Improving Data Center Efficiency Through Holistic Scheduling In Kubernetes
Paul Townend1, Stephen Clement1, Dan Burdett1, Renyu Yang1, Joe Shaw1, Brad Slater1, Jie Xu12
1Edgetic Ltd., 1 City Square, Leeds, LS1 2ES, UK
2School of Computing, University of Leeds, LS2 9JT
{ paul.townend, stephen.clement, dan.burdett, renyu.yang, joe.shaw, brad.slater, jie.xu } @ edgetic.com
Abstract— Data centers are the infrastructure that underpins
modern distributed service-oriented systems. They are
complex systems-of-systems, with many interacting elements,
that consume vast amounts of power. Demand for such
facilities is growing rapidly, leading to significant global
environmental impact. The data center industry has conducted
much research into efficiency improvements, but this has
mostly been at the physical infrastructure level. Research into
software-based solutions for improving efficiency is greatly
needed. However, most current research does not take a
holistic view of the data center that considers virtual and
physical infrastructures as well as business process. This is
crucial if a solution is to be applied in a realistic setting. This
paper describes the complex, system-of-systems nature of data
centers, and discusses the service models used in the industry.
We describe a holistic scheduling system that replaces the
default scheduler in the Kubernetes container system, taking
into account both software and hardware models. We discuss
the initial results of deploying this scheme in a real data center,
where power consumption reductions of 10-20% were
observed. We show that by introducing hardware modelling
into a software-based solution, an intelligent scheduler can
make significant improvements in data center efficiency. We
conclude by looking at some of the future work that needs to be
performed in this area.
Keywords- kubernetes, docker, containers, energy, power,
efficiency, data center, scheduling, behavior, modeling, analytics,
holistic, PUE, interference
I. INTRODUCTION
In recent years there has been a huge increase in the use
and proliferation of distributed service-oriented applications.
This has been driven by many factors, including increasing
numbers of users, IoT devices, streaming audio and video
services, cloud storage, and the rising popularity of
microservices. Furthermore, growth is predicted to accelerate
as driverless vehicles [12], connected devices, and smart
infrastructure become increasingly common [13][14].
These applications are typically hosted in data centers –
large facilities containing compute, storage, and network
resources. Data centers are digital factories that process
electrical power into digital services and generate enormous
quantities of waste heat that requires additional power to
remove. They are complex systems of systems, with many
interacting elements.
The data center industry currently consumes 2-3% of
global electrical power, with global data traffic more than
doubling every four years [15]. At the same time, the
utilization of any one data center is typically estimated to be
between 10-20% [1][2]. As the size and number of data
centers increases, their environmental impact (such as power
consumption and carbon emissions) and the impact of their
relative inefficiency becomes increasingly important.
Traditionally, the data center industry has addressed
inefficiencies primarily through hardware innovation – more
efficient CPUs, better cooling solutions, improved power
distribution systems, etc. However, there is huge scope to
offer better efficiencies through software-only solutions –
examples include more powerful monitoring and analysis of
data center systems [16], predictive capacity planning [17],
CFD-based floor layout tools [18], and intelligent scheduling
mechanisms [19]. One common factor that is necessary when
developing real-world solutions in this space is the need for
multi-disciplinary, holistic thinking – it is not enough to view
such a system in isolation; instead solutions need to consider
the interactions between the physical systems, software
systems, business processes, and user behaviors.
In this paper, we look in detail at the complex nature of
the data center infrastructure behind service-oriented systems
and discuss a number of the challenges faced by academia
and the industry. We discuss the need for improved metric
collection and monitoring, the need for better mathematical
models of hardware behavior, and the potential for better
scheduling mechanisms within data centers. We conclude by
describing in detail two case studies where improved
scheduling mechanisms were developed using advanced
hardware modelling to significantly reduce power
consumption in a realistic setting.
II. DATA CENTERS
Although data centers are the fundamental infrastructure
on which service-oriented computing is based, to date there
has been relatively little work [3][4][5][6] in the literature
that considers them in a truly holistic manner – with
hardware systems influenced by software and vice versa.
Such an approach is crucial if theoretical research is to be
translated into practical, real-world technology.
A. Data centers as systems-of-systems
A data center is a complex, interacting system of
systems, each of which is typically the concern of a different
156
2019 IEEE International Conference on Service-Oriented System Engineering (SOSE)
978-1-7281-1442-2/19/$31.00 ©2019 IEEE
DOI 10.1109/SOSE.2019.00030
discipline (computer science, mechanical engineering,
electrical engineering, etc.) Figure 1 identifies these
interactions at a high-level; from this view, the components
of a data center can be categorized into:
1) Physical infrastructure. The fundamental hardware
components that process data in a data center are servers.
Servers consist of a variety of components, the most
important of which are: CPU, Disk, Memory, and Network
interfaces. They consume electrical power and generate
heat. Servers are typically stored in racks, which are
enclosures consisting of multiple servers (typically with a
network switch). Racks are sometimes organised into pods,
and arranged into aisles to improve the efficiency of cooling
systems. Cooling systems typically (in the case of “air
cooling”) take heated air and through a variety of
mechanisms, cool this down before recirculating it. Some
systems use liquid cooling to a variety of degrees. Cooling
systems themselves consume a significant amount of
electrical power [7].
2) Power infrastructure. The physical infrasturcture of a
data center consumes significant amounts of power. In
addition to the power requirements of servers, physical
infrastructure needs include conversion from AC to DC
supply, backup generation systems, distribution systems,
and ancilliary functions such as lighting. Electrical power
may cost different amounts at different times of day,
offering opportunities for intelligent scheduling of non-
urgent software jobs; this will increasingly be a factor when
Smart Grid technology becomes more widespread.
3) Virtual infrastructure. This category is comprised of
all software systems running on the physical infrastructure
of the data center. This includes supervisory systems (often
known as DCIM – Data Center Infrastructure Management)
that monitor the physical infrastructure to ensure that
services are available, that service-level agreements (SLAs)
are maintained, and that no anomalous events have
occurred. Virtualisation software is typically also present;
this serves to create, manage, migrate and remove the co-
located containers and virtual machines that contain user
jobs, and also to ensure that security constraints (particularly
integrity and confidentiality) are maintained.
4) Business processes. Any solution proposed to alter
the working environment of a data center needs to be
compatible with the business processes and requirements of
that system. These include the (often variable) service-level
agreements offered to users, the decision making process
(holistic solutions can often struggle as budgets for facililty
and operations may be siloed, creating difficulty in
determining at which level the solution sits), and the public
perception of the data center.
These complex, interacting systems consume extremely
large amounts of electrical power. Although data centers
currently consume approximately 2-3% of the global
pass jobs
Waste heat
Net wor king systems
Power storage and
distributi on systems
Data centre operational boundary
Virtual infrastructure
End users External power provider(s)
info rm ene rgy flow
data flo w
data flow
generat es
energy flow
Coolin g
systems
passed to
digital services
On-site power
generation systems
energy flow (if appropriate)
Space heating
(if appropriate)
heat
recycling
energy flow
External environment
waste heat and carbon emissions
energy flow
(if appropriate)
Anci lliary f unct ions
(lighting, etc) energy
flow
Business
proc e sse s
energy flow (if appropria te)
SLAs
Ri sk ana lysis
Pub lic
perception
Best prac tic e
Lif ecycle
Up take
barriers
water
Rack
distri bution
Floor
distri bution
Decision
making
Power in frastru cture
Ph ysi cal in frast ructu re
SLA moni toring
Sche du ling and
virt ua lisa ti on
Security
Softwar e manageme nt
Policy
CPU and
Memory
Storage
Ra ck units
Figure 1. A Data Center as a complex system of systems
157
electrical supply, there is much speculation that this figure
will rise significantly in the coming decade. We now look at
some of the trends in data center energy consumption, as
well as the metrics used to gauge efficiency in the industry.
B. Energy usage of data centers and PUE
Figure 2, based on [15] shows an “expected case”
projection of energy usage for networks, consumer devices,
ICT production, and data centers. This predicts that data
center energy use will consume approximately 8% of global
electrical power by 2030 (approximately 8000 TWh.) It is
notable that in the same work, the “worst case” estimate
predicts that data centers will consume 20% of the global
electrical supply by 2030.
Currently, the data center industry measure energy
efficiency primarily through the use of a single metric – PUE
(Power Usage Effectiveness.) PUE was first proposed by [8]
and is the ratio of total facility energy used by a data center
to the energy delivered to computing equipment (e.g.
servers). Any resource in a data center that consumes energy
but is not a computational device is considered to contribute
to facility energy. PUE is therefore expressed as:
The largest consumer of facility energy is typically the
cooling systems within a data center; as racks of servers
produce waste heat, mechanisms are needed to cool this
down – often at considerable energy cost. A recent survey of
over 1200 data centers [9] showed that respondents, on
average, had a PUE of 1.89 – in other words, for every 1 watt
of energy used to power IT equipment, another 0.89 watts
was spent on facility energy (cooling, power distribution,
etc.) Separately, a recent technical report by the European
Commission [10] showed an average surveyed data center
PUE in the EU of 1.64. The industry generally perceives that
the lower a data center’s PUE score is, the more efficient that
data center is. This has been reflected by a sustained series of
innovations in the industry that has sought to continually
reduce PUE; figure 3 (also [10]) shows the downward trend
in average PUE values for surveyed data centers between
2009-2016.
It is notable that PUE is usually heavily affected by the
external environment of a data center; the warmer the
location of a data center, the higher the PUE (primarily due
to the need for more powerful cooling.) As efficiency
improvements at a facility level slow due to diminishing
returns as PUE gets closer to its minimum value of 1.00 (at
which point all facility power would be devoted to IT
equipment), research into IT equipment energy reduction
becomes increasingly important.
However, there are significant problems with the PUE
metric: for example, a single metric such as PUE cannot
differentiate between different carbon footprints (e.g. use of
renewable or non-renewable energy), water consumptions,
etc. Most notably, data center innovations which seek to
improve efficiency through reductions in IT energy
consumption may actually cause a PUE score to become
worse (higher) – if total facility energy remains at a similar
level, but through better resource management IT equipment
energy consumption can be reduced, PUE will increase. This
poses a significant barrier to the adoption of software-
based operational efficiency solutions in the current
climate. This is a consideration that must be addressed by
Figure 2. Expected global electrical power usage (%) 2010-2030
Figure 3. Long-term downward trend in average data
center PUE [10]
158
future research – possibly through the introduction of
improved efficiency metrics, etc.
Given the increasing importance of reductions in IT
equipment energy consumption within a data center, we
discuss in section 4 a case study into how software solutions
- utilizing a holistic approach to all aspects of a data center -
can offer potentially large reductions in power consumption.
III. DATA CENTER TYPES
Data centers come in many different types and
categories, which can be differentiated by size, ownership,
and service model. The category of a data center
significantly affects the type of software-based efficiency
solutions that can be placed on them.
A major distinction is between private (only accessible to
those within a single organisation and sometimes selected
partners) and public (accessible by many parties, who may
not be known to the data center owner.) Additionally, data
centers may be purposed in different ways. For example:
x Co-locational data centers require customers to
supply their own IT hardware. This hardware is
placed in the facility and provided with physical
security, cooling, and power, but the data center
provider has no control over the servers themselves
(either the software running on them or their power
status, BIOS status, etc.)
x Telecoms data centers are facilities used by
telecommunications providers; these typically
feature very high connectivity requirements, running
specialised software services.
x Dedicated-hosting data centers provide server
capacity to single customers, with no sharing of
machines (this is sometimes known as “bare metal”,
or MaaS.) Again, these data centers typically do not
have any control over the software running on the
servers themselves (although this can vary,
depending on the facility).
x Managed hosting data centers provide servers and
storage systems for customers, typically with a
platform-as-a-service (PaaS) or software-as-a-
service (SaaS) model. Services offered may include
database storage, web hosting, systems monitoring,
etc. Servers may be owned by the customer or the
data center, and the extent of control provided to
each party can vary significantly.
x Shared hosting data centers (of which cloud data
centers are an example) typically provide virtualised
and multi-tenant resources for multiple customers to
use. Such data centers typically provide user
interfaces that allow customers to automatically
deploy virtualised resources; the underlying physical
location of these resources is determined by the data
center’s scheduling software.
x Edge. Edge data centers are typically smaller than
traditional data centers and are located closer to
where data is generated – thus reducing delay and
cost in network transmission. Edge is considered a
significant growth area, driven by Internet-of-
Things, wireless sensor networks, streaming video
uptake, etc.
x Hybrid. A data center facility containing more than
one of the above service models.
There is an increasing trend in the data center industry for
the software running on physical servers to be virtualised and
co-hosted (and thus, a trend towards shared hosting data
centers). This offers a significant opportunity for
software-based efficiency solutions, as the resource
management within such systems is centralised, providing
realistic opportunities for metric collection and analysis, and
improved scheduling mechanisms.
A. Virtualised resources
From a user perspective, it is preferable to develop
applications and services that are agnostic to the underlying
system or geographic location. Additionally, users demand
configurable deployments of services, incorporating all
required resources, that are able to scale to demand.
Virtualisation solves this for computing by packing
applications alongside required libraries, for networking by
allowing reconfigurable software defined networks (SDN)
and for storage by allowing users to expand storage with
their requirements.
From the perspective of a data center, virtualisation
increases the value of individual servers by allowing multiple
users to be seamlessly collocated on a single physical
machine (PM). Virtualisation allows sharing of the PM while
ensuring isolation between users without any complicated
configuration requirements from the users – thus greatly
increasing capacity (i.e. the ability to take on far more users
than there are physical machines). Indeed, deployment and
migration between machines can become an automated
process, greatly reducing management overhead.
Furthermore, a failure of a virtualised resource is contained
and will (or at least should) not affect the running or
operation of any other virtual resource located on the same
physical host.
The two primary types of virtualised computing resource
used in modern data centers are virtual machines and
containers (operating system-level virtualisation). Virtual
machines are packages that include an operating system, set
of applications, and associated data. They function on top of
a hypervisor, which is located upon a base operating system
and both emulates a PM and provides isolation for each VM.
Containers are a similar concept but remove the need for
a hypervisor: a container image includes a set of applications
and library dependencies, occasionally alongside user data
but does not contain an operating system. Multiple
containers are hosted on a single operating system with the
operating system itself providing isolation between each
container. A container can be deployed on any machine that
159
runs the operating system it targets. The exclusion of an OS
provides a significant reduction in image size and thus means
that containers can be created, deployed, and destroyed in a
much faster manner. Furthermore, since the host OS
manages containers the density (the number of containers
capable of running simultaneously) can be far greater than
with virtual machines where the hypervisor often requires a
1-to-1 mapping from physical to virtual resources. Figure 4
shows a high-level architectural comparison of containers
and virtual machines.
Within the cloud community, there has been a significant
movement to container-based technology. Figure 5 shows a
normalised comparison of google searches between the term
“virtual machine” and “docker” (the most popular container
type, chosen for this comparison to reduce semantic
uncertainty in the search result) between 2014-2019.
Although this is only an indication of interest, the trend is
marked and significant. Interest in containers has been
fuelled by rising use of microservice-based architectures,
which are becoming increasingly common, especially in
connected sensor-based systems such as those found in
internet-of-things solutions [11].
IV. A HOLISTIC SOLUTION FOR IMPROVING EFFICIENCY
As has been discussed, there is not only a great need but
also great potential for software-based solutions for
improving efficiency within data centers. It is important to
consider that different types of data center require different
approaches, which need to take a holistic view of the data
center (including at least its physical and virtual
infrastructures) if they are to be applicative in real-world
scenarios. As an example of the effectiveness of a focused,
holistic software innovation, we now present a solution we
have developed that targets shared hosting data centers.
Specifically, we assume:
x The target data center will be a shared hosting
facility that uses virtualized resources
x The virtualized resources will be packaged within
Docker containers
x We can gain access to detailed metrics with regard
the data center environment (specifically: air
temperature) and servers.
x Kubernetes is used as the underlying container
orchestration system.
Kubernetes (https://kubernetes.io/) is an open-source
container orchestration system, originally developed by
Google and now maintained by the Cloud Native Computing
Foundation. Although the Docker system
(https://www.docker.com/) is becoming the de-facto standard
for hosting software containers, there are a number of
competing systems that automatically scale, manage, update
and remove containers across distributed resources.
Kubernetes is the market-leader and the standardized means
of orchestrating containers and deploying distributed
applications; uptake is growing rapidly across many
organisations, and increasing numbers of data centers are
using it to build distributed container infrastructures.
A. Intelligent scheduling in Kubernetes
By default, the Kubernetes system attempts to load-
balance all the nodes (physical servers) in the cluster that it
manages by spreading containers evenly across it. This
makes logical sense when considering the system from the
perspective of its virtual infrastructure only, as it reduces the
likelihood of individual nodes becoming unduly resource
Figure 5. Google searches: virtual machines and
containers (Docker) between 2014-2019
Physical server
Host operating system
Hypervisor
App
Guest O S
App
Guest OS
App
Guest OS
Physical server
Host operating system
Container engine (Docker, etc.)
App App App
Container 1 Container 2 Container 3
VM 1 VM 2 VM 3
Figure 4. Comparison of Containers and Virtual
Machines
160
constrained while others are relatively lightly loaded. In
reality, the underlying physical hardware in a cluster will
react to load (in other words – resource utilization -
particularly of the CPU, but also disk, memory, and network
transfer) in a wide variety of ways. Different levels of
hardware load will cause differing amounts of waste heat to
be generated, and different amounts power to be consumed,
depending on the type of server, the BIOS settings of that
server, and even the ambient temperature of the server
location.
We propose that with a significantly better understanding
of the hardware response of each server within a data center,
and a predictive capability to assess the impact of each
incoming container within a system, an intelligent
scheduling mechanism can be created whereby containers
are allocated to nodes in a more optimal fashion – tuned to
either reducing power consumption, increasing performance
(instructions-per-cycle), or to a balance in-between.
To achieve this, we need to establish detailed server
models, predictive container behaviour models, and detailed
knowledge of the environment of the data center. Each of
these is a complex task and requires a different solution.
Figure 6 shows the broad strategy to our scheme; hardware
behaviour to a range of different loadings is modelled at a
test facility. This is used to forecast the impact (in terms of
performance and power consumption) of container
placement within the target cluster, the outcome of which is
used to optimally place a container within the cluster.
Simultaneously, live metrics are collected from the system
and fed into container prediction models – using historical
and online learning to more accurately predict the behaviour
of each incoming software container (i.e. what resources it
will use at what time period, etc.)
B. Hardware modelling
One of the benefits of modelling server hardware
behaviour is that it allows us to treat a data center (or a
cluster of machines) as an optimisation problem whereby the
goal, be it to decrease power consumption or increase
performance, can be mathematically or analytically solved.
This is true whether a data center is made up of multiple
different kinds of servers or a homogenous set of servers.
To achieve this, it is necessary to experimentally
determine the link between multiple attributes - including
thermal environmental, power consumption, and internally
logged server metrics – before condensing these down into a
form of multivariate polynomial equation that can be acted
upon in machine learning.
To achieve this, we placed a server (specifically a Dell
R430) into an instrumented wind tunnel (see figure 7). We
controlled and monitored the thermal environment of the
server while running computational benchmarks within the
server to test components such as CPU, memory, disk, and
network. These tests satisfy a design of experiments of
varying complexities, depending on time availability and
accuracy requirements.
One of the biggest challenges we faced is being able to
properly explore the design space that is required to model
the behaviour of a server without dedicating an unreasonable
amount of time to testing. This is in part because such a
complicated system requires multiple variables to describe it,
and each additional variable has an exponential impact on
the size of the design space; additionally, the relationship
between the variables and the model is almost always of an
order higher than one, and each increase in order is a further
increase in the size of the design space. The issue is further
compounded by the amount of time required for each
individual test to achieve a steady state for one or more of
the variables. For this reason, a full factorial exploration of
such a space is unfeasible, and so specific Designs of
Experiments are employed that sample the space at required
points to capture the order of behaviour previously
determined experimentally, plus interactions and a margin to
allow for the unexpected.
The process of creating these models is being continually
updated. Contemporary models include metrics that were
only added when previous models were found to be missing
a variable that could describe their full behaviour at the time.
The counterpoint to this is that models existing currently
may also include variables that are in practice not
statistically significant in modelling behaviour for a certain
server, or even all servers in general. The evolution of this
understanding is an ongoing process.
TESTING
FACILITY
HARDWARE
MODEL(S)
CONTAINER
PREDICTION
FORECAST
IMPACT
COLLECT LIVE
METRICS
ADVISE /
SCHEDULE
DECISION
SUPPORT
OPTIMISE
SYSTEM
ANOMALY
DETECTION
KUBERNETES
Figure 6. High-level architecture of the Edgetic solution
161
C. Software metric collection
In addition to hardware metric collection, it is also
necessary to collect a large number of metrics from the
containers running across a distributed cluster; through
analysis of these metrics, predictions can be made about the
behaviour of newly submitted container jobs, which
combined with an appropriate hardware model, can inform a
more intelligent scheduling solution. However, this is not a
simple task – not only does the collection of metrics impose
a significant overhead itself on each node within a cluster,
but the amount of data generated for analysis can be
extremely large. There are many research challenges to be
addressed when deciding what metrics are of most
significance to predictive algorithms, and at what granularity
these should be collected (as often as required to give an
acceptable level of accuracy, but not so often as to impose
too much overhead in terms of either storage or analysis).
At first, creating a metric collection system seems to be a
simple task: many system metric collectors exist and are
“pluggable” in the sense that they could attach various extra
components and publish data into various storage systems.
However, this is not as simple as it first appears. An
important requirement to any metric collection system is to
have a very low resource footprint (ideally no more than 5%
of a CPU core), and little memory impact. Being able to
store metrics in an appropriate database for analysis is also
important.
There are a host of metric collection systems for
Kubernetes. A number of vendor specific solutions exist,
such as Datadog, and open source solutions, such as Elastic
Stack with Metricbeat (https://elastic.co/products
/beats/metricbeat). When considering a generic Kubernetes
setup consisting, typically, of Docker engines running
containers and using Linux cgroups for resource accounting
and constraints, the host level metric collectors are not as
informed as required. Ideally, a system needs to monitor the
host resources as well as those for individual Kubernetes
specific cgroups to provide both details of machine
utilisation and potential container contention.
Initially we looked at the native “out-the-box” solution,
Heapster. Now discontinued, Heapster pulls node specific
metrics from the Kubelets (Kubernetes node agent) at regular
intervals and can push these into a limited number of
databases. We used Heapster, Kafka and Kafka stream
processors initially to perform distributed power model
calculations for the scheduling component. However, it was
clear that the Heapster model would not scale, causing metric
lag. The time to detect newly started pods (collections of
containers) was poor, leading to poorer scheduling decisions.
Making the predictions and collecting metrics needed to
happen as close to the source as possible, before providing
scheduling scores. Rather than cannibalise an existing system
to do this, or set up a further complex processing pipeline,
we made a decision to create our own metric collector.
The Edgetic metric collector is written in the Go
programming language, with a very simple set of
abstractions allowing additions of collector types and
publisher types to be added/removed when required. The
metric agent runs on every node, monitoring node stats,
cgroups, performance events, etc. We can run models
generated from benchmarking directly within the agent.
Once the metric collector is in place, the next step is to
create a storage infrastructure. This is easy to achieve when
benchmarking a few servers with a timeseries database
publisher or similar; however, when storing metrics for a
large cluster, we need to leverage a queuing system system
(such as Kafka) to deal with back pressure and network
latency, before shipping the metrics into long term storage.
We use open source technology (such as Fluentd) to store
high resolution metrics, featuring hundreds of data points per
cycle depending on how many pods are running, at relatively
high frequency. Metric data compresses well, due to its
structured nature, and can be stored in time order for later
retrieval. As an example, a week of compressed metric logs
during one set of our experiments was approximately 800GB
compressed, and roughly 8TB when decompressed.
Heat
exchanger Fan
Server
under test
Monitoring
database Controller
Sensors
Server
metrics
Test
configuration
Wind tunnel
Figure 7. Wind tunnel used to generate server hardware behaviour models
162
Exposing this data for processing is a different matter. In-
cluster databases such as Elasticsearch or Prometheus can be
used for short term visibility and alerting, but the indexes
will quickly become very large, requiring frequent clean-up.
Long term analysis of data is a significant challenge; it is
possible that Spark or similar Map-reduce systems on top of
distributed storage may be most effective.
V. RESULTS
To test the effectiveness of our holistic approach, we
implemented the system described above and tested it in two
stages. Both stages of experimentation were performed in a
real data center: RISE SICS North in Lulea, Sweden.
A. Holistic scheduler experiment I
We applied our initial solution to a cluster of 56 Dell
R430 servers running Kubernetes, where server behaviour
was modelled using the wind tunnel and metric collection
methods above. As an example of how server settings
change the nature of behaviour within a data center, we
modelled and tested the servers using two distinct BIOS
settings: “performance mode” whereby the CPU and fans run
at full speed irrespective of server utilisation (in other words,
maximum performance and power consumption at all times),
and “power saving mode” whereby the CPU is scaled up
using DVFS (dynamic voltage frequency scaling) dependant
on load – this setting offers much reduced power, but at the
price of slow CPU performance and response at low
utilisation.
Workloads of known resource requirements were
submitted to the cluster and allocated based on the optimal
placement suggested by the hardware models; performance
and power consumption were measured and then compared
against the same workloads running on the default
Kubernetes scheduler. As workloads were deterministic, the
performance metrics for our scheduler were measured as the
percentage increase/decrease in workload completion time
over the default Kubernetes scheduler. Experimental runs
were made across both BIOS modes.
Results from the experiment demonstrate potentially
huge gains in overall energy efficiency (measured as
improvement in performance plus reduction in power
consumption – i.e. instructions-per-watt), although this is
dependent on overall data center / cluster utilisation. Results
shown for different levels of CPU utilisation across both
BIOS types are show in Figure 8.
One significant finding is that by using an intelligent
scheduler that utilised an accurate hardware model, we could
schedule containers onto physical machines in a way that
maintained performance even when in the “power saving”
BIOS mode. This allows us to make an idealised comparison
between the relative performance and efficiency of a data
center using the Edgetic scheduler in power-saving mode vs
the Kubernetes default scheduler in performance mode
(shown as the “Overall” result in Figure 8).
It should be noted that these results are idealised - there is
a strong assumption that the workload coming into the data
center is deterministic and known in advance; in reality, this
will almost never be the case, and so the results from the
holistic scheduler I experiments serve primarily as an
indication of what may be achieved with sufficiently
accurate workload prediction.
Following the success of these experiments, we began to
look at not only increasing node scale (to measure the
feasibility of our metric collection routines) but also
loosening the deterministic workload assumption.
Figure 8. Energy efficiency improvement: a) Edgetic vs. Kubernetes default scheduler in power-saving mode;
b) Edgetic vs. Kubernetes default scheduler in performance mode;
c) Edgetic scheduler in power-saving mode vs, Kubernetes default scheduler in performance mode
163
B. Holistic scheduler experiment II
For our second set of experiments, we targeted a
Kubernetes cluster running on 215 machines at RISE SICS
North. All the servers in this cluster were made up of OCP
(Open Compute Project) hardware – low-cost machines that
are often used in large (hyperscale) data centers. We
modelled the OCP server in our wind tunnel system, using an
improved model creation system based on feedback and
analysis from our first set of experiments. Furthermore, we
extended our scheduler to make basic predictions on
workload based on historical submission. This allowed us to
create a range of experimental workloads that could be
submitted in a deterministic fashion but did not need to be
known in advance by our scheduler.
Based on the findings of our new hardware model, the
Edgetic scheduler loaded fewer OCP servers to a higher level
(to the optimum level described in the model), keeping the
remaining servers in the cluster at idle until required. Over
the course of the experiment, an increasing number of
synthetic workloads were submitted to the data center in
batches that approximately corresponded to 10% total
utilisation, from 10% to 70% approximate total utilisation.
The batches were additive, so the 10% batch ran for the
whole experimental duration, while the 70% batch only ran
for the last period of the workload. The experimental
workloads were submitted to the default and Edgetic
schedulers in sequence, with a small delay to allow the
datacenter to return to an approximate steady-state.
The results of these experiments were extremely
encouraging; although performance remained at a similar
level on both the Edgetic scheduler and the default
Kubernetes scheduler, the Edgetic scheduler lowered the
power consumption of the cluster by 10-20% (shown in
Figure 9.) This was achieved purely through optimizing
container placement based on the hardware model.
Figure 10 shows the distribution of jobs across the server
racks for each batch. Here you can see the differing effects of
the Edgetic and Kubernetes schedulers. Notably, as the
Edgetic scheduler takes into account server inlet temperature
in its calculations we can see that certain locations in the
datacenter are preferred. These correspond to the cooling
outlet which is located closest to servers at index (10,10) in
the diagram.
A surprising result was discovered in the power
utilisation for each workload; the Edgetic workload
consistently uses less power even when the datacenter
becomes highly utilized, and the performance advantage of
the Kubernetes scheduler starts to disappear.
VI. CONCLUSIONS
Data centers are the fundamental infrastructure on which
modern distributed systems are constructed, and lend
themselves heavily to cloud and micro-service based
systems. However, as the size of data centers increases, their
power consumption is becoming an increasingly important
part of the global electrical supply, with significant financial
and environmental ramifications. Research into software-
based solutions for improving efficiency in these systems is
greatly needed; however, most existing work considers only
virtual infrastructure. To be applicable in the industry – and
to maximise effectiveness – it is essential that solutions take
a holistic view, considering virtual and physical
infrastructure as well as business processes.
We describe the complex, system-of-systems nature of
data centers, and provide a category of data center service
models; the selection of an appropriate service model is
crucial for any research into providing infrastructure
management software in the data center space. To illustrate
the effectiveness of a holistic approach, we describe a new
scheduler we have developed for Kubernetes-based clusters
and data centers, that considers both physical and virtual
infrastructures. We discuss the server modelling we
performed as part of this work, as well as the metric
collection tools we developed to model workload behaviour.
The developed scheduler was then tested in two experiments
performed at the RISE SICS data center in Sweden, on 50
and 215 physical servers respectively.
Our initial results demonstrate power consumption
reductions of between 10-20% depending on data center
utilisation. This shows that by using hardware modelling
alone, an intelligent scheduler can make significant
improvements in data center efficiency, even before further
optimisations are introduced.
A. Future work
There is much future research to be done in this space. A
particularly important strand of research is that of QoS and
performance interference modelling and prediction.
Multi-tenant servers in cloud data centers may run
heterogeneous workloads such as latency-critical services
(typically encapsulated in Kubernetes containers or virtual
machines) alongside other batch-like jobs with lower-
priorities. Some jobs in a cluster are allocated resources (i.e.,
provisioned) to handle maximum loads and unexpected load
spikes. As a result, a cluster might remain under-utilized. To
enable a fully utilized cluster system, thereby maximizing
Figure 9. Holistic scheduler experiment II power
consumption comparison between the Edgetic
scheduler and the Kubernetes default
164
the pay back of capital investment, temporarily unused
resources from over-provisioned workloads can be used for
running best-effort jobs.
There is a trend whereby increasing numbers of cloud-
based stateful applications may overwhelm conventional
batch jobs, particularly boosting the requirement for strict
QoS guarantees and performance interference throttling.
This type of interference can occur on almost any type of
shared resource, including CPU, storage, network, etc. A
typical way of minimizing the interference is to allocate
dedicated cores for applications and avoid oversubscribing
the cores. However, different cores may share the same
processors, which still leads to a great amount of resource
contention. In particular, the last-level cache (LLC) can
have a severe impact on the end-user experience, again
highlighting the need for better hardware understanding.
To quantify interference, we can deploy fine-grained
system counters to monitor and collect the application
performance information. Platform-level Performance
Monitoring Units (PMU) and performance-metric based
early detection can help achieve this goal. For instance, by
using kernel-level counters, interference indicators such as
average cycles per instruction (CPI), a certain percentile
response latency (e.g., 99 percentile tail latency), Last Level
Cache (LLC) misses, and especially misses per kilo
instructions (MPKI), can greatly help to detect the
emergence of performance interference.
Normally it is the case that such metrics have fairly
consistent values across running instances and time periods.
It is therefore possible to detect outliers from regular
behaviour; once the monitored value of one of these counters
surpasses the performance threshold of Service Level
Objectives (SLO) from a user’s perspective, an alert can be
used to quickly locate anomalies. Given the precise
prediction of interference level, a resource manager can
perform the runtime QoS-aware scheduling underpinned by
non-invasive performance isolation through fine-grained
resource control. An external QoS controller can
continuously monitor the resource allocation, resource usage
and other environmental variables This has a significant
applicability into the resource management of data centers:
x Resource estimation. A node agent can leverage a
QoS prediction model to calculate how many resources
should be reserved in order to meet a specific SLO
target. For instance, if a user can tolerate 5%
performance degradation, then the QoS target can be
slightly reduced to 95%. According to the QoS model,
we can roughly estimate a safe resource allocation
given the environmental condition.
x Resource oversubscription. If we want to target the
QoS goal, how many resources should be assigned --
calculate how many resources should be strictly
allocated to the pod (regular resource binding as default
scheduler did) and how many resources can be spared
and borrowed by other low-prioritized jobs/best-effort
jobs/other pods (flexible over-subscription).
x Interference-aware resource sharing. Furthermore,
through detecting the interference producers, we can
ideally throttle them rapidly and facilitate the
Figure 10. Comparison of cluster server utilization per job batch, using the
default Kubernetes scheduler and the Edgetic scheduler
165
performance recovery of performance victims. Given
this, the system can allow best-effort jobs even if they
slightly break the SLO violation of other co-resident
workloads.
x Energy-efficient scheduling with performance
considered. We can integrate the performance
interference consideration with the energy efficient
scheduling. Although, the QoS-sensitive policy may
conflict with the policy towards energy efficiency, we
can still leverage the performance indicators to shortlist
QoS-safe sub-candidates based on the primary energy
efficiency selection.
To better aid holistic approaches in future, there are also
significant challenges to be solved to improve the
performance overhead of metric collection in data center
servers. Current approaches, especially with perf event
metrics are slow and resource heavy. Due to this, it may be
necessary to look into lower level abstractions such as Linux
extended BPF (eBPF) tracing tools so that metrics can be
captured in the kernel.
Furthermore, when considering modelling of physical
infrastructure, there are concerns about how feasible it is to
rely on accurate external sensors being part of the model.
Currently a key attribute in each model is the temperature of
air going into the server, but this relies on the data center the
model is being employed upon to be well instrumented with
temperature sensors. Most servers include temperature
sensors of varying number and quality and a move to
utilising those instead of requiring external sensors would be
beneficial. However, issues with this will undoubtably arise
from a lack of uniformity regarding internal sensors.
ACKNOWLEDGMENTS
We would like to thank RISE SICS North for their
support and the provision of time and servers in their ICE
data center. We would also like to thank the University of
Leeds for additional computational and storage resources.
REFERENCES
[1] C. Reiss, A. Tumanov, G. R. Ganger, R. H. Katz, and M. A. Kozuch,
“Heterogeneity and dynamicity of clouds at scale: Google trace analysis,”
in ACM SoCC, 2012
[2] C. Delimitrou and C. Kozyrakis, “Quasar: resource-efficient and
qosaware cluster management,” in ACM ASPLOS, 2014
[3] T. Mastelic, I. Brandic. "Recent trends in energy-efficient cloud
computing.", IEEE Cloud Computing 2.1 (2015): 40-47.
[4] Y. Joshi, P. Kumar, eds. “Energy efficient thermal management of data
centers”, in Springer Science & Business Media, 2012
[5] A. Beloglazov, R. Buyya, “Energy efficient resource management in
virtualized cloud data centers”, in Proc. 10th IEEE/ACM Int. Conf. on
cluster, cloud and grid computing (pp. 826-831), May 2010
[6] I. S. Moreno, R. Yang, J. Xu, T. Wo, "Improved energy-efficien cy in
cloud datacenters with interference-aware virtual machine placement. " In
Proc. 11th IEEE Int. Symp. on Autonomous decentralized systems, 2013
[7] N. Rasmussen, "Electrical efficiency modeling of data centers.",
Schneider Electric White Paper 113 Revision 2, 2011
[8] C. Belady, “The green grid data center efficiency metrics: PUE and
DCIE:, Technical report, The Green Grid, Feb. 2007
[9] Super Micro Computer, “Data Centers and The Environment”,
https://www.supermicro.com/wekeepitgreen/Data_Centers_and_the_Envir
onment_Dec2018_Final.pdf, December 2018
[10] L. Castellazzi, M. Avgerinou, P. Bertoldi, “Trends in data center
energy consumption under the European Code of Conduct for data center
energy efficiency”, European Commission JRE Technical Report, DOI:
10.2760/358256, December 2017
[11] H. Zhu, I. Bayley, “If Docker Is The Answer, What Is The Question?”,
Proc. 12th Int. Conf. on Service-Oriented System Engineering, Bamberg,
March 2018
[12] P. Bansal, K. Kockelman, “Forecasting Americans’ long-term
adoption of connected and autonomous vehicle technologies”,
Transportation Research Part A: Policy and Practice, Vol. 95, 2017
[13] B. Silva, M. Khan, K. Han, “Towards sustainable smart cities: A
review of trends, architectures, componen ts, and open challenges in smart
cities”, Sustainable Cities and Society, Vol. 38, 2018
[14] M. H. Cintuglu, O. A. Mohammed, K. Akkaya, A. S. Uluagac, "A
Survey on Smart Grid Cyber-Physical System Testbeds," in IEEE
Communications Surveys & Tutorials, vol. 19, no. 1, 2017
[15] A. Anders, T. Edler, "On global electricity usage of communication
technology: trends to 2030.", Challenges 6, no. 1 (2015): 117-157
[16] J. Gustafsson et al, “A demonstration of monitoring and measuring
data centers for energy efficiency using opensource tools” in Proc. 9th Int.
Conf. on Future Energy Systems, Karlsruhe, German y, Jun 2018
[17] F. Kong, X. Liu, “Greenplanning: Optimal energy source selection and
capacity planning for green datacenters.", in Proc. 7th IEEE Int. Conf. on
Cyber-Physical Systems, 2016
[18] J. Sjölund, M. Vesterlund, N. Delbosc, A. Khan, J. Summers,
"Valida ted Thermal Air Management Simulations of Data Centers Using
Remote Graphics Processing Units." In Proc. 44th Annual Conf. of the
IEEE Industrial Electronics Society, 2018.
[19] Q. Shaheen et al., "Towards Energy Saving in Computational Clouds:
Taxonomy, Review, and Open Challenges," in IEEE Access, vol. 6, 2018.
166