ArticlePDF Available

A Novel Approach for Evaluating Eddy Current Loss in Wind Turbine Generator Step-Up Transformers

Authors:

Abstract and Figures

South Africa is aiming to achieve a generation capacity of about 11.4GW through wind energy systems, which will contribute nearly 15.1% of the country’s energy mix by 2030. Wind energy is one of the principal renewable energy determinations by the South African government, owing to affluent heavy winds in vast and remote coastal areas. In the design of newfangled Wind Turbine Generator Step-Up (WTGSU) transformers, all feasible measures are now being made to drive the optimal use of active components with the purpose to raise frugality and to lighten the weight of these transformers. This undertaking is allied with numerous challenges and one of them, which is particularly theoretical, is delineated by the Eddy currents. Many times the transformer manufacturer and also the buyer will be inclined to come to terms with some shortcomings triggered by Eddy currents. Still and all, it is critical to understand where Eddy currents emanate and the amount of losses and wherefore the temperature rise that may be produced in various active part components of WTGSU transformers. This is the most ideal choice to inhibit potential failure of WTGSU transformers arising from excessive heating especially under distorted harmonic load conditions. In the current work, an extension of the author’s previous work, new analytical formulae for the Eddy loss computation in WTGSU transformer winding conductors have been explicitly derived, with appropriate contemplation of the fundamental and harmonic load current. These formulae allow the distribution of the skin effect and computation of the winding Eddy losses as a result of individual harmonics in the winding conductors. These results can be utilized to enhance the design of WTGSU transformers and consequently minimize the generation of hotspots in metallic structures.
Content may be subject to copyright.
www.astesj.com 488
A Novel Approach for Evaluating Eddy Current Loss in Wind Turbine Generator Step-Up Transformers
Bonginkosi Allen Thango*, Jacobus Andries Jordaan, Agha Francis Nnachi
Department of Electrical Engineering, Tshwane University of Technology, Emalahleni, 1034, South Africa
A R T I C L E I N F O
A B S T R A C T
Article history:
Received: 25 December, 2020
Accepted: 03 February, 2021
Online: 17 March, 2021
South Africa is aiming to achieve a generation capacity of about 11.4GW through wind
energy systems, which will contribute nearly 15.1% of the country’s energy mix by 2030.
Wind energy is one of the principal renewable energy determinations by the South African
government, owing to affluent heavy winds in vast and remote coastal areas. In the design
of newfangled Wind Turbine Generator Step-Up (WTGSU) transformers, all feasible
measures are now being made to drive the optimal use of active components with the purpose
to raise frugality and to lighten the weight of these transformers. This undertaking is allied
with numerous challenges and one of them, which is particularly theoretical, is delineated
by the Eddy currents. Many times the transformer manufacturer and also the buyer will be
inclined to come to terms with some shortcomings triggered by Eddy currents. Still and all,
it is critical to understand where Eddy currents emanate and the amount of losses and
wherefore the temperature rise that may be produced in various active part components of
WTGSU transformers. This is the most ideal choice to inhibit potential failure of WTGSU
transformers arising from excessive heating especially under distorted harmonic load
conditions. In the current work, an extension of the author’s previous work, new analytical
formulae for the Eddy loss computation in WTGSU transformer winding conductors have
been explicitly derived, with appropriate contemplation of the fundamental and harmonic
load current. These formulae allow the distribution of the skin effect and computation of the
winding Eddy losses as a result of individual harmonics in the winding conductors. These
results can be utilized to enhance the design of WTGSU transformers and consequently
minimize the generation of hotspots in metallic structures.
Keywords:
Wind energy
Transformer
Eddy currents
Harmonics
Temperature rise
1. Introduction
South Africa remains engaged in diversifying the power mix
that will make it possible to reduce the subjection to coal power
generation. The ongoing decommissioning of various coal power
plants resulting from end of service life, can potentially make way
for a radically distinct power mix as opposed to the current
monopolization by coal power plants which have an installed
capacity of 40GW [1]. At the present day, South Africa’s
Department of Energy through the Renewable Energy Independent
Power Producer’s Procurement Programme (REI4P) has deployed
a total of 64 renewable energy facilities, of which 25 are wind
energy constituting of 961 wind turbines with a total generation
capacity of 2,1 GW [2]. Wind energy currently contributes 52% of
the country’s renewable energy capacity [3]. The wind energy
tariff is currently at about R0.62/kWh, in which is about 45% less
than the tariff for a coal plant. Each turbine generator in a wind
energy facility is furnished with a step-up transformer at the
bottom of the tower as shown in Figure 1 (a), which transforms its
output voltage to a desired medium voltage (MV) collector level.
In South Africa, these Wind Turbine Generator Step-Up
(WTGSU) transformers are failing at an unnerving rate and utility
owners are confound to ascertain the potential causes for these
prevailing deficiencies. A typical WTGSU transformer failure
arising from an insulation failure which is attributable to a disc-to-
disc short circuit failure to generate a spark that ignites the
transformer oil as shown in Figure 1 (b).
Field experience is indicating that these failures are triggered
by the use of regular distribution (RD) transformers that cannot
meet the required operational requirements of the wind energy
environment. With the objective to pledge future dependability of
wind energy in South Africa, WTGSU transformers must integrate
these requirements particularly with regard to a deformed loading
ASTESJ
ISSN: 2415-6698
*Corresponding Author: Bonginkosi Allen Thango, thangotech@gmail.com
Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com
Special Issue on Multidisciplinary Sciences and Engineering
https://dx.doi.org/10.25046/aj060256
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 489
cycle, harmonics and distortion, de-rating, switching over-voltages
and stray gassing.
(a)
(b)
Figure 1: (a) WTGSU transformer during service; (b) Ignition of a
WTGSU transformer.
Nonlinear loads and sporadic wind turbine generators are
infamous for producing harmonic load currents and call for
WTGSU transformers to connect them safely to the electrical
network [4-5]. Transformers are commonly designed under the
presumption of sinusoidal loading conditions [6-7]. It is widely
known that distorted harmonic load currents accentuates the
service losses in transformer and ultimately the temperature rise
and generation of hotspots in metallic structures, resulting in
degradation of insulation materials and untimely failures as shown
in Figure 1 (b) [8-10].
Transformer windings are conceivably the most crucial part of
WTGSU transformers, electrically and mechanically, and they are
one of the major contribution of untimely failures in WTGSU
transformers [11]. The contribution of winding conductors to
WTGSU transformer failures is about 80%, which is a significant
portion among the failures caused by other transformer parts [11].
In view of the increasing proclivity of nonlinear loads in the power
system, the WTGSU transformers are more notably susceptible to
fail. As a result, to minimize power losses and excessive heating in
winding conductors, magnetic shielding [12-13], and laminating
the core material [14-15] has been proposed in the literature.
At tender stage, it is essential to evaluate the transformer
winding stray losses triggered by the EMFs. In this way, the
inception of new formulae is recommendable and endeavor to
enhance the computation and evaluation methods. A number of
studies have been undertaken recently which take these objectives
into account [16-20]. Thus, analytical techniques have
demonstrated to be efficacious in computing the electromagnetic
service losses. In a broader sense, there are two commonly used
techniques in the transformer manufacturing industry to evaluate
the winding Eddy current losses: (i) direct computation of the EMF
using Maxwell’s equations in [21-22] and (ii) use of Poynting’s
theorem in [21-22]. Early attempts to compute the EMF using both
these methods are presented by authors in [23]. In the book
Transformer Engineering: Design and Practice [24], the authors
described these methods and how they can be embedded into
manufacturers internal design programs to compute the Eddy
currents. Design programs based on the Finite element Method to
compute the Eddy currents are witnessed in the publications [25-
28].
Owing to the increasing renewable energy market and
applications of nonlinear loads, the evaluation of the winding stray
losses in WTGSU transformer necessitates the consideration of the
harmonic load current spectrum (HLCS), with appropriate
computation of the electromagnetic fields (EMFs). Consequently,
it is essential to study the impact of the HLCS on the winding stray
losses and associated temperature rise of active part components.
In the current work, an extension of the author’s previous work
[29], comprehensive analytical formulae to calculate the winding
Eddy losses in the presence of harmonics by taking into account of
the winding conductor dimensions, EMF and skin effect are
derived. The acquired formulae ensure that the examination of the
contribution of individual harmonics to the power losses is done.
Therefore, these are effective formulae that can produce rapid
results for electrical designers without the requirement of costly
and high-class computational resources.
The remainder of this work is structured as follows. Section 2
outlines the challenges and electrical design considerations of
WTGSU transformers. In Section 3, a winding Eddy loss formula
is derived under normal operating conditions by taking into
account the fundamental frequency, EMF, local flux density and
winding conductor material properties. In section 4, a winding
Eddy loss formula is derived under harmonic load conditions and
takes into account the winding conductors, EMFs, skin effect,
additionally, a new and simplified harmonic loss factor (HLF) is
derived to account for the additional losses that will be seen by the
WTGSU transformer during service. In Section 5, a case scenario
of a WTGSU transformer supplying a distorted harmonic load is
presented and corresponding losses are computed using proposed
formulae. These results are then compared with the method for
calculating transformer losses recommended by the IEC standard
and simulation results obtained by Finite Element Method. Finally,
the conclusion is presented in Section 6.
2. Electrical design concerns
A large portion of wind turbine transformers currently in
service are afflicted with numerous electrical concerns. These are
prevalently on account of the unpredictable wind speed round the
clock during their service. These inefficacies are the main drivers
of the premature failures of these transformers.
2.1. Distorted load cycle
Wind turbines depend to a large extent upon regional wind and
other weather patterns, and their annual average capacity factor is
close to 40% [30]. A majority of the power producers in the past
projected the operational loading would be more than 50%. The
comparatively light loading of WTGSU transformer present two
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 490
distinct and operationally momentous challenges that must be
embedded into the design philosophy of WTGSU transformer.
The foremost challenge is that the WTGSU transformer’s
relatively low average capacity factor falsify purchasing
adjudication and invalidate classical economic models for regular
distribution transformers. On account of the ideational nature of
wind energy facility developments in South Africa, the
Engineering, Procurement and Construction (EPC) developer is
most frequently concerned with a cheaper initial transformer price.
The utility owner who takes over responsibility of the facility from
the EPC take a greater interest in the Total ownership cost (TOC)
of the WTGSU transformer over its designed service lifetime.
These costs include the initial purchase cost of the transformer, the
cost of service no-load and load losses and routine maintenance
costs [31-32]. The TOC models developed by authors in [31-34]
do not take into consideration the relatively low average capacity
factor of WTGSU transformers. Bearing in mind that the loading
cycle of WTGSU transformers is so distinct from regular
distribution transformers, EPCs must be mindful of the obsolete
loss capitalization formulae when evaluating the TOC for WTGSU
transformers.
Another challenge is that the WTGSU transformers are
susceptible to regular thermal load cycling on account of the
sporadic characteristic of the wind turbines. The latter give rise to
the generation of hotspots in the transformer active part
components including core, windings, clamping structure, flitch
plates, tank walls et cetera. Recurrent thermal stresses drives the
immersion of nitrogen gas into the hot insulating oil and it is
emancipated as the insulating oil cools down. This phenomena
results in the production of combustible gaseous bubbles that can
potentially generate partial discharges and consequently damage
the cellulose insulation. Additionally, sporadic thermal cycling can
expedite the aging of electrical connections within the transformer
tank.
2.2. Harmonics and distortion
The transformer design principle is formed on the rationale of
generating an alternating EMF from a steady sinusoidal power
supply voltage to instigate the flow of current and voltage potential
in the winding conductors across that EMF.
During service, a steady sinusoidal wave shape is not practical.
In the power system, the voltage and current wave shapes are
distorted from the theoretical sinusoidal wave shapes. In practical
terms, the total harmonic distortion (THD) ranging between 1 and
2 is prevalent at the point of common coupling (PCC). The
application of non-linear loads in the facility can further contribute
to distortion of the voltage and current wave shapes. These
accumulative distortions reiterate very cycle, embellishing peaks
that mount the voltage and current wave shapes and arise at distinct
frequencies from the fundamental frequency of 50 Hertz (Hz) as
shown in Figure 2.
The adverse effects of harmonics is that they trigger an upsurge
in the copper loss, winding Eddy loss and stray loss in other
metallic components. Eddy current and circulating current
generate overheating in the transformer active part components,
which must be treated by a sufficient cooling system design to
thermal aging and untimely failures of WTGSU transformers
during service. The wind turbine generator output, much like other
renewable energy sources is intermittent and will produce distorted
harmonic wave shapes. In this regard, the WTGSU transformer is
operated with solid state controls which furnish additional
harmonics and distortion.
Figure 2: Current wave shapes: With and without distortion
Electrical generator systems that employ electronic switching
devices and circuits also present specific problems for WTGSU
transformers. From a manufacturer perspective, design
philosophies to minimize the Eddy current loss to redress for
harmonic load currents are imperative. While harmonic filtering is
particularly not a function of a WTGSU transformer, magnetic
shields strategically positioned between the windings may act as
filters to mitigate the distorted harmonic currents into the collector
bus. As a result, magnetic shielding should be deemed compulsory
in the design of WTGSU transformers.
2.3. Switching Over-Voltages
A major concern with vast, wind turbine arrays is the necessity
for connecting individual WTGSU transformers to the utility
collector bus, leading to lengthy runs of cables. In large-scale wind
facilities with a cluster of wind turbine towers, the WTGSU
transformers may be positioned near the tower base as shown in
Figure 1 in order to minimize the costs of large and lengthy runs
of copper cables. Problems including excessive voltage drop,
cable losses and risk of ground faults may arise from lengthy cable
runs.
In view of the fact that wind energy facilities are in remote
areas, they are more susceptible to lightning surges. As a result,
surge arrestors must be mandatory for all WTGSU transformers.
Other things being equal, the biggest concern about switching
over-voltages may be that generated by the wind turbines. On a 24-
hours period, depending on the intermittent nature of wind; the
wind turbines may be connected and disconnected online and
offline when the wind speed increase and decline respectively. The
latter may also occur when circuit breakers opens and closes the
WTGSU transformer from the collector bus circuit. The switching
phenomena by circuit breaker operation trigger transient over-
voltages into the WTGSU transformers. This occurrence is
aggravated by the application of vacuum circuit breakers, which
have high-speed switching times. The fusion of the transient over-
voltages and capacitance of the copper cables either HV or LV
WTGSU transformer side may result in stationary waves and
ringing that exceed the sinusoidal voltage amplitude as shown in
Figure 3.
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 491
Figure 3: Typical switching surge [35]
Excessive transient over-voltages can trigger WTGSU
transformer insulation failures. The transient over-voltages as
shown in Figure 3 contains fast rise-time and high voltage
amplitudes which clash with the resonant frequencies on the
windings and can introduce electrical stresses exceeding the
dielectric capability of the windings.
3. Winding Eddy loss under normal conditions
During service the winding conductor is immersed in an
alternating magnetic field and subsequently the Eddy current start
to flow. The energy loss dissipated as thermal energy on account
of the Eddy current bring forth the Winding Eddy losses. The
phenomena in rectangular winding conductors is demonstrated in
Figure 4.
Figure 4: Harmonic current profiles [36]
The derivation of the winding Eddy loss formulae is reliant on
factors suchlike frequency, local flux density and the winding
conductor material properties. Provided that a winding conductor
has the parameters as indicated in Figure 4 namely the, length,
height and thickness are denoted by L, h and τ respectively. Then
the alternating magnetic flux characteristic that is perpendicular to
the height and thickness can be described by the eq. (1).

(1)
Taking into consideration a closed-path in a clock-wise
direction as shown in Figure 4, of thickness dx and distance x, a
presentation of a single conductor with an induced voltage in
closed-path is established. The area of this closed-path is expressed
as follows in Eq. (2).
(2)
The amount of magnetic flux passing through the unit area in
eq. (2) is expressed as follows in Eq. (3).
(3)
It follows then, that the amount of magnetic flux characteristic
that is perpendicular to the height and thickness in the closed-path
can be described by the eq. (4).

(4)
The induced voltage in the closed-path can be expressed in
accordance with the Faradays law of induction as expressed in Eq.
(5).

(5)
Equating the constant 4.44=√2 π yields the formula in Eq. (6)

(6)
Taking into account the amount of magnetic flux passing
through the closed-path unit area the eq. (6) yields the formula
expressed in Eq.(7).

(7)
Substituting the area of the closed-path in the induced voltage
formula in Eq. (7) yields eq. (8).

(8)
The resistance of the closed-path can then be expressed as
follows in Eq. (9).


(9)
The winding Eddy loss in the closed-path dx is then expressed
as shown in Eq. (10). Considering that the thickness of the closed-
path is extremely small in relation to the height, then the distance
x I negligible.


(10)
Substituting eq. (7) into eq. (10) yields the expression in Eq.
(11).

 
(11)
Equating the constant √2 π=4.44 in Eq. (11) yields the formula
in Eq. (12).

 
(12)
Removing the square and expressing each terms to the
exponent 2 yields eq. (13).
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 492


(13)
Integrating both sides of Eq. (13) and considering the closed-
path then the Eddy loss can be derived using Eq. (14).
 
 
(14)
Subsequently, the solution can be expressed as follows in Eq.
(15).

 
(15)
Dividing the Eddy loss by hLτ equates to the area per unit
volume as expressed in eq. (16).


(16)
Finally, the Winding Eddy loss at fundamental frequency is
expressed as follows in Eq. (17).

(17)
Here,

The skin depth of penetration at fundamental frequency 50Hz
may be calculated as follows in Eq. (18).
(18)
The depth of penetration under HLC is then computed as
follows in Eq. (19).
(19)
In principle, the following conclusions can be drawn with
regards to the Eddy current loss in relation to the area per unit
volume of winding conductor based on this derivation:
There is a direct proportion to the fundamental frequency,
conductor dimension and local flux density.
There is an inversely proportional relationship to the
resistivity of the copper conductor.
4. Transformer winding Eddy loss weighting factor
4.1. Winding Eddy loss under harmonic current loading
The winding Eddy loss along a winding height (H) can be
expressed as follows in Eq. (20) [37].
 
(20)
The standardized winding Eddy loss is then expressed by
dividing eq. (18) with the rated copper loss to yield eq. (21).

(21)
Taking into consideration that the copper loss has a directly
proportional relationship with the root mean square (RMS) load
current under harmonic conditions [38-40] then first part of eq.
(21) yields Eq. (22).




(22)
The contribution of the second part of Eq. (20) is as expressed
in Eq. (17). The magnetic flux leakage under harmonic conditions
has a directly proportional relationship to the RMS load current as
expressed in Eq. (23).
(23)
Under harmonic current conditions, the current I is expressed
in Eq. (24).
 


(24)
The harmonic current in Eq. (24) is expressed as. As such,
the Eq. (24) yields Eq. (25).
  


(25)
Here, the constant K is expressed in Eq. (17).
During service, when the transformer is operating at
fundamental frequency, the equivalent rated winding Eddy loss is
expressed as shown in Eq. (26).

(26)
Combining Eq. (25) and Eq. (26), the winding Eddy loss for a
transformer operating under harmonic current can be expressed as
shown in Eq. (27).
 


(27)
Subsequently, combining Eq. (22) and Eq. (27) yields Eq.
(28). This equation is formulated on the premise that induced
current is at fundamental load current of the transformer during
service.




  


(28)
Further simplification of Eq. (28) yields Eq. (29).
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 493










(29)
The allowance made in order to take into account of the
harmonic load current in relation to their effects on transformer
thermal performance is then expressed as follows in Eq. (30).









(30)
In principle, the following conclusions can be drawn with
regards to the Eddy current loss under harmonic current loading:
The winding Eddy loss is directly proportional to the RMS
load current and the harmonic order. This relationship is
similar in the computation of the stray loss in tank walls, core
clamps et cetera except that the harmonic order is expressed
to an exponent of 0.8 [35].
The skin effect is not taken into consideration at high
harmonic order. The magnetic flux under these conditions
does not completely penetrate the surface of the winding
conductors.
In the next section, a weighted loss factor that considers the
skin effect is derived.
4.2. Winding Eddy loss under harmonic current loading
The Eddy current problem form part to the area of quasi-
stationary electromagnetic effects of conductors. Insomuch that,
the displacement current enclosed by winding conductors may
incessantly be ignored in relation to the conductive current. This
is indeed the case even at high frequencies given that in practice
only winding conductors comprising high electric conductivity are
used. Eddy currents give rise to uneven dissemination of current
density in a studied cross sectional area of a conducting conductor.
This inherently leads to rise in joule heating as opposed to the state
produced by direct current (DC). The Eddy currents and related
uneven dissemination of the magnetic flux are known as the skin
effect. The rise in current density give rise to resistive heating as
opposed to the DC resistance as well as a reduction in the
inductance. In addressing the skin effect problem, this study
adopts the Maxwell equations in [38] and remodel these equations
to treat the quasi-stationary electromagnetic effects of conductors.
These equations are expressed as follows in Eq. (31) and Eq. (32).


(31)

(32)
On the above equations an add-on of the Ohm’s law as
expressed in Eq. (33).

(33)
The electric field intensity must fulfil Eq. (34).

(34)
Similarly, the magnetic field must fulfil Eq. (35).

(35)
In investigating the dissemination of current, small but
sufficiently long conductors are considered. The location of the
conductors in a coordinate system as demonstrated in Figure 5. The
height and ratio of these conductors fulfil the condition 
and the spatial dependence on the y-coordinate may be ignored
with insignificant error. When the current flows in the z-
coordinate, the magnetic field has one component as described in
Eq. (36).

(36)
In the same order, the electric field intensity has a single
component as expressed in Eq. (37).

(37)
In the event that a winding conductor has the
conductivity 
the permeability 
and time-
variant harmoniously at angular frequency 
, by
elimination the ordinary second-order differential Maxwell
equations for magnetic field intensity vector is expressed as
follows in Eq. (38).

(38)
Here, the constant k is expressed as shown in Eq. (39).

(39)
In investigating the skin effect in winding conductors with a
spasmodic magnetic flux, the rectangular copper conductors in
Figure 5 are considered.
Figure 5: Two winding conductors immersed in alternating EMFs
The spasmodic magnetic flux streams along in the z-coordinate
and the interaction of winding conductor 1 and 3 with respect to
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 494
winding conductor 2 is investigated in terms of the winding Eddy
loss under harmonic conditions. The effect of the remainder of
winding conductors will be disregarded in order to presume that
the impact of winding conductor 1 and 3 will be completely offset
in the center winding conductor. Presupposing a harmonic time
response of the 2nd order differential equation in Eq. (38), with
the initial conditions necessitated for symmetry along the edges of
the winding conductors shall be valid the equation 
 and will yield the solutions in Eq. (40) and Eq. (41) as
expressed below. It is evident that the solution in this case scenario
is of  nature.

(40)

(41)
Here, is the root mean square (RMS) magnetic field
strength. Additionally, the condition of  is valid since the
impact along the edges of the winding conductors
is
negligible if  is satisfied. The constants of integration from
Eq. (40) and Eq. (41) can then be expressed as follows in Eq. (42).

(42)
The solution of the magnetic field strength presume the format
expressed in Eq. (43).


(43)
By association, the magnetic flux density by Eq. (42) is
expressed as shown in Eq. (44).


(44)
Maxwell’s 1st equation in Eq. (33), can then be expressed as
follows in Eq. (45).


(45)
The constant k is introduced into the rationalization of the
equilateral hyperbola as shown in Eq. (46).
(46)
The skin depth of penetration a under harmonic conditions may
be calculated as follows in Eq. (47).

(47)
The skin depth at various harmonic orders is demonstrated in
Figure 6.
Figure 6: Depth of skin effect
The formulation of the current density is acquired and
expressed as shown in Eq. (48).


(48)
With the expansion of the equilateral hyperbola the modulus of
the current density is expressed shown in Eq. (49).






(49)
The dissemination of the magnetic flux density and current
density along the surface of the winding conductors is described
by Figure 7.
Figure 7: Distribution of the magnetic flux in the cross-section of a
winding conductor
The magnetic flux leakage impinging upon one conductor is
expressed by Eq. (50).
 
 
(50)
-2
0
2
4
6
8
10
12
-6 -4 -2 0 2 4 6
B
σ
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 495
The peak value of the magnetic flux leakage is given by Eq.
(51).





(51)
Similarly, the magnetic flux density is expressed by Eq. (52).
 





(52)
By employing Eq. (49) and introducing Eq. (52), the formulation
of the current density is expressed as shown in Eq. (53).








(53)
The variable is introduced here to account for expression of

above as shown in Eq. (54).

(54)
Forthwith, the Eddy loss per unit of volume of a winding
conductor can be calculated using Eq. (17), where the weighted
factor will be employed as expressed in Eq. (55).

(55)
Here, the weighting function that takes into consideration the
skin effect in winding conductors under harmonic conditions is
expressed as follows in Eq. (56).


(56)
This function is presented graphically at different conductor
dimensions as shown in Figure 8.
Figure 8: The function and
It is evident from Figure 8, that at higher harmonic order, the
magnetic flux leakage does not completely penetrate upon the
surface of the conductors. The latter addresses the short coming of
Eq. (30).
5. Materials and Methods
In this section, a WTGSU transformer rated at 5000 KVA,
11000/33000 volts, 3-phase, 50 cycles, oil-immersed, naturally
cooled (ONAN), core type, double wound with copper conductor
and fitted with on load tap changer is studied. The temperature rise
in oil and winding conductors is 50 ºC and 55 ºC respectively. The
rated losses under consideration are at 75ºC on normal Tap
position (in Watts) as shown in Table 1.
Table 1: Rated transformer losses
Type of loss
Rated Losses (Watts)
No load
4 500
Copper
25 000
Winding Eddy
938
Other Stray
1 253
Total
31 691
The studied transformer has a full load low voltage (LV)
winding current of 262,43A with a mean winding Eddy loss at the
highest loss ratio under rated conditions at 15% of the Copper
losses.
The load that will been seen by the studied WTGSU
transformer is described as shown in Figure 9. It is preferential that
this harmonic load spectrum (HLS) to which the WTGSU will be
susceptible be indicated to the transformer manufacturer during
bid stage. A precise evaluation for the appropriate sizing of
WTGSU transformers can only be designed by estimating the
particular HLS.
Figure 9: Harmonic Load Spectrum
The resultant HLFs and service losses are computed and
discussed in the next section.
6. Results
6.1. Computation of Harmonic Loss Factor
It is handy to specify a single digit that may have recourse to
evaluate the capability of the studied WTGSU transformer in
facilitating power to the supplied harmonic spectrum above. This
0
0.2
0.4
0.6
0.8
1
0 1 2 3 4 5 6
F_H
F_H 3/z
0
0.2
0.4
0.6
0.8
1
1357911 13 15 17 19
Harmonic spectrum (p.u)
Harmonic Order
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 496
value viz. the harmonic loss factor (HLF) illustrates the effective
RMS heating on account of the harmonic spectrum. The
calculation of the HLF is tabulated in Table 2. The HLF by FEM
is computed using the procedure described in [38].
Table 2: Computation of HLFs.
h


IEC
Proposed
FEM
1
0,97
0,941
0,941
0,941
0,941
3
0,37
0,137
1,232
1,090
1,213
5
0,35
0,123
3,063
2,569
2,924
7
0,1
0,010
0,490
0,100
0,448
9
0,028
0,001
0,064
0,063
0,055
11
0,11
0,012
1,464
1,455
1,184
13
0,071
0,005
0,852
0,807
0,640
15
0,026
0,001
0,152
0,135
0,106
17
0,057
0,003
0,939
0,925
0,600
19
0,047
0,002
0,797
0,774
0,468
Total
1,234
9,994
8,860
8,576

1.111
HLF
8,10
7,177
6,948
The ratio of the harmonic load current for each respective
method and the RMS current (p.u) yields the HLFs as indicated
previously.
6.2. Computation of Winding Eddy loss under harmonic current
loading
The evaluation of the total service losses as a result of the HLC
using the IEEE Std. C57.110-2018 is tabulated as shown in Table
3.
Table 3: Computation of total service losses: IEEE Std. C57.110-
2018.
Type of
loss
Rated
Losses
(W)
Load
Losses
(W)
HLF
Service Losses
(W)
No load
4 500
4 500
-
4 500
Copper
25 000
30 859
-
30 859
Winding
Eddy
938
1158
8,10
9 372
Other
Stray
1 253
1547
1,58
2 442
Total
31 691
38 064
47 173
Under the supplied HLS, the service losses are witnessed to
have a surge of about 33% and 19% from the rated and load losses
respectively. The computation of the HLF for other stray loss in
this work is similar to that of the winding Eddy loss as shown in
Eq. (27), however these losses generated by metallic components
such as tank walls, core clamp, windings, core, flitch plate et cetera
are proportional to the square of the harmonic load current and the
harmonic order to the exponent 0.8 as stated in [37]. The peak local
load loss ratio for the HLC is computed as follows:
 (57)

Given that the mean winding Eddy loss at the highest loss ratio
under rated conditions is 15% of the Copper losses, then the load
loss will be 1.15 p.u as shown below. The maximum permissible
harmonic load current with the supplied harmonic spectrum is as
follows:

 (58)


Consequently, with the supplied harmonic spectrum the
studied WTGSU transformer capability is about 261.048A.
Table 4: Computation of total service losses: Proposed method
Type of
loss
Rated
Losses
(W)
Load
Losses
(W)
HLF
Service
Losses (W)
No load
4 500
4 500
-
4 500
Copper
25 000
30 859
-
30 859
Winding
Eddy
938
1158
7,177
8 308
Other
Stray
1 253
1547
1,58
2 442
Total
31 691
38 064
46 110
Under the supplied HLS, the service losses are witnessed to
have a surge of about 31% and 17% from the rated and load losses
respectively. The peak local load loss ratio for the HLC is
computed as follows:


By applying proposed method, the maximum permissible
harmonic load current with the supplied harmonic spectrum is as
follows:


Consequently, with the supplied harmonic spectrum the
studied WTGSU transformer capability is about 259,85A. The
evaluation of the total service losses as a result of the HLC using
FEM [38] is tabulated as shown in Table 5.
Table 5: Computation of total service losses: FEM
Type of loss
Rated
Losses
(W)
Load
Losses
(W)
HLF
Service
Losses
(W)
No load
4 500
4 500
-
4 500
Copper
25 000
30 859
-
30 859
Winding
Eddy
938
1158
6,948
8 043
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 497
Other Stray
1 253
1547
1,58
2 442
Total
31 691
38 064
45 844
Under the supplied HLS, the service losses are witnessed to
have a surge of about 31% and 17% from the rated and load losses
respectively. The peak local load loss ratio for the HLC is
computed as follows:


Based upon the FEM procedure [38], the maximum
permissible harmonic load current with the supplied harmonic
spectrum is as follows:



Consequently, with the supplied harmonic spectrum the
studied WTGSU transformer capability is about 258,70A.
7. Conclusions
In the current work, an extension of the author’s previous work
[29], new analytical formulae for the Eddy loss computation in
transformer winding conductors have been explicitly derived, with
appropriate contemplation of the fundamental and harmonic load
current. These formulae allow the distribution of the skin effect
and computation of the winding Eddy losses as a result of
individual harmonics in the winding conductors. The rectangular
winding conductors considered are based on real transformer
geometries and represents the configuration of the conductors
carrying harmonic load current.
The new formulae were triumphantly corroborated by
comparing their performance with computationally intensive FEM
simulations, authenticating their adequacy and efficacy. On that
account, our findings are handy for the transformer manufacturing
industry, where the transformer anatomy and design necessitate
specific performance and inexpensive computational resources.
Additionally, it has been demonstrated that the harmonic load
currents minimizes the depth of skin effect, lead to an increase in
the copper losses and winding stray losses and, thereby,
consideration must be given for proper evaluation and design of fir
for purpose transformers capable of facilitating wind power. These
formulae can be applied in the transformer design systems for
calculating the effects of harmonics on the transformer active part
components. These results can be utilized to enhance the design of
transformer s and consequently minimize the generation of
hotspots in metallic structures. In this way, the developed
formulae are a critical furtherance to the existing methodologies
employed by manufactures.
The method herein provides a fundamental basis for
subsequent development such as analysis of thermal performance
of transformers in wind power technologies.
Future work involves the development of TOC model for
WTGSU transformers to evaluate their economic life by
considering the intermittent nature of wind turbine generators.
Conflict of Interest
The authors declare no conflict of interest.
References
[1] Department of Energy, Integrated Resource Plan (IRP2019)”, in 2019
Government Notice, 10-11, 2019, doi: IRP/2019/IRP-2019.pdf
[2] SAWEA,” South Africa’s Wind Industry. Stats and Facts SAWEA”, in 2020
Stats and Figures, 2020, doi: stats-and-facts-sawea.
[3] ESI Africa,”Tracking wind energy in South Africa”, in 2019 ESI Africa,
2019, doi: industry-sectors/renewable-energy/tracking-wind-energy-in-
south-africa.
[4] M.A. Kamarposhti, S.B. Mozafari, S. Soleymani, S.M. Hosseini, “Improving
the wind penetration level of the power systems connected to doubly fed
induction generator wind farms considering voltage, Journal of Renewable
and Sustainable Energy, 7(4), 2015, doi.org/10.1063/1.4927008.
[5] J.M. Carrasco, L. Garcia Franquelo, “Power-Electronic Systems for the Grid
Integration of Renewable Energy Sources: A Survey”, IEEE Transactions on
Industrial Electronics, 53(4), 1002 1016, 2006, doi:
10.1109/TIE.2006.878356.
[6] A.A. Adly, S.K. Abd-El-Hafizb, A performance-oriented power
transformer design methodology using multi-objective evolutionary
optimization”, Journal of Advanced Research, 6 (3), 2015, doi:
org/10.1016/j.jare.2014.08.003.
[7] M.B. Mallett, High-Voltage Power-Transformer Design”, in Transactions
of the American Institute of Electrical Engineers, 62 (8), 1943, doi:
10.1109/T-AIEE.1943.5058737.
[8] B. A. Thango, J. A. Jordaan and A. F. Nnachi, "Step-Up Transformers for
PV Plants: Load Loss Estimation under Harmonic Conditions," in 2020 19th
International Conference on Harmonics and Quality of Power (ICHQP),
Dubai, United Arab Emirates, 1-5, 2020, doi:
10.1109/ICHQP46026.2020.9177938.
[9] B. A. Thango, J. A. Jordaan and A. F. Nnachi, "Effects of Current Harmonics
on Maximum Loading Capability for Solar Power Plant Transformers," in
2020 International SAUPEC/RobMech/PRASA Conference, Cape Town,
South Africa, 1-5, 2020, doi:
10.1109/SAUPEC/RobMech/PRASA48453.2020.9041101.
[10] B.A. Thango, J.A. Jordaan, A.F. Nnachi, “Contemplation of Harmonic
Currents Loading on Large-Scale Photovoltaic Transformers," in 2020 6th
IEEE International Energy Conference (ENERGYCon), Gammarth, Tunis,
Tunisia, 479-483, 2020, doi: 10.1109/ENERGYCon48941.2020.9236514.
[11] J.N. Jagers, J. Khosa, P.J. De Klerk, C.T. Gaunt, “in 2007 Transformer
Reliability and Condition Assessment in South African Utilities”, in 2007
XVth International Symposium on High Voltage Engineering. University of
Ljubljana, Elektroinstitut Milan Vidmar, Ljubljana, Slovakia, 27-31, 2007,
doi:10.1.1.533.6250.
[12] V.M. Motalleb, M. Vakilian, A. Abbaspour, Tank shielding contribution on
reduction of Eddy current losses in power transformers”, in 2009 IEEE
Pulsed Power Conference. Washington, DC, 641-645, 2009, doi:
10.1109/PPC.2009.5386382.
[13] A.M. Milagre, M.V. Ferreira da Luz, G.M. Cangane, 3D calculation and
modeling of eddy current losses in a large power transformer”, in 2012 XXth
International Conference on Electrical Machines. Marseille, 2012, doi:
10.1109/ICElMach.2012.6350200.
[14] S. Saha, N. Fernando, L. Meegahapola, Multi magnetic material laminated
cores: Concept and modelling”, 2017 20th International Conference on
Electrical Machines and Systems (ICEMS), Sydney, NSW, 2017, doi:
10.1109/ICEMS.2017.8056247.
[15] O. Bottauscio, M. Chiampi, D. Chiarabaglio, “Advanced model of laminated
magnetic cores for two-dimensional field analysis”, IEEE Transactions on
Magnetics, 36, (3), 561-573, 2000, doi: 10.1109/20.846219.
[16] A.I. Korolev, On electromagnetic induction in electric conductors”, arXiv:
Cornell University, 2013, doi: 1303.0785.
[17] V. Sarac, G.Stefanov, Calculation of Electromagnetic Fields in Electrical
Machines using Finite Elements Method”, 2011 International Journal of
Engineering and Industries 2(1), 2011, doi: 10.4156/ijei.vol2.issue1.3.
[18] A. Srikanta Murthy, N. Azis, J.Jasni, M.L. Othman, M.F. Mohd Yousof,
M.A. Talib, Extraction of winding parameters for 33/11 kV, 30 MVA
B.A. Thango et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 6, No. 2, 488-498 (2021)
www.astesj.com 498
transformer based on finite element method for frequency response
modelling,” 2020 PLoS One, 15(8), e0236409,
doi.org/10.1371/journal.pone.0236409.
[19] J. Íñiguez, V. Raposo, M. Zazo, A. García-Flores, The electromagnetic
field in conductive slabs and cylinders submitted to a harmonic longitudinal
magnetic field”, American Journal of Physics, 77, 1074, 2009,
doi.org/10.1119/1.3160663.
[20] N. Amemiya, Y. Sogabe, S. Yamano, H. Sakamoto, Shielding current in a
copper-plated multifilament coated conductor wound into a single pancake
coil and exposed to a normal magnetic field”, Superconductor Science and
Technology, 32 (11), 2019, 10.1088/1361-6668/ab3f1c.
[21] B.A. Thango, J.A. Jordaan, A.F. Nnachi, Analysis OF Distributed solar
Photovoltaic System Harmonics on Transformers, Eliva Press, 2020.
[22] S.V. Kulkarni, S.A. Khaparde, Transformer Engineering: Design and
Practice, Taylor & Francis Group, 2004.
[23] A. Mor, S. Gavril, Eddy Current Effects on the Asynchronous Performance
of the Hysteresis Machine”, Journal of the Franklin Institute. 314(2), 1982,
doi.org/10.1016/0016-0032(82)90062-X.
[24] S.V Kulkarni, J.C Olivares, R. Escarela-Perez, V.K. Lakhiani, J. Turowski,
Evaluation of eddy losses in cover plates of distribution transformers”, IEE
Proceedings - Science, Measurement and Technology, 151(5), 313-318,
2004, doi: 10.1049/ip-smt:20040632 .
[25] A. Najafi, I. Iskender, Reducing losses in distribution transformer using
2605SA1 amorphous core based on time stepping finite element method”, in
2015 International Siberian Conference on Control and Communications
(SIBCON). Omsk, 2015, doi: 10.1109/SIBCON.2015.7146963.
[26] L. Betancourt, G. Martinez, D. Álvarez, J. Rosero, Losses characterization
on distribution transformer windings in frequency domain by means of finite
element method (FEM): Part I”, in 4th International Conference on Power
Engineering, Energy and Electrical Drives. Istanbul, 2013, doi:
10.1109/PowerEng.2013.6635589.
[27] G.U. Nnachi, A.O. Akumu, C.G. Richards, D.V. Nicolae, Estimation of
no-Load Losses in Distribution Transformer Design Finite Element Analysis
Techniques in Transformer Design”, in 2018 IEEE PES/IAS PowerAfrica,
Cape Town, 2018, doi: 10.1109/PowerAfrica.2018.8521142.
[28] L. Susnjic, Z. Haznadar, Z. Valkovic,Stray Losses Computation in Power
Transformer”, in 2006 12th Biennial IEEE Conference on Electromagnetic
Field Computation. Miami, FL, 2006, doi: 10.1109/CEFC-
06.2006.1633280.
[29] B. A. Thango, J. A. Jordaan and A. F. Nnachi, "A Weighting Factor for
Estimating the Winding Eddy Loss in Transformers for High Frequencies,"
in 2020 6th IEEE International Energy Conference (ENERGYCon),
Gammarth, Tunis, Tunisia, 2020, doi:
10.1109/ENERGYCon48941.2020.9236472.
[30] H. Kekana, G. Landwehr, Wind capacity factor calculator”, Journal of
energy South. Africa, 30 (2), Cape Town, 2019, doi:
https://dx.doi.org/10.17159/2413-3051/2019/v30i2a6451.
[31] B.A. Thango, J.A. Jordaan, A.F. Nnachi, Total Ownership Cost Evaluation
for Transformers within Solar Power Plants”, in 2020 6th IEEE International
Energy Conference (ENERGYCon).Gammarth, Tunis, Tunisia, 2020, doi:
10.1109/ENERGYCon48941.2020.9236613.
[32] C.A. Charalambous, A. Milidonis, A. Lazari, A.I. Nikolaidis, Loss
Evaluation and Total Ownership Cost of Power TransformersPart I: A
Comprehensive Method”, IEEE Transactions on Power Delivery, 28(3),
2013, doi: 10.1109/TPWRD.2013.2262506.
[33] J.F. Baranowski, P.J. Hopkinson, An alternative evaluation of distribution
transformers to achieve the lowest TOC”, IEEE Transaction Power Delivery,
7, 1992, doi: 10.1109/61.127057.
[34] A.L. Lazari, C.A. Charalambous, Probabilistic Total Ownership Cost of
Power Transformers Serving Large-Scale Wind Plants in Liberalized
Electricity Markets”, IEEE Transactions on Power Delivery, 30(4), August.
2015, 10.1109/TPWRD.2014.2365832.
[35] F. Lee and T. Wilson, "Voltage-spike analysis for a free-running parallel
inverter," in IEEE Transactions on Magnetics, 10 (3), 969-972, 1974, doi:
10.1109/TMAG.1974.1058474.
[36] D. Kusiak, The Magnetic Field and Impedances in Three-Phase
Rectangular Busbars with a Finite Length”, Energies 2019, 12(8), 1419,
doi.org/10.3390/en12081419.
[37] IEEE,” Recommended Practice for Establishing Liquid Immersed and Dry-
Type Power and Distribution Transformer Capability when Supplying
Nonsinusoidal Load Currents”, in IEEE Std C57.110-2018, 2018, doi:
10.1109/IEEESTD.2018.8511103.
[38] B.A. Thango, Jordaan, A.F. Nnachi, A Novel De-rating Procedure for
Distributed Photovoltaic Power (DPVP) Generation Transformers”, in 2021
International SAUPEC/RobMech/PRASA Conference, 2021, doi:
10.1109/TPWRD.2013.2262506.
... A method for evaluating the admissible operating conditions of a new and in-service transformer may be based on the computation of the transformer capacity by deriving a maximum current derating factor when supplying a harmonic load current. The winding loss that will be generated on account of supplying a harmonic load current at a region of high winding Eddy loss is calculated as follows in Equation (7) [8][9][10]. ...
... where nf Frequency of the sinusoidal magnetic field γ Specific conductor conductivity b, hWidth and height of the conductor B x ,B y Local induction axial and radial components δ bh b/h Ratio of width and height of the conductor F H Winding Eddy loss correction function. The corresponding correction function is based on the expression in Equation (10). ...
... In this work, a winding Eddy loss correction function that results in increased accuracy in the projection of the transformer capability under harmonic load currents is formulated. The corrected function in this work is published by the author in the article [10] as follows in Equation (12). ...
Article
Full-text available
In the new era of the renewable energy market in South Africa, there is a knowledge gap in the technical standards relating to distribution transformers, which are exclusively intended to serve in large-scale solar photovoltaic (PV) applications. The problem arises from the reality that these transformers are compelled to facilitate an environment with a potentially high risk of an unacceptable level of harmonics and distortion. What manufacturers currently need is a comprehensive transformer specification for DT transformers in PV applications, as the standards currently in use for regular transformers have so far proven to be inadequate. The latter triggers the need for this work to contribute to the advancement of this knowledge gap by mapping a comparative analysis of defining and specifying the design considerations for solar PV transformers. Initially, the computation of the various transformer losses at multifaceted active-part structures under normal conditions by employing the proposed finite element analysis (FEA) is presented. Then, two design case studies are described and the harmonic load current content to which the transformer will be susceptible during operation is specified and used for the analysis. Lastly, the design losses computed using the proposed FEA are substantiated using practical measurements.
... In core-type transformers, the HV and LV windings are cylinders with a common centre encircling vertical magnetic core limbs with circular cross-sections [60]. The vertical magnetic core limbs and the horizontal core yoke components are made of thin laminated sheets and provide a magnetic flux circuit. ...
... If load current flows within the winding copper conductors, a loss (I2R) will be generated. The individual currentcarrying conductors are encompassed by alternating electromagnetic fields with an intensity proportional to the load current [60]. The field composition generated by the load current is illustrated in Figure 6, which is a two-dimensional model of the transformer active part components as indicated [60]. ...
... The individual currentcarrying conductors are encompassed by alternating electromagnetic fields with an intensity proportional to the load current [60]. The field composition generated by the load current is illustrated in Figure 6, which is a two-dimensional model of the transformer active part components as indicated [60]. Individual winding conductors encompassed by alternating Energies 2022, 15, 2333 9 of 21 electromagnetic fields encounter an internally induced voltage that triggers the generation of the winding Eddy currents to flow in respective winding conductors [60]. ...
Article
Full-text available
The electricity production opus in South Africa has transformed over the last few years from predominantly coal power generation to a blend of renewable energy generation. The necessity emerges to ascertain whether electrical transformer design philosophies in local manufacturers are contemporary in reference to customer specifications, under increasing penetration of harmonics and distortion as a result of increasing deployment of decentralized power systems. Accurate computation of transformer stray load loss is imperative in localizing the hotspot regions and design of adequate insulation system and consequently cooling system. This loss must also be met by manufacturers based on the customer specifications to avoid penalties. The review of current scientific works affirms the ongoing interest in utilizing the advancement of computational power for painstaking evaluation and management of stray load loss in electric transformers. This article confers overview research, evolution and application of diverse computer-based tools for analyzing the stray load loss based on over 60 published scientific works. Mathematical formulations that can be practically employed by transformer designers during the design phase under normal and harmonic load current conditions are discussed.
... In this paper, an analytical formulation for evaluating the frequency response of the winding conductors when supplying non-sinusoidal load current in solar photovoltaic transformers is proposed based on the work the authors have published in [9] to improve the winding Eddy loss calculation method recommended in the C57.110-2018 standard. Additionally, a 2D Finite Element Method model is developed in efforts to compute the losses of the studied unit thereof. ...
Conference Paper
Full-text available
With the evolution of solar photovoltaics, the capacity of solar photovoltaic transformers is increasing. The winding conductor succumb to larger dimensions, to be able to withstand the extreme operational condition of solar photovoltaic application. The magnetic flux leakage responsible to produce Eddy currents in windings and other metallic components over and above that also increase. At the same time, the conventional method of estimating the winding Eddy losses result in significant errors when employed for large conductor dimensions at high harmonic orders.This paper conduct an investigation into the computation of the winding Eddy losses of a 300kVA solar photovoltaic transformer. The assumption made in the C57.110-2018 standard about the winding Eddy losses to be increasing in accordance with the non-sinusoidal load current with the exponent 2 is realized to be unsuitable for solar photovoltaic application. There is a shortfall in the C57.110-2018 standard method to take into consideration the tendency of a high- frequency alternating current flowing through only the outer surface of the winding conductor (skin effect) when the oil- immersed transformer is supplying non-sinusoidal current. The frequency response of the winding conductors under non- sinusoidal load current condition is examined by evaluating the dispersal of the magnetic flux leakage in the conductors, from which the skin effect and proximity effect are taken into account. In order to authenticate the soundness of the emendation method, a 2D Finite Element Method model of the transformer under study is developed for the computation of the winding Eddy losses. This method reflect on geometrical properties of the winding conductor and it is revealed some benefit for both the transformer manufacturer and the power utility.
Conference Paper
Full-text available
In this paper, a method for estimating the winding Eddy Loss based on an improved harmonic loss factor for transformers under harmonic conditions is presented. The method considers the skin depth of penetration of the field at higher harmonic orders, leading to a greater degree an accurate estimation of the winding Eddy losses under harmonic conditions.
Conference Paper
Full-text available
South Africa has established one of the most reputable renewable energy programmes in the world. The latter presents a new energy mix in the country, and as a consequence it is important to acknowledge the operational characteristics of each power utility. Subsequently, it is crucial then to evaluate the service lifetime cost of each kilowatt as far as the step-up transformers are concerned as it might be different. The Total Ownership Cost is a financial evaluation method meant to render transformer buyers the purchasing and after purchase costs of their transformer expenditure. The method applied in centralized electrical utilities does not quite satisfy the intermittent generation profile experienced by transformers within solar power plants. This paper presents an in-depth loss evaluation procedure to calculate the total ownership cost of transformers expected for service within utility-scale solar photovoltaic plants. These transformers could be owned by Independent Power Producers. More particularly, the proposed method recognizes the intermittent generation profile of the solar plant.
Conference Paper
Full-text available
A surge in harmonics and distortion in the South Africa’s electric power system has come to the fore in the early phases of integrating renewable energy resources to the national electric grid. Having said that, in this day and age a considerable number of harmonic producing apparatus are present. On the basis of their beneficial effects in efficacy and controllability, harmonic producing apparatus are presumed looking ahead to the realization of the 2030 Integrated Resource Plan (IRP 2030) to increase further. The IRP 2030 is aimed at increasing the total renewable energy generation capacity contribution to about 24.7% by year 2030. Further to this is a considerable increase in the amount of harmonics in the electric power network. The mushroomed harmonics and distortion may drive inflated winding stray loss and thereby peculiar temperature rise phenomena. Undue losses have classically been presumed to be varying in direct proportion with the harmonics order and load current. In this paper, the transformer losses that occur when facilitating solar PV farm environment are investigated based on seasonal basis. The study in particular draw attention to the injection of harmonics and distortion using the IEEE Std. C57.110-2018 recommended practice. In the worst-case scenarios for summer and winter the harmonic current measurements were taken to evaluate the guaranteed services losses. The hourly mean harmonic current profile for summer and winter solar irradiation of a solar PV farm are presented to investigate their effects on the operation of the transformer during service. The findings of the investigation is projected to be used as a foundation for the IPP’s and manufacturers for operating and designing transformers serving large-scale solar PV farms within acceptable maximum rating in taking into account the availability of solar irradiation on seasonal basis and robust parametric design at tender stage respectively.
Article
Full-text available
This paper proposes an alternative approach to extract transformer’s winding parameters of resistance (R), inductance (L), capacitance (C) and conductance (G) based on Finite Element Method (FEM). The capacitance and conductance were computed based on Fast Multiple Method (FMM) and Method of Moment (MoM) through quasi-electrostatics approach. The AC resistances and inductances were computed based on MoM through quasi-magnetostatics approach. Maxwell's equations were used to compute the DC resistances and inductances. Based on the FEM computed parameters, the frequency response of the winding was obtained through the Bode plot function. The simulated frequency response by FEM model was compared with the simulated frequency response based on the Multi-conductor Transmission Line (MTL) model and the measured frequency response of a 33/11 kV, 30 MVA transformer. The statistical indices such as Root Mean Square Error (RMSE) and Absolute Sum of Logarithmic Error (ASLE) were used to analyze the performance of the proposed FEM model. It is found that the simulated frequency response by FEM model is quite close to measured frequency response at low and mid frequency regions as compared to simulated frequency response by MTL model based on RMSE and ASLE analysis.
Conference Paper
Full-text available
�� ���� � ���� ������� ���������� ��� ���������� ���� ���� ������ ����� �������� ������ ��� �� �� ���� ��!� ������������������� � ����������"�� ��������������� � ��"�����"#� � �� "� ��� ��!��� ��� ��� ����� ���� � ���� ���"$� "����� ���!������ ���"�������%������� ��� #�&���!��� �����"����� '� ���"��������������� ����������(��������)���"��� ���������#� *���!�� � ��� "����� '� �������� ����� ��"�������� �����%� �"� ������� ��� ���� ��� ��"����� ��� ������ ����� ��� ����"� ���� ��"������ ������ �� ��� ���� ��� �� ��� ��� ��� � ���� �� ��� "������ ������������!����"������ ������������������������"#�� ��������� �""������ �� ����"�� � �"� ��� ��� ��"����� ������"��� �������""�"�������������"� ���������" ��� ��������������� ��""�"������ �"��!���#� �� ������ �� �� ��"���� ��� "� ���������� ��� ��"�� ������� �" � ��"� � ��� ��!���"����� �����"�!����� ��������� "�"���������� ����������"��� ����������"� ����� �� ������������������ ����� " ���� ��������������������"��� ��#�&����������""�"������!������� ����������� ������������ �������������"#�&����������""�"����� ���""���������� � �� ���� "�� ���""�"#� &��� � ����""�"� ���� ��� ��"�� � �������� � � ���� ����� ����������"� ���� ��"�� ���� �� �������� ��"��� ��#� +�� ���� ���� � ���� ����� ����������� ��� ��� "�� � ��""�"� ������ �!�� ��� � � �,��� �"� ����� ���� �������� � ����� � ��"������#������"� � �� ����-�.�/� ���������"�� �� ����� �� � ���"��� ��� �� ������� ���� �"� ��!��� ��� �� ������� �� �� ������""��"� ������ ��"�� �%������ �������� � ��������0� ���"� #� 1������� � ���� ����� ��� ������"� �� ���� ��� ������� � ����� ���0� ���"� � �� ����#� -���� � � ������ � ��"� �� ��������� �"� ���� ����������"���������� ����"����� �����������"�� �����#�
Conference Paper
Full-text available
Distribution transformers are commonly designed and manufactured to operate at fundamental frequency and to facilitate sinusoidal loads. The operation of loads that draw distorted currents culminate in higher losses, hotspot temperatures, degradation of insulation materials and declined service life. To avert these technical challenges, the continuous power rating of the transformer under current harmonics has to be reduced. This paper presents some analysis into the effect of current harmonics on the maximum loading capability of oil-filled transformers that are intended to operate within solar power plants. The harmonic spectrum derived by the presence of non-linear loads and seen by the transformer during service is presented. A recommended practice for derating the transformer described in the IEEE std. C57. 10-2018 is adopted in the study.
Article
Full-text available
A single pancake coil wound with a copper-plated multifilament coated conductor, with four filaments, was put in a cusp magnetic field, and the magnetic field was measured near the coil at 30 K. A similar experiment was performed by using another reference single pancake coil wound with a monofilament coated conductor. Numerical electromagnetic field analyses of these coils were carried out, and the calculated shielding current-induced fields (SCIFs) were compared with the measured ones in both coils. The temporal behaviour of the calculated SCIF in the coil wound with the four-filament coated conductor was also compared with a series of exponential components, in which a coupling time constant extrapolated from short sample experiments was used as the time constant of the primary component. Current distributions in the coated conductors wound into the pancake coils were visualised. In particular, the temporal behaviours of the current distributions in the four-filament coated conductor and their influence on the SCIF were discussed.
Article
Full-text available
The wind capacity factor calculator is developed to perform two main tasks: to estimate the annual energy production from the wind resource at any location in South Africa, and to compare the two datasets used in its operation with standard error analysis to determine whether both datasets are suitable for use. This paper focuses on how the software was developed and on error analysis between the CSIR PV/ wind aggregation study data and the latest Wind Atlas for South Africa data. The results will indicate the way forward after determining whether the error found between the two datasets is significant enough to replace the former with latter, going forward.
Article
Full-text available
The paper presents an analytical method for calculating impedances of rectangular bus ducts. The method is based on the partial inductance theory—in particular, the impedance of rectangular busbars in a three-phase system with a neutral conductor is described. The results of resistances and reactances of these systems of multiple rectangular conductors were obtained. Skin and proximity effects were taken into account. The measurements of the impedance of shielded and unshielded high-current busducts of rectangular conductors were also carried out. The magnetic field of the busbars was determined with several methods.