), the transformer at client #01 and #04 were exposed to max. 0.33Ah.
4. Discussion
The measurements covered a period of particularly low levels of geomagnetic activity throughout the end of solar
cycle 24 and the beginning of cycle 25. The maximum Kp of 8- was reached during the September 2017 storm.
During the last years of measurement, the geomagnetic activity was comparably low with very few periods of
increased activity. Nevertheless, with the recent storms we now have sufficient data to reliably calculate the GICs
in the Austrian power grid, which is unfortunately low for studying larger GIC events, however due to the relax-
ation of maximum measurement limits in the past year, we now have sufficient data to estimate GIC levels from
recent storms. A historical analysis has been carried out in another recent study (Bailey etal.,2022), giving an
estimate for the largest GICs during the 2003 Halloween storm that likely ranged from at least 30A up to 60A.
By splitting the GIC measurement data into time intervals matching Carrington rotation intervals, recurring solar
events could be identified in Figure6. High recurring changes in the magnetic field with time periods of 27days
can be seen magnetic field measurements as well as in neutral point measurements in the power grid. This un-
derlines the sensitivity of the power transmission grid, also to comparable small changes in the Earth magnetic
field. Small changes in the Earth's magnetic field can also have negative effects on the power grid. Low level
GICs cause an increased power loss in the system due to increased transformer windings losses and losses on the
overhead transmission lines (Forbes & St. Cyr,2010). In addition, the allowable transformer load can be reduced
by GICs (Girgis & Ko,1992).
Calculating mean values per minute for measurement periods reveals different noise sources with different fre-
quencies in the power grid. The noise sources do not only have specific frequency spectra, they also show daily
patterns, with changes every 15 or 30min. One of the noise sources was identified: by comparing time patterns
of GIC measurements, the influence of public transportation on transformer neutral point currents was discov-
ered. A change in the subways timetable due to COVID-19 restrictions, confirmed this theory. Typically, the
Vienna subways stops operation during weekday-night and continuous operation in weekend nights. However,
this changed in March 2020 due to COVID-19 restrictions. This effect on GIC measurements could only be
derived because of continuous and geographical distributed measurements. Further man-made sources of low
frequency currents in the transformer neutral point are currently investigated at the time of writing, but require
Figure 10. Measured currents during the September storm 2017 and related simulation results of two calculation approaches.
The selected transformers show the currents at two different neutral points in the same substation and the corresponding
Pearson's correlation coefficients: (a) client #01, (b) client #04; the drop in the measurement of client #01 after 12:30 UTC
and before 15:00 UTC is caused by maximum current measurable with the first version of the measurement system.
-10
-5
0
5
10
I in A
a)
Client #01 Measured
LFC Simulator r = 0.86
GIC fit r = 0.84
12:0012:30 13:0013:30 14:0014:30 15:00 15:30 16:0
0
Sep 08, 2017
-2
0
2
I in A
b)
Client #04 Measured
LFC Simulator r = 0.89
GIC fit r = 0.88
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
13 of 16
measurements with sample rates well above 1Hz. To address this, temporary
measurement recorders are being installed in various measurement locations.
The measurements are used for analyzing the influence of GICs on trans-
formers and calculating the theoretical influence on the power grid. Howev-
er, there are additional continuous long term measurements in power grids
available. Phasor measurements units (PMU) provide data from voltage, cur-
rents, angle and frequency measurements in the power grid. The correlation
of PMU data with high GICs will be done in future studies. Combining data
of multiple measurement types during geomagnetic active periods could also
reveal more direct influence on power grids, for example changes in power
flow or reactive power consumption. The combination could also reveal more
noise sources in the power grid DC measurements.
In addition to the current measurements, the GICsum value was calculated
to evaluate long-term effects of GICs on power transformers in addition to
short-term effects. The materials used in the transformers are designed for a
specific lifetime, and any increase of temperature above the design limits re-
duces the transformer lifetime (loss-of-life). Therefore, a thermal assessment
of the different transformer types in the fleet should be carried out in order to
determine the loss-of-life of transformers exposed to GICs. Regarding trans-
former overheating, Raith(2019) indicates that, for a specific transformer
design, a GICsum value of 1,000Ah, would be permissible without any over-
heating of the transformer. Note that the 1,000Ah could be reached with a transformer neutral point current of
60A and a duration of 1,000min or with a neutral point current of 10A and a duration of 6,000min (100hr,
4.17days). With this background, no transformer overheating is expected during the two presented GIC events
during the five year observation period, considering the same transformer design as in Raith(2019). But we
expect that increased moderate geomagnetic activity could cause a rise in transformer temperature. If an active
transformer cooling system is installed and not already in full operation, the cooling system could be used to
reduce the transformer operating temperature.
Besides uncertainties in geological structure, missing grid data is the main reason for differences between meas-
urement and simulation (see e.g., the model results for #08 in Figure7). A comparison of the magnetic field
variation over time with the three closest INTERMAGNET observatories shows a congruent pattern. Therefore,
the data from the single observatory (WIC) can be used in combination with the plane-wave method for GIC
studies in Austria. The Austrian power grid is a non-steady, varying infrastructure over the measurement period
of several years. This makes simulations difficult, as the current status of connections, outages or shutdowns is
not known for every day since 2016. The resistances of transformers and lines are well known, but the substation
grounding resistances are not available for all substations in Austria, and through experimentation with the sim-
ulation output versus measurements, these have been found to have a large effect on the modeled GICs (a change
of 0.1Ω lead to a maximum change of 32% or 2A in the specific transformer neutral). A dedicated measurement
campaign would be needed to gather more accurate grounding resistance data and account for this error source.
During the commission of substations the state-of-the-art is to measure the substation earthing impedance with
frequencies close to 50Hz. In order to improve the simulation, a substation earthing resistance measurement with
DC (0Hz) and/or with low-frequencies (below 50/60Hz nominal power system frequency).
Additionally, although we have data on the Austrian power grid, changes in neighboring countries are often
unknown but still have influence on our calculations. In the models we considered at least 2 substations into the
surrounding grids of DE, CH, CZ, SI, SK, CR and HU.
5. Conclusion
To conclude, we have presented an analysis of five years of DC measurements conducted with seven measurement
systems at multiple locations in the Austrian power grid. The maximum measured amplitude during the observa-
tion period was 13.83A during the geomagnetic storm on 2021 May 12th with a minimum Dst value of −61nT.
In addition to geomagnetic events and recurrent geomagnetic activity, we have identified the DC-powered public
Figure 11. Cumulative 1hr GICsum for September 2017 storm (a), (c) and
quiet (b), (d) period (data in during the quiet periods are below 0.02 Ah)
during September 2017.
a) active period; #01
Sep 07 Sep 08 Sep 09
2017
0
1
2
GIC
sum,1 h
in Ah
b) quiet period; #01
Sep 25 Sep 26
Sep 27
2017
0
1
2
c) active period; #04
Sep 07 Sep 08 Sep 09
2017
0
1
2
GIC
sum,1 h
in Ah
d) quiet period; #04
Sep 25 Sep 26
Sep 27
2017
0
1
2
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
14 of 16
transportation system as a contributor to the grounded transformer neutral point currents. Other sources such as
power electronic devices from renewable energy resources are also under investigation. Location-dependent daily
recurring noise patterns have been detected in two sets of measurements and shown in Figures4c and4d, but the
sources have not been identified yet.
Correlations between changes in the magnetic field and changing neutral point currents during high geomagnet-
ic activity are shown in Figure9. In order to confirm the consistency of the measurement data, the correlation
between the magnetic field changes and the changing neutral point current was calculated. The results reveals
location-dependent GIC sensitivity to specific directions of geomagnetic field changes, which is also shown by
the GIC fit method in the last column of Table1.
Regarding the effects of GICs on transformer the 1hr GICsum value is calculated for the two presented events, re-
vealing no transformer temperature increase could be expected during the events. A winding temperature increase
is very unlikely, due to the values stated in Raith(2019), but cannot be excluded. Nevertheless, an individual
transformer thermal-fleet screening should be carried out to determine the GIC sensitivity among the transformer
types in the fleet.
The long term measurements in the Austrian power grid have already led to improvements in the simulation
accuracy for GICs in the Austrian power grid by initiating further studies (not yet published) in the field of sub-
station grounding calculation and sensitivity to various grid data. In addition to geomagnetic sources, we also
identified other sources of low frequency currents. This work supports transmission grid operators to maintain
and improve the grid availability and security. In the future, power grid assets and transformers endangered by
GICs can be identified and protected by mitigation actions. In addition, other systems that interact with the power
grid can be identified through continuous monitoring, providing reliable data to the system operation and utility
manufacturers.
Data Availability Statement
The data this study is based on, namely the DC measurements in transformers in Austria, can not be openly
shared due to grid safety concerns, however the data may be shared in part for smaller studies, and any interested
party should contact the corresponding author for details. The geomagnetic field variations from the Conrad
Observatory (WIC) used to model the geoelectric field in Austria can be found under https://intermagnet.org/ or
by contacting the Observatory personnel. The LFC simulator used to model the GICs in the grid can be found
at https://github.com/P-Schachinger/LFC_simulator. The Dst used in this paper was provided by the WDC for
Geomagnetism, Kyoto (http://wdc.kugi.kyoto-u.ac.jp/wdc/Sec3.html). The Kp values used in this paper were
provided by the GZF German Research Centra for Geosciences, Potsdam (https://isdc.gfz-potsdam.de/kp-index/).
References
Ádám, A., Prácser, E., & Wesztergom, V. (2012). Estimation of the electric resistivity distribution (EURHOM) in the European lithosphere in the
frame of the eurisgic WP2 project. Acta Geodaetica et Geophysica Hungarica, 47(4), 377–387. https://doi.org/10.1556/AGeod.47.2012.4.1
Albert, D., Halbedl, T., Renner, H., Bailey, R. L., & Achleitner, G. (2019). Geomagnetically induced currents and space weather - A review of
current and future research in Austria. In 2019 54th International Universities Power engineering Conference (UPEC) (pp. 1–6). IEEE. https://
doi.org/10.1109/UPEC.2019.8893515
Albert, D., Schachinger, P., Renner, H., Hamberger, P., Klammer, F., & Achleitner, G. (2020). Field experience of small quasi DC bias on power
transformers A first classification of low-frequency current pattern and identification of sources. In Cigre Session 48. Paris (Vol. 137, pp.
427–436). https://doi.org/10.1007/s00502-020-00846-1
Alves, M. V., Echer, E., & Gonzalez, W. D. (2006). Geoeffectiveness of corotating interaction regions as measured by Dst index. Journal of
Geophysical Research, 111(A7), A07S05. https://doi.org/10.1029/2005JA011379
Bailey, R. L., Halbedl, T., Schattauer, I., Achleitner, G., & Leonhardt, R. (2018). Validating GIC models with measurements in Austria: Evalua-
tion of accuracy and sensitivity to input parameters. Space Weather, 16(7), 887–902. https://doi.org/10.1029/2018SW001842
Bailey, R. L., Halbedl, T., Schattauer, I., Römer, A., Achleitner, G., Beggan, C. D., etal. (2017). Modelling geomagnetically induced currents in
midlatitude Central Europe using a thin-sheet approach. Annales Geophysicae, 35(3), 751–761. https://doi.org/10.5194/angeo-35-751-2017
Bailey, R. L., & Leonhardt, R. (2016). Automated detection of geomagnetic storms with heightened risk of GIC. Earth, Planets and Space, 68(1),
716. https://doi.org/10.1186/s40623-016-0477-2
Bailey, R. L., Leonhardt, R., Möstl, C., Beggan, C., Reiss, M. A., Bhaskar, A., & Weiss, A. J. (2022). Forecasting GICs and geoelectric fields from
solar wind data using LSTMs: Application in Austria. Space Weather, 2021SW002907. https://doi.org/10.1002/essoar.10508699.1
Beltle, M., Schühle, M., & Tenbohlen, S. (2017). Galvanic coupling of direct currents in transmission grids and its effects on power transformers. In 20th
International Symposium on High Votlage Engineering. Institute of High Voltage and Power Transmission. Retrieved from https://www.research-
gate.net/publication/319703163_Galvanic_Coupling_of_Direct_Currents_in_Transmission_Grids_and_its_Effects_on_Power_Transformers
Acknowledgments
We would like to extend our thanks to
APG for giving us the opportunity to set
up and continuously operate the trans-
former neutral current measurements.
P. Schachinger and D. Albert thank the
TU Graz, APG and Siemens Energy for
funding. R. L. Bailey thanks the FFG and
ZAMG for funding. Supported by TU
Graz Open Access Publishing Fund.
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
15 of 16
Bolduc, L. (2002). GIC observations and studies in the Hydro-Québec power system. Journal of Atmospheric and Solar-Terrestrial Physics,
64(16), 1793–1802. https://doi.org/10.1016/S1364-6826(02)00128-1
Boteler, D. H., Pirjola, R., Blais, C., & Foss, A. (2014). Development of a GIC simulator. In 2014 IEEE PES general meeting (pp. 1–5). IEEE.
https://doi.org/10.1109/PESGM.2014.6939778
Boteler, D. H., & Pirjola, R. J. (1998). Modelling geomagnetically induced currents produced by realistic and uniform electric fields. IEEE Trans-
actions on Power Delivery, 13(4), 1303–1308. https://doi.org/10.1109/61.714500
Boteler, D. H., & Pirjola, R. J. (2017). Modeling geomagnetically induced currents. Space Weather, 15(1), 258–276. https://doi.
org/10.1002/2016SW001499
Choi, K.-C., Park, M.-Y., Ryu, Y., Hong, Y., Yi, J.-H., Park, S.-W., & Kim, J.-H. (2015). Installation of induced current measurement systems
in substations and analysis of GIC data during geomagnetic storms. Journal of Astronomy and Space Sciences, 32(4), 427–434. https://doi.
org/10.5140/JASS.2015.32.4.427
Forbes, K. F., & St. Cyr, O. C. (2010). An anatomy of space weather’s electricity market impact: Case of the PJM power grid and the performance
of its 500 kV transformers. Space Weather, 8(9), S09004. https://doi.org/10.1029/2009SW000498
Fritsch, F. N., & Carlson, R. E. (1980). Monotone piecewise cubic interpolation. SIAM Journal on Numerical Analysis, 17(2), 238–246. https://
doi.org/10.1137/0717021
Gaunt, C. T., Cilliers, P. J., Heyns, M. J., Lotz, S. I., Chisepo, H. K., Adebayo, A. V., & Oyedokun, D. T. O. (2020). Calculations leading to voltage
stability and transformer assessment in the presence of geomagnetically induced currents. In Cigre Session 48 (Vol. C4). Paris. Retrieved from
https://sessionpapersdoc.cigre.org/
Gertmar, L., Karlsson, P., & Samuelsson, O. (2005). On DC injection to AC grids from distributed generation. In European Conference on Power
Electronics and Applications, 2005 (p. 10). IEEE Service Center. https://doi.org/10.1109/EPE.2005.219420
GFZ German Research Centre for Geoscience. (2021). Geomagnetic observatories. Retrieved from https://www.gfz-potsdam.de/en/section/
geomagnetism/infrastructure/geomagnetic-observatories/
Gil, A., Modzelewska, R., Wawrzaszek, A., Piekart, B., & Milosz, T. (2021). Solar rotation multiples in space-weather effects. Solar Physics,
296(8), 1–13. https://doi.org/10.1007/s11207-021-01873-7
Girgis, R., & Ko, C.-D. (1992). Calculation techniques and results of effects of GIC currents as applied to large power transformers. IEEE Trans-
actions on Power Delivery, 7(2), 699–705. https://doi.org/10.1109/61.127070
Halbedl, T. (2019). Low frequency neutral point currents on transformer in the Austrian power transmission network. (PhD Thesis). Graz Univer-
sity of Technology. Retrieved from https://diglib.tugraz.at/download.php?id=5cc8220f5d096&location=browsethesis
Halbedl, T., Renner, H., Bailey, R. L., Leonhardt, R., & Achleitner, G. (2016). Analysis of the impact of geomagnetic disturbances on the Austrian
transmission grid. In 19th Power Systems Computation Conference (pp. 1–5). IEEE. https://doi.org/10.1109/PSCC.2016.7540833
Halbedl, T., Renner, H., Sakulin, M., & Achleitner, G. (2014). Measurement and analysis of neutral point currents in a 400-kV-network. In 2014
Electric Power Quality and Supply Reliability Conference (PQ) (pp. 65–68). IEEE. https://doi.org/10.1109/PQ.2014.6866785
Kelbert, A. (2020). The role of global/regional earth conductivity models in natural geomagnetic hazard mitigation. Surveys in Geophysics, 41(1),
115–166. https://doi.org/10.1007/s10712-019-09579-z
Kellerman, A. C., Mcgranaghan, R., Bortnik, J., Carter, B. A., Hughes, J., Arritt, R. F., etal. (2021). Geomagnetically induced currents at middle
latitudes: 1. Quiet–time variability. Space Weather. 19, e2021SW002729. https://doi.org/10.1029/2021SW002729
Lehtinen, M., & Pirjola, R. J. (1985). Currents produced in earthed conductor networks by geomagnetically-induced electric fields. Annales
Geophysicae, 3, 479–484.
Lowes, F. J. (2009). DC railways and the magnetic fields they produce—The geomagnetic context. Earth, Planets and Space, 61(8), i–xv. https://
doi.org/10.1186/BF03352944
Molinski, T. S. (2002). Why utilities respect geomagnetically induced currents. Journal of Atmospheric and Solar-Terrestrial Physics, 64(16),
1765–1778. https://doi.org/10.1016/S1364-6826(02)00126-8
Oughton, E. J., Skelton, A., Horne, R. B., Thomson, A. W. P., & Gaunt, C. T. (2017). Quantifying the daily economic impact of extreme space
weather due to failure in electricity transmission infrastructure. Space Weather, 15(1), 65–83. https://doi.org/10.1002/2016SW001491
Pfeiffer, M., Franck, C. M., & Schmutz, J. (2015). DC ion-currents in AC conductors in hybrid AC/DC transmission systems. In AC and DC
power transmission 2015. https://doi.org/10.1049/cp.2015.0022
Pirjola, R. (1982). Electromagnetic induction in the earth by a plane wave or by fields of line currents harmonic in time and space. (PhD Thesis).
Finnish Meteorological Institute. Retrieved from https://books.google.at/books?id=s33DwQEACAAJthesis
Pirjola, R. (1989). Geomagnetically induced currents in the Finnish 400 kV power transmission system. Physics of the Earth and Planetary
Interiors, 53(3–4), 214–220. https://doi.org/10.1016/0031-9201(89)90005-8
Price, P. R. (2002). Geomagnetically induced current effects on transformers. IEEE Transactions on Power Delivery, 17(4), 1002–1008. https://
doi.org/10.1109/TPWRD.2002.803710
Pulkkinen, A., Pirjola, R., & Viljanen, A. (2007). Determination of ground conductivity and system parameters for optimal modeling of geo-
magnetically induced current flow in technological systems. Earth, Planets and Space, 59(9), 999–1006. https://doi.org/10.1186/BF03352040
Raith, J. (2019). Risk assessment of power transformers under the influence of Geomagnetically Induced Currents (GIC). (Doctoral Thesis). TU
Graz. Retrieved from https://diglib.tugraz.at/risk-assessment-of-power-transformers-under-the-influence-of-geomagnetically-induced-cur-
rents-gic-2019thesis
Richardson, I. G., Cliver, E. W., & Cane, H. V. (2000). Sources of geomagnetic activity over the solar cycle: Relative importance of cor-
onal mass ejections, high-speed streams, and slow solar wind. Journal of Geophysical Research, 105(A8), 18203–18213. https://doi.
org/10.1029/1999JA000400
Rodger, C. J., Mac Manus, D. H., Dalzell, M., Thomson, A. W. P., Clarke, E., Petersen, T., & Divett, T. (2017). Long-term geomagnetically
induced current observations from New Zealand: Peak current estimates for extreme geomagnetic storms. Space Weather, 15(11), 1447–1460.
https://doi.org/10.1002/2017SW001691
Schachinger, P., & Albert, D. (2021). LFC simulator. Institute of Electrical Power Systems. Retrieved from https://github.com/P-Schachinger/
LFC_simulator
Simonyi, K. (1971). Theoretische Elektrotechnik (4., überarbeitete und ergänzte Auflage ed., Vol. Band 20). VEB Deutscher Verlag der
Wissenschaften.
Simpson, F. (2005). Practical magnetotellurics. Cambridge University Press. https://doi.org/10.1017/CBO9780511614095
Torta, J. M., Serrano, L., Regué, J. R., Sánchez, A. M., & Roldán, E. (2012). Geomagnetically induced currents in a power grid of northeastern
Spain. Space Weather, 10(6), S06002. https://doi.org/10.1029/2012SW000793
Space Weather
ALBERT ET AL.
10.1029/2021SW002912
16 of 16
Tsurutani, B. T., Gonzalez, W. D., Gonzalez, A. L. C., Guar nieri, F. L., Gopalswamy, N., Grande, M., etal. (2006). Corotating solar wind streams
and recurrent geomagnetic activity: A review. Journal of Geophysical Research, 111(A7), A07S01. https://doi.org/10.1029/2005JA011273
Zhang, J. J., Wang, C., Sun, T. R., Liu, C. M., & Wang, K. R. (2015). GIC due to storm sudden commencement in low-latitude high-voltage power
network in China: Observation and simulation. Space Weather, 13(10), 643–655. https://doi.org/10.1002/2015SW001263
... GIC values during the geomagnetic storms are usually in the order of tens of amperes (e.g., Švanda et al., 2021;Torta et al., 2021) and our results confirms these observation (we do not observe values higher than 100 A). Moreover, GICs computations correspond to values mentioned for mid-latitudes by (e.g., Albert et al., 2022;Bailey et al., 2022). It is worth underlining another observation. ...
... Moreover, the GIC problems at middle-and low-latitude transmission lines have increasingly gained attention (e.g., Albert et al., 2022;Bailey et al., 2022;Barbosa et al., 2015;Švanda et al., 2021;Torta et al., 2012;Tozzi et al., 2019;Zois, 2013). In the light of this task proposed procedure of the geoelectric field mapping, not based on SECS methods (appropriate for high latitudes) can be tested and applied. ...
Article
Full-text available
High temporal and high spatial resolution geoelectric field models of two Mäntsälä, Finnish pipeline geomagnetically induced current (GIC) intervals that occurred within the 7–8 September 2017 geomagnetic storm have been made. The geomagnetic measurements with 10 s sampling rate of 28 IMAGE ground magnetometers distributed over the north Europe (from 52.07° to 69.76° latitude) are the bases for the study. A GeoElectric Dynamic Mapping (GEDMap) code was developed for this task. GEDMap considers 4 different methods of interpolation and allows a grid of 0.05° (lat.) × 0.2° (lon.) spatial scale resolution. The geoelectric field dynamic mapping output gives both spatial and temporal variations of the magnitude and direction of fields. The GEDMap results show very rapid and strong variability of geoelectric field and the extremely localized peak enhancements. The magnitude of geoelectric fields over Mäntsälä at the time of the two GIC peaks were 279.7 and 336.9 mV/km. The comparison of the GIC measurements in Mäntsälä and our modeling results show very good agreement with a correlation coefficient higher than 0.8. It is found that the auroral electrojet geoelectric field has very rapid changes in both magnitude and orientation causing the GICs. It is also shown that the electrojet is not simply oriented in the east‐west direction. It is possible that even higher time resolution base magnetometer data of 1 s will yield even more structure, so this will be our next effort.
... This study confirmed the GIC event is not limited to high and mid-latitudes and extends to power systems in low-latitude regions. Albert et al. (2022) analyzed the long-term GIC measurements in transformers for five years in Austria's power grid. Using frequency analysis, they found artificial sources of low-frequency currents and frequent geomagnetic activities in different places. ...
... Many studies (e.g., Kirkham et al., 2011;Liu et al., 2013;Sokolova et al., 2018;Wang et al., 2019;Zhang & Liu, 2020;Albert et al., 2022) show that countries that have developed the space weather monitoring infrastructure to predict and recognize GMD events may prevent damage to their electric-based instruments. Developing solar and space weather monitoring centers helps to predict and protect against the effects of geomagnetic disturbances in middle-east countries that are on the road to development and space investigations. ...
Preprint
Solar activities may disturb the geomagnetic field and impact the power grid via geomagnetically induced currents. We study active and reactive powers as well as the power factor of Iran's power grid transformers (230 kV and 400 kV) and their correlations with geomagnetic disturbances indices (SYM-H < -30 nT and sizable horizontal geomagnetic field fluctuation) from 19 March 2018 to 20 March 2020. Out of 128,627 cases with a transformer power factor of less than 0.7, we observe that 12,112 samples correlated with SYM-H. Our investigation shows that about 4 percent of two years, the SYM-H has values less than -30 nT. Analysis of high-performance transformers (a power factor greater than 0.7 at 95 percent of working time) shows at least a 55 percent correlation of power factor less than 0.7 and SYM-H less than -30 nT. We observe that the transformers' power factor of Rafsanjan-Kerman and Sarcheshmeh-Kerman (wye connection on 230 kV side) substations decreased to less than 0.7 and correlated with SYM-H. We show that the reactive power of the Sefidrood-Guilan and Shahid Beheshti-Guilan transformers (wye configurations) increased considerably on 9 January 2020 and positively correlated with SYM-H may produce large GICs at this part of the grid. We observe that the increase in reactive power at the Shahid Beheshti-Guilan substation correlated with the sizable changes in the horizontal field recorded by the Jaipur station. However, more details (temperature and current of transformers) need records to estimate the impact of geomagnetic induction current on the power grid.
... This study confirmed the GIC event is not limited to high and mid-latitudes and extends to power systems in low-latitude regions. Albert et al. (2022) analyzed the long-term GIC measurements in transformers for five years in Austria's power grid. Using frequency analysis, they found artificial sources of low-frequency currents and frequent geomagnetic activities in different places. ...
... Many studies (e.g., Kirkham et al., 2011;Liu et al., 2013;Sokolova et al., 2018;Wang et al., 2019;Zhang and Liu, 2020;Albert et al., 2022) show that countries that have developed the space weather monitoring infrastructure to predict and recognize GMD events may prevent damage to their electric-based instruments. Developing solar and space weather monitoring centers helps to predict and protect against the effects of geomagnetic disturbances in middle-east countries that are on the road to development and space investigations. ...
... This is called the Nodal Admittance Matrix method [7]. As described by [12], this is equivalent to the well-known Lehtinen-Pirjola method and was proofed with real measurements in [7,13,14]. ...
Article
Full-text available
Solar storms impact electrical power grids by causing quasi‐DC neutral point currents in transformers. These currents lead to half‐cycle saturation as well as other related and unwanted effects in the grid. To reduce the effect of these currents on the grid, DC‐blocking devices can be installed or changes in the grid topology can be made. However, these counter measures often have unwanted side effects or cannot be applied to the grid due to operational restrictions. In this work, a novel mitigation approach, based on the distribution of currents on more transformers, is presented. The number and location of grounded transformer neutral points is optimized, taking grid related constraints such as the minimal number of transformer connections into account. It is shown that the algorithm can effectively reduce the stress on transformers without any additional assets and thus increase system security.
... GIC signals of small to medium amplitudes (units to tens of amps according to the above mentioned categorization) have been directly or indirectly measured (e.g., Albert et al., 2022;Mac Manus et al., 2017;Marsal et al., 2021;Torta et al., 2012), and signals of medium to large amplitudes (50-100 A to more than 100 A) have been predicted for scenarios for a return period of 100 or 200 years (Torta et al., 2014), or for worst-case scenarios in mid latitudinal power grids (Ingham et al., 2017;Liu et al., 2013). In addition to the system-wide operational impacts caused by severe GMDs that can occur at high latitudes, power transformers elsewhere can experience considerable loss of life because of cumulative stress from successive exposures to GIC, a fact that has been actually reported in transformers at latitudes as low as South Africa (Gaunt, 2014;Gaunt & Coetzee, 2007). ...
Article
Full-text available
The aim of this study is to evaluate the geomagnetically induced current (GIC) hazard in the power networks of the Canary and Balearic archipelagos. This is done in order to strictly complete the detailed assessment at national level of the power transmission system of mainland Spain, including the 400 and 220 kV levels. We have constructed models for the grids in each of the individual systems and used resistivity models of the lithosphere for each group of islands, from which we have calculated the surface impedances. The respective models of electrical admittances of the grids have been combined with the geoelectric field derived from the convolution of the recorded (or expected in an extreme scenario) geomagnetic storms and the impedances calculated from the geoelectrical models to derive the expected GICs in the power lines, substations, and transformers. The low geomagnetic latitude of the Canary Islands combined with the small size of their power networks, makes them one of the least likely electrified locations to record significant GICs, with less than 3 A for the 100‐year return period. Even the 13 A that could be reached for the upper limit of the 95% confidence interval at the 500‐year return period does not seem likely to have a significant impact. The Balearic Islands, being at higher latitude and with a system length of approximately 300 km, including alternating current power lines connecting the Islands, shows GIC signals of moderate amplitude with up to 40 A for the 100‐year return period.
... This is called the Nodal Admittance Matrix method [7]. As described by [12], this is equivalent to the well-known Lehtinen-Pirjola method and was proofed with real measurements in [7,13,14]. ...
Preprint
Solar storms impact electrical power grids by causing DC neutral point currents in transformers. These currents lead to half-cycle saturation as well as other related and unwanted effects in the grid. To reduce the effect of these currents on the grid, DC-blocking devices can be installed or changes in the grid topology can be made. However, these counter measures often have unwanted side effects or cannot be applied to the grid due to operational restrictions. In this work, a novel mitigation approach, based on the distribution of currents on more transformers, is presented. The number and location of grounded transformer neutral points is optimized, taking grid related constraints such as the minimal number of transformer connections into account. It is shown that the algorithm can effectively reduce the stress on transformers without any additional assets and thus increase system security.
... It was previously shown that GICs can affect transmission lines in mid-latitude countries, such as the Czech Republic (Svanda et al., 2020;Svanda, Smickova, and Vybostokova, 2021), Austria (Bailey et al., 2018Albert et al., 2022), Italy (Tozzi et al., 2019), Greece (Zois, 2013), Spain (Torta et al., 2012), and even in low-latitude regions (Barbosa et al., 2015;Zhang et al., 2016). ...
Article
Full-text available
A coronal mass ejection (CME) is an impulsive event that emerges rapidly from the Sun. We observed a quiet Sun without many spectacular episodes during the last decade. Although some fast halo and partial halo CMEs had taken place, among them was the backside CME on 23 July 2012. In this work, we verify the link between the variability of solar-wind, heliospheric and geomagnetic parameters and the transmission grid failures registered in southern Poland during 2010 – 2014 when many geomagnetic storms appeared, caused by halo and partial halo CMEs. We aim to apply three machine learning methods: Principal Components Analysis, Self-Organizing Maps, and Hierarchical Agglomerative Clustering to analyze sources on the Sun and the impacts of the intense geomagnetic storms in the first half of Solar Cycle 24. The conducted analyzes underline the importance of solar-wind proton temperature and point out other solar-wind and geomagnetic parameters independently indicated by all the methods used in this study.
... Due to the potential hazard that GIC poses to the operation of continuously expanding power systems around the world, monitoring systems such as that described above have been established in several countries [Albert et al., 2022;Choi et al., 2015;Mac Manus et al., 2017;Watari et al., 2021]. ...
Article
The main problem of electric utilities around the world is to ensure continuous power supply to consumers. One of the causes of power outages and blackouts can be geomagnetic storms during periods of the increased solar activity. They arouse geomagnetically induced currents (GICs) flowing in the long-distance high-voltage power grids on Earth’s surface. The history of this phenomenon investigation shows that GICs during strong geomagnetic storms had led to blackouts in certain regions of Canada, Sweden and the USA. To study these phenomena and assess the risks of such accidents for the regional system, a GICs registration system in 330 kV autotransformers neutrals of the Kola-Karelian power transit was developed in northwestern Russia. During 11 years of monitoring numerous cases of the flow of high values of quasi-dc currents with different time durations, induced by variations of the geomagnetic field, have been registered. In order to analyze the currents a wavelet transform was chosen, since this method allows to define not only the frequency composition but also changes in spectral characteristics over time, which is significant in the study of GIC. The paper presents a discussion of GIC scalograms obtained for four events of Solar Cycle 24: 13-14 November 2012, 17-18 March 2015, 7-8 September 2015 and 7-8 September 2017. The analysis showed that the characteristic duration of the peak of the considered GICs is from 4.6 to 11.1 min.
... The fit for Equation 1 was applied to measurements of direct currents from multiple transformer neutral points in Austrian power grid substations provided by the Graz University of Technology, a summary of which can be found in Albert et al. (2021). In this study, only measurements from two substations were used: one near Vienna (hereafter referred to SS1 for Substation 1) and another north of Salzburg (SS5), both with sampling rates of one second. ...
Preprint
Full-text available
High temporal and high spatial resolution geoelectric field models of two M\"ants\"al\"a, Finnish pipeline GIC intervals that occurred within the 7-8 September, 2017 geomagnetic storm have been made. The geomagnetic measurements with 10 s sampling rate of 28 IMAGE ground magnetometers distributed over the north Europe (from $52.07^\circ$ to $69.76^\circ$ latitude) are the bases for the study. A GeoElectric Dynamic Mapping (GEDMap) code was developed for this task. GEDMap considers 4 different methods of interpolation and allows a grid of $0.05^\circ$ (lat.)$\times 0.2^\circ$ (lon.) spatial scale resolution. The geoelectric field dynamic mapping output gives both spatial and temporal variations of the magnitude and direction of fields. The GEDMap results show very rapid and strong variability of geoelectric field and the extremely localized peak enhancements. The magnitude of geoelectric fields over M\"ants\"al\"a at the time of the two GIC peaks were 279.7 mV/km and 336.9 mV/km. The comparison of the GIC measurements in M\"ants\"al\"a and our modeling results show very good agreement with a correlation coefficient higher than 0.8. It is found that the auroral electrojet geoelectric field has very rapid changes in both magnitude and orientation causing the GICs. It is also shown that the electrojet is not simply oriented in the east-west direction. It is possible that even higher time resolution base magnetometer data of 1 s will yield even more structure, so this will be our next effort.
Article
Full-text available
Plain Language Summary Using satellites, we measure the state of the solar wind a short distance away from the Earth (at the so‐called Lagrange‐1 or L1 point) to see what is coming toward us at any given moment. Changes in the solar wind such as an increase in wind speed or a strong magnetic field can potentially impact satellite operation in orbit and power grid infrastructure on the ground ‐ in extreme cases, solar storms can damage power grids and transformers by inducing electrical currents in the power lines. These are called geomagnetically induced currents (GICs). Here, we attempt to forecast the scales of GICs by applying machine learning methods, specifically Long‐Short‐Term‐Memory recurrent neural networks, to take the solar wind data measured at the L1 point and predict the currents that would be seen in power grids in Austria. This gives us a lead time of around 10–40 min in the forecast. We discuss whether it is best to attempt to predict the ground electric field that leads to the GICs or the GICs themselves, and discuss the difficulties in this kind of prediction and the shortfalls in the model.
Preprint
Full-text available
The forecasting of local GIC effects has largely relied on the forecasting of dB/dt as a proxy and, to date, little attention has been paid to directly forecasting the geoelectric field or GICs themselves. We approach this problem with machine learning tools, specifically recurrent neural networks or LSTMs by taking solar wind observations as input and training the models to predict two different kinds of output: first, the geoelectric field components Ex and Ey; and second, the GICs in specific substations in Austria. The training is carried out on the geoelectric field and GICs modelled from 26 years of one-minute geomagnetic field measurements, and results are compared to GIC measurements from recent years. The GICs are generally predicted better by an LSTM trained on values from a specific substation, but only a fraction of the largest GICs are correctly predicted. This model had a correlation with measurements of around 0.6, and a root-mean-square error of 0.7 A. The probability of detecting mild activity in GICs is around 50%, and 15% for larger GICs.
Article
Full-text available
The solar rotation period is the most prominent mid-term periodicity in the temporal behaviour of solar, heliospheric, and geomagnetic parameters. It is also a cause of the repeatedly appearing geomagnetic storms originating from the corotating interaction regions (CIRs). Since geomagnetic CIR-driven storms have a natural periodic character, and geomagnetic storms impact energy infrastructure via geomagnetically induced currents, it is of interest whether this periodic character is also noticeable in the temporal behaviour of electrical-grid failures (EGFs), which, at least to some extent, might be of solar origin.
Article
Full-text available
Geomagnetically induced currents (GICs) at middle latitudes have received increased attention after reported power grid disruptions due to geomagnetic disturbances. However, quantifying the risk to the electric power grid at middle latitudes is difficult without understanding how the GIC sensors respond to geomagnetic activity on a daily basis. Therefore, in this study the question “Do measured GICs have distinguishable and quantifiable long‐period and short‐period characteristics?” is addressed. The study focuses on the long‐term variability of measured GIC, and establishes the extent to which the variability relates to quiet‐time geomagnetic activity. GIC quiet‐day curves (QDCs) are computed from measured data for each GIC node, covering all four seasons, and then compared with the seasonal variability of thermosphere‐ionosphere‐electrodynamics general circulation model (TIE‐GCM)‐simulated neutral wind and height‐integrated current density. The results show strong evidence that the middle‐latitude nodes routinely respond to the tidal‐driven Sq variation, with a local time and seasonal dependence on the direction of the ionospheric currents, which is specific to each node. The strong dependence of GICs on the Sq currents demonstrates that the GIC QDCs may be employed as a robust baseline from which to quantify the significance of GICs during geomagnetically active times and to isolate those variations to study independently. The QDC‐based significance score computed in this study provides power utilities with a node‐specific measure of the geomagnetic significance of a given GIC observation. Finally, this study shows that the power grid acts as a giant sensor that may detect ionospheric current systems.
Article
Full-text available
Geomagnetic disturbances cause perturbations in the Earth’s magnetic field which, by the principle of electromagnetic induction, in turn cause electric currents to flow in the Earth. These geomagnetically induced currents (GICs) also enter man-made technological conductors that are grounded; notably, telegraph systems, submarine cables and pipelines, and, perhaps most significantly, electric power grids, where transformer groundings at power grid substations serve as entry points for GICs. The strength of the GICs that flow through a transformer depends on multiple factors, including the spatiotemporal signature of the geomagnetic disturbance, the geometry and specifications of the power grid, and the electrical conductivity structure of the Earth’s subsurface. Strong GICs are hazardous to power grids and other infrastructure; for example, they can severely damage transformers and thereby cause extensive blackouts. Extreme space weather is therefore hazardous to man-made technologies. The phenomena of extreme geomagnetic disturbances, including storms and substorms, and their effects on human activity are commonly referred to as geomagnetic hazards. Here, we provide a review of relevant GIC studies from around the world and describe their common and unique features, while focusing especially on the effects that the Earth’s electrical conductivity has on the GICs flowing in the electric power grids.
Conference Paper
Power system damage and disruption initiated by geomagnetically induced currents (GICs) can arise from thermal damage to transformers, voltage instability and protection maloperation. All of them require suitable simulation studies as a basis for realistic assessments. Utilities’ GIC measurements from four continents show that particular directions of strong geo-electric fields characterise larger GICs. Past measurements of magnetic fields and GICs can be used to estimate accurately the GICs expected during stronger disturbances and benchmark events. GICs distort the magnetic flux distribution in transformers, causing partial half-wave saturation. We tested the magnetic performance of transformers by practical measurement, finite element method (FEM) modelling and equivalent circuit models in network analysis. Various core constructions showed unexpected results differing from other reports. Dissolved gas analysis interpretation identifies when degradation started, and FEM models can indicate possible regions of degradation. Conventionally described reactive power consumption of transformers carrying GICs over-simplifies the decrease of transformer incremental inductance during one half of the power cycle. Harmonic distortion, unbalance, voltage drop, decreased efficiency of power transfer through a network, and voltage stability are not represented well by models and calculations based on average inductance or reactive power. A new general power theory and time-domain load flow studies reveal the real power factor and voltage drop caused by GICs in networks with transformers of different core types. We conclude with suggestions for monitoring, calculations and assessment for planning mitigation.
Conference Paper
Low frequency currents (LFC) or quasi DC (QDC) in the electrical power transmission network, and especially in power transformers, are causing negative effects such as increase in noise level, in reactive power consumption and in power losses. Currently no classification of LFC is available to identify possible source. In order to identify the origin of undesired LFC, classifications of LFC in current and audio measurements are defined. They are based on a spectrum analysis of current and audio measurements. These classifications are successfully tested in laboratory and field measurements. Consequently, LFC sources are identified by field and laboratory measurements and analytical approaches. For power transformer operators a user-friendly and fast method is presented to identify LFC in the transformers. The method is based on audible measurements and serves as a first estimator for low frequency currents in power transformers.
Conference Paper
Conductive grounded electrical power transmission networks offer a low resistance path for currents induced in the ground. High latitude regions or those with low earth conductivity are especially affected by geomagnetically induced currents (GICs), which are caused by space weather events. Induced currents can cause damages of assets or system outages. Austria, as part of the European Alps with low conductive areas, tends to have a higher risk of induced currents in the electrical power transmission network, therefore, the effect of space weather in the power system has been investigated. Two independent models of GICs in Austria were set up and verified through comparison to ongoing transformer neutral point current measurements. Further research fields, such as space weather prediction, power transformers under dc bias and countermeasures for system operation are outlined.
Article
Space weather events can cause geomagnetically induced currents (GICs) in power transmission networks. Over the past years, these currents have been measured in multiple substations in Austria, and the measurements have been tested against a model of local GIC with the aim of producing an optimized model, which can be developed through evaluation of various input parameters. We show the impact the choice of the local resistivity, in particular the surface conductivity in thin-sheet modeling, and the source of geomagnetic variations has on GIC modeling. In addition, the sensitivity of the model to the accuracy of the network configuration is also investigated. This encompasses the inclusion of power grids outside of Austria in the model as well as the consequences of removal of a substation either through transformer failure or active disconnection. Results show that a detailed surface conductivity model brings benefits to areas with large lateral conductivity variations and that there are certain substations that lead to increases and decreases of GIC in the rest of the network when removed. The importance of regionally representative geomagnetic field measurements is also highlighted and shown to impact model accuracy. This study concentrates on regional effects, but the results are also valid for large-scale studies elsewhere.
Article
Geomagnetically induced current (GIC) observations made in New Zealand over 14 years show induction effects associated with a rapidly varying horizontal magnetic field (dBH/dt) during geomagnetic storms. This study analyzes the GIC observations in order to estimate the impact of extreme storms as a hazard to the power system in New Zealand. Analysis is undertaken of GIC in transformer number six in Islington, Christchurch (ISL M6), which had the highest observed currents during the 6 November 2001 storm. Using previously published values of 3,000 nT/min as a representation of an extreme storm with 100 year return period, induced currents of ~455 A were estimated for Islington (with the 95% confidence interval range being ~155-605 A). For 200 year return periods using 5,000 nT/min, current estimates reach ~755 A (confidence interval range 155-910 A). GIC measurements from the much shorter data set collected at transformer number 4 in Halfway Bush, Dunedin, (HWB T4), found induced currents to be consistently a factor of 3 higher than at Islington, suggesting equivalent extreme storm effects of ~460-1,815 A (100 year return) and ~460-2,720 A (200 year return). An estimate was undertaken of likely failure levels for single-phase transformers, such as HWB T4 when it failed during the 6 November 2001 geomagnetic storm, identifying that induced currents of ~100 A can put such transformer types at risk of damage. Detailed modeling of the New Zealand power system is therefore required to put this regional analysis into a global context.