ArticlePDF Available

Performance of a Cyclone-type Oil Separator with Tangential Inlet and Oleophilic Surface

Authors:
Korean Journal of Air-Conditioning and Refrigeration Engineering
Vol. 31, No. 3(2019), pp.118-123
ISSN 1229-6422(Print), 2465-7611(Online)
http://dx.doi.org/10.6110/KJACR.2019.31.3.118
118 SAREK
친유 처리를 한 접선 방향 입구를 갖는 사이클론 방식
유분리기의 성능 특성
Performance of a Cyclone-type Oil Separator with Tangential Inlet and Oleophilic Surfac
e
(Joon Ahn)1, 장성일(Seongil Jang)2
1국민대학교 기계공학부 교수, 2국민대학교 대학원 기계공학과 박사과정
1Professor, School of Mechanical Engineering, Kookmin University, Seoul, 02707, Korea
2Ph.D. Candidate, Department of Mechanical Engineering, Graduate School, Kookmin University, Seoul, 02707,
K
orea
(Received January 16, 2019; revision received February 1, 2019; Accepted: February 7, 2019)
Abstract CFD analysis shows that if the inlet of a cyclone type oil separator is eccentric; the pressure drop can
b
e
reduced while increasing the separation efficiency. It has also been shown that the application of oleophilic surfaces
can lead to higher separation efficiency but lead to increased pressure drop. In the present study, an oil separato
r
with an eccentric inlet was fabricated and the CFD prediction results tested through performance evaluation in the
actual refrigeration cycle. When the inlet of the cyclone type oil separator is eccentric, the improvement in the separation
efficiency was not significant compared with the result predicted using numerical analysis, but the pressure drop was
greatly reduced. In conclusion, the pressure loss is greatly reduced when the inlet is eccentric. The separation efficiency
was enhanced by about 15% with a 30% reduction in pressure drop with the application of an olephilic surface treatmen
t
on the geometry.
Key words Oil separator(유분리기), Inlet geometry(입구형상), Oil wettability(오일 젖음성), Separation
efficiency(분리효율), Pressure drop(압력강하)
Corresponding author, E-mail: jahn@kookmin.ac.kr
기호설명
CU :입구가 몸체 상단 중앙에 위치하고 내부에
표면처리를 하지 않은 유분리기
EU :입구가 접선 방향으로 위치하고 내부에
표면처리를 하지 않은 유분리기
CT 입구가 몸체 상단 중앙에 위치하고 내부에
표면처리를 한 유분리기
ET 입구가 접선 방향으로 위치하고 내부에
표면처리를 한 유분리기
1. 서 론
증기압축사이클을 채택한 냉동 시스템의 경우 동부로서 압축기가 존재한다. 압축기에는 마찰에 의해
되는 것을 방지하고 기밀을 유지하기 위해 윤활유를 주입한다.(1) 최근에는 스크롤 또는 스크류 방식의 압축기를
중심으로 다량의 윤활유를 주입하여 과윤활유 조건에서 압축기를 운전함으로써 압축기 성능을 높이는 사례도
보고되고 있다.(2, 3)
윤활유는 압축기의 성능을 확보하는 데는 필수적이지만 냉동 시스템 전체를 보았을 때는 문제를 유발하기도
한다. 윤활유는 압축기 내부에서 냉매와 혼합되어 토출되어 시스템 내부를 순환하게 되는데 과정에서
응축기와 증발기의 열전달 계수를 낮추고 추가적인 압력 손실을 유발하여 시스템의 효율을 저하한다. 이와
같은 문제들은 오일 순환량이 증가할수록 심각해진다.(4, 5)
친유 처리를 한 접선 방향 입구를 갖는 사이클론 방식 유분리기의 성능 특성
SAREK 119
(a) Commercial product(Henry S-5182) (b) Prototype of the present study
Fig. 1 Cross-sectional geometry of oil separator.
냉매와 함께 시스템을 순환하는 윤활유는 운전 중에 배관에 부착되면서 시간이 지날수록 압축기 내부의
윤활유의 양이 감소하게 된다. 최근 대형 건물이나 물류 시설 등에서 배관이 길고 낙차가 큰 냉동시스템이
널리 보급되면서 오일 회수 문제가 보다 심각하게 나타나고 있다.(6) 이와 같은 문제를 해결하기 위해 압축기
에서 냉매로부터 윤활유를 분리하여 압축기로 되돌려 보내는 유분리기를 설치한다.
냉매 중에 포함된 윤활유를 분리하는 데는 일반적으로 관성 충돌 원리가 적용된다.(7) 돌을 키기
위해 유분리기는 다공체를 포함하거나 사이클론 형태로 제작된다. 이 중에서 사이클론은 입자가 원심력에
의해 벽면에 충돌하도록 설계하며(8) 과정에서 추가적인 압력손실을 동반하게 된다.
일반적인 사이클론은 원추형이지만 압축기의 유분리기의 경우 Fig. 1에 보인 것과 같이 원주형으로 제작
하며 내부에 나선형 구조체를 삽입하여 사이클론 유동을 유발시킨다.(9) 원추형 사이클론의 경우 원추의 경사각도
등이 중요한 설계인자이나 압축기용 유분리기의 경우 나선형 구조체와 출구 형상이 주요 설계인자가 된다.
본 연구에 앞선 선행연구로서 CFD를 이용하여 나선형 구조물의 나선 피치와 출구 위치에 따른 유분리기의
성능 변화를 연구한 바 있다.(10, 11) 수치해석 연구를 통해 높은 분리효율을 유지하면서 압력강하를 줄일 수
있는 형상을 찾았으나 실험과 비교하였을 때 분리효율은 높게 예측되고 압력강하는 낮게 예측되었다.(12)
분리효율이 CFD에서 낮게 예측되는 이유로 해석에서는 벽면에 충돌한 윤활유 입자가 두 포집되는 것으로
가정하였으나 실제로는 그렇지 않음을 들 수 있다. 벽면에 충돌한 입자의 일부가 튕겨져 나오는 비율은 오일
젖음성에 따라 달라진다. 선행연구(5, 12)에서 윤활유에 대해 접촉각이 작은 표면이 분리효율 측면에서 유리한
것으로 나타났다. 하지만 실제 냉동 사이클에 연계한 실험에서 접촉각이 작은 표면의 경우 압력강하도 함께
증가하는 단점이 발견되었다.(12, 13) 수치해석을 통해 입구 유동이 유분리기 내부 구조물과 충돌하면서 난류 운동
에너지가 생성되는 것을 확인하였고(10, 11) 이를 피하기 위한 설계로서 Fig. 1(b)에 보인 것과 같이 유분리기의 입구를
유분리기의 접선 방향으로 바꾸는 것이 제안되었다. 이에 대해 수치해석을 수행한 결과 유분리기의 입구를
중심부에서 접선 쪽으로 이동하면 분리효율은 높게 유지하면서 압력강하를 크게 줄일 수 있을 것으로 예측되었다.(14)
이에 본 연구에서는 Fig. 1(b)와 같이 입구가 유분리기 몸체 중심에 연결한 시제품과 접하도록 연결한 시제품을
제작하여 성능평가를 수행하였다. 각각의 제품에 대해 친유처리를 하지 않은 상태에서 성능을 평가하고 친유
처리를 한 상태에서 다시 성능을 평가하여 친유 처리의 효과와 기하 형상의 효과를 각각 검토하였다. 또한
같은 조건에서 같은 방식의 유분리기 기성품(Henry S-5182)도 성능을 측정하여 본 연구에서 제작한 시제품들과
성능을 비교하였다.
2. 친유 표면 처리 및 유분리기 시제품 제작 과정
유분리기의 재료는 널리 사용되는 스테인리스 SS-400 소재를 채택하였다. 친유 성질을 갖는 구리와 달리
스테인리스는 친유도 소유도 아닌 28도의 접촉각을 나타낸다(Fig. 2(c) 참조). 최근 스테인리스 표면에 친유
소유 특성을 부과하는 공정을 개발하였고(13) 본 연구에서는 이를 적용하였다. 친유성 표면은 Fig. 2(a)에 보인
안 준, 장성일
120 SAREK
(a) treatment procedure (b) change of surface micro structure
(c) change of contact angle on the surface for mineral oil (d) temperature dependence of contact angle for treated surface
Fig. 2 Oleophilic surface treatment for SS400.(13)
(a) internal structure of conven-
tional oil separator(S-5182);
(b) components of prototype oil separator; (c) assembled prototype oil
separator
Fig. 3 Photographs of tested oil separators.
것과 같이 세척한 SS-40060의 아연 아세테이트, 질산은, 암모니아 수용액에 42시간 동안 담가서 제작하였다.
처리를 마치면 금속 표면에 Fig. 2(b)에 보인 것과 같이 꽃형태의 구조가 만들어지고 친유 특성을 갖는다. 친유성은
Fig. 2(d)에 보인 것과 같이 압축기 토출구 온도에 해당하는 높은 온도에서도 유지된다.
본 연구에서는 5가지 유분리기에 대하여 실험을 수행하였다. 비교를 위해 같은 방식의 기성품인 Henry사의
S-5182 제품의 성능을 평가하고 4가지 시제품을 평가하였다. Fig. 1에 보인 것과 같이 기성품은 시제품과
몸체의 직경이 갖고 Fig. 3(a)와 같이 유사한 내부구조를 갖는다. 시제품은 선행 연구 결과(10, 11)를 바탕으로
높은 분리효율을 유지하면서 압력강하를 줄일 수 있도록 나선 구조물의 피치와 출구 포트의 위치를 변경하여
Fig. 1에 제시한 것과 같이 해당 부분의 치수에서 기성품과 약간의 차이가 있다.
친유 처리를 한 접선 방향 입구를 갖는 사이클론 방식 유분리기의 성능 특성
SAREK 121
(a) P-h diagram of refrigeration cycle (b) piping and instrumentation diagram
(c) inside and outside photographs of experimental setup
Fig. 4 Performance test system of oil separator in refrigeration cycle.
표면 처리의 경우 선행 연구(12)에서 나선구조물과 몸체 두 친유처리를 한 경우에 가장 분리효율이
나타나 본 연구에서도 Fig. 3(b)보인 것과 같이 나선구조물과 벽면에 친유처리를 하였다. 입구 형상의 경우
기성품과 같이 유분리기 몸체의 상단 중앙에 설치한 시제품과 접선 방향으로 설치한 시제품을 제작하였다.
성능을 평가한 5가지 경우는 기성품(S-5182), 중앙 입구에 표면 처리를 하지 않은 시제품(CU), 중앙 입구에
표면 처리를 한 시제품(CT), 편심 입구에 표면 처리를 하지 은 시제품(EU) 및 편심 입구에 표면 처리를 한
시제품(ET)이 된다.
3. 유분리기의 성능평가 장치 및 방법
냉동 사이클은 R22 냉매를 채택하여 구성하였고 실험을 수행한 사이클의 P-h 선도를 Fig. 4(a)에 제시하였다.
냉동 용량은 8.3 kW이고 냉매순환량은 0.08 kg/s이다. 윤활유는 1.33 kg을 충전하였다. 실험장치는 Fig. 4(a)
제시한 사이클을 기반으로 Fig. 4(b)같이 구성하였다. 유분리기의 성능은 분리효율과 압력강하로 평가한다.
압력강하는 Fig. 4(b), Fig. 4(c)에 보인 것과 같이 유분리기 입구와 출구에 차압계를 연결하여 측정하였다.
분리효율은 ASHRAE에서 제시한 표준 측정법으로 측정하였다. ASHRAE표준 측정법은 냉매-오일 혼합물을
포집하여 성분을 분석하여 분리효율을 구한다. 이를 위해서 Fig. 4(c)표시한 것과 같이 유분리기 출구에
포집 탱크를 연결하였다.
실험 장치를 가동하면 1시간 후에 상상태에 들어가고 1간격으로 10시간 동안 자료를 획득하였다.
자료를 획득하는 10시간 동안 외기온도는 최대 1도씨 정도의 변화가 있었고 작동압력도 1% 정도의 변화가
있었다. 이와 같은 운전 중의 상태 변화와 계측장치의 정확도를 바탕으로 불확실성을 추정하였다. 분리효율의
경우 80%의 분리효율에서 0.82%, 압력강하의 경우 70 kPa에서 5.5 kPa의 불확실도를 갖는 것으로 예측되었다.
안 준, 장성일
122 SAREK
Fig. 5 Separation efficiency of oil-separators. Fig. 6 Pressure drop across oil-separators.
4. 유분리기 성능평가 결과 및 토의
CFD 이용한 해석 결과에서는(14) 입구를 편심하였을 경우 분리효율은 5% 가량 상승하고 압력강하는
40%가량 감소하는 것으로 예측되었다. 실제로 제작하여 실험을 한 결과에서는 표면처리를 하지 않을 경우 Fig.
5제시한 것과 같이 입구가 중앙에 위치한 경우(CU)74.8%, 편심된 경우(EU)75.8%1% 정도의 차이만
나타났다. 시제품의 경우 표면처리를 하지 않을 경우 기성품(76.9%)보다 분리효율이 1~2% 정도 낮았지만 표면
처리를 할 경우 기성품보다 높은 분리효율을 보였다. 표면처리를경우 입구가 중앙에 위치한 경우(CT)
에서는 91.3%, 편심된 경우에는(ET)91.9%기성품보다 15% 가량 향상된 결과를 얻었다. 분리효율의 측면
에서는 입구 편심의 효과가 수치해석으로 예측한 것보다 다소 작게 나타났고 표면처리 효과가 상대적으로 큰
것으로 나타났다.
Fig. 6에는 본 연구에서 평가한 5가지 유분리기에서 발생하는 압력강하 분포를 비교하였다. 형상개선 효과는
압력강하 측면에서 보다 두드러졌다. 입구튜브가 중앙에 배치된 시제품 유분리기(CU)는 압력강하가 28% 감소
하였고, 입구 튜브가 측면에 배치된 시제품 유분리기(EU)는 압력강하가 49% 감소하였다. 표면에 친유성 처리를
할 경우 친유성 표면처리를 하지 않은 시제품 유분리기에 비해서 압력강하가 32~38% 증가한다.
기성품과 성능을 비교하면 입구튜브가 중앙에 배치된 시제품 유분리기의 표면에 친유성 표면 처리를 할
경우(CT) 기성품 유분리기에 비해서 압력강하는 0.85% 감소하고, 분리효율은 15% 증가하였다. 입구튜브가
측면에 배치된 시제품 유분리기의 표면에 친유 처리를 경우(ET)에는 기성품 유분리기에 비해서 압력강하는
33% 소하고, 분리효율은 15% 증가하였다. 형상 개선을 통해서 압력강하가 상당히 감소하였기 때문에 친유성
표면 처리 이후 증가한 압력강하에도 불구하고, 기성품 유분리기에 비해서 압력강하는 감소하고 분리효율은
증가하였다.
5. 결 론
본 연구에서는 입구를 편심한 사이클론 방식의 유분리기를 제작하고 내부의 나선형 구조물과 몸체 벽면에
친유처리를 하여 냉동기에 장착한 후 성능을 평가하였다. 이를 통해 얻은 주요 결론은 다음과 같다.
(1) 사이클론 방식의 유분리기의 입구를 편심할 경우 수치해석으로 예측한 결과에 비해 분리효율의 향상은
크지 않으나 압력강하는 크게 저감할 수 있는 것으로 나타났다.
(2) 사이클론 방식의 유분리기에 친유성 표면을 적용할 경우 분리효율은 크게 향상되나 입구가 중앙에 위치한
경우와 편심한 경우 모두 추가적인 압력 손실이 유발되었다.
(3) 입구를 편심할 경우 압력손실을 크게 완화하여 친유성 표면처리를 병행하였을 때 기성품과 비교하였을
때 분리효율 15% 향상 및 압력강하 30% 저감을 동시에 달성할 수 있었다.
친유 처리를 한 접선 방향 입구를 갖는 사이클론 방식 유분리기의 성능 특성
SAREK 123
References
1. Youbi-Idrissi, M. and Bonjour, J., 2008, The effect of oil in refrigeration : current research issues and critical
review of thermodynamic aspects, International Journal of Refrigeration, Vol. 31, No. 2, pp. 165-179.
2. Bell, I. H., Groll, E. A., Braun, J. E., and Horton, W. T., 2013, Experimental testing of an oil-flooded hermetic
scroll compressor, International Journal of Refrigeration, Vol. 36, No. 7, pp. 1866-1873.
3. Bell, I. H., Groll, E. A., and Braun, J. E., 2011, Performance of vapor compression systems with compressor
oil flooding and regeneration, International Journal of Refrigeration, Vol. 34, No. 1, pp. 225-233.
4. Lottin, O., Guillemet, P., and Lebreton, J.-M., 2003, Effects of synthetic oil in a compression refrigeration system
using R410a, Part I : modeling of the whole system, International Journal of Refrigeration, Vol. 26, No. 7, pp.
772-782.
5. Kim, H. S., Kang, G. H., Yoon, P. H., Sa, Y. C., Chung, B. Y., and Kim, M. S., 2014, A study on the flow
characteristics and oil mixture in compressor suction line, International Journal of Refrigeration, Vol. 48, pp. 48-59.
6. Jang, S., Ahn, J., and Lim, S. H., 2015, Performance of oil-separator adopting nature-inspired surface, International
Journal of Precision Engineering and Manufacturing, Vol. 16, No. 10, pp. 2205-2211.
7. Flagan, R. C. and Seinfeld, J. H., Fundamentals of Air Pollution Engineering, Prentice Hall, pp. 391-478.
8. Lapple, C. E., 1950, Gravity and centrifugal separation, American Industrial Hygiene Association Quarterly, Vol.
11, No. 1, pp. 40-48.
9. Kim, H. S., Kang, G. H., Yoon, P. H., Sa, Y. C., Chung, B. Y., and Kim, M. S., 2016, Flow characteristics
of refrigerant and oil mixture in an oil separator, International Journal of Refrigeration, Vol. 70, pp. 206-218.
10. Jang, S. and Ahn, J., 2014, Design of helix pitch of a cyclone type oil separator for a compressor, Journal
Computational Fluids Engineering, Vol. 19, No. 4, pp. 8-13.
11. Jang, S. and Ahn, J., 2015, Design of the outlet-port tube of a cyclone-type oil separator for a compressor, Korean
Journal of Air-Conditioning and Refrigeration Engineering, Vol. 27, No. 8, pp. 402-408.
12. Ahn, J. and Jang, S., 2018, Effects of oil wettability on the performance of a cyclone-type oil separator, International
Journal of Air-Conditioning and Refrigeration, Vol. 26, No. 1, pp. 18500010.
13. Sumit, B., Kim, Y., Ahn, J., and Lim, S. H., 2016, Fabrication of a superamphiphilic ss-400 oil separator surface
using a ag-doped zno nanorod coating, Science of Advanced Materials, Vol. 8, No. 8, pp. 1595-1602.
14. Seon, G. and Ahn, J., 2016, Design of inlet port of the cyclone-type oil separator using CFD, International Journal
of Air-Conditioning and Refrigeration, Vol. 24, No. 4, pp. 1-8.
... The off-center inlet location, as shown in Fig. 2(b), improved the separation efficiency by 4.7 % and reduced the pressure drop compared to the previous configuration. To validate these numerical results, follow-up experiments were conducted by Jang et al. [12]. The experimental results showed that the separation efficiency was the same as that achieved using the conventional central inlet configuration, but the pressure drop was reduced. ...
... Based on the abovementioned analysis, the separation efficiencies are presented in Fig. 10 for three numerical simulations and a reference experiment previously conducted by the authors (from left to right: RANS simulation up until the inlet of the outlet tube [11], RANS simulation up until the exit of the outlet tube, LES up until the exit of the outlet tube, and experimental results [12]). Here, separation efficiency, s E is defined as Eq. ...
... The pressure drop for the three numerical simulations and experiment is summarized in Fig. 15 (from left to right: RANS simulation up to the inlet of the outlet tube [11], RANS simulation up to the exit of the outlet tube, LES up to the exit of the outlet tube, and the experimental results [12]). When the flow within the outlet tube is included in the simulation, the pressure drop is larger and closer to the experimental result, compared to the case where the outlet tube flow is not included. ...
Article
The effects of flow structure on the separation efficiency and pressure drop in a cyclone-type oil separator were investigated via Reynolds-averaged Navier-Stokes (RANS) simulations and large eddy simulations (LES), and the results were compared with experiments. Compared with the RANS simulations, the LES results were more similar to the experimental data as they simulated the complex flow structure more realistically. Swirling flow with strong turbulent kinetic energy (TKE) at the top section hindered the flow of particles toward the separator wall. In addition, a decrease in tangential velocity along the wall at the bottom reduced the centrifugal force, resulting in a decreased separation efficiency as particles were able to flow directly toward the outlet. The LES also predicted the pressure drop slightly better than the RANS simulation did, due to increased pressure drop caused by collision of the flow with the helix and outlet tube, which led to the formation of vortical flow structures with strong TKE.
Article
Full-text available
A simple fabrication technique is described for preparing Ag-doped ZnO nanorods using a rapid hydrothermal technique to create a superamphiphilic surface on SS-400 substrates. The high roughness resulting from Ag-doped ZnO nanorod surfaces is responsible for generating the superamphiphilic property of the SS-400 substrate. The fabricated surface shows contact angles (CAs) of almost 0° for water and olive oil, resulting in complete spreading of water and oily liquids. The fabricated surface also exhibits excellent superamphiphilic properties after long-term storage, thermal, and mechanical testing. However, after modification with a lowsurface-energy material (stearic acid), the fabricated surface exhibits superhydrophobic properties with water CAs of 158° and sliding angles (SAs) of less than 5°. We also applied our fabrication method to a helical-type oil separator. The oil separator, when treated with Ag-doped ZnO nanorods with a superamphiphilic surface, improved its oil separation efficiency and pressure drop compared with those of a commercial oil separator. Thus, our surface fabrication technique can be implemented easily to large-area, three-dimensional surfaces. Due to their ease and rapidity of manufacture and long-term wetting stability, these surfaces are potentially suitable for large-scale industrial applications in a variety of fields.
Article
The effects of oil wettability on the performance of a cyclone-type oil separator was studied through in situ experimentation and in a real refrigeration system. Based on previous research, the geometry of the oil separator in the present study was designed with an oil recovery device installed at its bottom to mount it on the actual refrigerator. The performance of the oil separator without surface treatment was predicted by applying design correlations proposed in the open literature, which were then compared with the experimental data. Through surface treatment, oleophilic or oleophobic properties were given to the inner wall and helix of the oil separator, and its performance was measured in a real refrigeration system. Oil wettability had a great effect on the performance of the oil separator, and in order to obtain high separation efficiency, oleophilic properties were found to be advantageous not only in the inner wall but also in the helix.
Article
Numerical analysis was performed in order to design the shape of the oil separator for the cyclone-type used in the refrigeration system, which can raise the separation efficiency, and which can reduce the pressure drop. Based on the result of the existing research, the total length of the oil separator, the length of the outlet-port, and the pitch, the turn-number of the spiral structure inside the cylinder was determined. This research was performed to compare and to analyze the separation efficiency and pressure drop of the oil separator while the location of the inlet-port was changed. According to three locations in the entrance, the separation efficiency was predicted from 95.0% to 100%, and the pressure drop ranged from 2.33 to 19.8(Formula presented.)kPa. In conclusion, the shape, which was made eccentric to the edge, had the separation efficiency of 100% and the pressure drop of 2.33(Formula presented.)kPa, which could get the most excellent performance.
Article
A series of numerical simulations have been carried out to study the performances of cyclone-type oil separators, which are designed for refrigeration-system compressors. The corresponding working fluid is R22, which is a typical refrigerant, whereby a mineral-oil droplet is supplied (Ed-highlight-My interpretation). The outlet-tube length in relation to the total chamber volume is considered a design parameter. Depending on the tube length, the separation efficiency varies from 98.7% to 99.3%, while the predicted pressure drop is between 5.1 kPa and 6.4 kPa. Considering both the pressure drop and separation efficiency, the length of the outlet-port tube of the separator is 152 mm.
Article
The efficiency and pressure drop in the oil separator of a multi heat pump system were experimentally investigated. R410A and polyvinylether (PVE) oil were used as the refrigerant and lubricant of the system, respectively. The refrigerant mass flow rate and the liquid circulation ratio were varied between 30 and 150 g s⁻¹ and between 1.5% and 4.5%, respectively. Five different oil separators were considered, and the measured efficiencies and pressure drops were analyzed with respect to the height and diameter of the oil separators. The analytical results were used to develop empirical equations for predicting the efficiency and pressure drop of the oil separator. The mean absolute percentage errors between the predicted and measured efficiencies and pressure drops for the oil separators were 0.4% and 11.7%, respectively.
Article
In order to improve a refrigeration system’s energy efficiency, the separation efficiency of its oil separator should be improved. To do so, we turned to nature for inspiration. A Namib Desert beetle collects water in fog by using its skin, which combines hydrophilic and hydrophobic surfaces. Inspired by nature’s design, we applied a surface with oleophilic and oleophobic patterns to an oil separator used in a refrigeration system. In order to make the oil separator, an appropriate design was established using computational fluid dynamics. A cyclone-type oil separator was produced with an oleophobic-treated surface on its lower cup. The efficiency of the treated surface of this oil separator was tested with an open-type experimental setup using an oil mist generator. To obtain conditions similar to those of a refrigeration system in the open-type experimental setup, the oil particle diameter and working fluid pressure were set to yield a Stokes number similar to that of oil particles in the oil separator of the refrigeration system. The oil separator with the treated oleophilic–oleophobic surface improved its oil separation efficiency by 1.67% and its pressure drop by 2.48% compared to a conventional cyclone-type oil separator. © 2015, Korean Society for Precision Engineering and Springer-Verlag Berlin Heidelberg.
Article
A series of numerical simulation has been carried out to study performance of a cyclone type oil separator, which is designed for the compressor of a refrigeration system. Working fluid is R22, which is a typical refrigerant, and mineral oil droplet is supplied. Pitch of the helix is considered as design parameters to make a compact separator. Depending on the helix pitch, separation efficiency varies from 97.5 to 99%, while predicted pressure drop ranges from 5 to 6.5 kPa. Considering both of the pressure drop and separation efficiency, helix pitch of the separator has been designed as 50 mm.
Article
In this work, a residential air conditioning compressor designed for vapor injection has been modified in order to inject large quantities of oil into the working chamber in order to approach an isothermal compression process. The compressor was tested with oil injection mass flow fractions of up to 45%. At an evaporating temperature of −10 °C and condensing temperature of 30 °C, the overall isentropic efficiency was up to 70% at the highest oil injection rate. Overall, over the testing envelope investigated, there are no significantly negative effects experienced for the compressor and the compressor isentropic efficiency and refrigerant mass flow rate improve monotonically as the oil injection rate is increased.
Article
This paper discusses the experimental results of oil retention amount and pressure drop in the gas line of refrigerant. R410A and polyvinylether oil were used as refrigerant and lubricant, respectively. The experiment was conducted under various pipe inner diameters of 14.1, 17.3 and 26.0 mm, and refrigerant mass flux and oil circulation ratio (OCR) were varied from 40 to 250 kgm-2s-1 and 0.5 to 4.0%, respectively. The oil retention amount tends to increase as refrigerant mass flux decreases and OCR increases. The oil retention amount in vertical pipe was higher than that in horizontal pipe. The empirical expressions for predicting the oil retention amount and pressure drop were suggested. The mean absolute percentage errors of each expression for predicting the oil retention amount in horizontal and vertical pipes were 18.1% and 14.1%, respectively, and those for predicting the pressure drop in horizontal and vertical pipes were 22.2% and 20.1%, respectively.
Article
Vapor compression refrigeration technology has seen great improvement over the last several decades in terms of cycle efficiency through a concerted effort of manufacturers, regulators, and research engineers. As the standard vapor compression systems approach practical limits, cycle modifications should be investigated to increase system efficiency and capacity. One possible means of increasing cycle efficiency is to flood the compressor with a large quantity of oil to achieve a quasi-isothermal compression process, in addition to using a regenerator to increase refrigerant subcooling. In theory, compressor flooding and regeneration can provide a significant increase in system efficiency over the standard vapor compression system. The effectiveness of compressor flooding and regeneration increases as the temperature lift of the system increases. Therefore, this technology is particularly well suited towards lower evaporating temperatures and high ambient temperatures as seen in supermarket refrigeration applications. While predicted increases in cycle efficiency are over 40% for supermarket refrigeration applications, this technology is still very beneficial for typical air-conditioning applications, for which improvements in cycle efficiency greater than 5% are predicted. It has to be noted though that the beneficial effects of compressor flooding can only be realized if a regenerator is used to exchange heat between the refrigerant vapor exiting the evaporator and the liquid exiting the condenser.