Conference PaperPDF Available

Effect of installation of photovoltaic (PV) generation to power quality in industrial and residential customers distribution network

Authors:

Abstract

Objective of research is to analyze the influence of the photovoltaic (PV) generator installation to power quality on distribution network. There are two models of load distribution network, namely industrial and residential costumers distribution network. Reseach show that the value of bus voltage THD on distribution network of industrial and residential customers are still under of voltage THD limit recomended by IEEE 519-1992 equal as 5%. The majority of the value of TDD conductor in two models of the distribution network is under the limit conductor current TDD recommended by IEEE 519-1992. In network industries and residential customers, the more number of PV plants installed, then the value of current harmonic (TDD) at PCC bus will be even greater. The most value of conductor current TDD average generated by conductor that is connected directly to the PV generator bus The using of single tuned passive filter able to improve THD Bus and TDD conductor which still does not meet the standart requirements.
1
Effect of Installation of Photovoltaic (PV)
Generation to Power Quality in Industrial and
Residential Customers Distribution Network
Amirullah1,4),
1,2,3)Electrical Engineering Department,
Industrial Engineering Faculty,
Kampus ITS Sukolilo Surabaya
Jl. Arief Rahman Hakim Surabaya Indonesia 60111
am9520012003@yahoo.com1,4)
Ontoseno Penangsang2), Adi Soeprijanto3)
4)Electrical Engineering Study Program,
Engineering Faculty,
University of Bhayangkara Surabaya
Jl. Ahmad Yani 114 Surabaya Indonesia
Zenno_379@yahoo.com2), adisup@ee.its.ac.id3)
Abstract-Objective of research is to analyze the
influence of the photovoltaic (PV) generator installation to
power quality on distribution network. There are two
models of load distribution network, namely industrial and
residential costumers distribution network. Reseach show
that the value of bus voltage THD on distribution network of
industrial and residential customers are still under of
voltage THD limit recomended by IEEE 519-1992 equal as
5%. The majority of the value of TDD conductor in two
models of the distribution network is under the limit
conductor current TDD recommended by IEEE 519-1992. In
network industries and residential customers, the more
number of PV plants installed, then the value of current
harmonic (TDD) at PCC bus will be even greater. The most
value of conductor current TDD average generated by
conductor that is connected directly to the PV generator bus
The using of single tuned passive filter able to improve THD
Bus and TDD conductor which still does not meet the
standart requirements.
Keywords: Photovoltaic Generator, Harmonics, Total
Harmonic Distortion, Total Demand Distortion
I. INTRODUCTION
Utility customers are becoming more and more
demanding in energy consumption and they need good
supply to operate reliably. At the same time they tend to
disrupt the utility supply with the equipment used for their
main daily activities. Such kind of equipment may include
variable speed drives, computers, electronic ballasts, and
power electronic devices. This is imposing of higher
burden on utilities to supply good quality electrical
energy. Consequently, renewable energy sources and
distributed generator (DG) will play a significant role in
the energy mix in the future and a number of further
research is require to optimize the number of grid
development strategies and improve of power quality [1].
Microgrid is a group of loads and generators that operate
as a controlled system that provides electricity to a
particular region with relatively limited power. The
concept provides a new view to define the operation of
distributed generator [2], [3]. In microgrid technology,
which is commonly used plant is a plant with renewable
energy sources. One source of renewable energy is
photovoltaic (PV) generator. The use of PV as an energy
source requires an inverter to convert DC into AC
voltage. In addition to function as a kind of change of
voltage, inverter also cause damage to existing
fundamental wave and commonly called harmonics. If it
can not be controlled, then the harmonics will cause
damage to equipment such as transformers, cables, and
other electrical devices. One way to reduce the harmonics
is using a filter [4].
The purpose of research is to analyze the
influence of the photovoltaic (PV) generator installation
to power quality on distribution network. There are two
models of load distribution network, namely industrial
and residential costumers distribution network. The
research method begins by determining network modeling
is connected to PV system, PV array circuit model, PV
inverter circuit topology model, and network topology
model of industrial and residential costumers. The next
step is to determine a mathematical model of current
control circuit PV inverter. The next process is to
determine the strategy of the PV generator installation in
the distribution network of industrial and residential
customers. The next stage is to determine the value of bus
voltage THD, conductor current TDD, and conductor
power factor in the distribution network of industrial and
residential customers on a different strategies PV
generator installation.Futhermore is comparing value of
bus voltage THD and conductor current TDD refers to
IEEE Standard 519-1992 and conductor power factor
refers on to the standard Indonesian Electricity Company
(PLN) as a basis for determining level of power quality in
industrial and residential costumer distribution network.
Single tuned passive filter are selected to improve THD
bus and TDD conductor value which still does not meet
the standart requirements.
II. THEORY
A. Power Quality Standart
Power quality has become a major concern in
electrical world for recent decades. One issue that arises is
the emergence of the current and voltage waveform is not
sinusoidal or defects caused by the emergence of
harmonics generated by the power system [5]. Figure 1
shows distorted waveform signal due to harmonics.
191
2015 International Seminar on Intelligent Technology and Its Applications
978-1-4799-7711-6/15/$31.00 © 2015 IEEE
2
Figure 1. Distorted Wave Cause Harmonics. Where: a = Fundamental
Frequency Wave, b.1 = 3rd Harmonics Wave, b.2 = 5th Harmonics
Wave, c. = Distorted Harmonics.
The first parameter is the Total Harmonic
Distortion (THD). THD is the ratio of the rms value of the
harmonic components to rms value of fundamental
component and is commonly expressed in percent (%).
This index is used to measure periodic waveform
deviations contains harmonics of a perfect sine wave [6].
In a perfect sine wave THD value is zero percent. THD
value is expressed in Equation 1 as follows:
%100
1
2
2
U
U
THD
k
nn
(1)
Where: Un = Harmonic Component; U1 = Fundamental Component; K =
Maximum Harmonic Component
The second parameter is Individual Harmonic
Distortion (IHD) is ratio of the rms value of individual
harmonics to the rms value of fundamental component.
The third parameter is Total Demand Distortion (TDD) is
amount of current harmonic distortion and defined in the
following Equation 2 [7]:
%100
2
2
L
k
nn
I
I
TDD
(2)
Where IL is maximum load current (for 15 or 30 minutes) at fundamental
frequency at the Point of Common Coupling (PCC), is calculated from
current average of maximum load of 12 months before.
Maximum THD value which allowable for each
country is different depending on the standard used. THD
standards is most often used in the electric power system
is the IEEE Standard 519-1992. There are two criteria that
are used in the analysis of harmonic distortion is the limit
voltage distortion and current distortion limits. Table I
shows voltage distortion limit (THD) on power
distribution system. Table II shows current distortion limit
is based on the IEEE Standard 519-1992 [5].
B. Single Tuned Shunt Passive Filter
Shunt passive filters always considered as agood
solution to solve harmonic current problems [8], shunt
passive filters can be classified into three basic catagories
as follows:
1. Band pass filters (of single or double tuned).
2. High pass filters (of first, second, third-order or C-
type).
3. Composite filters.
The single tuned filter (Figure 2) consisting of
inductor Lf, capacitor Cf and small damping resistor Rf are
connected in parallel with non linear loads to provide
low-impedance paths for specific harmonic frequencies,
thus resulting in absorbing the dominant harmonic
currents flowing out of the load. Furthermore it also
compensates reactive power at system operating
frequency.
Rf
Lf
Cf
Figure 2. Single Tuned Shunt Passive Filter
The impedance versus frequency of this filter is shown
[9]:
SC
SCLSCR
SZ
f
ffff
f
2
1
)(
(3)
Where S = j2πf
Generally the filter capasitor is sized for known reactive
power compensation Qc required to improve power factor,
Cf can be expressed as:
22
1
1
1
21nUf
Cf
(4)
Where U is the supply voltage, n is the harmonic order
and f1 is a fundamental frequency.
At the harmonic frequency fn = n f1 the filter reactor
provides a series resonance.
nf
nf fC
fL
21
2
(5)
The inductive value of filter can be obtained from
equation 6 as:
fn
fCf
L2
)2( 1
(6)
The value of the low-impedance Rf for each single tuned
filter is affected by the quality factor of filter Q.
Q
L
nfR f
f1
2
(7)
The quality factor Q determines the sharpness of tuning.
Usually, a value of Q ranges between 20 and 100. High
Q-value filter give the best reduction in harmonic
distortion. The interaction of the filter with the source
reactance Ls, creates a parallel resonance condition
addition to the series resonance frequency of the filter.
(8)
C. Photovoltaic System
Photovoltaic systems (PV) or solar panels is one
of renewable energy power generator that utilize sun as
main source and then converted into electrical energy. In
general, solar power has to be accepted as an alternative
energy source. The issue now is the price is still
192
3
expensive compared to electricity generated by other
energy sources, so its use is now limited to a limited scale
such as in electrical devices and are also used as power
generator in areas that are still inaccessible by electrical
network [10]. Figure 3 shows PV characteristic curve.
(a) I-V curve for PV panel PV for fix radiation and temperature change
(b) I-V curve for PV panel for radiation level change and fix
temperature
(c) Curve of current versus voltage and power
Figure 3. Curve of PV panel characteristic
III. METHODOLOGY
A. Research Method
Research method begins by determining network
model (grid) is connected to the PV system, PV array
circuit model, PV inverter circuit topology models, as
well as the distribution network topology model of
industrial and residential customers. The next step is to
determine a mathematical model of current control circuit
of PV inverter. The next process is to determine the
strategy of PV power generator installation in the
distribution network of industrial and residential
customers. PV system model which has been
subsequently simulated in two distribution network
topology. The first network representing industrial area
measurements made before and after the installation of
150 kW PV system and the residential area. In the
industrial customer case studies, three 150 kW PV system
connected to the distribution network and subsequent
evaluation of response of distribution network. A
residential customer distribution topology then proposed
with a 150 kW PV system. The next stage is to determine
value of bus voltage THD, current TDD, and power factor
(power factor) conductor in the distribution network of
industrial and residential customers on a number of
strategies installation of PV generator. Futhermore,
comparing value of bus voltage THD and current
conductor TDD refers to IEEE Standard 519-1992 and
conductor power factor refers to the standard PLN. Single
tuned passive filters are installed to improve THD bus and
TDD conductor value still does not meet the standart
requirements. Simulation and analysis of research using
ETAP 7.0 software.
B. PV Model Description
The PV system model proposed for the
simulation consists of PV array, diode, inverters and a
power grid interface as shown in Figure 4. The PV array
is modeled according to its equivalent circuit shown in
Figure 5, by using the equation deriving from
aforemention circuit representation.
DC AC
PV Array
Blocking
Diode
PV Inverter
Circuit
Breaker
Power Grid
Figure 4. Proposed model for grid-connected photovoltaic system
In particular, the behavior of the PV array model
is affected by the solar irradiance, the temperature and the
specific characteristics of the chosen PV module
technology. The PV inverter circuit is composed of a DC
to DC converters which is necessary to determine
maximum power point tracking of PV arrays, a DC to AC
converter to transform DC power into AC, means of
energy transfer to absorb fast voltage variations and filters
to eleminate undesirable harmonic components. The
modular circuit of the PV inverter is shown in Figure 6.
NpIph
Ns
Np
p
p
sR
N
N
s
p
sR
N
N
VPV
IPV
Figure 5. Equivalent circuit of PV array
A maximum power point tracking mechanism to
extract the maximum power available from the PV array
is also considered. The maximum power point tracking
adopted is the incremental conductance method with
integral regulator to minimize the errors in tracking MPP.
More information about the specific algorithm is found in
reference [1]. Distribution network model of industrial
and residential customers is shown in Figure 7 and 8.
DC DC
PV Inverter Circuit Topology
DC AC FILTER
DC Link
DC Link
MPPT
Mechanism Control
Circuit
Voltage and
Current
Meauserement and
Calculation
Figure 6. PV inverter circuit topology
193
4
PV 150 kW Park
No. 3
0.2 km
25 kW Load
with pf = 0.98
0.3 km
35 kW Load
with pf = 0.97 50 kW Load
with pf = 1
0.25 km
0.15 km
PV 150 kW Park
No. 2
PV 150 kW Park
No. 1
0.15 km
0.4/11 kV
Distribution Substation
External Grid
(a) Industrial costumer
0.25 km
Feeder 1
23 kW Load
with pf = 0.96
0.24 km
Feeder 3
27 kW Load
with pf = 0.91 Feeder 4
12 kW Load
with pf = 0.975
0.15 km
PV 150 kW Park
0.25 km
0.4/11 kV
Distribution Substation
Feeder 2
10 kW Load
with pf = 0.78
0.32 km
0.28 km
Feeder 5
20 kW Load
with pf = 0.945
0.33 km Feeder 6
17 kW Load
with pf = 0.97
External Grid
(b) Residential costumer
Figure 7. Two model of distribution network
(a) Industrial costumer
(b) Residential costumer
Figure 8. Two model of distribution network for industrial and
residential customer using ETAP
IV. RESULT AND DISCUSSION
Research was conducted on the condition of system
is connected to microgrid. There are two models of
network topology, namely distribution network of
industrial and residential customers. Both grid distribution
network supplied by a power transformer 1000 kVA,
11/0.4 kV Δ /Y connection, which is connected to the
external grid MVAsc 9000. The first distribution network
connected to 5 buses, respectively 2 load buses,
connected to the PV plant, as well as one other bus
connected to the PV generator and also serves as a bus
load. The second distribution networks connected to 7
buses, each 6 load buses and 1 bus is connected to PV
generator. Data load, transformer, conductor, and PV
generator on the distribution network of industrial and
residential costumer are shown in Table III. PV generator
in addition to functioning supplying power to the
distribution network, is also a source of harmonics due to
the presence of inverter as a medium to transform the DC
voltage into AC voltage. Data of harmonic current
generated by the PV generaton is shown in Table IV [11].
Harmonic order are generated according to the ability of
ETAP 7.0 software.
TABLE IV. HARMONIC CURRENT GENERATE BY PV
Order
Mag (%)
Order
Mag (%)
2
0.71
11
0.24
3
1.85
12
0.08
4
0.57
13
0.16
5
0.52
14
0.25
7
0.61
15
0.05
8
0.07
17
0.06
9
0.08
19
0.05
10
1.12
23
0.07
Based on the above data, then analyzed using
ETAP 7.0 software help to determine the value of the bus
voltage THD, current TDD, and conductor power factor
in the distribution network of industrial and residential
customers on a number of installation strategies of PV
generator. Analysis of three parameters shown in Table V,
VI, and VII.
TABLE V. COMPARATION OF VOLTAGE QUALITY USING
DIFFERENT STRATEGY OF PV INSTALATION ON INDUSTRIAL
COSTUMER
Strategies
Bus
V(pu)
VTHD (%)
VTHD Std
(%)
Without PV
1
0.998
0.01
5
2
0.988
0.01
5
3
0.985
0.00
5
4
0.985
0.00
5
5
0.989
0.01
5
6
0.989
0.01
5
7
1.000
0.00
5
8
0.989
0.01
5
PV1
1
0.998
0.07
5
2
0.981
0.18
5
3
0.986
0.13
5
4
0.986
0.13
5
5
0.991
0.13
5
6
0.991
0.13
5
7
1.000
0.00
5
8
0.998
0.13
5
PV1 + PV2
1
0.999
0.15
5
2
0.989
0.32
5
3
0.987
0.27
5
194
5
4
0.986
0.27
5
5
0.991
0.31
5
6
0.991
0.27
5
7
1.000
1.00
5
8
0.991
0.27
5
PV1 + PV2+ PV3
1
0.999
0.22
5
2
0.991
0.45
5
3
0.988
0.40
5
4
0.987
0.40
5
5
0.992
0.44
5
6
0.993
0.44
5
7
1.000
0.00
5
8
0.998
0.40
5
TABLE VI. COMPARATION OF VOLTAGE QUALITY USING
DIFFERENT STRATEGY OF PV INSTALATION ON
RESIDENTIAL COSTUMER
Strategies
Bus
V(pu)
VTHD (%)
VTHD
Std (%)
Without PV
1
0.997
0.01
5
2
0.986
0.00
5
3
0.987
0.00
5
4
0.986
0.01
5
5
0.997
0.00
5
6
0.998
0.00
5
7
0.986
0.02
5
8
0.986
0.01
5
9
0.988
0.00
5
10
1.000
0.00
5
PV
1
0.998
0.07
5
2
0.987
0.13
5
3
0.988
0.13
5
4
0.987
0.13
5
5
0.998
0.13
5
6
0.990
0.17
5
7
0.987
0.13
5
8
0.987
0.13
5
9
0.989
0.13
5
10
1.000
0.00
5
Table V dan VI shows that bus voltage THD
value on distribution network of industrial and residential
customers ranged between 0 through 0.45%. This value is
still below limit of voltage THD recommended by IEEE
519-1992 by 5%. The addition of PV generator in both
distribution network generates increasing of voltage THD
value. On industrial customer network without PV,
maximum bus voltage THD value is 0.01%, while
network using three PV maximum bus voltage THD value
increased to 0.45%. The maximum bus voltage THD
value on residential customer networks without PV of
0.02% and if using PV maximum bus voltage THD value
increased to 0.17%.
Figure 9 and 10 show that on industrial and
residential customers network, the more the number of
PV generator installed then value of current harmonics
(TDD) at PCC bus will be even greater. This is because in
addition to functioning PV generator supplying power to
the distribution network, is also generating harmonics due
to presence of inverter as a media to convert DC to AC
voltage.
Table VII shows that the value of conductor currents
TDD in the industrial customers distribution network has
already meet current TDD recommended by IEEE 519-
1992 except on conductor 2, 5, and 6. Current TDD value
on conductor 2 has a minimum because value of the
power factor is 1.0. Improvement of TDD current only
can be done on conductor 5 and 6 for the condition of P1
+ PV1 and PV1+ PV2 + PV3 connected to the grid by
increasing power factor of both conductor becomes 1.0.
By using the power triangular method, we will obtain
reactive power compensation value to get value of C, L,
and R is based on the most dominant-order harmonics
with a single passive filters tuned using Equation 4 to 7.
The most dominant-order harmonics are 3rd, 5th, 7th, 11th,
and 14th. By using the same procedure, migitation of
current TDD can be done on conductor 6 in the residential
distribution network for PV installed to the grid. Table
VIII shows designed single tuned passive filters, current
TDD without and with filter. From Table VII, we can see
that nominal current TDD on conductor 5 and 6 in the
industrial costumer distribution network before using
single tuned passive filters are 224.9 and 39.4. After using
3rd order single tuned passive filter, as shown in Table
VIII, the value of current TDD for both conductor has
reduced to 154.68 and 28.26. Improvement of current
TDD using filter also happens on conductor 6 in the
residential distribution network for PV installed to the
grid. Figure 11 and 12 show harmonic current spectrum of
conductor 6 for PV1 + PV 2 + PV 3 connected to grid on
industrial costumer network before and after installed
single tuned passive filter.
Figure 11. Harmonic current spectrum of conductor 6 for PV1 + PV 2 +
PV 3 connected to grid on industrial costumer network without filter
Figure 12. Harmonic current spectrum of conductor 6 for PV1 + PV 2 +
PV 3 connected to grid on industrial costumer network with filter
Table VII also shows that the addition of PV
generator in two models distribution network produce
conductor current TDD value is increasing. The most
value of conductor current TDD average generated by
conductor that is connected directly to the PV generator
bus. V. CONCLUSION
The simulation results show that the THD value
on the bus voltage distribution network of industrial and
residential customers are still under voltage THD limit
recommended by the IEEE 519-1992 by 5%. The
majority of the value of TDD conductor in two models of
the distribution network is under the limit conductor
current TDD recommeded by IEEE 519-1992. In
industrial and residential customer networks, the more the
195
6
number of PV generator installed, then the value of
current TDD at PCC bus will be even greater. This is
because in addition to functioning PV plants supplying
power to the distribution network, is also generates
harmonics due to the presence of the inverter as a medium
to transform DC into AC voltage. Using of single tuned
passive filter 3rd order give better solution to improve
current TDD. The value of power factor in the distribution
network of industrial and residential customers on
average already meet minimum requirements set PLN
limits by 85%.
VI. ACKNOWLEDGMENT
The authors would like to acknowledge to
Directorate General of Human Recource for Science,
Technology, and Higher Education Indonesia for financial
support by BPP-DN Scholarships to pursue Doktoral
Program in Electrical Engineering, Sepuluh Nopember
Institute of Technology (ITS) Surabaya.
[1] Minas Patsalides, George E. Georghiu, Andreas Stavrou, and
Venizelos Efthimiou, “Assesing The Power Quality Behaviour of
High Photovoltaic (PV) Penetration Levels Inside The
Distribution Network”, 3rd IEEE International Symposium on
Power Electronics for Distributed Generator Systems (PEDG),
Nicosia Syprus 2012.
[2] B. Lasseter. Microgrids [distributed power generator]. In IEEE
Power Engineering Society Winter Meeting, 2001., volume 1,
pages 146149, Columbus, Ohio, Feb 2001.
[3] R. Lasseter. Microgrids. In IEEE Power Engineering
Society Winter Meeting, 2002., volume 1, pages 305308, New
York, NY, 2002.
[4] M. Patsalides, A. Stavrou, G. Makrides, V. Efthimiou and
G. E. Georghiou, “Harmonic Response of Distributed Grid
Connected Photovoltaic System”.
[5] Thomas M. Bloming, P.E. and Daniel J. Carnovale, P.E.,
“Application of IEEE Standar 519-1992 Harmonic Limits”,
Presented at The 2005 IEEE IAS Pulp and Paper Industry
Conference in Appleton, WI.
[6] Arrilaga, Jos and Watson, Neville, “Power System Harmonics”,
Chicester: John Willey and Sons, 2003.
[7] Sankaran C, “Power Quality”, CRC Press LLC, 2002.
[8] S. Chun-Lien, H. Ci-Jhang, “Design of Passive Harmonic Filters
to Enhance Power Quality and Energy Efficience in Ship Power
Systems”, IEEE 49th Industrial and Commercial Power System (I
and CPS) Technical, pp. 1-8, 2013.
[9] Mouna Tali, Abdellatif Obbadi, Abdelkrim Elfajri, Youssef
Errami, “Passive Filter for Harmonics Migitation In Standalone
PV System for Non Linier Load”, Laboratory: Electronics,
Instrumentation and Energy Team: Exploitation and Processing of
Renewable Energy, Faculty of Science University Chouaib
Doukalli Department of Physics Route Ben Maachou, 24000 El-
Jadida, Marocco, IRSEC 2014.
[10] F.D. Kanellos, A. I. Tsouchinkas and N.D. Hatziargryi-ouo,
“Microgrid Simulation during Grid Connected and Islanded
Modes of Operation”, International Conference on Power
Systems Transients, Montreal, 2005, Paper. IPST05-113.
[11] Soonwook Hong and Michael ZuercherMartinson, White
Paper, “Harmonics and Noise in Photovoltaic (PV) Inverter and
the Mitigation Strategies”, Solaria Renewables.
[12] Wilson W.W., “Teknologi Sel Surya: Perkembangan Dewasa Ini
dan Yang Akan Datang”, Edisi Keempat, Elektro Indonesia,
1996.
APPENDIXS: TABLE I. IEEE 519-1992 HARMONIC VOLTAGE LIMIT
Bus Voltage on PCC
Individual Voltage
Distortion (%)
Total Voltage
Distortion THD (%)
69 kV and below
3,0
5,0
69,001 kV through 161 kV
1,5
2,5
161,001 kV and above
1,0
1,5
Tabel II. IEEE 519-1992 HARMONIC CURRENT LIMIT
Maximum Harmonic Current Distortion in Percent of IL
Individual Harmonic Order (Odd Harmonics)
Isc/IL
<11
11≤h<17
17≤h<23
23≤h<35
35≤h
TDD
<20*
4
2
1,5
0,6
0,3
5
20 s/d 50
7
3,5
2,5
1
0,5
8
50 s/d 100
10
4,5
4
1,5
0,7
12
100 s/d 1000
12
5,5
5
2
1
15
>1000
15
7
6
2,5
1,4
20
TABLE III. DISTRIBUTION NETWORK DATA OF INDUSTRIAL AND RESIDENTIAL COSTUMERS
Network models
Generator and Transformers
Conductors
Loads
Industrial costumer
External grid 9000 MVAsc (Swing)
Transformer 1000 kVA, 11/0.4 kV, ∆/Y
PV 1 (Bus 2) 150 kW (Mvar Control)
PV 2 (Bus 5) 150 kW (Mvar Control)
PV 3 (Bus 6) 150 kW (Mvar Control)
Frekuensi 50 Hz
Bus 1-8, Al 3/C 120 mm2
Bus 8-2, CU 3/C 35 mm2
Bus 8-3, CU 3/C 35 mm2
Bus 8-4, CU 3/C 35 mm2
Bus 8-5, CU 3/C 35 mm2
Bus 8-6, CU 3/C 35 mm2
Bus 2, 25 kW cos φ = 0.980
Bus 3, 35 kW cos φ = 0.970
Bus 4, 35 kW cos φ = 1.000
Residential costumer
External grid 9000 MVAsc (Swing)
Transformer 400 kVA, 11/0.4 kV, ∆/Y
PV (Bus 6) 150 kW (Mvar Control)
Frequency 60 Hz
Bus 1-9, Al 3/C 120 mm2
Bus 9-2, CU 3/C 35 mm2
Bus 9-3, CU 3/C 35 mm2
Bus 9-4, CU 3/C 35 mm2
Bus 9-5, CU 3/C 35 mm2
Bus 9-6, CU 3/C 35 mm2
Bus 9-7, CU 3/C 35 mm2
Bus 9-8, CU 3/C 35 mm2
Bus 2, 23 kW cos φ = 0.960
Bus 3, 10 kW cos φ = 0.780
Bus 4, 27 kW cos φ = 0.910
Bus 5, 25 kW cos φ = 0.975
Bus 7, 20 kW cos φ = 0.945
Bus 8, 35 kW cos φ = 0.970
196
7
TABLE VII. COMPARATION OF CURRENT QUALITY ON A NUMBER PV INSTALLATION STRATEGY
Network Models
Strategies
Conductors
PF (%)
Isc (A)
IL (A)
Isc/IL
TDD (%)
TDD Std (%)
Industrial
Costumer
Without PV
1
99.2
13900
157.7
88.1420
0.000
12
2
98.1
8100
36.30
223.141
0.000
15
3
97.1
6700
51.20
130.860
0.000
15
4
100.0
7300
71.10
102.673
0.000
15
5
0.0
8960
0.000
N/A
0.000
20
6
0.0
9040
0.000
N/A
0.000
20
PV1
1
99.6
13860
145.5
95.2580
3.920
12
2
100.0
8083
24.00
336.792
23.87
15
3
97.2
6900
51.30
134.503
0.090
15
4
100.0
7600
71.10
106.892
0.000
15
5
0.0
9390
0.000
N/A
0.000
20
6
0.0
9480
0.000
N/A
0.000
20
PV1 + PV2
1
99.7
13860
143.3
96.7200
7.970
12
2
100
8441
24.00
351.709
23.83
15
3
97.2
7150
51.30
100.422
0.180
15
4
100
7890
71.20
110.815
0.180
15
5
85.7
9390
6.300
1490.48
224.5
20
6
0.0
9930
0.000
N/A
0.000
20
PV 1 + PV2 + PV3
1
100.0
13860
130.7
106.045
13.10
15
2
100.0
8800
24.10
365.146
23.74
15
3
97.2
7400
51.40
143.968
0.260
15
4
100.0
8190
71.20
115.029
0.270
15
5
85.8
9840
6.300
1561.91
224.9
20
6
85.1
9930
15.60
636.539
39.54
20
Residential
costumer
Without PV
1
93.6
13860
165.0
84.0000
0.000
12
2
96.1
7300
34.00
214.710
0.000
15
3
77.3
6430
18.40
349.460
0.000
15
4
91.0
7450
41.60
179.090
0.000
15
5
97.5
6810
17.50
389.143
0.000
15
6
0.0
9040
0.000
N/A
0.000
20
7
94.5
7210
30.00
240.334
0.000
20
8
97.0
6230
24.90
250.201
0.000
20
PV
1
94.3
13860
150.9
91.8900
3.780
12
2
96.1
7590
34.10
222.581
0.090
15
3
77.3
6600
18.50
356.757
0.070
15
4
91.3
7750
41.60
186.298
0.080
15
5
97.5
7070
17.50
404.000
0.090
15
6
85.0
9040
14.60
619.178
39.44
15
7
94.5
7500
30.00
250.000
0.130
15
8
97.0
6450
24.90
259.036
0.130
15
(a) Without PV
(b) PV1
(c) PV1 + PV2
(d) PV1 + PV2 + PV3
Figure 9. Harmonic current spectrum in the number of PV installation strategies on industrial costumer network at PCC
197
8
(a) Without PV
(b) PV
Figure 10. Harmonic current spectrum in the number of PV installation strategies on residential costumer network at PCC
TABLE VIII. DESIGN SINGLE TUNED PASSIVE FILTERS AND TOTAL DEMAND DISTORTION
Strategies
Conductors
Tuned
Filter
C (μF)
L (mH)
R (Ω)
TDD
Without Filter
With Filter
Industrial Costomer
PV 1 + PV2
5
3rd
17.4690
44.7459
0.5062
224.50
154.65
5th
17.4690
16.1113
0.3037
224.50
157.08
7th
17.4690
8.22000
0.2167
224.50
156.65
11th
17.4690
3.3288
0.1381
224.50
160.06
14th
17.4690
2.0055
0.1059
224.50
163.06
PV 1 + PV2 + PV3
5
3rd
17.4690
44.746
0.5062
224.90
154.68
5th
17.4690
16.111
0.3037
224.90
156.97
7th
17.4690
8.2200
0.2167
224.90
156.47
11th
17.4690
3.3288
0.1381
224.90
159.91
14th
17.4690
5.0055
0.1059
224.90
161.10
6
3rd
87.3713
8.9480
0.1012
39.540
28.260
5th
87.3713
3.2213
0.0608
39.540
28.540
7th
87.3713
1.6435
0.0434
39.540
28.880
11th
87.3713
0.6656
0.0276
39.540
29.490
14th
87.3713
0.4109
0.0217
39.540
30.190
Residential Costumer
PV
6
3rd
87.3713
8.9480
0.1012
39.440
28.270
5th
87.3713
3.2213
0.0608
39.440
28.480
7th
87.3713
1.6435
0.0434
39.440
28.280
11th
87.3713
0.6656
0.0276
39.440
29.160
14th
87.3713
0.4109
0.0217
39.440
29.280
198
... A single tuned filter consisting of inductor L f , capacitor C f and small damping resistor R f are connected in parallel with nonlinear loads to provide low-impedance paths for specific harmonic frequencies, thus resulting in absorbing the dominant harmonic currents flowing out of the load. Furthermore it also compensates reactive power at system operating frequency [15]. Single tuned passive filters are used to suppress single harmonics e.g. 5 th , 7 th , 9 th , 11 th , or 13 th harmonics. ...
... Where Q is defined as the ratio of the inductance (or capacitance) to resistance at the resonant frequency and n  is the tuned angular frequency (rad/s). The impedance versus frequency of this filter is shown [15]: ...
Conference Paper
Full-text available
Photovotaic (PV) other than capable to result power, it also generates harmonics due to the presence of an inverter as a medium to convert DC to AC voltage so can reduce power quality. PV generator also has intermitten characteristic and generate power depend on environment condition e.g. temperature and irradiance level. The paper presents performance improvement of power quality due to the influence of multi PV integration to low voltage distribution line of 380 kV (phase-phase) 50 Hz on point common coupling (PCC) bus under variable solar temperature and irradiance level. The model consists of three PV generator groups with 100 kW active power. In addition to connecting on a three phase grid, PV generator is also connected to three groups of three phase loads with 20 kW active power each. The power quality parameters studied are voltage and current unbalance as well as voltage and current harmonics in eight scenarios PV generator connected on three phase grid. The single tuned filter is used to improve power quality using two conditions before and after filter installed. Multi PV models with three phase generators connected three phase grid, without and with single tuned filters at all irradiance and temperature levels results phase maximum voltage (phase A, B, and C) in relatively stable of 308 and 310 Volt respectively, and generating unbalanced voltage of 0%. The maximum phase current value, for system without single tuned filter at all irradiance and temperature levels are different as 12.5, 9.8, and 10 A, respectively, resulting in unbalanced current of 16.0991%. Under the same condition, single tuned filters are capable to balance maximum phase currents (phase A, B, and C) of 10.45 A respectively, so able to reduce unbalanced current to 0%. The implementation of single tuned filter can reduce unbalanced current values according limit ANSI/IEEE 241-1990. At a constant temperature and irradiance levels are increasing, voltage and current average harmonics (total harmonics distortion) are also increasing. The use of single tuned filter is the most effective in suppressing 5 th harmonics so can reduce average value of voltage and current harmonics significantly within IEEE 519-1992. Keywords: Power Quality, Total Harmonic Distortion, Multi PV Generator, Temperature, Irradiance
... Furthermore, particularly in developing countries, the power generation main distributor often fails to meet the required demands of general usage, especially in residential purposes [3], [4]. Continuous research on renewable energy harvesting has been a vital point in the response of carbon emission issues combined with a high demand for an even electricity distribution throughout the area [5]. However, the variety of renewable sources are highly dependent on its geographical locations [6], as in the type of renewable energy accumulated at tropical regions quite differ from sub-tropical counterparts which could diverge from geothermal energy for volcanic locations, wind energy for temperate maritime climates and solar energy (photovoltaic) for high daylight distributed areas, [7] which will be covered specifically on the modification and development of the inverter unit topology and design [8]. ...
Conference Paper
Full-text available
The increasing electricity demands for residential purposes results in the development of renewable photovoltaic standalone systems. With power converter technology as the core of the design; an undesirable harmonic distortion which affects the durability of electric equipment emerges from the construction that is above recommended practice standards. For decades, continuous research for the means to reduce harmonics in the power inverter unit of the system leads to multilevel technology. Nevertheless, the conventional topology of inverters would often deal with volume building and analysis complexity as the number of level increases. This paper discusses a further hardware implementation of the unique asymmetrical design of an 11-level inverter with an efficient number of reduced switches to achieve a higher level demand. This inverter is designed for single phase off-grid photovoltaic system application. The first verification of this research is a simulation design of the proposed topology. Finally, the hardware implementation which is done in a laboratory test environment, the THD i test value is recorded 3.43% for the fundamental current of 4.72A at a frequency of 50Hz measured with the HIOKI 3286-20 power meter THD record function.
... They also emphasized the need for good design of the inverter so that the SPP does not adversely affect the power quality. Amirullah et al. (2015) investigate how total harmonic distortion and total demand distortion are affected by the coupling of SPPs to the networks to which residential and industrial loads are separately connected. As a result, both values are understood to comply with IEEE standards. ...
Article
Full-text available
Demand for electricity is increasing due to population growth, the development of technology and the level of prosperity of communities. Coal, natural gas, oil, etc., which are called traditional sources can no longer meet this demand. In addition, these resources are harmful to the environment and have high costs. For all these reasons, the trend towards alternative energy sources is increasing. These sources are called renewable energy sources. Solar, wind, water, geothermal etc. as examples of renewable energy sources. In addition to producing enough energy, it is also necessary to use the produced energy efficiently. This is defined as the energy quality (power quality). The power quality parameters are defined to keep the obtained electric energy within certain limits in terms of quality. These parameters include; harmonic, voltage flicker, voltage deviation etc. Through this study; it has been analyzed, with the increasing number of solar power plants connecting to the network, what kind of changes occurred in the electricity network and how the solar power plants affect the network in terms of energy quality. The analysis was carried out by evaluating the one month data from a 5 MW solar power plant.
... Research on the effects of installation of PV generator to power quality in three phase industrial and residential distribution network has been discussed. However, PV generator which installed is still static which is based on level of solar irradiance, temperature, and current and voltage harmonic generated by PV generator with a fixed value [5]. Objective of research is to analyze the influence of solar irradiance and integration of PV generator to power quality of three phase grid on the constant temperature and load, based on changes in some level of integration of PV generator. ...
Article
Full-text available
Objective of research is to analyze the influence of solar irradiance and integration of photovoltaic (PV) generator to power quality of three phase grid on the constant temperature and load, based on changes in some level of integration of PV generator. Power quality aspects studied are fluctuation or changing, and harmonics of voltage and current on eight scenarios PV generator connected to three-phase grid, using passive filter circuit model double band pass (double tuned). Research shows that voltage and current values on the PCC bus before use double tuned passive filter on the condition only connect single generator is still stable. However, if the PV generator connected to the three phase grid, amounted to more than one generation, voltage and current grid becomes unstable (fluctuation). At the level of solar radiation remains, the greater number of PV generators connected to the grid threephase, then the values of voltage and current THD increases. At the level of solar irradiance increases, average THD of voltage and current grid also increased. Avarage THD of voltage and current grid is reduced after double tuned passive filter installed. Therefore, double tuned passive filter able to improve profile of voltage and current THD grid as a result of the integration of a number of PV power generators in three-phase grid according IEEE Standard 519-1992.
Article
Full-text available
Over the last few years, a dynamic increase in the installed capacity of distributed energy sources has been observed, with the largest share being photovoltaic sources. The power grid is a system of connected vessels, and changing the structure of electricity production has a specific impact on the operation of this network, which makes it necessary to study the impact of the sources on the power system. The current and projected increase in the number of connected installations will make the issues of interaction and cooperation of distributed sources with the network extremely important. The article presents an analysis of the impact of a photovoltaic farm on selected parameters of the quality of electricity supply. This analysis was made on the basis of simulation results in a computer program and measurement tests carried out on a real photovoltaic farm with a capacity of 1.8 MW connected to the medium voltage power grid. The impact of the farm-generated power on the values of fundamental indicators of the quality of electricity supply, such as voltage deviations, voltage asymmetry factors, and voltage distortions factors, is presented. These relationships were determined based on the correlation and regression analysis of individual electrical quantities.
Article
Full-text available
Rapid growth in the integration of new consumers into the electricity sector, particularly in the industrial sector, has necessitated better control of the electricity supply and of the users’ op-erating conditions to guarantee an adequate quality of service as well as the unregulated dis-turbances that have been generated in the electrical network that can cause significant failures, breakdowns and interruptions, causing considerable expenses and economic losses. This research examines the characteristics of electrical variations in equipment within a company in the industrial sector, analyzes the impact generated within the electrical system according to the need for operation in manufacturing systems, and proposes a new solution through automation of the regulation elements to maintain an optimal system quality and prevent damage and equipment failures while offering a cost-effective model. The proposed solution is evaluated through a reliable simulation in ETAP (Energy Systems Modeling, Analysis and Optimization) software, which emulates the interaction of control elements and simulates the design of electric flow equipment operation. The results demonstrate an improvement in system performance in the presence of disturbances when two automation schemes are applied as well as the exclusive operation of the capacitor bank, which improves the total system current fluctuations and improves the power factor from 85.83% to 93.42%. Such a scheme also improves the waveform in the main power system; another improvement result is when simultaneously operating the voltage and current filter together with the PV system, further improving the current fluctuations, improving the power factor from 85.83% to 94.81%, achieving better stability and improving the quality of the waveform in the main power grid.
Article
Full-text available
Several studies have been presented regarding the harmonics mitigation by using different types of filters. Passive filter is one of them and is employed due to his simplicity, economical cost and high reliability in power system. This paper presents an analysis and study of three types of passive filters to minimize harmonics distortion caused by non linear loads in standalone PV system. In order to achieve the certain filtering effect, it is necessary to combine different filter topologies; generally these topologies can be divided into two categories: series AC reactor and shunt passive filter such as tuned filters and high pass filters. This paper presents firstly the basic design and components of PV system, secondly describes the causes of harmonics and their effects and presents the means to improve power quality and to protect the equipment in our power system. The proposed system is verified by the simulation using Matlab/Simulink environment.
Article
Full-text available
The growth in the use of power electronic devices and the introduction of an increasing number of renewable sources of energy in the distribution network, which produce voltage and current disturbances, can give rise to power quality problems in power systems. With the expected growth of connection densities of PV systems in distribution networks, environmental factors and in particular the fluctuation in solar irradiance can lead to undesirable variations of power and supply quality. In order to be able to predict the harmonic pollution due to PV generation, the simple harmonic model for the grid has been adopted and analyzed. Then a typical distribution system topology has been modeled and the findings of the measurements on PV systems have been applied to the distribution system model. On that basis the solar irradiance dependent level of harmonic distortion due to PV generation has been assessed. The results have been compared with already existing standards in an attempt to evaluate the validity of the use of PQ standards in the modern distribution systems.
Article
Full-text available
Technology evolution, environmental concerns associated with central electric power plants and deregulation of the electric utility industry are providing the opportunity for small distributed generators to become very important in order to satisfy the on – site customer expanding power demand. In this paper, the steady state and transient operation of a typical microgrid are studied. The models of two dispersed generation units (photovoltaic system, wind turbine) are presented. Models of the power electronics interface and control strategies for fast control of frequency and voltage magnitude without communication are derived.
Conference Paper
Full-text available
IEEE Std 519-1992 is a useful document for understanding harmonics and applying harmonic limits in power systems. Despite many years of good use there is still some confusion about how to apply certain aspects of the standard. This paper discusses some of those, as well as related issues that are helpful in working with harmonic limits. There is considerable debate as to precisely how some elements of IEEE Std 519-1992 should be interpreted. This paper presents the authors' views on some of the more ambiguous elements of the standard and on the application of harmonic limits in general
Conference Paper
Several studies have been presented regarding the harmonics mitigation by using different types of filters. Passive filter is one of them and is employed due to his simplicity, economical cost and high reliability in power system. This paper presents an analysis and study of three types of passive filters to minimize harmonics distortion caused by non linear loads in standalone PV system. In order to achieve the certain filtering effect, it is necessary to combine different filter topologies; generally these topologies can be divided into two categories: series AC reactor and shunt passive filter such as tuned filters and high pass filters. This paper presents firstly the basic design and components of PV system, secondly describes the causes of harmonics and their effects and presents the means to improve power quality and to protect the equipment in our power system. The proposed system is verified by the simulation using Matlab/Simulink environment.
Conference Paper
Variable frequency drives (VFDs) driven motors for pumps, blowers and fans, and heating, ventilation and air conditioning (HVAC) equipment on ships are rapidly growing in number. Due to their nonlinear nature, they become the major sources of harmonics in electrical power systems on board. To mitigate the harmonics, passive harmonic filters that are an LC circuit tuned to each harmonic order to be filtered have been used. In compliance with the new rule in the emission regulation of the maritime industry, the installation of passive filters has attracting more attention in managing service power energy efficiency. This paper proposed a design of passive filters to reduce the voltage and current distortions in ship power systems while increasing energy efficiency with power factor corrected by passive filters. The inductance and capacitance in the filter are designed according to harmonic currents and reactive power required. The on-board power system of a practical ship with a great number of VFDs is analyzed to illustrate the filter design. The field testing results verified the performance of system with the filter designed by the proposed method.
Article
Application of individual distributed generators can cause as many problems as it may solve. A better way to realize the emerging potential of distributed generation is to take a system approach which views generation and associated loads as a subsystem or a "microgrid." The sources can operate in parallel to the grid or can operate in island, providing utility power station services. The system will disconnect from the utility during large events (e.g., faults and voltage collapses), but may also intentionally disconnect when the quality of power from the grid falls below certain standards. Utilization of waste heat from the sources will increase total efficiency, making the project more financially attractive. University of Wisconsin laboratory verification of microgrid control concepts are included.
Conference Paper
In recent years, increasing concerns about climate change and the liberalisation of energy market have provided the necessary impetus for a revolutionary restructuring of the electricity network at every level, namely production, transmission and distribution. Increased electricity production from renewable energy sources (RES) coupled with energy efficiency lie at the heart of the ambitious targets set by Europe in the quest to curb greenhouse gas emissions and to reach energy sustainability. Therefore the security and stability of the power system should be considered carefully to identify possible impacts due to uncontrolled deployment of RES. This paper focuses on the study of varying concentrations of photovoltaic (PV) systems on a proposed electricity grid in an attempt to assess the power quality response of the power system. The study has been performed using a detailed PV system model. The model is initially validated using data from the output of PV systems and then this is used for the study of varying PV penetrations on common distribution system topologies. The results are compared to international power quality standards.
Conference Paper
The MicroGrid concept assumes a cluster of loads and microsources (<100 kW) operating as a single controllable system that provides both power and heat to its local area. This concept provides a new paradigm for defining the operation of distributed generation. To the utility the MicroGrid can be thought of as a controlled cell of the power system. For example this cell could be controlled as a single dispatchable load, which can respond in seconds to meet the needs of the transmission system. To the customer the MicroGrid can be designed to meet their special needs; such as, enhance local reliability, reduce feeder losses, support local voltages, provide increased efficiency through use waste heat, voltage sag correction or provide uninterruptible power supply functions. This paper provides an overview of the MicroGrid paradigm. This includes the basic architecture, control and protection and energy management.