ArticlePDF Available

Masonry’s Resistance to Driving Rain: Mortar Water Content and Impregnation

MDPI
Buildings
Authors:

Abstract and Figures

Alongside well-researched themes such as water and moisture, the service life and function of masonry veneers are often compromised by precipitation combined with poor design considerations, execution, and selection of materials. Little research has been carried out on the subject of the impact of mortar consistency on masonry's resistance to driving rain. Water-repellent (WR) impregnation is typically considered a quick fix when problems occur. Wall-panels of 1 m² built with different flow table values for the mortar have been tested in a driving rain chamber, where both time-lapse videos and the measuring of penetrated water are used to evaluate performance. Subsequently, the panels were impregnated with the most common types of WR products and re-tested. The analysis shows that changing the mortar mix from dry to wet can decrease the penetration of driving rain by a factor of ten. The test results presented in this article show that mortar with low water content gives a porous interfacial transition zone (ITZ), thereby increasing the rate of water penetration. The tested WRs are found to be ineffective in increasing masonry's resistance to high pressure driving rain. The results, combined with what is already known about WR treatments on masonry, call for careful consideration before applying such treatment. This proves especially true in countries with much driving rain followed by frequent freeze-thaw cycles.
Content may be subject to copyright.
buildings
Article
Masonry’s Resistance to Driving Rain: Mortar Water
Content and Impregnation
Fredrik Slapø 1, *, Tore Kvande 1, Noralf Bakken 2, Marit Haugen 2and Jardar Lohne 1
1Department of Civil and Environmental Engineering, Norwegian University of Science and
Technology (NTNU), NO-7491 Trondheim, Norway; tore.kvande@ntnu.no (T.K.); jardar.lohne@ntnu.no (J.L.)
2SINTEF Building and Infrastructure at Department Architecture, Materials and Structures,
NO-7465‘Trondheim, Norway; noralf.bakken@sintef.no (N.B.); marit.haugen@sintef.no (M.H.)
*Correspondence: slapoe@gmail.com; Tel.: +47-926-40-717
Received: 16 June 2017; Accepted: 3 August 2017; Published: 9 August 2017
Abstract:
Alongside well-researched themes such as water and moisture, the service life and
function of masonry veneers are often compromised by precipitation combined with poor design
considerations, execution, and selection of materials. Little research has been carried out on the
subject of the impact of mortar consistency on masonry’s resistance to driving rain. Water-repellent
(WR) impregnation is typically considered a quick fix when problems occur. Wall-panels of 1 m
2
built
with different flow table values for the mortar have been tested in a driving rain chamber, where
both time-lapse videos and the measuring of penetrated water are used to evaluate performance.
Subsequently, the panels were impregnated with the most common types of WR products and
re-tested. The analysis shows that changing the mortar mix from dry to wet can decrease the
penetration of driving rain by a factor of ten. The test results presented in this article show that
mortar with low water content gives a porous interfacial transition zone (ITZ), thereby increasing
the rate of water penetration. The tested WRs are found to be ineffective in increasing masonry’s
resistance to high pressure driving rain. The results, combined with what is already known about
WR treatments on masonry, call for careful consideration before applying such treatment. This proves
especially true in countries with much driving rain followed by frequent freeze-thaw cycles.
Keywords: driving rain; mortar flow; impregnation; clay brick masonry; workmanship techniques
1. Introduction
Climate changes are assumed to result in a warmer and wetter climate in Norway [
1
,
2
], leading
to an increased risk of defects and the early decay of buildings. The construction industry has a
considerable challenge in adapting buildings to the new and harsher climate. Masonry veneers are
regarded to be a long life, low maintenance façade material and thereby well adapted to a harsh
climate. However, warmer and moister conditions will lead to new challenges for the performance
of masonry within the Norwegian context [
3
], particularly related to increased amounts of rain.
This proves especially true in combination with the increased challenge posed by more frequent
freeze-thaw conditions in new regions of the country, in particular the densely populated areas around
the capital Oslo.
The increased risk of defects and early decay in buildings inflicted by the new physical conditions
caused by climate change are clearly not limited to Norway. This country, however, experiences some
challenges that are exemplary, in that they push the consequences of the changes to a conceptual and
physical endpoint. In particular, the very common (and frequent) freeze-thaw conditions generally
experienced in the coastal regions of Norway will spread, exposing huge parts of the mass of buildings
and infrastructure to new and potentially very harmful conditions. Norway, with its geographical and
Buildings 2017,7, 70; doi:10.3390/buildings7030070 www.mdpi.com/journal/buildings
Buildings 2017,7, 70 2 of 16
physical conditions, is in many respects unique, but lessons from this country will serve less exposed
countries and regions with data on how to tackle similar problems, if to a lesser degree.
Even though masonry ought to endure driving rain well over time, the extent of costly faults
and defects is discouraging. Problems are in general caused by water, or rather by the combination of
water, lack of knowledge, and poor design or execution [
4
]. Of particular consequence to the quality of
masonry is the influence of frost. Limiting the water content of masonry veneers limits the risks of
damages influenced by frost [
5
]. Masonry in Norway is especially exposed to this challenge since large
parts of the country experience very frequent freeze-thaw cycles [
5
]. Though the actual influence of
frost is not assessed in this article, frost challenges render the analysis carried out in this article, on the
permeability of masonry under driving rain conditions, crucial to the Norwegian industry.
One common measure to improve the resilience of masonry to driving rain is impregnation [
6
].
Two types of studies have been found; studies using brick or parts of bricks and studies with masonry.
When only looking at the bricks, studies generally show a good effect of impregnation with various
water-repellents [
7
,
8
], significantly slowing down water absorption into the brick, thus rendering them
more resistant to frost degradation. Studies on masonry show a potential to decrease the durability
of the treated masonry. Šadauskien
˙
e et al. [
9
] found that hydrophobic treatment was unable to
significantly reduce the water permeability of masonry, allowing water to penetrate through the brick
mortar (ITZ). This poses a problem since the treatment has reduced the vapour conductivity of the
masonry. This leads to the treated masonry failing prior to the untreated masonry during a simulated
climate load of moistening-freezing-heating cycles.
Specifications on the workmanship are equally imposed to improve the performance of masonry.
Design guidelines in Norway demand full bed and head joints in masonry, identified as the prime
factor for assuring the resistance of masonry to rain [
10
]. The main reason for this demand is the
perceived need to obtain impermeable masonry to the greatest extent possible. ‘Full’ is defined [
11
] as
85% for head joints and 90% for bed joints, with no holes in the outer half of the joints. The standard
NS 3420-N [
10
] does not, however, specify the choice of bricks or the properties of the fresh masonry
mortar to be used.
Based on the experience of the main author in this article, being an experienced practitioner in
the field, the water content in fresh masonry mortar actually found on building sites varies strongly.
The hypothesis of this article is that mortar water content is crucial to achieve high quality masonry.
This, however, seems to be a rather neglected factor in the research literature aiming to achieve high
quality masonry. To address this general challenge, we address the following research questions:
What is the influence of fresh mortar water content on the resistance to driving rain of
un-impregnated masonry?
What is the influence of impregnating masonry against driving rain?
To address the first of these questions, four panels were tested. The panels varied with respect to
the water content of the mortar used (dry, medium, wet) and the workmanship techniques (panels
built with the wet mortar were built with two separate techniques). To address the second, the same
panels underwent impregnation prior to retesting in order to assess the potential for improving the
driving rain resistance of masonry using impregnation.
2. Theoretical Framework
2.1. Principal Function of Masonry Veneer: Common Practice in Norway
Bricks are commonly used as non-structural veneers, where their function is to protect buildings
from wind, rain, and sun. Loading is mostly limited to self-weight, wind, and thermal expansion
loads. Brick veneers are normally half a brick thick and water permeable. Water that penetrates the
veneer is drained down the backside of the bricks and out through weep holes. The weep holes also
provide some ventilation of the air gap and help to dry the wall. Stiff mineral wool insulation plates
Buildings 2017,7, 70 3 of 16
are designed for masonry veneers. The arrangement of bricks stopping most of the rain combined
with a vented and drained cavity before the wind barrier complies with the dual layer climate screen
principle; see Figure 1[12].
Buildings 2017, 7, 70 3 of 16
provide some ventilation of the air gap and help to dry the wall. Stiff mineral wool insulation plates
are designed for masonry veneers. The arrangement of bricks stopping most of the rain combined
with a vented and drained cavity before the wind barrier complies with the dual layer climate screen
principle; see Figure 1 [12].
Figure 1. Masonry veneer: principal function.
The specificities of the traditional Norwegian manner of constructing masonry buildings helps,
effectively, to surpass the problem of flooding caused by an excess of rain. In Figure 1, a principle
outline of a traditional masonry structure is illustrated. In this, the masonry structure is lifted from
the ground, whilst sub-terrain structures are typically constructed in concrete, separated by a
moisture barrier.
There are no explicit requirements to the degree of water-tightness of masonry veneers in
Norway. Full bed and head joints are required [12], and the recommended workmanship technique
to ensure full head joints is to butter the head of the brick prior to laying [13].
2.2. Driving Rain in Norway
Driving rain is rain driven by winds to fall at an angle, allowing it to hit vertical surfaces. Factors
like local conditions affecting the wind, mountains, and fjords or buildings can cause large
precipitation variations [14]. The driving rain map of Norway (Figure 2) is based on long term
averaged values and is representative of long term events such as the accumulation of moisture in
porous materials [3]. The map presents the amounts of annual driving rain (illustrated with a colour
scale) from the main wind direction (indicated with arrows) that gives the highest amounts of driving
rain at each observing station.
Figure 1. Masonry veneer: principal function.
The specificities of the traditional Norwegian manner of constructing masonry buildings helps,
effectively, to surpass the problem of flooding caused by an excess of rain. In Figure 1, a principle
outline of a traditional masonry structure is illustrated. In this, the masonry structure is lifted
from the ground, whilst sub-terrain structures are typically constructed in concrete, separated by
a moisture barrier.
There are no explicit requirements to the degree of water-tightness of masonry veneers in Norway.
Full bed and head joints are required [
12
], and the recommended workmanship technique to ensure
full head joints is to butter the head of the brick prior to laying [13].
2.2. Driving Rain in Norway
Driving rain is rain driven by winds to fall at an angle, allowing it to hit vertical surfaces.
Factors like local conditions affecting the wind, mountains, and fjords or buildings can cause large
precipitation variations [
14
]. The driving rain map of Norway (Figure 2) is based on long term
averaged values and is representative of long term events such as the accumulation of moisture in
porous materials [
3
]. The map presents the amounts of annual driving rain (illustrated with a colour
scale) from the main wind direction (indicated with arrows) that gives the highest amounts of driving
rain at each observing station.
Buildings 2017,7, 70 4 of 16
Buildings 2017, 7, 70 4 of 16
Figure 2. Annual precipitation and driving rain map of Norway for the normal period from 1961 to
1990. Raw data provided in [15].
2.3. Defects in Masonry
Masonry veneers are designed to withstand harsh climate conditions even if they are not
watertight, provided they are designed and built correctly. Even so, there are costly and unnecessary
defects to both new and old masonry veneers in Norway today. Most of these defects (up to 80%) [16]
are related to moisture. Defects vary and are often caused by a combination of factors. Kvande and
Lisø [16] have categorized the defects of masonry in Norway from 1983 to 2002. In this categorization,
they found ‘deficient rain barrier’ to be the main cause in 14% of the cases and ‘lack of compatibility
(adhesion)’ in 6%. These two categories amount to a total of 20% and are regarded by the authors to
be directly related to the scope of this article. Other common causes of defects regarded to be
indirectly related are ‘deficient flashing’, ‘insufficient durability of masonry units’, ‘deficient drainage
of the wall’, ‘reinforcement corrosion’, ‘aesthetic problems’, and ‘salt eruption’. These indirect causes
amount to a total of 39% of the defects.
2.4. Clay Brick Masonry Resistance to Driving Rain
There are three ways for water to penetrate a sound brick wall: through the bricks, through the
mortar, or through the brick mortar interfacial transition zone (ITZ). According to Groot and
Gunneweg [17], the main ways are through the bricks for high suction (high initial rate of absorption
(IRA)) bricks and the ITZ for low to moderate suction bricks. Water-penetration and bond are closely
related. Goodwin and West [18] report that researchers, when investigating the bond, often test
water-penetration and use the indirect values as an indication of bond strength. If the bond has a
strong correlation to the water-penetration, then the water-penetration also has a strong correlation
to the bond. Groot and Gunneweg [17] also state that hydraulic mortar has significantly improved
the barrier effect, compared to mortars lacking hydraulic components.
Figure 2.
Annual precipitation and driving rain map of Norway for the normal period from 1961
to 1990. Raw data provided in [15].
2.3. Defects in Masonry
Masonry veneers are designed to withstand harsh climate conditions even if they are not
watertight, provided they are designed and built correctly. Even so, there are costly and unnecessary
defects to both new and old masonry veneers in Norway today. Most of these defects (up to 80%) [
16
]
are related to moisture. Defects vary and are often caused by a combination of factors. Kvande and
Lisø [
16
] have categorized the defects of masonry in Norway from 1983 to 2002. In this categorization,
they found ‘deficient rain barrier’ to be the main cause in 14% of the cases and ‘lack of compatibility
(adhesion)’ in 6%. These two categories amount to a total of 20% and are regarded by the authors to be
directly related to the scope of this article. Other common causes of defects regarded to be indirectly
related are ‘deficient flashing’, ‘insufficient durability of masonry units’, ‘deficient drainage of the
wall’, ‘reinforcement corrosion’, ‘aesthetic problems’, and ‘salt eruption’. These indirect causes amount
to a total of 39% of the defects.
2.4. Clay Brick Masonry Resistance to Driving Rain
There are three ways for water to penetrate a sound brick wall: through the bricks, through
the mortar, or through the brick mortar interfacial transition zone (ITZ). According to Groot and
Gunneweg [
17
], the main ways are through the bricks for high suction (high initial rate of absorption
(IRA)) bricks and the ITZ for low to moderate suction bricks. Water-penetration and bond are closely
related. Goodwin and West [
18
] report that researchers, when investigating the bond, often test
water-penetration and use the indirect values as an indication of bond strength. If the bond has a
strong correlation to the water-penetration, then the water-penetration also has a strong correlation to
the bond. Groot and Gunneweg [
17
] also state that hydraulic mortar has significantly improved the
barrier effect, compared to mortars lacking hydraulic components.
2.5. The Influence of Mortar Water Content on Driving Rain Resistance
Bowler et al. [
19
] found that mortar cohesivity strongly correlated with rain penetration. The more
cohesive the mortar, the better the resistance to the penetration of water. Mortar cohesivity is defined
Buildings 2017,7, 70 5 of 16
as the mortar’s ability to hold together and to stick to various surfaces. Bowler judged the cohesivity
of the mortar by the use of a flow table, wherein a smaller spread (for a constant consistency) indicated
more cohesivity. The consistency was measured by a plunger test.
Internationally, no articles addressing the specific question of the influence of water content
in mortar on the water permeability of masonry veneers has been identified through the literature
review preceding the research presented in this article. Baker [
20
], however, analyzed the effect mortar
flow has on the bond strength of brickwork. They concluded that ‘[t]he flow of mortar is a sensitive
and important parameter influencing the flexural-bond strength of brickwork. Maximum strength is
obtained with mortars of wettest workable consistency’ (p. 86). This analysis lies, in fact, very close
to the research reported on in this article. Baker [
20
] uses, however, terms like ‘the wettest workable
mix’ and ‘the driest workable mix’ without reporting on the specific flow of the mortar employed.
In addition, the IRA of the brick used by Baker [
20
] is high (3.2 kg/m
2
/min). These analyses do not
address questions concerning resistance to rain penetration and deviate from the most common brick
properties within the Norwegian context (IRA approx. 1.0 kg/m2/min.).
A recent study by Costigan and Pavia [
21
] uses bricks with an IRA of 1.0 kg/m
2
/min; that is,
similar to Norwegian conditions. Their findings and conclusions none the less coincide with those of
Baker [
20
]. Costigan and Pavia [
21
] focused on low-flow valued difference mortars (165 mm versus
170 mm flow). The analysis presented lacks, however, any operational analysis of what the actual flow
variation can be in workplace conditions. In addition, their analysis focused on lime-based mortar
and not on cement-based mortar (being most commonly used within the Norwegian Architecture,
Engineering and Construction (AEC) Industry). Neither do they consider resistance to rain.
2.6. The Influence of Impregnation of Clay Brick Masonry on Driving Rain Resistance
As mentioned in the introduction, water repellents seem to work well with bricks (masonry
units). Masonry (structurally assembled) with cracks and pores on the other hand is problematic.
Water-repellent (WR) treatments are non-film and non-crack-bridge forming. As early as 1963,
Hutcheon [
22
] concluded that silicone masonry water repellents are unable to prevent water from
entering though cracks and large pores. Equally, he maintained that the rate of evaporation may
decrease and walls could be worse off with regard to freeze-thaw cycles. The conclusion that
impregnation could be destructive has since been shared in full or partially by others [
9
,
23
,
24
]. Table 1
provides an overview of four common types of WR impregnation products.
Table 1. Types of water-repellent impregnation.
Water Repellent Water Vapour
Transmission
Water
Repellence
Service
Life Years Characteristic
Silicone (resins) Fair [23] Varies [23] 1 [23]
Low resistance to alkaline building materials [
25
]
Silane Very good [23] Very good [23] 10+ [23]
Highly volatile. Reacts with moisture to form its
water repellent characteristics.
Composed of smaller molecules and, therefore,
can penetrate deeper into the masonry. Alkali
resistant. Effectiveness depends on the presence
of alkaline materials [25]
Siloxane Very good [23] Very good [23] 10+ [23]
Contains a built-in catalyst, reducing
dependency on alkaline materials for
effectiveness. Can penetrate deeply into the
masonry substrate. Evaporates slower than
silanes [25]
Nano Excellent [26] Very good [26] N/A
Show similar properties as traditional
silane-siloxane products with respect to reducing
water ingress. Affect drying of the material much
less than traditional products [26]
Buildings 2017,7, 70 6 of 16
2.7. Knowledge Gap
Some studies have been carried out on different mortar and brick qualities. None have been
identified, however, that consider the relationship between water content in fresh mortar and resistance
to driving rain. Equally, the influence of impregnation to driving rain resistance seems to have been
little scrutinized. For impregnation, the effect on bricks and mortar is known, also with regards to
durability (especially under freeze-thaw conditions). The rain penetration resistance of veneers before
and after impregnation seems, however, to have been largely unscrutinised. The study reported on in
this paper addresses precisely these knowledge gaps.
3. Materials and Methods
3.1. Material Selection and Properties
Mortar and bricks were selected to best represent a typical Norwegian brick veneer wall.
The mortar is a Portland cement (with some lime for workability) named Weber M5. This is the
most used mortar in Norway. The bricks are Haga red perforated clay bricks from Wienerberger.
Impregnation was chosen to test the four principal types of masonry water-repellent (WR) treatment,
notably silicone, silane, siloxane, and nano-particulate. The materials are presented in Tables 2and 3.
Table 2. Masonry materials.
Material Name Producer Details
Clay brick Haga red Wienerberger WA 8% [27], IRA 1.0 kg/m2/min *
Masonry mortar M5 Weber Portland Cement 11.7%, Lime 1–5%, Filler 11.4%,
Chemicals 0.5% Natural sand 0–2 mm 60–100% [28,29]
* Water absorption (WA )is a declared valuel the initial rate of absorption (IRA) was measured.
Table 3. Water-repellent impregnation materials.
Material Name Producer
Silicone WR Aquasil Hey’di
Silane WR Planisil WR-100 Mapei
Siloxane WR 1..2..fugeimpreg Mira
Waterbased nano WR SurfaPore C SurfaProducts Scandinavia
3.2. Building and Impregnation of Panels
Four panels were built with different mortar flow and workmanship techniques as variables.
Panels named A, B, and C were built using low, medium, and high water content mortar. The cases
addressed in this article all fall within the recommendations of the mortar producer. The range of
mortar consistency is thus not arbitrary but follows accepted standards. The factor of driving rain
penetration is thus generalizable.
The building of A, B, and C was done using the recommended workmanship technique of
buttering. Panel D was built with high water content like C but with another workmanship technique,
notably that of pushing head joints. Different batches of the same mortar gave considerable variation
in consistency with precisely the same dry mortar to water ratio. Therefore, even though water content
was the variable we wanted to investigate, the mortar was judged by consistency, i.e., the flow table
value rather than the amount of water. The flow value of the panels were A 135 mm, B 174 mm,
C and D 186 mm. Thus, water content, flow and consistency can be seen as synonymous in the
following. This might not be the case in other study designs since mortar composition or additives
can change the consistency while keeping water content constant. Also, consistency could include
properties of the mortars rheology other than only the flow table value.
Buildings 2017,7, 70 7 of 16
The panels tested were 990 mm
×
990 mm. The exposed front of the panels after mounting in
frames was 950 mm
×
950 mm; the joints were on average 13 mm for both bed and head joints, with a
brushed concave finish. Bricks for adjustment were cut with a mason’s brick chisel. The construction
of the panels was carried out in order to simulate real on-site conditions. More precisely, this means
that the panels were built between fixed corner poles from the front side only, and, after completion,
excess mortar was removed. The panels were built and cured for 28 days (27 for B and D) in laboratory
air, uncovered. The average temperature in the laboratory was 19.8
C with a standard deviation of
0.5
C, whereas the average relative humidity was 21.5%, with a standard deviation of 7.3%. After the
first round of rain testing, the panels were dried for 11 weeks and then impregnated according to the
producer’s recommendations. The panels were dried after exposure in laboratory climate conditions.
A fan (using in-situ laboratory air) was used to quicken the process. The drying period of 11 weeks
was chosen on pragmatic grounds, with the objective of rendering the specimens (the brick panels) to
the same weight as they had prior to the first rain exposure. See Table 4for details on the application
of impregnation.
Table 4. Application of impregnation.
WR Panel Coats * Drying
between Coats
Recommended
Consumption
Actual
Consumption
Aquasil A 2 2.5 h 0.2–0.4 L/m20.30 L/m2
Planisil WR-100
B 2 10 min 0.1–0.2 L/m20.15 L/m2
1..2..fugeimpreg
C 2 None 0.10–0.05 L/m20.15 L/m2
SurfaPore C D 1 - 0.13–0.10 L/m20.11 L/m2
* Both the recommended and applied number of coats.
3.3. Test Procedure NBI 29/1983
The tests were carried out in a driving rain chamber in accordance with NBI method 29/1983 [
30
]
(internal SINTEF building and infrastructure method). The panels were assembled in the opening
of the apparatus, with the exposed side facing inwards into the chamber. A joint sealant (tape) was
used to seal the joint between the chamber and the panels’ frames. A determination of driving rain
resistance was carried out according to the following exposure procedure:
The panels were subjected to five hours with a static overpressure of 750 Pa (corresponding to
wind with hurricane force) and sprayed with water 1.2 L/(m
2
min). The spraying of water was
located at the upper part of the test panels, in the third course from the top;
The panels were subjected to five hours without air pressure and with spraying water but with a
stream of air on the panel surface (fan continues to operate, cabinet is opened);
The panels were subjected to thirty-six hours with a static overpressure of 750 Pa and sprayed
with water of 1.2 L/(m2min).
The test procedure includes monitoring the panels during testing. Here the panels were
photographed every 5 min, resulting in time-lapse videos. In the testing of the unimpregnated
panels, they were monitored in person for the first two hours. In the testing of the impregnated panels,
sporadic in-person monitoring was carried out. The weighing of panels before and after was also
carried out according to the procedure.
3.4. Assessment of Water Penetration Following Driving Rain
The procedure used to assess water penetration following driving rain is not standardized or
previously described, although the collection and measuring of water that penetrates a masonry wall
has been carried out previously [
17
,
31
]. The aim was to collect solely the water that went through the
panel, avoiding water that was running down on the inside of the panel or took the shortcut around
Buildings 2017,7, 70 8 of 16
the sealant in the corners. Following visual observation of the panels being completely soaked, the
penetrating water was collected. Troughs were folded from heavy-duty aluminium foil slightly longer
than the panels, 30 mm wide and 50 mm high. They were placed underneath the backside of the panels.
See the principle cross section illustration in Figure 3. A period of 20 min was found to be the best
practical compromise between not overfilling (reducing the risk of spilling) and still having sufficient
water to minimize the measurement error by the water left in the troughs after emptying them into the
measuring cups. The amount of water was assessed in the same measuring cup. This was found to be
sufficiently accurate for comparing the different panels.
Buildings 2017, 7, 70 8 of 16
has been carried out previously [17,31]. The aim was to collect solely the water that went through the
panel, avoiding water that was running down on the inside of the panel or took the shortcut around
the sealant in the corners. Following visual observation of the panels being completely soaked, the
penetrating water was collected. Troughs were folded from heavy-duty aluminium foil slightly
longer than the panels, 30 mm wide and 50 mm high. They were placed underneath the backside of
the panels. See the principle cross section illustration in Figure 3. A period of 20 min was found to be
the best practical compromise between not overfilling (reducing the risk of spilling) and still having
sufficient water to minimize the measurement error by the water left in the troughs after emptying
them into the measuring cups. The amount of water was assessed in the same measuring cup. This
was found to be sufficiently accurate for comparing the different panels.
Figure 3. Collecting water, principal cross-section.
3.5. Thin Sections
Three thin sections (A, B, and C) of 48 mm × 28 mm were prepared from masonry built with
approximately the same flow table values (A 148 mm, B 165 mm, and C 196 mm) as for the wall
panels. The preparation of the thin sections was carried out by the Thin Section Laboratory at the
Norwegian University of Science and Technology. The preparation included fluorescence
impregnation and polishing. Microscopy analysis with UV filters was performed with Nikon,
ECLIPSE LV 100 POL, Tokyo, Japan. This analysis equally included the measurement of actual
contact between the bricks and the mortar (bond) and a visual assessment of the density of the mortar.
3.6. Influence of Workmanship
From professional experience and from the previously mentioned building site visits, it is known
that pushing the head joint is a common technique in Norway. This stands in contrast to the
recommended technique, which is to butter the end of bricks prior to laying to ensure full joints [13].
The recommended technique is used for all three mortar mixes (panels A, B, and C). To evaluate the
influence of workmanship, panel D was built by pushing the head joints. The only difference between
C and D was the technique used to fill the head joints.
4. Results
4.1. Water Penetration
Figure 3. Collecting water, principal cross-section.
3.5. Thin Sections
Three thin sections (A, B, and C) of 48 mm
×
28 mm were prepared from masonry built with
approximately the same flow table values (A 148 mm, B 165 mm, and C 196 mm) as for the wall
panels. The preparation of the thin sections was carried out by the Thin Section Laboratory at the
Norwegian University of Science and Technology. The preparation included fluorescence impregnation
and polishing. Microscopy analysis with UV filters was performed with Nikon, ECLIPSE LV 100 POL,
Tokyo, Japan. This analysis equally included the measurement of actual contact between the bricks
and the mortar (bond) and a visual assessment of the density of the mortar.
3.6. Influence of Workmanship
From professional experience and from the previously mentioned building site visits, it is
known that pushing the head joint is a common technique in Norway. This stands in contrast to the
recommended technique, which is to butter the end of bricks prior to laying to ensure full joints [
13
].
The recommended technique is used for all three mortar mixes (panels A, B, and C). To evaluate the
influence of workmanship, panel D was built by pushing the head joints. The only difference between
C and D was the technique used to fill the head joints.
Buildings 2017,7, 70 9 of 16
4. Results
4.1. Water Penetration
The main results are based on visual observations, seeing when, where, and how much water
penetrated the panels; see Figure 4. The authors recommend seeing the time-lapse videos documenting
the procedure, to which a link is included in the Supplementary Materials section. The panels were
first tested without any form of coating and later impregnated with four types of WR; see Table 3.
Buildings 2017, 7, 70 9 of 16
The main results are based on visual observations, seeing when, where, and how much water
penetrated the panels; see Figure 4. The authors recommend seeing the time-lapse videos
documenting the procedure, to which a link is included in the Supplementary Materials section. The
panels were first tested without any form of coating and later impregnated with four types of WR;
see Table 3.
Figure 4. Panels A, B, C, and D after 45 min of simulated driving rain.
First presented, in Figure 4 and in the upper part of Table 5, are the results for the untreated
panels. Panel C is clearly better than the others; in order of best to worst performance, the panels in
Figure 4 appear in the order C, B, A, and D. The first or major points of leakage seem to be somewhat
randomly distributed. Even so, some assumptions can be made from knowledge about the panels
and observation of the test. The panels were built between corner poles. Consequently, there was no
room to compress the last joint on each course. The last joint can be seen on the left (back) side of the
panels in Figure 4. All panels show signs of leaking more easily at the last joint. A corner pole or the
meting point between two masons would be the equivalent on a construction site. It also looks like
the head joints are worse than the bed joints. An exception is panel D, where the bed joints appear to
be somewhat worse than for the other panels. This implies that taking mortar from bed joints to fill
head joints has a negative impact on the bed joint.
Prior to testing, it was expected that the incomplete filling of mortar in some of the joints could
create weak points. This appears, however, not to be the case. It can be seen in Figure 4 that the joints
are not completely filled on the backside of the panels. Even by means of careful observation it was
not possible to observe any additional weakness in these areas.
From visual inspection during testing, the impregnated panels showed some resilience to the
wetting of the façade surface, confirming that they were to some degree water repellent. Table 5
shows that all panels were, in fact, more resistant to rain penetration in the early stages of the test.
Even so, both the visual results in Table 5 and the measuring of water passing through the panels in
Figure 4. Panels A, B, C, and D after 45 min of simulated driving rain.
First presented, in Figure 4and in the upper part of Table 5, are the results for the untreated
panels. Panel C is clearly better than the others; in order of best to worst performance, the panels in
Figure 4appear in the order C, B, A, and D. The first or major points of leakage seem to be somewhat
randomly distributed. Even so, some assumptions can be made from knowledge about the panels
and observation of the test. The panels were built between corner poles. Consequently, there was no
room to compress the last joint on each course. The last joint can be seen on the left (back) side of the
panels in Figure 4. All panels show signs of leaking more easily at the last joint. A corner pole or the
meting point between two masons would be the equivalent on a construction site. It also looks like the
head joints are worse than the bed joints. An exception is panel D, where the bed joints appear to be
somewhat worse than for the other panels. This implies that taking mortar from bed joints to fill head
joints has a negative impact on the bed joint.
Prior to testing, it was expected that the incomplete filling of mortar in some of the joints could
create weak points. This appears, however, not to be the case. It can be seen in Figure 4that the joints
are not completely filled on the backside of the panels. Even by means of careful observation it was
not possible to observe any additional weakness in these areas.
From visual inspection during testing, the impregnated panels showed some resilience to the
wetting of the façade surface, confirming that they were to some degree water repellent. Table 5shows
Buildings 2017,7, 70 10 of 16
that all panels were, in fact, more resistant to rain penetration in the early stages of the test. Even so,
both the visual results in Table 5and the measuring of water passing through the panels in Table 6
indicate little to no improvement in the water-tightness of the panels, stemming from impregnation
with water-repellent silicone, silane siloxane, or nanoparticulated.
Table 5. Wetting of the backside of panels [%].
Time State 1Panel A Panel B Panel C Panel D 2
D M W D M W D M W D M W
5 min 95 5 0 95 5 0 95 5 0 85 10 5
15 min 90 5 5 90
10
0 95 5 0 80 15 5
30 min 80
10
10 85
10
5 90
10
0 70 20 10
1 h 60
20
20 70
15
15 90
10
0 55 25 20
2 h 25
40
35 50
30
20 85
10
5 40 30 30
5 h 15
20
65 30
45
25 65
20
15 15 15 70
<5% D 6 h 20 min 8 h 25 min 11 h 50 min 5 h 25 min
Time State 1A silicone B silane C siloxane D nano-particulate
D M W D M W D M W D M W
5 min 100 0 0 100 0 0 100 0 0 100 0 0
15 min 90 5 5 90
10
0 100 0 0 95 5 0
30 min 80
15
5 80
15
5 95 5 0 90 10 0
1 h 45
35
20 50
40
10 95 5 0 75 20 5
2 h 15
45
40 20
65
15 95 5 0 30 65 5
5 h 10
55
35 10
80
10 85
10
5 15 75 10
<5% D 36 h 30 min 7 h 25 min 13 h 0 min 5 h 45 min
1
State describes dy (no sign of moisture), moist (dark fields/spots), and wet (visible free water, shiny surface); the
values are visually derived from the time lapse videos, with accuracy limited to 5%;
2
Note that panel D has been
built by pushing the head joints, unlike the rest of the panels, wherein the mortar for the head joints was placed on
the brick prior to laying; 3Time until more than 95% of the backside surface is wet or moist.
Table 6. Water penetration towards the end of the testing.
Comments Panel A Panel B Panel C Panel D
Flow - mm 135 174 186 186
Penetration - l/h·m21.14 0.97 0.14 0.67
Water-repellent Silicone Silane Siloxane Nano-particulate
Treated penetration 1.15 1.38 0.06 0.50
Weighing before and after testing forms part of NBI method 29/1983 [
30
], and the results are
presented in Table 7. All panels were soaking wet after the completion of the test procedure so the
results do not provide much information except from the mass increase (
115 N). This accords well
with the panel size and the declared water absorption of the bricks (8% see Table 2).
Table 7. Mass gain of panels [N].
Finishing Panel A Panel B Panel C Panel D
Untreated 138 98 111 109
Impregnated 111 107 117 115
The prescribed breaking of the panels in accordance with NBI method 29/1983 [
30
], carried out to
measure how far the water has penetrated, was not carried out since the panels clearly were wet all
the way through.
Buildings 2017,7, 70 11 of 16
According to the different suppliers, all the tested WRs are supposed to be transparent and were
in fact invisible after application. After testing, it looked like all the panels had a weak brown/yellow
discoloration of the three upper joints. These joints were above the water spraying heads during
testing. Also, panel A and panel B have rust brown deposits running down their walls from some of
the ITZ between the brick and mortar; see the example in Figure 5a. A simple spray test to evaluate
water repellence was performed. All panels proved to be water repellent, and all panels absorbed
some water. Ranking the WRs from best to worst based on visual impressions gave the following
order: Nano was best, Silane and Siloxane were similar, and Silicone had the poorest performance.
Figure 5b shows a part of panel D (Nano) during spray testing.
Buildings 2017, 7, 70 11 of 16
some water. Ranking the WRs from best to worst based on visual impressions gave the following
order: Nano was best, Silane and Siloxane were similar, and Silicone had the poorest performance.
Figure 5b shows a part of panel D (Nano) during spray testing.
(a) (b)
Figure 5. (a) Rust brown deposits from the ITZs of panel B after drying; (b) Water repellency of panel D.
4.2. Microscopy Analysis of Thin Sections
The quality of the interface between the brick and the mortar differs between the three thin
sections; see Table 8. In the areas without contact, elongated air voids and some cracks were observed.
The samples made from masonry with dry and medium mortar both had one interface (brick to
mortar), loosened during the preparation of the thin sections.
Table 8. Contact in/on the brick and mortar interface.
Thin Section Dry Medium Wet
Upper ITZ of joint Fracture Fracture 35%
Lower ITZ of joint 10% 20% 50%
In the dry sample, a somewhat lower porosity can be observed in the mortar from the interface
of the brick surface to a maximum of 0.4 mm from the brick. The reason for this is most likely that the
brick has sucked water from the mortar during the hydration process. This phenomenon can hardly
be observed for the medium water content sample and not at all for the wet sample.
Figure 6 is an example of an area with good bond and where the contact zone between the mortar
(on top) and the brick (bottom, dark area) is good. Good contact between mortar and brick leaves less
pores for water to penetrate. In Figures 6 and 7, the yellow parts are air voids, filled with yellow
epoxy. Both Figures 6 and 7 are made from samples that were built using wet mortar. Figure 6
illustrates good contact between mortar and bricks. Figure 7 show large, elongated air voids in the
ITZ, where water easily can penetrate.
Figure 5.
(
a
) Rust brown deposits from the ITZs of panel B after drying; (
b
) Water repellency of panel D.
4.2. Microscopy Analysis of Thin Sections
The quality of the interface between the brick and the mortar differs between the three thin
sections; see Table 8. In the areas without contact, elongated air voids and some cracks were observed.
The samples made from masonry with dry and medium mortar both had one interface (brick to
mortar), loosened during the preparation of the thin sections.
Table 8. Contact in/on the brick and mortar interface.
Thin Section Dry Medium Wet
Upper ITZ of joint Fracture Fracture 35%
Lower ITZ of joint 10% 20% 50%
In the dry sample, a somewhat lower porosity can be observed in the mortar from the interface of
the brick surface to a maximum of 0.4 mm from the brick. The reason for this is most likely that the
brick has sucked water from the mortar during the hydration process. This phenomenon can hardly
be observed for the medium water content sample and not at all for the wet sample.
Figure 6is an example of an area with good bond and where the contact zone between the mortar
(on top) and the brick (bottom, dark area) is good. Good contact between mortar and brick leaves less
pores for water to penetrate. In Figures 6and 7, the yellow parts are air voids, filled with yellow epoxy.
Both Figures 6and 7are made from samples that were built using wet mortar. Figure 6illustrates good
Buildings 2017,7, 70 12 of 16
contact between mortar and bricks. Figure 7show large, elongated air voids in the ITZ, where water
easily can penetrate.
Buildings 2017, 7, 70 12 of 16
Figure 6. Microscopy image of a thin section; an area with good contact. The yellow parts are air voids,
whilst the white parts are aggregate, and the contact zone is the interface between the dark and the
charcoal-coloured cement paste.
Figure 7. Microscopy image of a thin section; an area with large, elongated air voids. The yellow parts
are air voids, whilst the white parts are aggregate, and the contact zone is the interface between the
dark and the charcoal-coloured cement paste.
Figure 6.
Microscopy image of a thin section; an area with good contact. The yellow parts are air voids,
whilst the white parts are aggregate, and the contact zone is the interface between the dark and the
charcoal-coloured cement paste.
Buildings 2017, 7, 70 12 of 16
Figure 6. Microscopy image of a thin section; an area with good contact. The yellow parts are air voids,
whilst the white parts are aggregate, and the contact zone is the interface between the dark and the
charcoal-coloured cement paste.
Figure 7. Microscopy image of a thin section; an area with large, elongated air voids. The yellow parts
are air voids, whilst the white parts are aggregate, and the contact zone is the interface between the
dark and the charcoal-coloured cement paste.
Figure 7.
Microscopy image of a thin section; an area with large, elongated air voids. The yellow parts
are air voids, whilst the white parts are aggregate, and the contact zone is the interface between the
dark and the charcoal-coloured cement paste.
Buildings 2017,7, 70 13 of 16
5. Discussion
The research reported on in this paper set out to find (1) the influence of fresh mortar water content
on the resistance to driving rain of un-impregnated masonry and (2) the influence of impregnating
masonry against driving rain. The following discussion is organised according to this.
5.1. The Influence of Fresh Mortar Water Content
Using wet masonry mortar has been shown to be effective in achieving good bonding between
mortar and brick, thus strongly reducing water permeability and improving the resistance to driving
rain. This appears to contradict Bowler et al. [
19
], maintaining that a smaller flow table spread would
be more resistant to driving rain penetration. By measuring flow at a constant consistency (measured
by a plunger), Bowler et al. [
19
] measured the properties of the mortar itself rather than the effect of
added water. Therefore, both conclusions could be sound, and the combined conclusion would be that
masonry mortar should have both good cohesion and a high flow value.
Placing mortar consistency in a broader context, it seems probable that changing from dry to wet
mortar would lead to reducing moisture related defects and decay, improving structural properties
and, according to the experience of the main author, an increased pace of building. The disadvantages
could be challenges in achieving aesthetic quality equal to that obtained by using dry mortar since wet
mortar increases spilling and the need for the cleaning of new walls.
According to the analysis, workmanship techniques seem to be significant. Table 5shows that
the untreated panel D had the poorest early stage performance of all panels. This is so, even if it was
built with the same wet mortar as panel C, which was the best in all aspects. This indicates that using
the recommended technique of buttering the bricks can significantly improve the masonry quality.
Due to only one panel having been built by pushing the head joint, the research reported in this
article is not sufficient to make general recommendations concerning workmanship. Einstadblad and
Westbye [
31
] found in their tests of workmanship techniques that buttering was better for red bricks
(IRA 1.0 kg/m
2
/min) but not for yellow bricks (IRA 4.0 kg/m
2
/min). Their conclusion was that the
most important factor was the mason’s professional pride or work ethic. Their masonry techniques
(especially in that the mortar used was drier than what is used in the research reported on in this
paper) differ in a manner that renders comparison challenging. None the less, we agree that these are
important factors. Even so, we maintain that knowledge about other more specific factors is equally
important. Amongst these, knowledge of mortar water content and workmanship is essential both for
practitioners seeking to deliver the best they can and for imposing quality standards.
5.2. The Influence of Impregnating Masonry
Hydrophobic impregnation reduced water penetration in all four tested WRs in the first minutes.
After this, no measurable improvement could be observed. The observed failure to reduce water
permeability could, to some extent, be due to the extreme conditions of the testing procedure, especially
the overpressure of 750 Pa (equal to hurricane wind speed). Such conditions have earlier been shown
to influence the performance of rendered masonry compared to testing without overpressure [32].
Since the WRs were tested on substantially different panels, there is no basis for the evaluation of
the different WRs against each other. The ambition here was not, however, to quantify or compare
different impregnation solutions but rather to assess the possible potential for improving the driving
rain resistance of masonry using impregnation.
Both the abilities of the specific WR and the properties of the panel could contribute to the
recorded performance. Testing WRs on similar panels with a more realistic wind load would be
beneficial in evaluating their performance. Figure 7, with large, elongated air voids of around 200
µ
m,
can explain why the WRs are unable to increase the resistance to driving rain. Impregnated veneers
allow moisture to enter and hinders it from escaping. Water retained in the masonry increases the risk
of frost deterioration, as reported by Šadauskien
˙
e et al. [
9
], and salt eruption, as described by Ioannou
Buildings 2017,7, 70 14 of 16
and Hoff [
33
]. Blom [
6
] recommend using WR impregnation on masonry veneers, stating that it will
efficiently reduce moisture in veneer walls and reduce the moisture load on the internal part of the
wall. He does, however, question the efficiency if the wall has cracks that can lead to capillary suction
of water into the wall. Based on the driving rain test and the thin section analysis, we find it reasonable
to assume that the ITZ between mortar and brick masonry does in fact have air voids that cannot be
protected from moisture ingress by applying WR impregnation.
6. Conclusions
High flow, i.e., high water content masonry mortar, strongly improves masonry veneers’ resistance
to driving rain, even for low to moderate IRA bricks. Within the workable range of mortar consistency,
more water unequivocally provides improved results. The test results presented in this article show
that mortar with low water content gives a porous ITZ, thereby increasing the rate of water penetration.
According to the test results, WR treatment cannot be expected to improve masonry veneers’
resistance to high pressure driving rain. The results reported in this article, combined with what is
already known about WR treatments on masonry, call for careful consideration before applying such
treatment. This proves especially true in Norway and other countries with much driving rain followed
by frequent freeze-thaw cycles.
Supplementary Materials:
The following are available online at www.mdpi.com/2075-5309/7/3/70/s1. Videos:
S1 Time-lapse of Untreated A and B, S2 Time-lapse of Untreated C and D, S3 Time-lapse of Silicone A and Silane
B, S4 Time-lapse of Siloxane C and Nano D.
Acknowledgments:
We would like to present our gratitude to Klima 2050 as the founding participant of the
research presented in this article. Likewise, Weber has been very welcoming. A special thanks to CAD operator
Remy Eik.
Author Contributions:
Fredrik Slapø initiated and carried out the main bulk of the research. The research has
been conducted according to his initial ideas, concerning the problem to be addressed, the research design, and
the test program. He has been responsible for the literature review and the carrying out of the main part of the
laboratory work and has been the main person responsible for drafting the article. Tore Kvande has served as
the main supervisor during the process and has, together with Noralf Bakken, contributed in the design of the
research program and in the analysis and interpretation of the results. Noralf Bakken initiated the impregnation
part of the study and has, together with Fredrik Slapø, been responsible for the performance of the rain testing.
Marit Haugen has executed the thin sections analysis. Jardar Lohne contributed to the research design and
has been responsible for an efficient scientific writing process and the analytic cohesion of the analysis. All the
co-authors have provided critical comments on the prepared manuscript by Fredrik Slapø during the process, and
they have all given final approval of the version to be published.
Conflicts of Interest: The authors declare no conflict of interest.
References
1.
IPCC. Climate Change 2014: Synthesis Report. In Contribution of Working Groups I, II and III to the Fifth
Assessment Report of the Intergovernmental Panel on Climate Change; Core Writing Team, Pachauri, R.K.,
Meyer, L.A., Eds.; IPCC: Geneva, Switzerland, 2014; p. 10.
2.
Andreassen, L.M.; Beldring, S.; Bjune, A.; Breili, K.; Dahl, C.A.; Dyrrdal, A.V.; Isaksen, K.;
Haakenstad, H.; Haugen, J.E.; Hygen, H.O.; et al. Klima i Norge 2100—Kunnskapsgrunnlag for
klimatilpasning oppdatert i 2015 (Knowledge basis for climate adaption updated version 2015).
NCCS Report No. 2/2015. Available online: https://cms.met.no/site/2/klimaservicesenteret/rapporter-og-
publikasjoner/_attachment/6616?_ts=14ff3d4eeb8 (accessed on 4 June 2017).
3.
Lisø, K.R. Building Envelope Performance Assessments in Harsh Climates: Methods for Geographically
Dependent Design. Ph.D. Thesis, Norwegian University of Science and Technology, Trondheim,
Norway, 2006.
4.
Lisø, K.R.; Kvande, T.; Thue, J.V. Learning from experience—An analysis of process induced building defects
in Norway. In Proceedings of the 3rd International Building Physics/Science Conference, Montreal, QC,
Canada, 27–31 August 2006.
5.
Lisø, K.R.; Kvande, T.; Hygen, H.O.; Thue, J.V.; Harstveit, K. A frost decay exposure index for porous,
mineral building materials. Build. Environ. 2007,42, 3547–3555. [CrossRef]
Buildings 2017,7, 70 15 of 16
6.
Blom, P. Fuktsikker innvendig etterisolering av mur- og betongvegger (Moisture safe internal insulation on
existing masonry and concrete walls). In SINTEF Fag Prosjektrapport; SINTEF: Oslo, Norway, 2014; Volume 22,
ISBN 978-82-536-1404-5.
7.
Stefanidou, M.; Karozou, A. Testing the effectiveness of protective coatings on traditional bricks.
Constr. Build. Mater. 2016,111, 482–487. [CrossRef]
8.
Defreece, N.; Charola, E. Coatings on Brick Masonry: Are They Protective or Can They Enhance
Deterioration? J. Am. Inst. Conserv. 2007,46, 39–52.
9.
Šadauskien
˙
e, J.; Ramanauskas, J.; Stankeviˇcius, V. Effect of Hydrophobic Materials on Water Impermeability
and Drying of Finish Brick Masonry. Mater. Sci. 2003,9, 94–98.
10.
NS 3420-N:2012. Specification texts for building, construction and installations Part N: Masonry and
rigid tile work. Standard, Norway, 2012. Available online: http://www.standard.no/no/Nettbutikk/
produktkatalogen/Produktpresentasjon/?ProductID=588807 (accessed on 7 August 2017).
11. Rocky Mountain Masonry Institute. Mortar Joints—How Full is Full? Masonry Tech Memo 1996,1, 1–2.
12.
Kvande, T. Murt forblending (masonry veneers). In SINTEF Building Research Design Guide 542.301; SINTEF:
Oslo, Norway, 2013.
13.
Madsø, F.E.; Wold-Hansen, G.; Høiby, A. Murkatalogen Anvisning P1 Skallmurvegger (Masonry Catalog—Guide
P1 Masonry Veneers); Mursenteret: Oslo, Norway, 1998.
14.
Blocken, B.; Carmeliet, J. A review of wind-driven rain research in building science. J. Wind Eng. Ind. Aerodyn.
2004,92, 1079–1130. [CrossRef]
15.
Kvande, T.; Lisø, K.R.; Hygen, H.O. Klimadata for dimensjonering mot regnpåkjenning (Climate data for
design to rain). In SINTEF Building Research Design Guide 451.031; SINTEF: Oslo, Norway, 2013.
16.
Kvande, T.; Lisø, K.R. Climate adapted design of masonry structures. Build. Environ.
2009
,44, 2442–2450.
[CrossRef]
17.
Groot, C.J.W.P.; Gunnweg, J.T.M. The influence of materials characteristics and workmanship on rain
penetration in historic fired clay brick masonry. Heron 2010,55, 141–153.
18.
Goodwin, F.; West, H. A Review of the Literature on Brick/Mortar Bond. In Proceedings of the British Masonry
Society, Load Bearing Brickwork (7); British Ceramic Society: Stoke-on-Trent, UK, 1982; pp. 23–37.
19.
Bowler, G.K.; Jackson, P.J.; Monk, M.G. The Role of Mortar Workability (Cohesivity) in the Rain Penetration
of Masonry. Int. Masonry Soc. 1996,10, 25.
20.
Baker, L. Some Factors Affecting the Bond Strength of Brickwork. In Proceedings of the Fifth International
Brick Masonry Conference, Washington, DC, USA, 5–10 October 1979; pp. 84–89.
21.
Costigan, A.; Pavia, S. Effect of mortar water content in the properties of masonry. In Proceedings of the 9th
International Masonry Conference, Guimarães, Portugal, 7–9 July 2014.
22. Hutcheon, N.B. Silicone Masonry Water Repellents. Natl. Res. Counc. Can. 1963. [CrossRef]
23.
Colorless Coatings for Brick Masonry. In Technical Notes on Brick Construction; The Brick Industry Association:
Reston, VA, USA, 2008; Available online: http://www.gobrick.com/portals/25/docs/technical%20notes/
tn6a.pdf (accessed on 18 May 2017).
24.
Kvande, T. Fuging og tynne overflatebehandlinger på teglfasader (Jointing and thin surface treatments
on masonry veneers). In SINTEF Building Research Design Guide 542.801; SINTEF: Oslo, Norway, 2015;
Available online: https://www.byggforsk.no/dokument/485/fuging_og_tynne_overflatebehandlinger_
paa_teglfasader (accessed on 4 June 2017).
25.
Types of Masonry Water Repellents. Available online: https://www.gsa.gov/portal/content/112042
(accessed on 18 May 2017).
26.
Lubelli, B.; van Hees, R.P.J. Evaluation of the Effect of Nano-Coatings with Water Repellent Properties on
the Absorption and Drying Behaviour of Brick. In 6th International Conference on Water Repellent Treatment of
Building Materials; Aedificatio Publishers: Freiburg, Germany, 2011; pp. 125–136. ISBN 978-3-931681-99-9.
Available online: http://www.hydrophobe.org/pdf/rome/VI_12.pdf (accessed on 09 June 2017).
27.
Wienerberger. Decleration of Performance, DoP-Number: 21115190-A1W2111; Wienerberger AB: Malmö,
Sweden, 2016.
28.
Saint-Gobain Byggevarer as (2014) NEPD00130E Rev1, weber Murmørtel M5, dry mortar. Available online:
https://www.weber-norge.no/fileadmin/user_upload/EPD/NEPD00130E_Rev1_weber_murmoertel_
M5_GODKJENT.pdf (accessed on 31 May 2017).
Buildings 2017,7, 70 16 of 16
29.
Weber Saint Gobain (2016) Decleration of Performance, Nr. DoP-NO-M418972222, Version 2.
Available online: https://www.weber-norge.no/uploads/tx_weberproductpage/dop-1_Weber_Murm_
rtel_M5.pdf (accessed on 31 May 2017).
30.
NBI 29/1983 Mørtler. Tetthet mot slagregn (Mortars. Resistance to driving rain); Norges byggforskningsinstitutt:
Oslo, Norway, 1983; pp. 75–76. ISBN 82-536-0184-0.
31.
Einstadblad, H.; Westbye, A. Murverk av tegl—Sammenheng mellom utførelse og kvalitet (Clay brick
masonry—Relations between workmanship and quality). Master Thesis, Norwegian University of Science
and Technology, Trondheim, Norway, December 1999.
32. Kvande, T.; Lisø, K.R. Regendichter Putz für gemauerte Fassaden. Das Mauerw. 2003,2, 59–65.
33.
Ioannou, I.; Hoff, W.D. Water repellent influence on salt crystallisation in masonry. Proc. Inst. Civil Eng.
Constr. Mater. 2008,161, 17–23. [CrossRef]
©
2017 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
... When wind and rain co-occur (i.e., WDR), the driving rain vector becomes oblique, and the water is transported through the wall in several different ways. While the brick-mortar interfacial zone is often cited as the primary path offering the least resistance [12,[23][24][25], other deficiencies like cracks and voids increase water penetration considerably [15,22,26,27]. ...
... Water penetration arising from WDR depends on several factors such as climate conditions (WDR intensity and wind pressure) [28,29], water flow pattern, the presence and size of openings or deficiencies [15], the type and quality of masonry units [12,30,31], the type of mortar and its consistency [12,23], the compatibility of units and mortar [12,32], joint thickness [32,33], the profile of mortar joints [33,34], and the workmanship [12,23]. Owing to the complexity of the phenomenon, there is no general agreement on how to determine the amount of water that penetrates through brick masonry claddings nor how to consider this penetration in hygrothermal analyses [10,11,28,29,35]. ...
... Water penetration arising from WDR depends on several factors such as climate conditions (WDR intensity and wind pressure) [28,29], water flow pattern, the presence and size of openings or deficiencies [15], the type and quality of masonry units [12,30,31], the type of mortar and its consistency [12,23], the compatibility of units and mortar [12,32], joint thickness [32,33], the profile of mortar joints [33,34], and the workmanship [12,23]. Owing to the complexity of the phenomenon, there is no general agreement on how to determine the amount of water that penetrates through brick masonry claddings nor how to consider this penetration in hygrothermal analyses [10,11,28,29,35]. ...
Thesis
Full-text available
Clay brick masonry façades are widely used because of their extended durability and aesthetic appeal. They also offer good protection against wind-driven rain (WDR), one of the most common moisture sources in Northern Europe. In clay brick masonry, WDR is associated with elevated water content and the possibility of water penetration, which may negatively impact the hygrothermal performance of building envelopes. Maintenance measures are thus recommended to address elevated moisture content and water penetration associated with WDR, where repointing is a commonly used maintenance technique. Presently, in Sweden, repointing is typically scheduled every 40–50 years from the construction of the building, regardless of the condition of the façade. Given that repointing is a labor-intensive and expensive undertaking, there is a pressing need for a systematic approach to evaluating the necessity for repointing based on rational grounds. Within this Ph.D. project, a new laboratory test setup is developed to study water absorption and penetration in clay brick masonry. The key feature is to enable uniform water spray exposure at considerably lower water spray rates than in existing test setups while continuously recording both the amount of absorbed and penetrated water. The developed test setup is used in four experimental campaigns to study the interaction of clay brick masonry exposed to water spray. In the first two experimental campaigns, two series of clay brick masonry specimens without known cracks, built with two different types of bricks and three different mortar joint profiles, are exposed to water spraying. The obtained results indicate that in clay brick masonry without known cracks, water penetration starts when the masonry is nearly saturated (average moisture content above 90% saturation level). As there is a lack of consensus regarding the quantity of WDR penetration through clay brick masonry claddings and the appropriate methodology for incorporating penetration in hygrothermal analyses, a novel water penetration criterion in clay brick masonry is introduced. As cracks provide low resistance pathways for water penetration, clay brick masonry specimens with different crack widths, created artificially, are exposed to water spray in the third campaign. Subsequently, in the fourth campaign, specimens tested in the third campaign were repointed and tested once again to study the effect of repointing on water absorption and penetration in clay brick masonry. The results indicate a reasonable correlation between the crack width and the average water penetration rate. Further, a strong correlation is observed between the saturation level and the start of water penetration; the larger the crack width, the lower the saturation level at the start of water penetration. The obtained results suggest that repointing can effectively reduce water penetration in cracked clay brick masonry. Finally, the experimental results are implemented in hygrothermal simulations, providing an understanding of scenarios where repointing may mitigate moisture risks in building envelopes. The results of the simulations suggest that repointing has the potential to notably decrease the mold risk of timber frame walls and reduce the moisture content of autoclaved aerated concrete (AAC) walls. The positive effects of repointing are particularly pronounced when the brick veneer exhibits signs of poor workmanship or visible cracks, especially when walls are exposed to high WDR loads.
... Water penetration due to WDR occurs as a result of several factors, including deposition, driving forces, and structures that permit its passage [6]. The deposited water on a masonry façade can be transported through the wall in several different ways; the brick-mortar interfacial zone is often cited as the path offering the least resistance [7][8][9][10]. Likewise, many masonry façades contain cracks stemming from moisture and temperature movements combined with frequent freeze-thaw from the erection. ...
... The results obtained indicate that in the absence of known cracks, the start of water penetration would vary significantly, which can be related to the quality of the brick-mortar interface, which is counted as an important parameter in leakage. Similar results were obtained in studies done by Groot and Gunneweg [7], Slapø et al. [8], and Kahangi Shahreza et al. [25], where the penetration appeared to be mainly caused by brick-mortar interfaces, particularly in masonry built with low or medium suction bricks. Further, earlier water penetration would be expected in the case of cracked specimens, as cracks might exhibit low resistance to water penetration. ...
... This further plays an important role in determining the quality of the bond/contact formed between the brick and mortar. The microstructure of mortar and other mortarrelated parameters [43], including mortar water content during bricklaying (flowability of the mortar) [8], mortar retention, and the type of workmanship in applying the mortar affect the contact zone between brick and mortar. However, it should be noted that water penetration predominantly occurs through the voids and gaps in the brick-mortar interface (which is mainly related to the workmanship), especially at head joints [7,8,25], rather than through the mortar or brick unless the brick has very high suction [7]. ...
Article
This research study investigates the response of clay brick masonry with different crack widths before and after repointing subjected to water spray. In doing so, 3-course masonry prisms containing artificial cracks were exposed to a water spray during 23 hours of testing. Forty-nine cracked 3-course masonry prisms were prepared with a crack width varying between 0.3 mm and 0.9 mm, whereas thirteen specimens were built without known cracks for comparison. The results indicate a reasonable correlation between the crack width and the average water penetration rate. Compared to the reference specimens, those with crack widths of 0.3, 0.5, 0.7, and 0.9 mm showed average water penetration rates of 1.7, 2.4, 3.0, and 5.1 times higher, respectively. Further, a strong correlation was observed between the saturation level and the start of water penetration. In the reference specimens, water penetration started when the water content reached above 90% of the saturation capacity. Depending on the crack width, water penetration in the cracked specimens started when the saturation level was between 72-87%. The specimens were repointed and once again exposed to water spray. On average, the water penetration rate decreased by around 54% in the reference specimens and between 47-74% in the specimens with cracks. Raking of the specimens during repointing revealed that many head joints contained voids and gaps, confirming that head joints are probably the weakest part of clay brick masonry concerning water penetration. The results show that repointing has the potential to significantly reduce water penetration in clay brick masonry with and without known cracks exposed to water spraying.
... Researchers characterised the hydrophobicity, water absorption, and vapour transmission of some of these products when applied to masonry substrates [23][24][25][26]. However, controversial findings are reported, even with products based on similar chemical composition [27,28]. Further, the real-life performance of water-repellent-treated elements can be very different to the lab environment due to the complex factors that govern their behaviour [29] and the application technique may influence the penetration depth of the treatment [30]; the workmanship can impact the uniformity of the performance across the façade [27,31]; the effectiveness of the water-repellent material can change depending on the suitability of its physical-chemical properties to the smoothness and unevenness of the substrates [32]. ...
... However, controversial findings are reported, even with products based on similar chemical composition [27,28]. Further, the real-life performance of water-repellent-treated elements can be very different to the lab environment due to the complex factors that govern their behaviour [29] and the application technique may influence the penetration depth of the treatment [30]; the workmanship can impact the uniformity of the performance across the façade [27,31]; the effectiveness of the water-repellent material can change depending on the suitability of its physical-chemical properties to the smoothness and unevenness of the substrates [32]. Indeed, the interface between brick and mortar is reported to be a critical location of water ingress [33] as the diverse porous structures of the mortar joints compared to those of bricks makes them more vulnerable to WDR [27]. ...
... Further, the real-life performance of water-repellent-treated elements can be very different to the lab environment due to the complex factors that govern their behaviour [29] and the application technique may influence the penetration depth of the treatment [30]; the workmanship can impact the uniformity of the performance across the façade [27,31]; the effectiveness of the water-repellent material can change depending on the suitability of its physical-chemical properties to the smoothness and unevenness of the substrates [32]. Indeed, the interface between brick and mortar is reported to be a critical location of water ingress [33] as the diverse porous structures of the mortar joints compared to those of bricks makes them more vulnerable to WDR [27]. The role that defects and other surface irregularities play on the surface waterproofing performance are commonly reported in the field [29], as most existing masonry buildings in exposed areas have various levels and types of damage to their façades. ...
Article
Full-text available
Moisture ingress is a major cause of damage to masonry cavity walls. Products of various chemical compositions are available for wall surface treatment, aimed at reducing/eliminating water ingress. This study presents the results of full-scale wall tests designed to quantify water absorption into uninsulated and insulated brick masonry cavity walls exposed to wind-driven rain (WDR) with and without surface waterproofing. Two different waterproofing products were used: acrylic and silane-siloxane mixture. Untreated and treated walls were exposed to cycles consisting of 10 min wetting at 2.25 L/m 2 ·min every 60 min. The results show that both treatments lead to a reduction in water ingress ranging from 90% to 97%. However, while a more consistent performance was obtained for the silane/siloxane-treated walls under repeated exposure, the results for the acrylic treatment were dominated by the original wall conditions, improved with a reapplication of the treatment. The testing protocol proposed in this study is effective in determining the performance of waterproofing treatments exposed to different levels of WDR. Both treatments prove to be effective in preventing moisture uptake in walls in moderate WDR exposure conditions, while in extreme WDR exposure conditions, the acrylic treatment is less effective.
... The use of wet masonry mortar has reduced water penetration and shown to be effective in achieving excellent bonding between mortar and brick units, thus improving the resistance to driving rain (Slapø et al., 2017). Within the workable range of mortar consistency, more water enhanced the results. ...
... The use of mortar with high water content, that is, high flow mortar, has sharply improved the resistance of the masonry to wind-driven rain, even for bricks with low to moderate IRA. Low water content mortar gives a porous texture, thereby increasing water penetration (Slapø et al., 2017). The use of wet mortar over the dry mortar reduced moisturerelated defects and decay, thereby improving structural properties. ...
... The challenging part is while using wet mortar is to achieve an aesthetic quality. This is because, the wet mortar increases the need to clean the spilled mortar on a new wall (Slapø et al., 2017). ...
Thesis
Rainwater penetration through building enclosures is one of the critical factors affecting building performance and durability. Understanding and assessing rainwater penetration within and through the veneer is crucial to controlling and avoiding moisture-related problems such as biological growth and corrosion in interior structural elements. Adding a layer of clay bricks as a cladding to the windward surface of a building envelope is customary in Canadian residential building construction. Cladding made of clay bricks (often known as clay brick veneer) serves multiple purposes, such as providing additional thermal insulation, aiding in weather resistance, and improving the building’s aesthetics. Though clay brick veneer provides adequate weather resistance for the building, it does not offer complete resistance to rainwater penetration. Rainwater tends to seep through masonry walls, especially when rain is combined with heavy wind conditions. The accumulated excess moisture inside the building may degrade building materials, reduce the insulation quality, and facilitate the growth of fungal mold, endangering the health of the occupants of the building. Hence, studying the resistance of commonly used cladding systems to water penetration is of utmost importance. The experimental program involved the through-wall water penetration of nine full-scale test panels as per ASTM E514/E514M - 20 and supplement surface treatment tests. The water permeance of the brick veneer under air pressure was studied in the laboratory. This research project is laid out to evaluate and compare the resilience of four commonly used clay bricks and stucco cladding systems when subjected to wind-driven rain.
... Controversial results are often presented and there are still many open questions that need to be answered before it can be concluded that any water-vapor-permeable coatings will improve the durability of masonry [10]. For example, the nature of the mortar joints was reported to have a critical role, hence careful consideration should be given before applying water-repellents to masonry, especially in countries with much driving rain followed by frequent freeze-thaw cycles [11]. In many cases, defects and problems were reported [12] and, according to some authors, further research is needed to understand the mechanisms of failure of hydrophobic treatments [13]. ...
... The graph then shows how the temperature varies with time in space. In the transect the acquisitions at times t 1,2,5,7,11,12 have been considered, to follow the trend during the whole experiment. t 1 is the initial time, just before wetting, t 2, 5, 7 refer to the wetting phase (on the same day), while t 11,12 refer to the drying phase in Fig. 9. Examples of thermal images taken during the tests. ...
... In the transect the acquisitions at times t 1,2,5,7,11,12 have been considered, to follow the trend during the whole experiment. t 1 is the initial time, just before wetting, t 2, 5, 7 refer to the wetting phase (on the same day), while t 11,12 refer to the drying phase in Fig. 9. Examples of thermal images taken during the tests. Internal wetting before the treatments' application: during wetting (a) and during drying (b). ...
Article
Moisture is one of the main problems that affect new and historic masonry buildings, which are the most common ones in Europe and worldwide. The application of surface treatments based on water-repellents is a very common solution to protect masonry from rain and hence from moisture-related problems. However, there are very few studies on the monitoring of water-repellents in real buildings and a deeper knowledge would be necessary on the long-term effectiveness and compatibility of water repellents, especially considering that defects and flaking issues are often reported in-the-field. In this paper, infrared thermography was proposed as a totally non-invasive technique to monitor the behaviour of brick masonry subjected to wetting, both from outside (rain) and inside (internal moisture). An active thermal approach was used to simulate internal and external wetting. The behaviour of the masonry during wetting and drying was investigated both in laboratory walls and in brick samples, to elucidate their water transport properties. All the materials were tested both in untreated conditions and after the application of two different hydrophobic coatings. The results show that the drying behaviour of treated masonry materials is a critical issue, as the coatings may strongly slow down the drying of internal moisture, even if the coefficient of resistance to water vapour diffusion of the products is very low. The results also suggest that the methodology used to process thermal images using multi-temporal analysis is a promising way to interpret the water transport in treated walls and to monitor real buildings where water-repellents were applied.
... In most existing studies, water penetration in brick masonry is investigated by applying a high water spray rate on one face of an already saturated masonry specimen while measuring the mass of water collected on the other side. The mass of the absorbed water, which defines the saturation level of the masonry itself, is rarely measured [10,[23][24][25][26][27]. These test setups may give a phenomenologically misleading picture of the evolution of water penetration caused by WDR by ignoring the water buffering capacity of non-saturated masonry [22]. ...
... In clay brick masonry, water absorption (water content) and water penetration depend on parameters such as material properties (absorption properties of brick and mortar), mortar water content at bricklaying, joint thickness, presence of cracks in the brick itself, brick-mortar interface, and wall thickness [1,7,18,23,30,31]. In addition, masonry walls with the same prescribed characteristics may differ widely in performance due to workmanship during bricklaying [10,[18][19][20]23]. ...
... In clay brick masonry, water absorption (water content) and water penetration depend on parameters such as material properties (absorption properties of brick and mortar), mortar water content at bricklaying, joint thickness, presence of cracks in the brick itself, brick-mortar interface, and wall thickness [1,7,18,23,30,31]. In addition, masonry walls with the same prescribed characteristics may differ widely in performance due to workmanship during bricklaying [10,[18][19][20]23]. There are several hygrothermal analysis tools to simulate temporal moisture content variations in masonry claddings. ...
Article
Full-text available
Despite the impact of water penetration on the performance of building envelopes, no general agreement is available on implementing water penetration due to wind-driven rain (WDR) in hygrothermal and moisture safety analyses. This study proposes a novel criterion for water penetration in clay brick masonry that depends on the water content level of masonry. An experimental campaign investigating water penetration in clay brick masonry exposed to uniform water spray is conducted on masonry triplets prepared from bricks with different water absorption properties and three mortar joint profiles. During each test, water absorption and water penetration are registered continuously. The results show that no water penetration occurs unless the water content of the specimens is above 90% of their saturation capacity. The saturation level at which penetration starts is consistent across all joint profiles and brick types. Accordingly, exposure to driving rain at levels below the threshold may not lead to water penetration. The utility and implications of the proposed criterion are briefly demonstrated by analyzing water content and water penetration in a clay brick masonry façade. The resulting water penetration is compared with the results obtained using a commonly accepted reference model that assumes one percent of all wind-driven rain deposited on the façade to penetrate the clay brick cladding. By linking water penetration in clay brick masonry to the water content, the proposed criterion is an attempt to logically explain a phenomenon of high scientific and practical relevance for moisture analyses of a frequently used type of building envelope.
... The primary pathways for water penetration in brick walls are identified as imperfections at brick-mortar interfaces (Groot and Gunneweg, 2004;Groot and Gunneweg, 2010;Slapø et al., 2017;Kahangi Shahreza et al., 2021;Kahangi Shahreza et al., 2022; and preexisting cracks or deficiencies (Groot and Gunneweg, 2004;Calle and Van Den Bossche, 2017), which vary in terms of width and location. These vulnerabilities become increasingly significant over time, with crack formation in claddings exacerbated by temperature and moisture gradients, frost action, settlements, and dynamic loads. ...
Article
Repointing is a prevalent maintenance practice in Northern Europe aimed at mitigating moisture-related damage in brick masonry buildings. Although commonly used, evidence of its effectiveness is limited. This study assesses repointing's role in reducing damage risks by conducting a probabilistic hygrothermal analysis of two wall types: timber frame walls and masonry cavity walls. Results indicate that repointing could reduce the mold index in timber frame walls and moisture content in the autoclaved aerated concrete (AAC) layer of masonry cavity walls, particularly in walls with visible defects. However, its impact is minimal on walls without significant deficiencies. Moreover, the study suggests that repointing, given its labor-intensive and costly nature, may not always be the most judicious maintenance strategy. It recommends a selective repointing approach, suiting the specific conditions and needs of the wall based on its location, orientation, and existing state, rather than a blanket application across all façade sections.
... Adaptation measures must address such concrete challenges. Masonry is a good example here, where research shows that an alteration in the wetness of the concrete employed can provide a more resilient masonry [87,88]. In addition, the altered precipitation patterns following frequent occurrences of torrential rains lead to novel needs for maintenance, e.g., where gutters formerly needed cleaning each autumn, they now ought to be cleaned before the rains of the summer season as well. ...
Article
Full-text available
This article analyses adaptation to climate induced challenges in form of torrential rains hitting urban landscapes in Norway with increased frequency. Specifically, it investigates the influence of the industry structure on ethical challenges when the climate changes. A meta-analysis of the scientific output from a major multi-disciplinary research program is carried out. In addition, the methods include use of expert opinions, literature review and document studies. Climate change adaptation challenges disciplines within civil engineering and natural sciences. Following this, established practices need alteration as specialists face new ethical challenges. Practical climate change adaptation requires the ability to overcome silo mentality among the involved disciplines. Challenges involve acknowledging responsibility, transparency, and information quality. Engineering takes place in an environment of incomplete knowledge. In addition, there is a high degree of decentralised decision-making and directives, and laws and regulations are often lagging after the experienced challenges. Consequently, individual experts experience increased ethical challenges. Systemic circumstances apprehension is necessary for reducing societal risks within climate change adaptation. Both education of engineers and cooperation between specialists from different disciplines is needed to master the altered framework conditions.
... In vertical surfaces, it is due to the rain penetration inside superficial layers through the hair cracks of the topcoat and the following absorption by capillarity in underlying layers [21][22][23] . If the finishing layer shows a high vapour resistance, the water absorbed does not evaporate and it stagnates in the wall leading to the deterioration of the plaster and the detachment of the superficial layers. ...
Article
The moisture in masonries is one of the main responsible for the deterioration of historical buildings. Moisture increases U-values, weakens the structure, damages the surfaces and, finally, promotes the growth of fungi and moulds which reduce the Indoor Air Quality and can affect the artefacts, when present. Several factors contribute to this phenomenon: accidents (burst of pipes and ducts), design errors in the restoration of an ancient building (superficial and interstitial condensation), geotechnical factors (e.g., rising damp, presence of embankments), the degradation of materials promoted by rainwater infiltrations and the construction techniques (e.g., preparation of mortars and plasters during construc-tion/restoration works). However, intervention strategies require the correct qualitative and quantitative identification of the cause of the presence of moisture. This paper deals with the objective diagnosis of the presence of humidity in masonries. After an overview of the main causes of the phenomenon, and related strategies of intervention, an objective diagnostic methodology is presented and described. The methodology has been designed for rising damp and it is also suitable in the case of other causes of humidity (e.g., soil moisture, accidental moisture, condensation, etc.). Finally, a case study focused on the diagnosis and planning of the restoration of a building of great historical interest has been analysed.
... Surface treatment of brick veneer is expected to reduce water penetration and area of wet (damped) surface. Slapø et al. [23] applied water-repellent on masonry panels to study its effectiveness on water penetration. The study found that water repellent does not improve the water penetration resistance to a high-pressure wind-driven rain event. ...
Article
Rainwater penetration through building enclosures is a critical factor affecting building performance and durability. Understanding and assessing rainwater penetration and its prevention through the brick veneer and brick wall is crucial to controlling and avoiding moisture-related problems such as fungal growth and damages in interior structural elements. Addition of a layer of clay bricks as a cladding (veneer) to the exposed surface of a building envelope is a common practice in Canada. Though clay brick veneer provides adequate weather resistance for the building, it does not offer complete resistance to wind-driven rainwater penetration unless other measures such as surface treatment or additional layer of cladding is incorporated. Hence, studying the aspects of resistance to water penetration of commonly used cladding systems is of utmost importance. This paper presents outcomes of an experimental study conducted to determine water penetration of brick veneer specimens with two different initial rate of absorption values, two void amounts, and three different surface treatments. The study found that the surface treatment is a viable method for improving the resistance of water penetration inside the building envelope and the plastering was found to be the most effective method. The study also found that the initial rate of absorption and thickness of the bricks affect the water penetration; however, void amount in the brick does not affect much on water leakage of the masonry walls.
Article
Full-text available
Moisture is a major source of damage in historic solid masonry. Therefore, control of moisture movement in masonry is instrumental to the durability of masonry buildings. From research and practical experience it is known that many factors may play a role regarding permeability problems in masonry. This paper is focused on materials aspects regarding water penetration in historic fired clay masonry walls, constructed with moderate-to-high absorption bricks and lime mortars; the occurrence and influence of parameters such as brick porosity, interface leakage and mortar joint resistance are discussed. Subsequently, quantitative tests results show the effects of these parameters on leakage of solid walls of different thicknesses. The results of the investigations lead to a number of recommendations to be used in case of repair of historic solid masonry. Finally, attention is paid to the influence of workmanship on the permeability behaviour of historic solid walls.
Article
For millenniums, bricks were the main building material for the load-bearing structural elements of constructions. They were produced manually and they were fired at low temperature. They also present low apparent specific density, high absorption, high surface roughness and relatively low compressive strength. Nowadays, bricks used for restoration works should be compatible to the old ones. As the existing line of modern brick manufacturing is far from the above mentioned criteria, the way to solve the problem is to manually produce these special building materials which render them expensive and laborious. Additionally, their high porosity and soft nature make them easily deteriorated by different environmental conditions. The protection of traditional bricks is an important step towards their durability and a challenge especially nowadays where nanotechnology has been proven efficient when it is incorporated in coatings for building materials. In the present paper, hand-made brick samples were treated with different coatings by the technique of total immersion. The solutions tested were both traditional such as linseed oil but also silanes and alkosiloxanes both neat and nano-modified. In order to compare the physical properties of the treated bricks, parameters like capillarity, porosity, absorption and durability have been tested. It was concluded that silica nano-particles and micro-clay enrichment of alkosiloxane was the most sufficient way to protect those special building materials.
Article
This paper presents a comprehensive review of process induced building defects investigated by SINTEF Building and Infrastructure in the 10-year period 1993-2002 (2,423 cases registered and described in 2,003 assignment reports). Defects related to the building envelope constitute 66% of the investigated cases. A bulk of the defects (76%) is related to moisture, and many types of building defects are recurring items, indicating a general lack of knowledge concerning fundamental principles of building physics. A wide range of classical problems is recorded e.g. unfortunate design and use of materials, inaccurate craftsmanship, structure and composition of rendering layers and paint on porous, mineral building materials, inappropriate rendering layers on facade systems with rendering directly on thermal insulation, and insufficient efforts to protect against moisture in general. These findings support earlier investigations concluding that the construction industry is not able to learn from past experience and that the exchange of knowledge is not satisfactory.
Article
The study examines the protection from deterioration by salt provided by four coatings applied to new, commonly used, high-quality brick. The coatings are Keim Granital, a silicate-based mineral paint; Benjamin Moore Acrylic Exterior Masonry Paint, an acrylic latex paint; PROSOCO Siloxane WB, a siloxane water repellent; and Atofina Kynar RC-10, 152 PWD PVDF, a fluoropolymer-based water repellent. Masonry samples were artificially weathered using sodium carbonate as the deteriorating salt. Results show that a brick surface will be protected by a coating by: 1) reducing water infiltration from driving rain, 2) reducing the depth of the damage zone by moving the crystallization front to the surface (when salts are present and water infiltrations occur), 3) extending the lifetime of the substrate, and 4) providing a more visible warning of moisture-related deterioration by the spalling of the coating. This protection is provided when the formulation of coating is matched to the nature, porosity, and water vapor permeability of the substrate. In addition, the adhesion of a coating to the substrate will determine whether the coating will exacerbate deterioration when it fails.
Article
This paper assesses the effectiveness and effects of a water repellent (sodium methylsiliconate in aqueous solution) on crystallisation in stone and brick masonry materials. The salt crystallisation method adopted in this study is based on capillary rise, concentration by evaporation and consequent crystallisation and prevention of efflorescence by surrace treatment. The results confirm that cryptoflorescence (salt growth within pores) is considerably more damaging than efflorescence (salt growth on surfaces). They also provide strong evidence that treatment with sodium methylsiliconate can have a harmful effect on masonry materials and may promote their decay by suppressing the capillary transport of water and salt solution to the surface, thus forcing the formation of cryptoflorescence.
Article
The disintegrative process of freezing and thawing of porous, mineral materials represents a significant challenge in the design and construction of building enclosures. In this paper, we present a simple method for assessing the relative potential of a climate to accelerate frost decay based on multi-year records of daily air temperatures and rainfall, with special emphasis on masonry. Distributions of 4-day rainfall prior to days with freezing events provide quantitative information on the geographically dependant frost decay risk in porous, mineral building materials in a given climate. Data from 168 weather stations in Norway are analysed, using weather data from the reference 30-year period 1961–1990.
Article
This paper presents challenges concerning design of masonry structures in severe climates. Empirical data on the design and performance of masonry buildings in Norway are presented, based on a comprehensive analysis of 302 process induced masonry defect assignments over a 20-year period from 1983 to 2002. Analyses of building defects are necessary in order to further develop tools, solutions and preventive measures ensuring high-performance building envelopes. The results illuminate the vulnerability of masonry under varying climatic exposure. The amount of masonry defects in Norway illustrates that it is not only the extreme weather events that need to be studied as a foundation for geographically dependent design guidelines. Driving rain and frost action are the principal climatic challenges to be considered in the pursuit of high-performance masonry structures. Shrinkage and thermal movement, the most frequent defect category, dominate independent of the climatic impact. Merely small errors or mistakes can bring about major and often irreparable defects or damage to masonry structuresA large part of the cases could have been avoided through more detailed engineering and applied knowledge on existing design guidelines. Finally, performance requirements for better design guidelines are presented. The need for design guidelines to ensure local climate adaptation and improved design guidelines on movement joints is also revealed.