RAPL in Action: Experiences in Using RAPL for Power Measurements

Authors:
  • Unisanté

Abstract

To improve energy efficiency and comply with the power budgets, it is important to be able to measure the power consumption of cloud computing servers. Intel’s Running Average Power Limit (RAPL) interface is a powerful tool for this purpose. RAPL provides power limiting features and accurate energy readings for CPUs and DRAM which are easily accessible through different interfaces on large distributed computing systems. Since its introduction, RAPL has been used extensively in power measurement and modeling. However, the advantages and disadvantages of RAPL have not been well investigated yet. To fill this gap, we conduct a series of experiments to disclose the underlying strengths and weaknesses of the RAPL interface by using both customized microbenchmarks and three well-known application level benchmarks:Stream, Stress-ng and ParFullCMS. Moreover, to make the analysis as realistic as possible, we leverage two production-level power measurement datasets from the Taito, a supercomputing cluster of the Finnish Center of Scientific Computing (CSC) and also replicate our experiments on Amazon EC2. Our results illustrate different aspects of RAPL and document the findings through comprehensive analysis. Our observations reveal that RAPL readings are highly correlated with plug power, promisingly accurate enough and have negligible performance overhead. Experimental results suggest RAPL can be a very useful tool to measure and monitor the energy consumption of servers without deploying any complex power meters. We also show that there are still some open issues such as driver support, non-atomicity of register updates and unpredictable timings that might weaken the usability of RAPL in certain scenarios. For such scenarios, we pinpoint solutions and workarounds.
9
RAPL in Action: Experiences in Using RAPL for Power
Measurements
KASHIF NIZAM KHAN and MIKAEL HIRKI,Helsinki Institute of Physics and
Aalto University, Finland
TAPIO NIEMI,Helsinki Institute of Physics and University of Lausanne, Switzerland
JUKKA K. NURMINEN,Helsinki Institute of Physics, Aalto University and VTT Technical Research
Centre of Finland
ZHONGHONG OU,Beijing University of Posts and Telecommunications, China
To improve energy eciency and comply with the power budgets, it is important to be able to measure the
power consumption of cloud computing servers. Intel’s Running Average Power Limit (RAPL) interface is a
powerful tool for this purpose. RAPL provides power limiting features and accurate energy readings for CPUs
and DRAM, which are easily accessible through dierent interfaces on large distributed computing systems.
Since its introduction, RAPL has been used extensively in power measurement and modeling. However, the
advantages and disadvantages of RAPL have not been well investigated yet. To ll this gap, we conduct a series
of experiments to disclose the underlying strengths and weaknesses of the RAPL interface by using both
customized microbenchmarks and three well-known application level benchmarks: Stream,Stress-ng,and
ParFullCMS. Moreover, to make the analysis as realistic as possible, we leverage two production-level power
measurement datasets from the Taito, a supercomputing cluster of the Finnish Center of Scientic Computing
and also replicate our experiments on Amazon EC2. Our results illustrate dierent aspects of RAPL and
document the ndings through comprehensive analysis. Our observations reveal that RAPL readings are
highly correlated with plug power, promisingly accurate enough, and have negligible performance overhead.
Experimental results suggest RAPL can be a very useful tool to measure and monitor the energy consumption
of servers without deploying any complex power meters. We also show that there are still some open issues,
such as driver support, non-atomicity of register updates, and unpredictable timings that might weaken the
usability of RAPL in certain scenarios. For such scenarios, we pinpoint solutions and workarounds.
CCS Concepts: • Hardware Energy metering;Enterprise level and data centers power issues;
Emerging architectures;•Computer systems organization Cloud computing;
Additional Key Words and Phrases: RAPL, power modeling, RAPL accuracy, RAPL validation, DRAM power
ACM Reference format:
Kashif Nizam Khan, Mikael Hirki, Tapio Niemi, Jukka K. Nurminen, and Zhonghong Ou. 2018. RAPL in
Action: Experiences in Using RAPL for Power Measurements. ACMTrans.Model.Perform.Eval.Comput.
Syst. 3, 2, Article 9 (March 2018), 26 pages.
https://doi.org/10.1145/3177754
Author Kashif Nizam Khan would like to thank Nokia Foundation for a grant which helped to carry out this work. Author
Zhonghong Ou would like to thank the Fundamental Research Funds for the Central Universities and National Natural
Science Foundation of China (Grant No. 61702046) for the support. The authors would also like to thank CSC, IT Center
for Science, Finland for the datasets.
Authors’ addresses: K. N. Khan (corresponding author), M. Hirki, T. Niemi, J. K. Nurminen, and Z. Ou (corresponding
author); emails: {kashifnizam.khan, mikael.hirki}@gmail.com, tapio.niemi@unil.ch, jukka.k.nurminen@vtt., zhonghong.
ou@bupt.edu.cn.
Permission to make digital or hard copies of all or part of this work for personal or classroom use is granted without fee
provided that copies are not made or distributed for prot or commercial advantage and that copies bear this notice and
the full citation on the rst page. Copyrights for components of this work owned by others than ACM must be honored.
Abstracting with credit is permitted. To copy otherwise, or republish, to post on servers or to redistribute to lists, requires
prior specic permission and/or a fee. Request permissions from permissions@acm.org.
© 2018 ACM 2376-3639/2018/03-ART9 $15.00
https://doi.org/10.1145/3177754
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:2 K. N. Khan et al.
1 INTRODUCTION
Energy eciency in data centers has become one of the major concerns in the past decade, not
only because of the monetary cost but also for environmental sustainability. The electricity con-
sumption of data centers is constantly increasing and there is an urge to apply optimizations in
hardware and software to achieve the best performance per watt.
As such, a number of studies have been directed toward predicting and/or modeling energy
consumption in large-scale data centers [24,31,43]. Many such models or prediction techniques
require an accurate measure of the energy consumption of the data center on the go. Until recently,
measuring the power consumption of a computer system required separate metering hardware [3].
Besides the diculties of purchasing, deploying, and using external power meters, their measur-
ing accuracy and granularity are usually inadequate for detailed analysis. Moreover, dividing the
power to dierent parts of the computing system inside the chip is not possible. There are also
tools like the Intelligent Platform Management Interface (IPMI), which reports the power mea-
surement readings through sensors mounted with the system. Existing studies [21] nd that the
accuracy of such sensors is not promising and therefore these sensors cannot be practically used
as a substitute for more accurate watt meters on a per-machine basis.
The other option is model-based power estimation, which uses a set of performance counters
and a computational model to turn the performance readings into estimates of electricity consump-
tion. The accuracy of this approach strongly depends on the quality of the model and typically is
not able to give good results, especially with highly uctuating workloads [30]. McCullough et al.
[30] performed a comprehensive evaluation of the power modeling of computing systems and
concluded that power modeling techniques pose several limitations caused by the increased com-
plexity and variability of software and hardware. Their results motivate more toward low cost,
direct, and instantaneous energy measurement tools.
Intel’s Running Average Power Limit (RAPL) [40] is one such hardware feature that allows us
to monitor energy consumption across dierent domains of the CPU chip, attached DRAM, and
on-chip GPU with promising accuracy. This feature was introduced in Intel’s Sandy Bridge archi-
tecture and has evolved in the later versions of Intel’s processing architecture. With RAPL, it is
possible to programmatically get real-time data on the power consumption of the CPU package
and its components, as well as of the DRAM memory that the CPU is managing. RAPL is thus
a good tool to measure, monitor, and react to the power consumption of computing. It has po-
tential for new and innovative ideas to better deal with the electricity consumption of computing
[24,38,43]. Skrenes et al. [36] use RAPL as an “always on” energy-metering tool in their pro-
posed speed-scaling simulator, Prolo.Prolo measures the energy consumption of the CPU with
a goal to quantify the dierences between dierent speed-scaling strategies and uses RAPL as an
eective measurement tool in their automated simulation process. Kelley et al. [22] use RAPL as
a power-tracing tool to prole peak power under core scaling, which reduces the proling time
signicantly. Their approach shows that RAPL measurements are reliable enough to be used as a
power-measurement tool as they use RAPL to collect the power trace for a sampling period and
then this trace is used to predict peak power under dierent settings and across dierent architec-
tures.
Despite the merits and potentials of RAPL, it is not clear whether RAPL also has weaknesses
in measuring and monitoring the energy consumption of various CPU components. Thus, an in-
depth study of the RAPL interface itself is still needed to reveal its underlying principles. In this
article, we conduct a thorough study of RAPL by utilizing a series of customized benchmarks, and
two well-known application-level benchmarks, that is Stream and ParFullCMS. To make the anal-
ysis as realistic as possible, we leverage a production-level power measurement dataset from the
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:3
Taito supercluster of the Finnish Center of Scientic Computing (CSC) and also use ve dierent
instance types from Amazon EC2 as testbeds.
This article substantially enhances the work presented in References [17,23,24]. In addition to
the prior works, in this article, we analyze RAPL’s capability to predict the full-system power con-
sumption with dierent modeling techniques using the large CSC dataset. The in-depth analysis
of RAPL as an energy measurement tool in terms of dierent aspects like performance overhead
or high sampling rate is also a signicant addition. Last, the RAPL measurement experiences with
Amazon EC2 is a considerable enhancement. In summary, we make the following major contribu-
tions in this work:
(1) With detailed measurements, we investigate the accuracy, granularity, and performance
of the RAPL measurements. Accuracy of RAPL measurements is measured by determin-
ing how closely the RAPL measurements predict the overall power consumption of the
system. The “closeness” or “predictability” of RAPL’s measurement is obtained through
modeling and tting the RAPL measurements with full-system power consumption ob-
tained from high-accuracy external power meters.
(2) We also highlight a few aspects that need to be considered for the proper use of RAPL, as
well as issues that would require further development.
(3) We pinpoint a few major dierences in the performance, granularity, and accuracy of
RAPL in dierent Intel architectures: Sandy Bridge, Haswell, and Skylake.
(4) We present a study of RAPL’s performance in virtualized cloud computing environment
using Amazon EC2.
Key ndings from our study are listed below:
(1) The promising accuracy of RAPL measurements to predict full-system power consump-
tion is established by modeling the full-system power consumption from RAPL readings
using a large production dataset from CSC.
(2) The performance overhead of RAPL measurements is considerably low and negligible.
(3) There is a measurable correlation between RAPL’s package power and temperature, at
least in the Haswell architecture.
(4) In the case of Skylake, RAPL updates the PP0 domain in the order of μs(50–70μs).
(5) RAPL’s support in Amazon EC2 can be useful but it needs more careful considerations.
The rest of the article is organized as follows: Section 2presents detailed information about
RAPL in general. Section 3highlights the related literature. Section 4discusses the experimental
setup and benchmark specications. In Section 5, we discuss the good aspects of RAPL such as
its accuracy, granularity, and so on. Section 6discusses the weak aspects of RAPL. We also dis-
cuss possible solutions to overcome a few of the weak aspects of RAPL in Section 6. In Section 7,
we present RAPL measurement results and experiences with Amazon EC2 instances. Section 8
summarizes our ndings, and Section 9presents the conclusion with possible future directions.
2 RUNNING AVERAGE POWER LIMIT
The RAPL interface is a feature introduced in the Intel Sandy Bridge architecture. Generally speak-
ing, RAPL provides two dierent functionalities. First, it allows energy consumption to be mea-
sured at very ne granularity and a high sampling rate. Second, it allows limiting (or capping) the
average power consumption of dierent components inside the processor, which also limits the
thermal output of the processor [40]. We will focus on the energy-measuring functionality in this
article.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:4 K. N. Khan et al.
Fig. 1. Power domains supported by RAPL.
RAPL supports multiple power domains. The RAPL power domain is a physically meaningful
domain (e.g., Processor Package, DRAM, etc.) for power management. Each power domain informs
the energy consumption of the domain, allows us to limit the power consumption of that domain
over a specied time window, monitors the performance impact of the power limit, and provides
other useful information, that is, energy measurement units, minimum or maximum power sup-
ported by the domain [20].
Figure 1shows the hierarchy of the power domains graphically. RAPL provides the following
power domains for both measuring and limiting energy consumption:
Package: Package (PKG) domain measures the energy consumption of the entire socket. It
includes the consumption of all the cores, integrated graphics and also the uncore compo-
nents (last level caches, memory controller).
Power Plane 0: Power Plane 0 (PP0) domain measures the energy consumption of all pro-
cessor cores on the socket.
Power Plane 1: Power Plane 1 (PP1) domain measures the energy consumption of proces-
sor graphics (GPU) on the socket (desktop models only).
DRAM: DRAM domain measures the energy consumption of random access memory
(RAM) attached to the integrated memory controller.
PSys: Intel Skylake has introduced a new RAPL Domain named PSys. It monitors and con-
trols the thermal and power specications of the entire SoC and it is useful especially when
the source of the power consumption is neither the CPU nor the GPU. As Figure 1suggests,
PSys includes the power consumption of the package domain, System Agent, PCH, eDRAM,
and a few more domains on a single-socket SoC.
For multi-socket server systems, each socket reports its own RAPL values (for example, a two-
socket computing system has two separate PKG readings for both the packages, two separate PP0
readings, etc.).
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:5
Table 1. Comparison of RAPL Power Domains Supported by
Dierent Intel Processor Models
Power domain supported?
Model PKG PP0 PP1 DRAM PSys
Sandy Bridge yes yes yes No No
Sandy Bridge-EP yes yes No yes No
Haswell yes yes yes yes No
Haswell-EP [12]yes No No yes No
Skylake yes yes yes yes yes*
The -EP models are server-grade processors.
*Not All Skylake versions support PSys.
Listing 1. Reading RAPL package energy using the MSR method on Haswell.
The support for dierent power domains varies according to the processor model. Table 1
presents a comparison of RAPL domains supported by dierent models. Power Plane 1 is present
only in desktop models. In Haswell, Intel added support for the DRAM domain to desktop mod-
els. Both Power Planes 0 and 1 are absent in the Haswell server models. Thus, the only univer-
sally supported power domain is the Package domain. In the case of Skylake, unlike PKG, PSys
requires an additional system-level implementation, and so it is not supported in all Skylake
versions.
The RAPL energy counters can be accessed through model-specic registers (MSRs). The coun-
ters are 32-bit registers that indicate the energy consumed since the processor was booted up. The
counters are updated approximately once every 1ms. The energy is counted in multiples of model-
specic energy units. Sandy Bridge uses energy units of 15.3μJ, whereas Haswell and Skylake uses
units of 61μJ. In some CPU architectures such as Haswell-EP, DRAM units dier from CPU en-
ergy units. The units can be read from specic MSRs before doing energy calculations. There is no
specic implication of dierent energy units in dierent architectures.
The MSRs can be accessed directly on Linux using the msr driver in the kernel. Listing 1 shows
an example of this. For direct MSR access the MSR driver must be enabled and the read access per-
mission must be set for the driver [40]. Reading RAPL domain values directly from MSRs requires
detecting the CPU model and reading the RAPL energy units before reading the RAPL domain
(i.e., PKG, PP0, PP1, etc.) consumption values.
Once the CPU model is detected, the RAPL domains can be read per package of the CPU by read-
ing the corresponding “MSR status” register. For example, MSR_PKG_ENERGY _STATUS holds the
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:6 K. N. Khan et al.
energy readings for package domain (PKG). There are basically two types of events that RAPL
events report: static and dynamic events. Static events reported by RAPL events are thermal spec-
ications, maximum and minimum power caps, and time windows. The RAPL domain energy
readings from the chip such as PKG, PP0, PP1, or DRAM are the dynamic events reported by
RAPL.
Apart from directly reading MSRs, RAPL readings can also be read from sysfs interface, perf
events, or through the PAPI library. RAPL support for the sysfs powercap interface is enabled from
Linux Kernel version 3.13 and the perf_event_open support requires Linux Kernel version 3.14.
PAPI library is used for gathering performance-related data. It is platform independent, and it has
a RAPL interface that uses the MSR driver to report RAPL values.
3 RELATED WORKS
Hähnel et al. [14] evaluated whether RAPL can be used to measure short code paths. They showed
that RAPL updates do not occur precisely every 1ms but instead they have some jitter. They also
compared the RAPL measurements (Sandy Bridge) with external measurements with a manually
instrumented board and showed that RAPL measurements do correlate nicely with external mea-
surement with a xed oset.
Hackenberg et al. [11] provided a comparison of power measurement techniques. They pointed
out that the RAPL updates have no timestamps, which can lead to signicant inaccuracy when
sampling the RAPL counters. They also showed that the Sandy Bridge-EP implementation of RAPL
suers from systematic errors.
In 2015, Hackenberg et al. [13] studied RAPL on the Intel Haswell-EP platform. They compared
the accuracy of RAPL between Sandy Bridge-EP and Haswell-EP and showed that Haswell has
improved RAPL measurements. They also showed that RAPL measurements correlate very well
with external power measurements.
Ilsche et al. [19] compared dierent power measurement techniques, including RAPL and
showed that the key advantages of RAPL are: low cost and the ability to isolate the power
consumption of the processor package from the rest of the system.
Huang et al. [18] evaluated RAPL for Haswell-EP processors and compared RAPL with tradi-
tional power monitoring tools. They showed that monitoring with RAPL using the Performance
Application Programming Interface (PAPI) can consume 28.6% more power than an idle system.
This is, however, when RAPL is monitored with all its 28 attributes and not all of these attributes are
related to power or energy monitoring. They also claimed that if RAPL is monitored with selected
attributes (PKG, PP1, PP0, etc.), this power overhead can be reduced by 90%. These measurements,
however, do not account for the PAPI library’s power consumption and dierent granularities of
RAPL measurements will also aect the energy overhead.
Spencer et al. [6] validated the RAPL DRAM values. We discuss their ndings and contributions
in Section 6.4 in more detail. Zhang et al. [44] validate RAPL’s power limiting features based on
stability, accuracy, settling time, overshoot, and eciency. They show that RAPL power limiting
performs well in terms of accuracy, settling time, overshoot and stability. They, however, argue
that RAPL power limiting can underperform at low-power limits and with high-power limits it
can achieve performance that is within 90% of optimal.
Apart from these studies, there is a signicant body of literature [7,8] that independently veri-
es the accuracy of RAPL readings with dierent workloads, architectures, systems, and settings.
RAPL has also been quite extensively used in energy proling [23,28,41], full-system power mod-
eling [24,26], application-level power modeling [43], and power limiting under dierent scenarios
[33,37,45].
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:7
Table 2. System Specifications
Processor (Intel) Architecture Type Sockets Cores L3 Cache Memory
Core i7-4770 @ 3.40GHz Haswell Workstation 1 4 8MB 16GB
i5-6500 @ 3.20GHz Skylake Desktop 1 4 6MB 8GB
Some of the above-mentioned studies have performed the analysis of RAPL energy measure-
ments in specic scenarios. In this work, we present a detailed analysis and technical know-how of
RAPL with respect to accuracy, granularity, and performance overhead, and we identify the essen-
tial issues regarding the usage of RAPL (we term them as “bad” in this article). Our contributions
in this work are twofold. First, there are unique discoveries regarding RAPL such as the relation
between RAPL power readings and temperature, the non-atomic nature of RAPL updates and the
detailed study of RAPL with the CSC data. Second, we also complement and conrm previous
observations, such as RAPL performance overhead and RAPL DRAM energy accuracy. We also
include our rst-hand experience of RAPL in Skylake, which adds to the analysis of previous
literature.
4 EXPERIMENTAL SETUP
We used both Haswell- and Skylake-based systems in our experiments. The latest Skylake mi-
croarchitecture also supports RAPL [20]. Skylake features higher performance than Haswell and
added energy-eciency features. These factors make Skylake an attractive platform for energy
measurement.
Table 2shows more details of the systems. Haswell was a workstation-grade system, while
Skylake was a desktop-grade system. For Haswell, we performed experiments with two software
congurations. We rst disabled turbo boost, huge-pages, and some background processes to cre-
ate a simple conguration. Then, we compared this with the default conguration, which had
those optimizations enabled. No major dierences were found in the RAPL analysis for these two
cases. With optimizations (especially turbo boost) enabled, the software ran slightly faster: 2–3%
speed dierence with the experiments in Table 4. For Skylake experiments, we used the default
conguration without disabling any such congurations.
For the analysis of RAPL behavior, we used multiple sources:
Microbenchmarks. We wrote a set of microbenchmarks in our previous article [17]. These
benchmarks1are designed to exercise specic parts inside the CPU (execution units,
caches, and the instruction decoders). Our benchmarks perform simple mathematical op-
erations like Stream [29]; however, unlike Stream our microbenchmarks do not write any-
thing to memory essentially. The motivation behind writing such microbenchmarks is to
examine the power expenditure of a system when dierent components inside the CPU
are exercised with dierent types of loads and operations. While we previously were
specically interested in the instruction decoder, this time we are using the code as a
more generic benchmark. Our benchmark code is published in a Git repository [16].
Application level benchmarks. We also used a few well-known benchmarks namely:
Stream and ParFullCMS.Stream [29] is a well-known benchmark designed to measure
sustainable memory bandwidth. Using Stream helps us understand the characteristics of
dierent systems in terms of power consumption when running a memory intensive task.
Stress-ng is originally designed to stress dierent subsystems of a computer. In our work,
1https://github.com/mhirki/rapl-tools.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:8 K. N. Khan et al.
we use Stress-ng to stress the CPU cores at 100% load. ParFullCMS is a Geant4 [10]
benchmark, which is a multi-threaded high energy physics workload. This benchmark
employs complex geometry for simulation and essentially exhibits similar properties like
Compact Muon Solenoid (CMS) experiments in CERN. Using ParFullCMS helps us to un-
derstand whether RAPL is able to measure the power consumption of complex scientic
applications with acceptable accuracy and granularity.
Traces from data center. We used two data sets from the Finnish Center of Scientic Com-
puting. The datasets are from the production site of CSC data center Taito [4]. The rst
data set contains 0.5Hz sample rate data over a period of 48h and the other one 0.2Hz sam-
ple rate data over 10 days. The datasets include the output of the Linux vmstat (Virtual
memory statistics) tool, RAPL readings, and the plug power consumption for almost 1,000
machines from the Taito super cluster (around 460 Haswell computing nodes, around 400
Sandy Bridge computing nodes, and a few other special purpose nodes). vmstat vms [1]
is a Linux tool, which reports the usage summary of memory, interrupts, processes, CPU
usage, and block I/O. We used this dataset to validate the accuracy of RAPL readings.
Measurement Methodology. The RAPL power readings are collected using our trace-energy
tool. This tool captures the power consumption of RAPL package, PP0, PP1, and DRAM
domain by reading the corresponding msr registers. The frequency of energy tracing is
supplied as a command line argument to the tool. The benchmark program/application
program for which we want to measure the power consumption is attached to the trace-
energy tool as a command line argument. For our in-house experiments, we used the
Plugwise [34] power meter to capture the plug power consumption of the system from
the wall socket. This device has the highest frequency of 0.1Hz, and we used the same
frequency to capture the power-consumption data. The CSC datasets captured the vm-
stat, RAPL, and plug power from the IMPI tool at a frequency of approximately 0.5Hz and
0.2Hz. The metrics collection for these datasets was done manually. For the continuous
collection and analysis of such data, we need high-resolution automatic energy measure-
ment tools, which should ideally work on a cross-platform basis across dierent hardware
and batch job schedulers.
5 GOOD FEATURES OF RAPL
In this section, we discuss desirable features of RAPL such as high accuracy and small performance
overhead.
5.1 Accuracy of RAPL Energy Readings
The accuracy of RAPL energy readings is high even though it is based on activity counters [11,
14] and the accuracy varies across dierent processing architectures.
We performed experiments with the Stream benchmark on a Haswell machine that show a
strong correlation between RAPL package power and full-system power consumption from the
wall socket. The results are presented in Figure 2. The results show that RAPL power values are
promisingly accurate, and these values can be used to predict or model full-system power con-
sumption.FromFigure2, we can see that when we run the Stream benchmark at dierent proces-
sor frequencies on a Haswell machine, the full-system power consumption from the wall strongly
correlates with RAPL package power. The correlation coecient between the two values is 0.99.
We also compared the accuracy of RAPL using two large datasets collected from a supercom-
puting cluster containing almost 1,000 computing nodes. The RAPL and IPMI power (plug) read-
ings were collected in the rst dataset every 2s for a period of 2 days and in the second data set
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:9
Fig. 2. Wall and RAPL package power consumption with time—Stream.
every 5s for a period of 10 days. We tested cross correlation among RAPL values and plug power
measurements and noticed that there is a signicant time dierence between these. Therefore, we
computed several lagged plug variables. Since the measurements are strongly autocorrelated, we
took a random sample of 30,000 measurements for both SandyBridge and Haswell nodes and di-
vided the sample into 80% training and 20% testing sets. The distribution of plug measurements
does not follow any standard distribution very well but the normal distribution gives the best
results in the prediction models.
We tted both linear regression and Generalized Additive Models (GAM) with the data to esti-
mate the plug measurements using the RAPL values. Generalized additive models (GAMs) [42]are
regression models in which the expected value of the response variable Ydepends on unknown
smooth functions of some predictors x1,2,...,mas follows:
E(Y)=β0+f1(x1)+f2(x2)+···+fm(xm),
where β0denotes the intercept, and f1,2,...,mare smooth functions of covariates.
The benet of GAM over linear regression is that it can also model non-linear relationships. For
the Haswell architecture nodes, we used the following linear regression model:
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:10 K. N. Khan et al.
And the following GAM model:
For SandyBridge, the models omitted DRAM parameters, since the RAPL does not support them
in that architecture.
The best results gave a lag of 10s in the case of Haswell and 24s in SandyBridge. However, we
cannot be sure whether this dierence is caused by dierent versions of the IPMI plug power mea-
surement or RAPL itself. The results for the 0.5Hz data set are shown in Table 3. The linear model
performs well but GAM still gives slightly better results. This may indicate that the relationship
(RAPL and plug) has a small non-linear eect. The large ten day data set gave similar but slightly
better results (e.g., MAE 1.0 and RMSE 5.7 for Haswell). However, these are not directly comparable
with the 48 hours data set because of dierent sampling rates.
The regression models for Haswell include DRAM values of RAPL but this feature is not sup-
ported in SandyBridge. Therefore, we also tested whether the better accuracy in Haswell is due to
the DRAM measurements. Results indicate that DRAM does improve the accuracy but even with-
out DRAM the RAPL seems to perform better in Haswell (mean absolute percentage error 3.1%)
than SandyBridge (mean absolute percentage error 4.0%).
When trying to estimate power consumption using only OS counters (vmstat outputs), the re-
sults are clearly worse than using RAPL. For SandyBridge, the Mean Absolute Percentage Error
(MAPE) using the linear model was 11% and 6% when using a GAM model. The same errors for
Haswell were 15% and 5%. These results conrm that RAPL readings are accurate enough to pre-
dict full-system power consumption and can provide better estimation models when compared to
the models that are based on OS counters.
Studies have also shown that RAPL power readings show promising accuracy. Hackenberg et al.
[12] compared the RAPL implementation in Sandy Bridge-EP and Haswell-EP platforms. They
compared power consumption predicted by RAPL with calibrated external readings. The results
show that RAPL in Sandy Bridge-EP suers from systematic errors while the Haswell-EP has a
nearly perfect correlation with external measurements across all workloads. Therefore, Haswell-
EP is clearly a better choice for accurate power estimates. This applies to the entire family of
models based on the Haswell microarchitecture, as we have shown here. Similar to our approach,
Khan et al. [24] used RAPL package power reading to propose an empirical power model to predict
the full-system power.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:11
Table 3. Regression Models for the Plug Power (Mean
Absolute Error, Root Mean Square Error, and Mean
Absolute Percentage Error)
Model Architecture MAE RMSE MAPE
Linear Haswell 5.6 9.8 1.8%
GAM Haswell 5.2 9.8 1.7%
Linear Sandy Bridge 10.5 17.2 4.3%
GAM Sandy Bridge 9.8 16.3 4.0%
Table 4. RAPL Performance Overhead
Application 100Hz 200Hz 500Hz 1,000Hz 1,100Hz
Idq-bench-oat-array-l1-schoenauer 0.07% 0.15% 0.35% 0.70% 0.75%
Idq-bench-oat-array-l2-schoenauer 0.15% 0.23% 0.42% 0.78% 0.86%
Idq-bench-oat-array-l3-schoenauer 0.15% 0.17% 0.40% 0.75% 0.84%
STREAM-NTIMES-2000 0.46% 0.35% 0.89% 1.20% 0.70%
Idq-bench-int-algo-prng 0.07% 0.14% 0.34% 0.66% 0.70%
Idq-bench-int-algo-prng-multi4 0.07% 0.14% 0.34% 0.67% 0.72%
5.2 Performance Overhead
The RAPL energy calculations are implemented in the hardware. There is no need to do any
complex calculations, such as numerical integration in the software. Energy consumption can be
measured on the same machine without signicant overhead. No additional equipment is needed,
which makes RAPL a very-low-cost option for energy measurements. We performed experiments
to measure the performance overhead caused by RAPL measurements with dierent applications
and measurement frequencies. The results are presented in Table 4.
To measure the RAPL measurement overhead on performance, we used our instruction decoder
benchmarks for dierent caches and data types. In addition, we also used the well-known Stream
[29] benchmark. For the overhead measurement, we pinned the application and the RAPL mea-
surement program on the same CPU core. In such a manner, the application program will be slowed
down depending on the sampling rate of the measurement program. Our schoenauer benchmarks
are based around the following loop:
D += A[j] + B[j] * C[j].
By changing the sizes of these arrays, we can make them t in the L1, L2, or L3 cache. The
Idq-bench-int-algo-prng is simply a linear congruential generator used to generate pseudo-random
numbers. This code has no dependency on any cache. The multi4 version has four generators in
a single loop, creating a bigger loop. Since switching to another process involves ushing the L1
cache, we expect that the benchmarks with a heavier cache dependency will suer from a bigger
overhead.
Table 4depicts the percentage performance overhead (wall clock time) for RAPL measure-
ments on frequencies 100, 200, 500, 1,000, and 1,100Hz. As we can see, for Idq-bench-oat-array-
l1-schoenauer the highest performance overhead is 0.75% at 1,100Hz over a normal run when no
RAPL measurement is performed. The results follow the same trend for other applications: for
Idq-bench-oat-array-l2-schoenauer, the highest overhead is 0.86% at 1,100Hz, for Idq-bench-oat-
array-l3-schoenauer, the same value is 0.84% and so on. Interestingly, for Stream, the highest perfor-
mance overhead is 1.20%, which occurs at 1,000Hz and for 1,100Hz the overhead is smaller: 0.70%.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:12 K. N. Khan et al.
Fig. 3. Package Temperature and Package Power over time with a constant load on CPU.
We tested this 10 times and for every run the result had no signicant dierence. This might be due
to the nature of Stream; however, we cannot verify this in the scope of this article. Nevertheless,
from Table 4it is clear that even for a sampling rate of 1,100Hz, the performance overhead will
be less than 2% in most cases. Since the overhead is small, it is possible to take advantage of high
sampling rates without disturbing the system too much.2
5.3 Correlation with Temperature
We performed experiments to analyze how CPU package temperature relates to package power
for both Haswell and Skylake architectures. To do this, we used our own microbenchmark named
idq-bench-oat-array-l3-schoenauer. This benchmark was originally written to stress specic parts
inside the CPU such as execution units, caches and the instruction decoders. This benchmark is
used here as it exhibits stable and steady power consumption proles and it also consumes quite a
lot of power, which makes the CPU heat up. The results are presented in Figure 3. The temperature
and package power data are collected using 250Hz sampling rate. For the sake of simplicity in
visualizing data, we take the average of every 50 data points in time so that the trend in data can
be visible in the gure.
As Figure 3indicates, it is important to control the temperature of the CPU to obtain accurate
power readings through RAPL. The initial data for Haswell suggests that the package power grows
by approximately 10–12% between 37Cand74
C. In the case of Skylake the package power grows
by approximately 8–10% between 23Cand32
C. We can see that the package power drifts 5–
10W for Haswell; however, the Skylake package power readings are quite stable. The correlation
2Note that for calculating the overhead we used “real” time taken for a program to complete (as measured by the time com-
mand). The RAPL MSR registers are read from user space and the average latency of reading the MSR (RDMSR instruction
execution + a system call) le is 393ns. So, if RAPL is read from kernel space, the system call time would be eliminated.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:13
Fig. 4. Wall and RAPL package power consumption with time.
coecient between Haswell’s package reading and temperature is 0.93 and the same for Skylake
is 0.34. The high correlation coecient for Haswell suggests that in case of Haswell temperature
can have a measurable impact on the package power consumption and thus it is important to
take the temperature of the system into account while measuring power using RAPL. Skylake
have improved this phenomenon and there is a smaller correlation between the package power
and temperature. The standard deviation for the Haswell package power reading is 1.29 and for
Skylake it is 0.28. This also conrms that Skylake power draw is fairly stable while the temperature
of a system grows. One possible reason for this might be the optimized use of the fan in case of
Skylake.
The Linux coretemp driver only provides a time resolution of 1Hz. However, the MSR registers
for the temperature sensors are actually updated every 1ms. This coincides with the RAPL update
interval. There is a good correlation with the RAPL package power and temperature. Neverthe-
less, Figure 3shows that CPU temperature can inuence the CPU package power draw. To obtain
accurate RAPL power readings it would be good to warm up the CPU before obtaining any RAPL
measurements. A 2min warm-up period should be enough for any suitable program that keeps the
CPU package busy.
5.4 High Sampling Rate
RAPL updates the energy counters approximately once every 1ms, that is, 1,000Hz. This frequency
is much higher compared to external power meters that typically measure power only once a
second. Servat et al. [35] demonstrated that many HPC benchmarks have phases with dierent
package and DRAM power consumption characteristics. We found that the RAPL sample rate is
sucient to distinguish dierent execution phases in applications.
We tested this phenomenon with a scientic computing application ParFullCMS benchmark
on a Haswell based system. Figure 4demonstrates that the multi-threaded ParFullCMS has two
broad distinct phases: the rst phase is the initialization phase, which sets up the events to be
processed and consumes relatively less power; the second phase is the compute-intensive phase,
which performs the bulk of simulation tasks and consumes relatively more power. It is evident
from the gure that RAPL package power sampling is able to capture distinct phases in ParFullCMS
like High Energy Physics (HEP) benchmarks. We performed another experiment with Stress-ng to
compare RAPL’s sampling rate with a plug power capturing device. Stress-ng was invoked as CPU
intensive workload with uctuating loads. The RAPL PKG consumption value was captured every
5ms and the plug value was captured every 100ms (10Hz is the highest frequency of sampling
supported by the Plugwise device we used). The results are presented in Figure 5.Theplugpower
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:14 K. N. Khan et al.
Fig. 5. RAPL Sampling Rate Experiment with Stress-ng.
Fig. 6. PP0 sampled every 5ms with a constant load on one CPU core.
metering device was unable to capture the distinct phases as the phases changed faster than the
metering device’s frequency. RAPL could actually capture the phase changes at a 5ms sampling
frequency (RAPL can be sampled in 1ms frequency). The zoomed area of RAPL package power
in Figure 5shows the distinct phase changes in computation (and thus in power consumption) in
ner detail.
Our Skylake experiments also reveal that Intel has improved the temporal resolution of PP0
updates in Skylake in comparison to Haswell and previous architectures. PP0 in Skylake updates 20
times on an average in between a single update for other domains (PKG, PP1 and DRAM). Figure 6
shows the time gap between two consecutive PP0 updates in case of Haswell and Skylake for about
10,000 updates. This gure shows that for Haswell most of the PP0 update happen at a time gap
of nearly 1ms or 1,000μs, whereas for Skylake the bulk of the updates happen between 50 and
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:15
70μs with a few outliers. This new improvement for Skylake allows a more granular temporal
resolution and as a result it improves the possibility to determine the energy consumption of short
code paths.
5.5 Always Running
RAPL starts running as soon as the processor boots up. There is no need to congure it if one
wants to measure energy consumption, which makes it very easy to use. Since RAPL is always
running, there is very little additional overhead introduced by reading the energy counters.
6 RAPL LIMITATIONS
This sections discusses the weaker aspects of RAPL, which should be properly addressed in specic
scenarios. We also discuss solutions to overcome these issues in this section.
6.1 Poor Driver Support
Sandy Bridge processors supporting RAPL were released in 2011. Full RAPL driver support was
introduced as late as 2013 to the Linux kernel. Currently, there are three ways to read the energy
counters on Linux.
As mentioned in Section 2,themsr driver supports raw access to any MSR including the RAPL
energy counters. It is nearly universally supported regardless of the kernel version. The main
drawback is that root access is required to use the msr driver. The earlier Listing 1shows how to
access the counters using the msr driver. Popular libraries, such as PAPI, rely on the msr driver
interface. Thus, root access is also required when using these libraries.
The powercap driver allows reading the energy counters and conguring the power consump-
tion limits. The counters can be found under /sys/devices/power/events/. They can be read without
root access. The powercap driver was introduced in the kernel version 3.13.
The performance events (also called perf_events) subsystem in the Linux kernel supports RAPL
energy counters since the kernel version 3.14. This allows the Perf tool to read the counters. Weaver
[39] provided an example of how to programmatically read the counters using the perf_events API.
6.2 Register Overflows
The energy counters are limited to 32bits even though the MSRs are 64bit wide. Therefore, they
will eventually overow. Fortunately, these overows are quite rare. We can calculate the time to
overow toverow using the following equation:
toverow =232 ×Eu
P.(1)
Here, Euis the energy units used (61μJ for Haswell) and Pis the power consumption. For ex-
ample, a Haswell processor consuming 84W would cause an overow every 52min:
232 ×61μJ
84W =3120s.
The overows can be mitigated easily by sampling the energy counters more frequently than
toverow. Frequent-enough sampling allows detecting every overow that occurs. As a general rule,
sampling the counters every 5min should be sucient for any CPU model.
6.3 Non-atomic Register Updates
Our measurements show a time delay between updates to dierent energy counters, which means
that the RAPL updates are not atomic. The non-atomicity introduces errors when sampling mul-
tiple counters at high sampling rates. It is possible to read both fresh and stale values of dierent
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:16 K. N. Khan et al.
Fig. 7. The time gap between updates to dierent RAPL registers (Haswell). The timing is measured in
microseconds.
counters. Figure 7shows the timing dierence between updates to dierent RAPL registers for our
Haswell machine. In this experiment, we perform busy polling to two RAPL registers alternately.
For example, Figure 7(a) shows the timing gap between the RAPL Package (PKG) and PP0 regis-
ters. We record the timestamp of every update for both the registers and calculate the dierence
between the two timestamps. In the case of Haswell, we observe that RAPL registers are always
updated in a specic order. The PP0 register is updated either 2.8 or 3.6ms after the PKG register.
The DRAM register is updated either 4.4ms or 5.2ms after the PKG register. The 0.8ms dierence
between these numbers is due to our limited polling frequency. The average latency of reading
the MSR (RDMSR instruction execution + a system call) le is 393ns [15]. Therefore, polling two
registers takes approximately 0.8ms.
There is a measurable delay between updates of dierent RAPL registers. We observe similar
behavior in case of Skylake. Nevertheless, Figure 6has already shown us that there are measurable
gaps between two Skylake RAPL register updates. It is quite obvious that RAPL registers are not
updated atomically. This means that it is possible to accidentally read both fresh and stale energy
values when sampling multiple RAPL registers. Specic precautions should be taken to avoid this.
For example, we can rst identify the correct sequence of RAPL register updates for a specic
processor architecture and then if busy polling is used to detect RAPL updates, one should poll the
last register updated (in our Haswell experiment DRAM register appears to be the last updated).
6.4 DRAM Energy Accuracy
A few articles [5,25,32] have focused on validating the RAPL values specically for the RAPL
DRAM domain. The initial ndings suggest that RAPL DRAM values were unstable and unreliable
for earlier versions of processors that included RAPL. DRAM values were only available to server-
grade systems prior to Haswell. Prior to Haswell, the RAPL DRAM values followed dierent trends
depending on the benchmark, and the values also diered substantially at times with reference
values. Since the introduction of Haswell, RAPL DRAM values are now more reliable and follow
a strong correlation with AC reference measurements [13,24].
In our own analysis, DRAM measurements clearly improve accuracy. Modeling the plug power
using only CPU measurements gives 3.1% error, including DRAM measurements reduces this error
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:17
to 1.7%. However, using only DRAM measurements alone for estimating the plug power yields
quite a large error, 7.7%.
A more recent work on the validation of RAPL DRAM power measurements [6] also conrms
these results. According to Spencer et al. [6] RAPL DRAM values now closely match the overall
energy power and energy trends by a constant power oset for Haswell processors. They also
show that there are dierences in RAPL DRAM energy measurements across dierent architec-
tures although the results with newer architectures are more accurate. Thus it is important to pay
attention to the underlying architecture before relying on RAPL DRAM energy measurements.
6.5 Unpredictable Timings
The update interval of the RAPL energy counters is approximately 1ms. Intel documentation states
that the time unit used by RAPL is 0.976ms. Our experiments show that the actual interval is
much closer to 1ms. Unfortunately, the updates do not have any timestamps associated with them
[11]. In addition, there seems to be no way to predict the exact timing of future RAPL updates.
Nevertheless, there are several solutions for coping with this problem.
First solution: busy polling. It is possible to determine the exact timing of the RAPL updates by
busy polling the counters for updates. This technique allows for exact synchronization with the
RAPL updates. Hähnel et al. [14] demonstrated that this method can be used to measure the energy
consumption of short functions. They use busy polling to detect the start of a RAPL measurement
period. They then execute a function they want to measure. Subsequently, they use busy polling
to wait until the end of the RAPL period. They obtain the energy used by the function itself by
deducting the energy used for busy polling. The downside of this method is the overhead in terms
of time and energy.
Second solution: supersampling. Every update can be observed without the timing by sampling
more often than every 1ms, for example, every 0.9ms. We call this method supersampling. The
method will occasionally produce duplicate values, but they can be ltered out easily. The main
advantage is the reduced overhead compared to busy polling. However, the relative overhead is
still quite large.
Third solution: High frequency sampling. Sampling frequencies in the range 50–1,000Hz fall into
this category. The advantage is lower overhead due to lower sampling rate. A 50Hz sampling rate
is still sucient to distinguish dierent execution phases, as Servat et al. [35] demonstrated. A
drawback of this solution is that the number of updates in one sampling period is not predictable.
For example, when sampling at 200Hz, most samples correspond to ve RAPL updates. However,
occasionally one sample contains four or six updates. This will create spikes in the data. The spikes
can be ltered out but this leads to a small loss of data.
Figure 8shows an example of the spikes when sampling at 200Hz. In this case, the spikes come in
two avors: (1) a spike that is 20% below the mean, and (2) a spike 20% above the mean combined
with a second spike 20% below the mean. The rst avor is caused by the fact that the mean
time between RAPL updates is 1.00229ms. Thus, in a 10s time period, there will be only 10,000 ÷
1.00229 =9,977 updates. The second avor is caused by the random spread in the timings, which
allows six updates to be observed inside a 5ms period. We have drawn circles around the points
that are 20% above the mean.
Fourth solution: Low frequency sampling. At sampling rates slower than 50Hz, the relative error
due to the spikes is less than 0.5%, which is small enough to be ignored. The energy values should
remain accurate even with long sampling periods, since they are calculated by the hardware. Thus,
the only drawback with slow sampling is the loss of temporal precision.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:18 K. N. Khan et al.
Fig. 8. Package and DRAM energy sampled every 5ms with a constant load on one CPU core.
6.6 Individual Core Measurement Not Supported
RAPL does not support measuring the power consumption of individual CPU cores. The Power
Plane 0 domain only gives the total energy consumed by all cores in a single package. Each core
has its own MSRs, but we found that all cores show the same values for the RAPL counters. This
prevents us from separating the power consumption of dierent processes or threads running
concurrently on the same processor.
There are still alternatives that allow examining the power consumption of individual threads.
The rst alternative is to run an application in single-threaded mode. We measured the Power
Plane 0 power consumption, which is nearly zero when all the cores are sleeping. Thus, Power
Plane 0 is equivalent to the power consumption of a single CPU core when only one core is active.
The second alternative is to use multiple cores and divide the power consumption by the number
of active cores. This method works best if all threads are performing the same task. For example,
microbenchmarks can execute identical workloads across multiple threads.
Individual core measurement is further complicated by hyperthreading. Hyperthreading allows
one core to simultaneously execute instructions from two threads. There is no way to separate the
power consumption of one thread from the other. However, there are techniques that use hardware
counters to model and attribute the power consumption to individual threads such as HaPPy [43].
Such models tend to have large errors (10%) and therefore, it is advisable to either explicitly
enable or disable hyperthreading depending on what needs to be measured.
6.7 Fixed Sampling Rate and Energy Units
It is not possible to increase the sampling rate from the default of 1,000 samples per second, which
limits our ability to measure the energy consumption of individual functions using for example,
IgProf [23]. One solution is to force the application to sleep before and after the execution of a
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:19
Table 5. Amazon EC2 Instance Specifications
Instance Type Processor Architecture Cores Memory
t2.micro Intel(R) Xeon(R) CPU E5-2676 v3 @ 2.40GHz Haswell-EP 1 1GB
t2.xlarge Intel(R) Xeon(R) CPU E5-2676 v3 @ 2.40GHz Haswell-EP 4 16GB
t2.2xlarge Intel(R) Xeon(R) CPU E5-2676 v3 @ 2.40GHz Haswell-EP 8 32GB
c3.xlarge Intel(R) Xeon(R) CPU E5-2680 v2 @ 2.80GHz IvyBridge-EP 4 7.5GB
c4.xlarge Intel(R) Xeon(R) CPU E5-2666 v3 @ 2.90GHz Haswell-EP 4 7.5GB
single function. In this manner only a single function is executed during one RAPL update period.
Hähnel et al. [14] have shown that this method works. The size of the RAPL energy units limits
how accurately a single function can be measured. There are dierences in the energy units be-
tween dierent models, which means that some models are better for measuring small variations
in energy consumption. For example, Haswell models use units of 61μJ, while Sandy Bridge models
use units of 15.3μJ.
7 RAPL MEASUREMENTS IN AMAZON EC2
To further quantify and qualify RAPL measurements, we performed several experiments with
Amazon Elastic Compute Cloud (Amazon EC2). The motivation behind choosing a cloud envi-
ronment is to examine how RAPL performs in popular cloud based services like Amazon EC2.
Energy consumption in such a cloud environment is very crucial and tools like RAPL can simplify
the energy consumption monitoring of individual users and instances and trigger new energy
based pricing mechanisms such as $/joule instead of $/core/hour. In this section, we present our
experiences while using RAPL in Amazon EC2. With respect to RAPL, we performed the follow-
ing experiments: performance overhead, correlation with temperature, and sampling rates. The
methodologies used in these experiments are the same as those mentioned in Sections 4and 5.
Amazon EC2 allows to read RAPL’s MSR registers. Currently, with all of the processor family
available in Amazon EC2, it is possible to read the package and DRAM power consumptions. We ex-
perimented with ve dierent Amazon EC2 instances: t2.micro, t2.xlarge, t2.2xlarge, c3.xlarge, and
c4.xlarge [9]. The specications of these instances are presented in Table 5. t2 instances are general
purpose computing instances with mostly Intel’s Haswell-EP architecture, whereas c3 and c4 in-
stances are compute optimized instances with a mix of Intel’s Haswell-EP,Broadwell-EP,IvyBridge-
EP,andSandybridge-EP architectures. We could not obtain the plug power consumption in EC2
instances from sources like IPMI and as a result we could not establish or verify the accuracy of
the RAPL readings in virutalized cloud computing platforms like EC2. Our rst-hand experience
of using RAPL in Amazon is discussed in the following.
Performance overhead. We used the same benchmarks and same frequency settings as men-
tioned in Table 4for measuring performance overhead in Amazon EC2. The impact of RAPL mea-
surement on performance overhead in a cloud environment is particularly interesting to examine,
because the same physical resources are shared between dierent users in a virtualized cloud en-
vironment and there is an expected measurable impact of other co-running user instances on the
overall power consumption and load of the system. In our experiments, we mainly focused on
t2 instances for examining performance overhead. The results are presented in Table 6. The per-
formance overheads of RAPL measurements in the case of Amazon t2 instances are quite similar
to our observations with Haswell-based standalone systems as presented in Table 4. In t2.micro
the maximum overhead was observed in Idq-bench-int-algo-prng-multi4, while reading the RAPL
MSRs at a frequency of 1,100Hz and the overhead was 2.30%. In t2.micro, we observed a lot of
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:20 K. N. Khan et al.
Table 6. Amazon EC2- RAPL Performance Overhead
t2.micro
Application 100Hz 200Hz 500Hz 1,000Hz 1,100Hz
Idq-bench-oat-array-l1-schoenauer 0.38% 0.60% 1.00% 1.63% 1.75%
Idq-bench-oat-array-l2-schoenauer 0.04% 0.05% 0.64% 1.50% 1.64%
Idq-bench-oat-array-l3-schoenauer 0.09% 0.63% 0.77% 1.84% 2.05%
STREAM-NTIMES-2000 0.08% 0.54% 0.98% 1.36% 1.28%
Idq-bench-int-algo-prng 0.19% 0.26% 0.69% 1.40% 1.64%
Idq-bench-int-algo-prng-multi4 0.91% 1.10% 1.39% 1.97% 2.30%
t2.xlarge
Application 100Hz 200Hz 500Hz 1,000Hz 1,100Hz
Idq-bench-oat-array-l1-schoenauer 0.18% 0.53% 1.08% 1.61% 2.24%
Idq-bench-oat-array-l2-schoenauer 0.09% 0.24% 0.43% 1.23% 1.42%
Idq-bench-oat-array-l3-schoenauer 0.25% 0.48% 0.73% 1.33% 1.25%
STREAM-NTIMES-2000 0.08% 0.54% 0.98% 1.36% 1.28%
Idq-bench-int-algo-prng 0.27% 0.43% 0.84% 1.49% 1.59%
Idq-bench-int-algo-prng-multi4 0.10% 0.31% 0.79% 1.37% 1.56%
t2.2xlarge
Application 100Hz 200Hz 500Hz 1,000Hz 1,100Hz
Idq-bench-oat-array-l1-schoenauer 0.41% 0.65% 1.45% 1.59% 1.79%
Idq-bench-oat-array-l2-schoenauer 0.14% 0.10% 0.61% 1.70% 1.70%
Idq-bench-oat-array-l3-schoenauer 0.19% 0.43% 0.92% 1.95% 1.81%
STREAM-NTIMES-2000 0.11% 0.41% 0.46% 1.48% 1.52%
Idq-bench-int-algo-prng 0.17% 0.27% 0.64% 1.43% 1.48%
Idq-bench-int-algo-prng-multi4 0.47% 0.62% 1.02% 1.51% 1.59%
performance variations due to variable load on the system. In such cases, the benchmark itself
took unusually longer time to completion compared to cases where sampling frequency was even
higher. We carefully discarded the unstable results. We present an example of such a scenario in a
later discussion. For the t2.xlarge instance, the maximum overhead was 2.24%, which was reported
in Idq-bench-oat-array-l1-schoenauer at 1,100Hz and in t2.2xlarge the maximum overhead was
1.95%, which was measured at 1,000Hz for the Idq-bench-oat-array-l3-schoenauer benchmark. For
t2.2xlarge, the overhead measurements were less than 2.0%, which was also the case for the stan-
dalone Haswell based workstation. Since t2.2xlarge was an 8 core Haswell-EP-based system, the
possibility of load variation due to CPU or resource sharing was quite low, since the number of
virtual CPUs in the instances and number of physical CPUs of the architecture are the same and
the observations were more stable. In brief, the performance overhead observed in Amazon EC2
was less than 2.5%.
Correlation with temperature. The correlation between the RAPL package power and the
core temperature could not be veried in the case of Amazon EC2. Although, it was possible to
read the MSRs like IA32_THERM_STATUS and IA32_PACKAGE_THERM_STATUS, we obtained a
constant value of 25°C as the PKG temperature. We veried this with dierent benchmarks like
Stress-ng,Stream, and our Instruction decoder benchmark (presented in Table 4) and the package
temperature remained static at 25°C. We assume that Amazon EC2 lters out the temperature
sensor value and presents a dummy constant value for package temperature. Apparently, Liu et al.
reported in Reference [27] that it was possible to read the CPU temperature readings but things
have changed since then.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:21
Fig. 9. PKG power timing gap between consecutive updates.
Timing gap in consecutive RAPL updates. We performed experiments to identify the timing
gaps in consecutive RAPL updates and to verify the high resolution of RAPL updates similar to
experiments presented in Figure 6. The experiments were performed using t2.xlarge, t2.2xlarge,
c3.xlarge, and c4.xlarge instances. The timing gaps (in ms) for 10,000 consecutive RAPL PKG power
updates is plotted in Figure 9. As indicated in this gure, the timing gaps are very sporadic for
t2.xlarge, t2.2xlarge, and c4.xlarge ((a), (b), and (d), respectively, in Figure 9). The timing gaps in
c3.xlarge ((c) in Figure 9) show a certain pattern but it is still inconclusive and does not show a
uniform update interval (which should be ideally 1ms for Haswell) if we compare it with Figure 6.
Interestingly, among the four types of instances examined here, only c3.xlarge has the Ivybridge-
EP processor architecture and the remaining three have Haswell-EP processor architecture. The
results show that there is a dierence in RAPL implementation between the two architectures. We
found a measurable dierence in polling delay between standalone workstations and Amazon EC2
instances. The hypervisor in EC2 instances traps the MSR reads, which can add to the polling delay.
The CPU in EC2 also runs at a lower clock rate, which might also add to the delay. Nevertheless,
it is hard to pinpoint whether the timing gaps are produced by the hardware or interference from
the hypervisor. Further investigation is required to make such claims.
Reading RAPL values with Amazon EC2 is challenging, since the current implementation of
RAPL does not give the per-core energy consumption measurements. Additionally, it is not neces-
sary for a virtual CPU to be mapped to a physical CPU in a cloud environment. The RAPL readings
in such a scenario are also aected by other virtual instances running on the physical server. We
proled the c4.xlarge instance for 500s, where we simply captured the RAPL readings at a 250Hz
sampling rate without doing anything. Figure 10 shows the power consumption during that 500s,
when we executed no workload but just listened to the RAPL updates. This gure shows that dur-
ing the experiment period the PKG power consumption of the instance highly uctuated between
the mid 30W to close to 100W. Therefore, it is very hard to do the energy accounting in such a
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:22 K. N. Khan et al.
Fig. 10. Amazon EC2 Power profiling.
Table 7. Summary
Aspects Findings
Accuracy Correlation 0.99 with AC power
Plug Power Estimation MAPE 1.7%
Correlation with
temperature
High Correlation with package power in Haswell: 0.93
Less correlation with package power in Skylake: 0.34
Sampling rate High sampling rate 1ms
Skylake PP0 sampling rate 50 μs
Performance overhead Negligible: <1% overhead for standalone systems <2.5%
for Amazon EC2
DRAM energy 20% deviation from actual measurements [6]
virtualized environment and RAPL needs to address this issue to make it more usable in cloud
environments like EC2. A few straightforward enhancements that could make RAPL more usable
in virtual environment are listed below:
Reducing the delay of reading RAPL MSRs through hypervisors.
Adding per core energy accounting instead of per package. This would also make the RAPL
implementation more secure, since it would not be possible to see the activities of other
instances sharing the same package through power consumption patterns.
Adding timestamps to RAPL updates to allow per job or per process energy proling.
8 DISCUSSION
Table 7summarizes the important aspects of RAPL that we have discussed in detail in the previ-
ous sections. We have pinpointed our ndings about Intel RAPL’s accuracy, plug power estimation
capability, relation with temperature, sampling rate, performance overhead, and some other im-
portant aspects that we need to quantify about RAPL through our own experiments and a thorough
review of the literature. Our study shows that Intel RAPL can provide accurate enough results for
the power consumption of a CPU or attached DRAMs without manually instrumenting the system.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:23
The sampling rate is high enough and the performance overhead for reading RAPL counters at a
higher rate is low enough for most of the general cases.
On the contrary, there are some aspects of RAPL that might not make it a suitable tool for cases
where we need to determine the power consumption of short code paths [14] or cases where we
need to know the exact timestamps attached with each RAPL update. We have discussed all of these
aspects to highlight the advantages as well as weaker aspects of RAPL. For future references, we
pinpoint a few of our proposed workarounds in brief:
Register overow problem can be mitigated by sampling more frequently than the time to
overow.
Non-atomicity of register updates can be dealt with correctly by identifying the sequence
of RAPL register updates and then busy polling the last register in the sequence.
In case of DRAM energy measurements, Haswell and later processor architectures should
be used.
To mitigate the lack of timestamps in RAPL updates, one can use busy polling, supersam-
pling, high frequency sampling or low frequency sampling depending on the requirements.
(Please refer to Section 6.5 formoredetails)
Individual core measurements can be obtained either by running a single threaded mode of
a workload or by dividing the power consumption by the number of active cores given that
all the threads perform the same task.
RAPL measurements in Amazon EC2 instances suggest that although it is possible to obtain
power consumption readings in Amazon EC2, the power consumption of such a virtualized cloud
computing environment itself varies depending on the load on the actual systems, and therefore the
current implementation of RAPL may not be so useful in such scenarios compared to standalone
systems. RAPL implementation should properly address this in the future architectures to make it
useful and ecient in cloud computing systems.
The promising aspect of RAPL is that it has evolved through generations of architecture. Sandy-
bridge RAPL energy consumption values are based on modeling approaches. On the contrary,
Haswell is able to achieve higher levels of accuracy because of the introduction of on-chip voltage
regulators and more ne grained control of frequencies [13]. We have also shown that Skylake
has improved from Haswell in granularity for measuring the PP0 domain and it introduces a new,
PSys domain to monitor and control the power consumption of the platform domain. Our limited
experiments with Skylake already show improvements in RAPL implementation and in the future
we plan to perform a detailed study on Skylake’s RAPL validation.
We do not particularly focus on GPU workloads in this article, since our focus here is tradi-
tional CPU or memory intensive workloads. In the future, we plan to extend our work with such
enhancements. There are alternatives for RAPL in case of AMD, ARM processors and NVIDIA
GPUs. Prior works suggest AMD processor can report “Current Power In Watts” using MSRs like
RAPL [14], ARM has cross-platform chip monitor integrated with recent versions of processors
[2], and recent NVIDIA GPUs can also report power usage via the NVIDIA Management Library
(NVML) [14].
Despite a few dierences in RAPL and reference measurements, Intel’s RAPL can be a useful
tool to track a program’s power consumption behavior in large-scale data centers and it can be a
good alternative to metering devices specically as it does not require a complex manual instru-
mentation of every system of interest. It will be more useful to use RAPL if it addresses some of the
concerns that we discuss in this article: adding timestamps to individual updates, atomic register
updates, individual core measurement features, handling register overows more gracefully, and
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:24 K. N. Khan et al.
perhaps adding more features such as handling even the power consumption of the other system
components rather than only the CPU chip.
9 CONCLUSION
The study of energy-eciency in computing has been a hot topic for a long time. The introduction
of RAPL has enabled a number of experiment scenarios that were not possible before. Nevertheless,
there are also weaknesses that are associated with such an approach. In this article, we conducted a
comprehensive study to demonstrate how Intel RAPL performs in terms of accuracy, performance,
granularity, usability, and other important aspects of user experiences. We also pinpointed several
directions toward the improved handling of some of the issues that might arise in certain scenar-
ios. Our overall study suggests that RAPL has evolved toward a better energy measurement tool
since its introduction in Sandybridge, and it has appeared to be a useful and ecient alternative
for manually instrumented complex power monitors. With the Haswell architecture, RAPL has
improved considerably, its power readings now closely match plug power readings and it has now
introduced the new measurement domain PSys and improved the power performance in Skylake.
In the future, we plan to continue our work with a comparative analysis of RAPL performance in
Haswell and Skylake.
REFERENCES
[1] VMSTAT. Retrieved from http://www.linuxcommand.org/man_pages/vmstat8.html.
[2] David Abdurachmanov, Peter Elmer, Giulio Eulisse, Robert Knight, Tapio Niemi, Jukka K. Nurminen, Filip Nyback,
Goncalo Pestana, Zhonghong Ou, and Kashif Nizam Khan. 2014. Techniques and tools for measuring energy eciency
of scientic software applications. CoRR abs/1410.3440 (2014). Retrieved from http://arxiv.org/abs/1410.3440.
[3] Xi Chen, Chi Xu, Robert P. Dick, and Zhuoqing Morley Mao. 2010. Performance and power modeling in a multi-
programmed multi-core environment. In Proceedings of the 47th Design Automation Conference (DAC’10).ACM,New
York, NY, 813–818. DOI: http://dx.doi.org/10.1145/1837274.1837479
[4] CSC. 2017. Taito supercluster. Retrieved from https://research.csc./taito-supercluster.
[5] Howard David, Eugene Gorbatov, Ulf R. Hanebutte, Rahul Khanna, and Christian Le. 2010. RAPL: Memory power
estimation and capping. In Proceedings of the 16th ACM/IEEE International Symposium on Low Power Electronics and
Design (ISLPED’10). ACM, New York, NY, 189–194. DOI: http://dx.doi.org/10.1145/1840845.1840883
[6] Spencer Desrochers, Chad Paradis, and Vincent M. Weaver. 2016. A validation of DRAM RAPL power measurements.
In Proceedings of the 2nd International Symposium on Memory Systems (MEMSYS’16). ACM, New York, NY, 455–470.
DOI: http://dx.doi.org/10.1145/2989081.2989088
[7] Mohammed El Mehdi Diouri, Manuel F. Dolz, Olivier Glück, Laurent Lefèvre, Pedro Alonso, Sandra Catalán, Rafael
Mayo, and Enrique S. Quintana-Ortí. 2014. Assessing power monitoring approaches for energy and power analysis
of computers. Sustain. Comput.: Informat. Syst. 4, 2 (2014), 68–82.
[8] Jack Dongarra, Hatem Ltaief, Piotr Luszczek, and Vincent M. Weaver. 2012. Energy footprint of advanced dense
numerical linear algebra using tile algorithms on multicore architectures. In Proceedings of the 2012 2nd International
Conference on Cloud and Green Computing (CGC’12). IEEE, 274–281.
[9] Amazon EC2. Instance Types. Retrieved from https://aws.amazon.com/ec2/instance-types/.
[10] S. Agostinelli et al. 2003. Geant4- A simulation toolkit. Nucl.Instrum.MethodsPhys.Res.Sec.A:Accel.Spectrom.Detect.
Assoc. Equip. 506, 3 (2003), 250–303.
[11] Daniel Hackenberg, Thomas Ilsche, Robert Schone, Daniel Molka, Maik Schmidt, and Wolfgang E Nagel. 2013. Power
measurement techniques on standard compute nodes: A quantitative comparison. In Proceedings of the 2013 IEEE
International Symposium on Performance Analysis of Systems and Software (ISPASS’13). IEEE, 194–204.
[12] Daniel Hackenberg, Robert Schöne, Thomas Ilsche, Daniel Molka, Joseph Schuchart, and Robin Geyer. 2015. An en-
ergy eciency feature survey of the intel haswell processor. In Proceedings of the International Parallel and Distributed
Processing Symposium (IPDPS’15).
[13] D. Hackenberg, R. Schöne, T. Ilsche, D. Molka, J. Schuchart, and R. Geyer. 2015. An energy eciency feature survey of
the intel haswell processor. In Proceedings of the 2015 IEEE International Parallel and Distributed Processing Symposium
Workshop. 896–904. DOI: http://dx.doi.org/10.1109/IPDPSW.2015.70
[14] Marcus Hähnel, Björn Döbel, Marcus Völp, and Hermann Härtig. 2012. Measuring energy consumption for short
code paths using RAPL. ACM SIGMETRICS Perform. Eval. Rev. 40, 3 (2012), 13–17.
[15] Mikael Hirki. 2015. Energy and Performance Proling of Scientic Computing. Master’s thesis. Aalto University.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
RAPL in Action: Experiences in Using RAPL for Power Measurements 9:25
[16] Mikael Hirki. 2017. RAPL Testing and Instruction Decoder Benchmarks. Retrieved from https://github.com/mhirki/
idq-bench2.
[17] Mikael Hirki, Zhonghong Ou, Kashif Nizam Khan, Jukka K Nurminen, and Tapio Niemi. 2016. Empirical study of
the power consumption of the x86-64 instruction decoder. In Proceedings of the USENIX Workshop on Cool Topics on
Sustainable Data Centers (CoolDC’16). USENIX Association.
[18] Song Huang, Michael Lang, Scott Pakin, and Song Fu. 2015. Measurement and characterization of haswell power and
energy consumption. In Proceedings of the 3rd International Workshop on Energy Ecient Supercomputing (E2SC’15).
ACM, New York, NY. DOI: http://dx.doi.org/10.1145/2834800.2834807
[19] T. Ilsche, D. Hackenberg, S. Graul, R. Schöne, and J. Schuchart. 2015. Power measurements for compute nodes: Im-
proving sampling rates, granularity and accuracy. In Proceedings of the 2015 6th International Green and Sustainable
Computing Conference (IGSC’15).18.DOI: http://dx.doi.org/10.1109/IGCC.2015.7393710
[20] Intel Corporation 2015. Intel® 64 and IA-32 Architectures Software Developer’s Manual, Volume 3, System Programming
Guide. Intel Corporation.
[21] R. Kavanagh, D. Armstrong, and K. Djemame. 2016. Accuracy of energy model calibration with IPMI. In Proceedings
of the 2016 IEEE 9th International Conference on Cloud Computing (CLOUD’16). 648–655. DOI: http://dx.doi.org/10.
1109/CLOUD.2016.0091
[22] Jaimie Kelley, Christopher Stewart, Devesh Tiwari, and Saurabh Gupta. 2016. Adaptive power proling for many-core
HPC architectures. In Proceedings of the International Conference on Autonomic Computing.
[23] K. N. Khan, F. Nybäck, Z. Ou, J. K. Nurminen, T. Niemi, G. Eulisse, P. Elmer, and D. Abdurachmanov. 2015. Energy
proling using IgProf. In Proceedings of the 2015 15th IEEE/ACM International Symposium on Cluster, Cloud and Grid
Computing. 1115–1118. DOI: http://dx.doi.org/10.1109/CCGrid.2015.118
[24] Kashif Nizam Khan, Zhonghong Ou, Mikael Hirki, Jukka K. Nurminen, and Tapio Niemi. 2016. How much power
does your server consume? Estimating wall socket power using RAPL measurements. Comput. Sci. Res. Dev. 31, 4
(2016), 207–214. DOI: http://dx.doi.org/10.1007/s00450-016- 0325-4
[25] R. Khanna, F. Zuhayri, M. Nachimuthu, C. Le, and M. J. Kumar. 2011. Unied extensible rmware interface: An
innovative approach to DRAM power control. In Proceedings of the 2011 International Conference on Energy Aware
Computing.16.DOI: http://dx.doi.org/10.1109/ICEAC.2011.6136703
[26] Gary Lawson, Masha Sosonkina, and Yuzhong Shen. 2015. Towards modeling energy consumption of Xeon Phi.
arXiv:1505.06539 (2015).
[27] H. Liu. 2011. A measurement study of server utilization in public clouds. In Proceedings of the 2011 IEEE 9th Interna-
tional Conference on Dependable, Autonomic and Secure Computing. 435–442. DOI: http://dx.doi.org/10.1109/DASC.
2011.87
[28] Ioannis Manousakis, Foivos S. Zakkak, Polyvios Pratikakis, and Dimitrios S. Nikolopoulos. 2015. TProf: An en-
ergy proler for task-parallel programs. Sustainable Computing: Informatics and Systems 5 (2015), 1–13. http://www.
sciencedirect.com/science/article/pii/S2210537914000390.
[29] John D. McCalpin. 1995. Memory bandwidth and machine balance in current high performance computers. IEEE
Comput. Soc. Tech. Committee Comput. Architect. (TCCA) Newsletter (Dec. 1995), 19–25.
[30] John C. McCullough, Yuvraj Agarwal, Jaideep Chandrashekar, Sathyanarayan Kuppuswamy, Alex C. Snoeren, and
Rajesh K. Gupta. 2011. Evaluating the eectiveness of model-based power characterization. In Proceedings of the 2011
USENIX Conference on USENIX Annual Technical Conference (USENIXATC’11). USENIX Association, Berkeley, CA,
12–12. Retrieved from DOI: http://dl.acm.org/citation.cfm?id=2002181.2002193.
[31] C. Möbius, W. Dargie, and A. Schill. 2014. Power consumption estimation models for processors, virtual machines, and
servers. IEEE Trans. Parallel Distrib. Syst. 25, 6 (June 2014), 1600–1614. DOI: http://dx.doi.org/10.1109/TPDS.2013.183
[32] Chad M. Paradis. 2015. Detailed Low-cost Energy and Power Monitoring of Computing Systems. Master’s thesis. Uni-
versity of Maine.
[33] Tapasya Patki, David K. Lowenthal, Barry Rountree, Martin Schulz, and Bronis R. de Supinski. 2013. Exploring
hardware overprovisioning in power-constrained, high performance computing. In Proceedings of the 27th Inter-
national ACM Conference on International Conference on Supercomputing (ICS’13). ACM, New York, NY, 173–182.
DOI:http://dx.doi.org/10.1145/2464996.2465009
[34] Plugwise. 2017. Energy management systems of the 21st century. Retrieved from https://www.plugwise.com/.
[35] Harald Servat, Germán Llort, Judit Giménez, and Jesús Labarta. 2016. Detailed and simultaneous power and perfor-
mance analysis. Concurrency and Computation: Practice and Experience 28, 2 (2016), 252–273.
[36] A. Skrenes and C. Williamson. 2016. Experimental calibration and validation of a speed scaling simulator. In Proceed-
ings of the 2016 IEEE 24th International Symposium on Modeling, Analysis and Simulation of Computer and Telecom-
munication Systems (MASCOTS’16). 105–114. DOI:http://dx.doi.org/10.1109/MASCOTS.2016.49
[37] Balaji Subramaniam and Wu-chun Feng. 2015. On the energy proportionality of scale-out workloads. CoRR
abs/1501.02729 (2015). Retrieved from DOI: http://arxiv.org/abs/1501.02729.
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
9:26 K. N. Khan et al.
[38] Balaji Subramaniam and Wu-chun Feng. 2013. Towards energy-proportional computing for enterprise-class server
workloads. In Proceedings of the 4th ACM/SPEC International Conference on Performance Engineering (ICPE’13).ACM,
New York, NY, 15–26. DOI:http://dx.doi.org/10.1145/2479871.2479878
[39] Vincent Weaver. 2015. rapl-read.c. Retrieved from http://web.eece.maine.edu/ vweaver/projects/rapl/rapl-read.c.
[40] V. M. Weaver, M. Johnson, K. Kasichayanula, J. Ralph, P. Luszczek, D. Terpstra, and S. Moore. 2012. Measuring energy
and power with PAPI. In Proceedings of the 2012 41st International Conference on Parallel Processing Workshops. 262–
268. DOI:http://dx.doi.org/10.1109/ICPPW.2012.39
[41] Vincent M. Weaver, Matt Johnson, Kiran Kasichayanula, James Ralph, Piotr Luszczek, Dan Terpstra, and Shirley
Moore. 2012. Measuring energy and power with PAPI. In Proceedings of the 2012 41st International Conference on
Parallel Processing Workshops (ICPPW’12). IEEE Computer Society, Washington, DC, 262–268. DOI:http://dx.doi.org/
10.1109/ICPPW.2012.39
[42] Simon N. Wood. 2017. Generalized Additive Models: An Introduction with R. CRC Press.
[43] Yan Zhai, Xiao Zhang, Stephane Eranian, Lingjia Tang, and Jason Mars. 2014. HaPPy: Hyperthread-aware power
proling dynamically. In Proceedings of the 2014 USENIX Annual Technical Conference (USENIXATC’14). USENIX As-
sociation, Philadelphia, PA, 211–217.
[44] Huazhe Zhang and Henry Homann. 2015. A quantitative evaluation of the RAPL power control system. In Proceed-
ings of the 10th International Workshop on Feedback Computing.
[45] Huazhe Zhang and Henry Homann. 2016. Maximizing performance under a power cap: A comparison of hard-
ware, software, and hybrid techniques. In Proceedings of the 21st International Conference on Architectural Sup-
port for Programming Languages and Operating Systems (ASPLOS’16). ACM, New York, NY, 545–559. DOI:http://
dx.doi.org/10.1145/2872362.2872375
Received June 2017; revised October 2017; accepted January 2018
ACM Trans. Model. Perform. Eval. Comput. Syst., Vol. 3, No. 2, Article 9. Publication date: March 2018.
... We use Intel's RAPL monitoring interface [23,27,55] to measure the SoC (package) and DRAM power consumption. Next, we discuss the two configurations we use to determine each one of the four power deltas between PC1A and PC6. ...
... To keep uncore power consumption similar in the two configurations, we disable uncore power savings techniques such as package C6, DRAM opportunistic self-refresh (OSR) , memory power-down (CKE off), uncore frequency scaling [20,26,57]. We measure the power of the two configurations using RAPL.Package [23,27,55] 9 and calculate the difference. Our measurements shows that P cores_di f f ≈ 12.1W P IOs_diff and P dram_diff : The IOs power includes PCIe, DMI, UPI, and memory controllers and their corresponding physical layers (PHYs) but it does not include the devices' (e.g., DRAM) power. ...
... To place the system in these power modes, we use BIOS configurations to i) place the cores in core CC6 and set the package C-state limit to PC2 to allow the IOs to enter to local power mode but prevent the system from entering PC6 [34], ii) set the PCIe/DMI/UPI active state power management to L0s/L0s/L0p for the first configuration and to L1/L1/L1 for the second configuration [57], and iii) configure the memory to enter power-down (CKE off) and opportunistic self refresh (OSR) [20,26,57] for the first and second configuration, respectively. To obtain P IOs_di f f (P dram_di f f ) we measure the power of the two configurations using RAPL.Package (RAPL.DRAM) [23,27,55] and calculate the difference.Our measurements shows that P IOs_di f f ≈ 3.5W and P dram_di f f ≈ 1.1W P PLLs_diff : All PLLs are on in PC1A, but off in PC6. We estimate the PLLs power consumption difference between our new PC1A and PC6, denoted by P PLLs_di f f , by: number of system PLLs times a PLL power. ...
Preprint
Full-text available
This paper presents the design of AgilePkgC (APC): a new C-state architecture that improves the energy proportionality of servers that operate at low utilization while running microservices of user-facing applications. APC targets the reduction of power when all cores are idle in a shallow C-state, ready to transition back to service. In particular, APC targets the power of the resources shared by the cores (e.g., LLC, network-on-chip, IOs, DRAM) which remain active while no core is active to use them. APC realizes its objective by using low-overhead hardware to facilitate sub-microsecond entry/exit latency to a new package C-state and judiciously selecting intermediate power modes for the different shared resources that offer fast transition and, yet, substantial power savings. Our experimental evaluation supports that APC holds the potential to reduce server power by up to 41% with a worst-case performance degradation of less than 0.1% for several representative workloads. Our results clearly support the research and development and eventual adoption of new deep and fast package C-states, like APC, for future server CPUs targeting datacenters running microservices.
... The powercap interface includes multiple power capping drivers and tools, such as Intel Running Power Average Limit (RAPL), and Idle Injection. The Intel RAPL tool was first introduced for Intel Sandy Bridge architecture [27] that allows to monitor and control several energy/power consumption attributes from different power zones. The RAPL interface groups the entire processor in four power domains and allows to control/monitor power attributes in the individual domains. ...
Preprint
Full-text available
Microarchitectural attacks have become more threatening the hardware security than before with the increasing diversity of attacks such as Spectre and Meltdown. Vendor patches cannot keep up with the pace of the new threats, which makes the dynamic anomaly detection tools more evident than before. Unfortunately, previous studies utilize hardware performance counters that lead to high performance overhead and profile limited number of microarchitectural attacks due to the small number of counters that can be profiled concurrently. This yields those detection tools inefficient in real-world scenarios. In this study, we introduce MAD-EN dynamic detection tool that leverages system-wide energy consumption traces collected from a generic Intel RAPL tool to detect ongoing anomalies in a system. In our experiments, we show that CNN-based MAD-EN can detect 10 different microarchitectural attacks with a total of 15 variants with the highest F1 score of 0.999, which makes our tool the most generic attack detection tool so far. Moreover, individual attacks can be distinguished with a 98% accuracy after an anomaly is detected in a system. We demonstrate that MAD-EN introduces 69.3% less performance overhead compared to performance counter-based detection mechanisms.
Article
Time series analysis (TSA) comprises methods for extracting information in domains as diverse as medicine, seismology, speech recognition and economics. Matrix Profile (MP) is the state-of-the-art TSA technique, which provides the most similar neighbor to each subsequence of the time series. However, this computation requires a huge amount of floating-point (FP) operations, which are a major contributor (≈ 50%) to the energy consumption in modern computing platforms. In this sense, Transprecision Computing has recently emerged as a promising approach to improve energy efficiency and performance by using fewer bits in FP operations while providing accurate results. In this work, we present TraTSA, the first transprecision framework for efficient time series analysis based on MP. TraTSA allows the user to deploy a high-performance and energy-efficient computing solution with the exact precision required by the TSA application. To this end, we first propose implementations of TraTSA for both commodity CPU and FPGA platforms. Second, we propose an accuracy metric to compare the results with the double-precision MP. Third, we study MP’s accuracy when using a transprecision approach. Finally, our evaluation shows that, while obtaining results accurate enough, the FPGA transprecision MP (i) is 22.75× faster than a 72-core server, and (ii) the energy consumption is up to 3.3× lower than the double-precision executions.
Article
Parallel applications often rely on work stealing schedulers in combination with fine-grained tasking to achieve high performance and scalability. However, reducing the total energy consumption in the context of work stealing runtimes is still challenging, particularly when using asymmetric architectures with different types of CPU cores. A common approach for energy savings involves dynamic voltage and frequency scaling (DVFS) wherein throttling is carried out based on factors like task parallelism, stealing relations, and task criticality. This article makes the following observations: (i) leveraging DVFS on a per-task basis is impractical when using fine-grained tasking and in environments with cluster/chip-level DVFS; (ii) task moldability, wherein a single task can execute on multiple threads/cores via work-sharing, can help to reduce energy consumption; and (iii) mismatch between tasks and assigned resources (i.e., core type and number of cores) can detrimentally impact energy consumption. In this article, we propose EneRgy Aware SchedulEr (ERASE), an intra-application task scheduler on top of work stealing runtimes that aims to reduce the total energy consumption of parallel applications. It achieves energy savings by guiding scheduling decisions based on per-task energy consumption predictions of different resource configurations. In addition, ERASE is capable of adapting to both given static frequency settings and externally controlled DVFS. Overall, ERASE achieves up to 31% energy savings and improves performance by 44% on average, compared to the state-of-the-art DVFS-based schedulers.
Article
This paper describes the results of our measurement-based study, conducted on an Intel Core i7 processor running the SPEC CPU2017 benchmark suites, that evaluates the impact of dynamic voltage frequency scaling (DVFS) on performance (P), energy efficiency (EE), and their product (PxEE). The results indicate that the default DVFS-based power management techniques heavily favor performance, resulting in poor energy efficiency. To remedy this problem, we introduce, implement, and evaluate four DVFS-based power management techniques driven by the following metrics derived from the processor's performance monitoring unit: (i) the total pipeline slot stall ratio (FS-PS), (ii) the total cycle stall ratio (FS-TS), (iii) the total memory-related cycle stall ratio (FS-MS), and (iv) the number of last level cache misses per kilo instructions (FS-LLCM). The proposed techniques linearly map these metrics onto the available processor clock frequencies. The experimental evaluation results show that the proposed techniques significantly improve EE and PxEE metrics compared to the existing approaches. Specifically, EE improves from 44% to 92%, and PxEE improves from 31% to 48% when all the benchmarks are considered together. Furthermore, we find that the proposed techniques are particularly effective for a class of memory-intensive benchmarks – they improve EE from 121% to 183% and PxEE from 100% to 141%. Finally, we elucidate the advantages and disadvantages of each of the proposed techniques and offer recommendations on using them.
Preprint
Full-text available
These are the proceedings of the first teacher training of the Erasmus+ project No. 2020-1-PT01-KA203-078646 -- Sustrainable. The full title of this project is Promoting Sustainability as a Fundamental Driver in Software Development Training and Education and the interested reader may know more about it at: https://sustrainable.github.io The flagship contribution is the organization of two summer schools on sustainable software production. The first summer school is moved due to the Corona pandemic. It is now scheduled for July 2022 in Rijeka, Croatia. This summer school will consist of lectures and practical work for master and PhD students in the area of computing science and closely related fields. There will be contributions from Plovdiv University, University of Ko\v{s}ice, University of Coimbra, University of Minho, E\"otv\"os Lor\'and University, University of Rijeka, Radboud University Nijmegen, University of Pula, University of Amsterdam and Babe\c{s}-Bolyai University. To prepare and streamline this summer school, the consortium organized a teacher training in Nijmegen, the Netherlands. This was an event of five full days on November 1-5, 2022 organized by Ingrid Berenbroek, Mart Lubbers and Pieter Koopman on the campus of the Radboud University Nijmegen, The Netherlands. Sustainability is one of the themes within the strategy of the Radboud University called `A Significant Impact', see https://www.ru.nl/sustainability/organisation/radboud-sustainable/. Sustainability plays an important role in education, research, and management. The contributions were reviewed and give a good overview of what can be expected from the summer school. Based on these papers and the very positive and constructive atmosphere, we expect a high quality and pleasant summer school. We are looking forward to contributing to a sustainable future.
Article
Evolutionary Algorithms (EAs) are routinely applied to solve a large set of optimization problems. Traditionally, their performance in solving those problems is analyzed using the fitness quality and computing time, and the effect of evolutionary operators on both metrics is routinely used to compare different versions of EAs. Nevertheless, scientists face nowadays the challenge of considering the energy efficiency in addition to computational time, which requires studying the energy consumption of algorithms. This paper discusses the interest of introducing power consumption as a new metric to analyze the performance of standard genetic programming (GP). Two well-studied benchmark problems are addressed on three different computing platforms, and two different approaches to measure the power consumption have been tested. Analyzing the population size, the results demonstrates its influence on the energy consumed: a non-linear relationship was found between size and energy required to complete an experiment. This analysis was extended to the cache memory and results show an exponential growth in the number of cache misses as the population size increases, which affects the energy consumed. This study shows that not only computing time or solution quality must be analyzed, but also the energy required to find a solution. Summarizing, this paper shows that when GP is applied, specific considerations on how to select parameter values must be taken into account if the goal is to obtain solutions while searching for energy efficiency. Although the study has been performed using GP, we foresee that it could be similarly extended to EAs.
Article
Adoption of renewable energy in power grids introduces stability challenges in regulating the operation frequency of the electricity grid. Thus, electrical grid operators call for provisioning of frequency regulation services from end-user customers, such as data centers, to help balance the power grid’s stability by dynamically adjusting their energy consumption based on the power grid’s need. As renewable energy adoption grows, the average reward price of frequency regulation services has become much higher than that of the electricity cost. Therefore, there is a great cost incentive for data centers to provide frequency regulation service. Many existing techniques modulating data center power result in significant performance slowdown or provide a low amount of frequency regulation provision. We present PowerMorph , a tight QoS-aware data center power-reshaping framework, which enables commodity servers to provide practical frequency regulation service. The key behind PowerMorph is using “complementary workload” as an additional knob to modulate server power, which provides high provision capacity while satisfying tight QoS constraints of latency-critical workloads. We achieve up to 58% improvement to TCO under common conditions, and in certain cases can even completely eliminate the data center electricity bill and provide a net profit.
Article
Full-text available
Full system electricity intake from the wall socket is important for understanding and budgeting the power consumption of large scale data centers. Measuring full system power, however, requires extra instrumentation with external physical devices, which is not only cumbersome, but also expensive and time consuming. To tackle this problem, in this paper, we propose to model wall socket power from processor package power obtained from the running average power limit (RAPL) interface, which is available on the latest Intel processors. Our experimental results demonstrate a strong correlation between RAPL package power and wall socket power consumption. Based on the observations, we propose an empirical power model to predict the full system power. We verify the model using multiple synthetic benchmarks (Stress-ng, STREAM), high energy physics benchmark (ParFullCMS), and non-trivial application benchmarks (Parsec). Experimental results show that the prediction model achieves good accuracy, which is maximum 5.6 % error rate.
Conference Paper
Recent Intel processors support the Running Average Power Level (RAPL) interface, which among other things provides estimated energy measurements for the CPUs, integrated GPU, and DRAM. These measurements are easily accessible by the user, and can be gathered by a wide variety of tools, including the Linux perf_event interface. This allows unprecedented easy access to energy information when designing and optimizing energy-aware code. While greatly useful, on most systems these RAPL measurements are estimated values, generated on the fly by an on-chip energy model. The values are not documented well, and the results (especially the DRAM results) have undergone only limited validation. We validate the DRAM RAPL results on both desktop and server Haswell machines, with multiple types of DDR3 and DDR4 memory. We instrument the hardware to gather actual power measurements and compare them to the RAPL values returned via Linux perf_event. We describe the many challenges encountered when instrumenting systems for detailed power measurement. We find that the RAPL results match overall energy and power trends, usually by a constant power offset. The results match best when the DRAM is being heavily utilized, but do not match as well in cases where the system is idle, or when an integrated GPU is using the memory. We also verify that Haswell server machines produce more accurate results, as they include actual power measurements gathered through the integrated voltage regulator.
Conference Paper
Power and thermal dissipation constrain multicore performance scaling. Modern processors are built such that they could sustain damaging levels of power dissipation, creating a need for systems that can implement processor power caps. A particular challenge is developing systems that can maximize performance within a power cap, and approaches have been proposed in both software and hardware. Software approaches are flexible, allowing multiple hardware resources to be coordinated for maximum performance, but software is slow, requiring a long time to converge to the power target. In contrast, hardware power capping quickly converges to the the power cap, but only manages voltage and frequency, limiting its potential performance. In this work we propose PUPiL, a hybrid software/hardware power capping system. Unlike previous approaches, PUPiL combines hardware's fast reaction time with software's flexibility. We implement PUPiL on real Linux/x86 platform and compare it to Intel's commercial hardware power capping system for both single and multi-application workloads. We find PUPiL provides the same reaction time as Intel's hardware with significantly higher performance. On average, PUPiL outperforms hardware by from 1:18-2:4 depending on workload and power target. Thus, PUPiL provides a promising way to enforce power caps with greater performance than current state-of-the-art hardware-only approaches.
Conference Paper
State of the art schedulers use workload profiles to help determine which resources to allocate. Traditionally, threads execute on every available core, but increasingly, too much power is consumed by using every core. Because peak power can occur at any point in time during the workload, workloads are commonly profiled to completion multiple times in an offline architecture. In practice, this process is too time consuming for online profiling and alternate approaches are used, such as profiling for k% of the workload or predicting peak power from similar workloads. We studied the effectiveness of these methods for core scaling. Core scaling is a technique which executes threads on a subset of available cores, allowing unused cores to enter low-power operating modes. Schedulers can use core scaling to reduce peak power, but must have an accurate profile across potential settings for number of active cores in order to know when to make this decision. We devised an accurate, fast and adaptive approach to profile peak power under core scaling. Our approach uses short profiling runs to collect instantaneous power traces for a workload under each core scaling setting. The duration of profiling varies for each power trace and depends on the desired accuracy. Compared to k% profiling of peak power, our approach reduced the profiling duration by up to 93% while keeping accuracy within 3%.
Article
Power and thermal dissipation constrain multicore performance scaling. Modern processors are built such that they could sustain damaging levels of power dissipation, creating a need for systems that can implement processor power caps. A particular challenge is developing systems that can maximize performance within a power cap, and approaches have been proposed in both software and hardware. Software approaches are flexible, allowing multiple hardware resources to be coordinated for maximum performance, but software is slow, requiring a long time to converge to the power target. In contrast, hardware power capping quickly converges to the the power cap, but only manages voltage and frequency, limiting its potential performance. In this work we propose PUPiL, a hybrid software/hardware power capping system. Unlike previous approaches, PUPiL combines hardware's fast reaction time with software's flexibility. We implement PUPiL on real Linux/x86 platform and compare it to Intel's commercial hardware power capping system for both single and multi-application workloads. We find PUPiL provides the same reaction time as Intel's hardware with significantly higher performance. On average, PUPiL outperforms hardware by from 1:18-2:4 depending on workload and power target. Thus, PUPiL provides a promising way to enforce power caps with greater performance than current state-of-the-art hardware-only approaches.
Conference Paper
Energy consumption in Cloud computing is a significant issue and affects aspects such as the cost of energy, cooling in the data center and the environmental impact of cloud data centers. Monitoring and prediction provides the groundwork for improving the energy efficiency of data centers. This monitoring however is required to be fast and efficient without unnecessary overhead. It is also required to scale to the size of a data center where measurement through directly attached Watt meters is unrealistic. This therefore requires models that translate resource utilisation into the power consumed by a physical host. These models require calibrating and are hence subject to error. We discuss the causes of error within these models, focusing upon the use of IPMI in order to gather this data. We make recommendations on ways to mitigate this error without overly complicating the underlying model. The final result of these models is a Watt meter emulator that can provide values for power consumption from hosts in the data center, with an average error of 0.20W.
Article
Power and energy are increasingly important metrics in modern computing systems. Large supercomputers utilize millions of cores and can consume as much power as a small town; monitoring and reducing power consumption is an important task. At the other extreme, power usage of embedded and mobile devices is also critically important. Battery life is a key concern in such devices; having detailed power measurement allows optimizing these devices for power as well. Current systems are not set up to allow easy power measurement. There has been much work in this area, but obtaining power readings is often expensive, intrusive, and not well validated. In this work we propose a low-cost, easy-to-use, power measurement methodology that can be used in both high-end servers and low-end embedded systems. We then validate the results gathered against existing power measurement systems. We extend the existing Linux perf utility so that it can provide real-world fine-grained power measurements, allowing users easy access to these values, enabling new advanced power optimization opportunities.
Book
The first edition of this book has established itself as one of the leading references on generalized additive models (GAMs), and the only book on the topic to be introductory in nature with a wealth of practical examples and software implementation. It is self-contained, providing the necessary background in linear models, linear mixed models, and generalized linear models (GLMs), before presenting a balanced treatment of the theory and applications of GAMs and related models. The author bases his approach on a framework of penalized regression splines, and while firmly focused on the practical aspects of GAMs, discussions include fairly full explanations of the theory underlying the methods. Use of R software helps explain the theory and illustrates the practical application of the methodology. Each chapter contains an extensive set of exercises, with solutions in an appendix or in the book’s R data package gamair, to enable use as a course text or for self-study.