This paper describes a platform for obtaining and analyzing real-time measurements in Microgrids. A key building block in this platform is the Empirical Mode Decomposition (EMD) used to analyze the electrical voltage and current waveforms to identify the instantaneous frequency and amplitude of the monocomponents of the original signal. The method was used to analyse the frequency fluctuation and obtain information about the linearity of electrical current and voltage waveforms measured in the field. Comparison between grid-connected and stand-alone microgrid voltage and currents’ monocomponents were conducted. Fluctuations in the grid frequency occurred in both the grid-connected and stand-alone microgrid, but the degree of the observed fluctuations were different, revealing more apparent nonlinear distortions in the latter. The observed instantaneous frequency from the collected data indicates potential nonstationary electrical signals when compared to synthetic data containing periodic signals coming from nonlinear loads. This observation leads us to expect the next generation of real-time measuring devices for the micro power grids to be designed on the principle of instantaneous frequency detection. Further efforts will be directed to a more rigorous characterization of the nonstationary nature of the signals by analyzing more and longer set of data.
Content may be subject to copyright.
Procedia Engineering 159 ( 2016 ) 94 103
1877-7058 © 2016 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/4.0/).
Peer-review under responsibility of the Organizing Committee of HumTech2016
doi: 10.1016/j.proeng.2016.08.070
ScienceDirect
Available online at www.sciencedirect.com
Humanitarian Technology: Science, Systems and Global Impact 2016, HumTech2016
Towards a Real-time Measurement Platform for Microgrids in
Isolated Communities.
Geir Kuliaa,, Marta Molinasb, Lars Lundheima, Bjørn B. Larsena
aDepartment of Electronics and Telecommunications, NTNU, 7491 Trondheim
bDepartment of Engineering Cybernetics, NTNU, 7491 Trondheim
Abstract
This paper describes a platform for obtaining and analyzing real-time measurements in Microgrids. A key building block
in this platform is the Empirical Mode Decomposition (EMD) used to analyze the electrical voltage and current waveforms to
identify the instantaneous frequency and amplitude of the monocomponents of the original signal. The method was used to analyse
the frequency fluctuation and obtain information about the linearity of electrical current and voltage waveforms measured in the
field. Comparison between grid-connected and stand-alone microgrid voltage and currents’ monocomponents were conducted.
Fluctuations in the grid frequency occurred in both the grid-connected and stand-alone microgrid, but the degree of the observed
fluctuations were dierent, revealing more apparent nonlinear distortions in the latter. The observed instantaneous frequency from
the collected data indicates potential nonstationary electrical signals when compared to synthetic data containing periodic signals
coming from nonlinear loads. This observation leads us to expect the next generation of real-time measuring devices for the micro
power grids to be designed on the principle of instantaneous frequency detection. Further eorts will be directed to a more rigorous
characterization of the nonstationary nature of the signals by analyzing more and longer set of data.
©2016 The Authors. Published by Elsevier Ltd.
Peer-review under responsibility of the Organizing Committee of HumTech2016.
Keywords: Instantaneous frequency, Hilbert-Huang Transform, Empirical mode decomposition, Microgrid, Frequency stability, Power systems
1. Introduction
Access to modern energy services is a necessity for economic development and particularly challenging in isolated
communities. The fall in prices of photovoltaic (PV) cells opens the possibility for aordable, clean and sustainable
energy to rural areas where, in most cases, extending the power grid is too expensive to be a realistic alternative. The
nature of the location for such systems require near to maintenance free supervisory control systems. Good access
to reliable data is essential to the supervisory control system to make correct actions. The nonlinearities of modern
power electronic equipment and the stochastic nature of the photovoltaic sources of energy advocate the need for
Corresponding author. Tel.: +47 992 99 867
E-mail address: geir@kulia.no
© 2016 The Authors. Published by Elsevier B.V. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/4.0/).
Peer-review under responsibility of the Organizing Committee of HumTech2016
95
Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
data acquisition systems based on real-time measurements and estimation of essential values, such as instantaneous
amplitude and frequency. Existing measurement devices for microgrids do not fulfill this requirement, as they are
generally based on average value calculations [1].
This paper explores methods for decomposing the electrical waveforms to extract their instantaneous frequency
components. The frequency components are used to investigate the frequency stability of the waveforms. The resulting
analysis will lay the foundation for future development of a real-time software platform for detection, analysis and
correction capabilities for electrical waveform distortions in microgrid power systems, based on the principle of
instantaneous frequency.
As physical data is the first step for a meaningful analysis, this project has, through a collaboration between
Norwegian University of Science and Technology (NTNU) and the Royal University of Bhutan (RUB)’s College
of Science and Technology, collected current and voltage measurements from two nearly identical systems: one
was a grid-connected PV microgrid, and the other was the same PV microgrid in stand-alone mode. Voltage and
current waveforms measured at Hundhammerfjellet windmill park in Norway were used as a reference for a qualitative
comparison. The data obtained were analysed using the Hilbert-Huang Transform (HHT).
2. Analysis Method
The concept of instantaneous frequency and amplitude for a general signal is not well-defined. For near-sinusoidal
signal shapes, such as those coming from a stable rotary generator, the instantaneous frequency can be associated with
the rotational speed, and other variations could be ascribed to an instantaneous amplitude. In other situations with
more complicated waveform, it is less clear how such parameters should be defined.
The voltage and current shapes studied in our context could be characterized as near periodic. In that case, using
several (more or less) near-sinusoidal components, each with its own instantaneous frequency and amplitude is a
possible approach. One method along these lines is the one suggested by Huang [2]. This approach, called the
Hilbert-Huang Transform (HHT)1, has been chosen for application on microgrid power systems in this paper, and is
outlined in the following.
2.1. Instantaneous frequency
Any real signal X(t) can be represented as an analytic signal Z(t) in the form given by (1)
Z(t)=X(t)+jY(t)=a(t)·ejθ(t)(1)
where Y(t) is the Hilbert transform of X(t), a(t) is the amplitude and θ(t) are the phase of Z(t). From this, it is possible
to define the instantaneous frequency of X(t) as in (2) [2, pp. 911-915].
ω(t)=dθ(t)
dt (2)
2.2. Hilbert-Huang Transform
Central to the HHT is the notion of Intrinsic Mode Functions (IMFs). An IMF is a function whose extrema are
alternatingly positive and negative, i.e. there is always a zero crossing between each extremum. For such functions
the instantaneous frequency will always be positive. By using a method called the Empirical Mode Decomposition
(EMD) as described in [2, pp. 917-923] it is possible to decompose a genaral signal s(t) into a set of IMFs, c1(t),
c2(t),...,cN(t) such that
s(t)=r(t)+
N
i=1
ci(t) (3)
1The version of the method used in this paper was the Normalized Hilbert-Huang Transform [3, p. 15].
96 Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
s
-1
0
1
cs1
-1
0
1
cs2
-1
0
1
cs3
-1
0
1
time
[
s
]
0 0.02 0.04 0.06 0.08
rs
-1
0
1
Fig. 1: Intrinsic mode functions and residue of s(t) normalized between -1 and 1.
where r(t) is a residual part of the signal that cannot be modeled as an IMF.
As an example of the EMD we will consider a normalized test signal s(t). It’s defined by (4) and corresponds to a
three-term Fourier series.
s(t)=cos(2π50 ·t)+1
3
·sin(2π150 ·t)+1
5
·cos(2π500 ·t) (4)
By applying the EMD on the simulated waveform s(t) the IMFs were obtained. The IMFs of the signal s(t)is
depicted in fig. 1. The first row is the original signal. The intrinsic mode functions follow this. The first IMF, c1(t),
has the highest frequency, the second, c2(t), has the second highest frequency and so on until the lowest frequency
component. In this example, there are only three frequency components, i.e. cs1(t), cs2(t), and cs3(t). The sum of
all the IMFs should ideally be equal to the raw data. For electrical systems, the last IMF (cs3(t) for s(t)) is the grid
frequency, i.e. the 50 Hz sine component of the signal. The previous IMFs contain all distortions, such as noise and
harmonics.
2.3. Hilbert Spectrum
The Hilbert Spectrum is a way to represent the instantaneous frequency and amplitude as a function of time for all
IMFs. By applying the EMD the intrinsic mode function of the signal are obtained. Each IMF, ci(t), can be represented
as an analytic signal, Zi(t) as shown in (1), with the amplitude ai(t), and frequency ωi(t) as defined in (2). Equation
(5) shows the definition of the Hilbert spectrum, Hi(ω, t), for a given IMF, ci.
Hi(ω, t)=
ai(t) for ω=ωi(t)
0 otherwise (5)
Fig. 2(a) displays the Hilbert spectrum of s(t)’s third intrinsic mode function, c3(t). It is possible to obtain the
Hilbert spectrum of any signal by summing all the intrinsic mode functions as shown in (6).
H(ω, t)=
N
i=1
Hi(ω, t) (6)
The Hilbert spectrum, Hs,ofs(t), is depicted in fig. 2(b). For all Hilbert spectra in this paper, the amplitudes are
normalized between -1 and 1, such that 0 dB =1.
97
Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
30
35
40
45
50
55
60
65
70
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(a) Hilbert spectrum of s(t)’s third intrinsic mode func-
tion, cs3(t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
0
100
200
300
400
500
600
700
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(b) Hilbert spectrum of s(t).
Fig. 2: Hilbert spectra of s(t)
Table 1: Summary of frequency fluctuations on the generated test signal s(t).
cs3cs2cs1
Mean frequency 49.96 Hz 150.10 Hz 499.99 Hz
Max frequency 51.12 Hz 153.16 Hz 501.35 Hz
Min frequency 49.12 Hz 147.79 Hz 498.49 Hz
Deviation from mean frequency 2.32 % 2.04 % 0.30 %
The generated test signal s(t) should be represented as perfect, horisontal lines in the frequency spectrum. Fig. 2
shows ripples on s(t) up to 2.32 % (see table 1). This is an error introduced by the implementation of the method.
20 ms of samples on the start and end of the signals were discarded from the summary in the tables to remedy for
end-eects when calculating the instantanious frequency.
3. Measurements
Electrical current and voltage measurements were performed at RUB College of Science and Technology’s two
PV microgrids. The grids are similar, with the exception that one is connected to the public power grid while the
other is not. Fig. 4(a) and 4(b) shows the grid-connected and stand-alone microgrid respectively. The load is the load
impedance of the parts of the college that the microgrid provide with electricity.
The point of measurements is marked on both figures. The resulting measurements of the electrical voltage and
current waveforms are displayed in fig. 3.
Measurements of the Norwegian grid, shown in fig. 3(a) and 3(b), was used as a reference. The measurements
were conducted by Sintef Energi AS at Hundhammerfjellet windmill park.
The voltage waveforms should ideally be pure 50 Hz sine waves. Harmonics on the power system is caused by
nonlinear loads and is undesirable. By visual inspection, it is apparent that the waveforms measured in Bhutan are far
more distorted compared to the waveforms measured in Norway. It is also evident that the stand-alone microgrid has
more distortions compared to the grid-connected one.
All the measurements are normalized between -1 and 1.
98 Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
time [s]
0 0.02 0.04 0.06 0.08
vs
(
t
)
-1
-0.5
0
0.5
1
(a) Normalized voltage measured, vs, at Hundhammerf-
jellet windmill park, Norway.
time [s]
0 0.02 0.04 0.06 0.08
is
(
t
)
-1
-0.5
0
0.5
1
(b) Normalized current measured, is, at Hundhammerfjel-
let windmill park, Norway.
time [s]
0 0.02 0.04 0.06 0.08
von
t
-1
-0.5
0
0.5
1
(c) Normalized voltage, von , measured at the grid-
connected microgrid (see setup in fig. 4(a)).
time [s]
0 0.02 0.04 0.06 0.08
ion
t
-1
-0.5
0
0.5
1
(d) Normalized current, ion, measured at the grid-
connected microgrid (see setup in fig. 4(a)).
time [s]
0 0.02 0.04 0.06 0.08
voff
t
-1
-0.5
0
0.5
1
(e) Normalized voltage, vo, measured at the standalone
microgrid (see setup in fig. 4(b)).
time [s]
0 0.02 0.04 0.06 0.08
ioff
t
-1
-0.5
0
0.5
1
(f) Normalized current, io, measured at the standalone
microgrid (see setup in fig. 4(b)).
Fig. 3: Electrical waveforms measured.
99
Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
  




(a) Voltage and current measurement setup for a grid-
connected PV-microgrid.
  



(b) Voltage and current measurement setup for a stand
alone PV-microgrid.
Fig. 4: The two dierent voltage and current measurement setups.
Table 2: Summary of frequency fluctuations measured at Hundhammerfjellet windmill park.
cvs1cis2
Mean frequency 47.75 Hz 47.80 Hz
Max frequency 48.89 Hz 51.72 Hz
Min frequency 46.53 Hz 44.76 Hz
Deviation from mean frequency 2.57 % 8.2074 %
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
30
35
40
45
50
55
60
65
70
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(a) Hilbert spectrum of vs(t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
0
500
1000
1500
2000
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(b) Hilbert spectrum of is(t).
Fig. 5: Hilbert spectra of electrical waveform data collected at Hundhammerfjellet windmill park, vs(t) and is(t).
4. Results
4.1. Analysis of electrical waveform data collected at Hundhammerfjellet windmill park, Norway
The voltage and current waveforms collected at Hundhammerfjellet windmill park in Norway, vs(t) and is(t), were
analyzed using the Hilbert-Huang transform. Their Hilbert spectra are shown in fig. 5. vs(t) is a monocomponent
signal and have therefore only one IMF, cvs1(t)=vs(t). The fluctuation of the instantaneous frequency was measured
and a summary is shown in table 2. The frequency fluctuations observed on vs(t) are relatively modest, and slightly
higher than the frequency fluctuation artifacts introduced on s(t). It’s important to note that the mean frequency
measured using HHT is 47.75 Hz, while it was 50 Hz using zero crossing frequency. While our current implementation
of HHT can analyze frequency patterns, it often struggles to determin the exact frequency values for short samples.
In contrast, is(t) consists of two IMF, cis1(t) and cis2(t). The first intrinsic mode function, cis1(t), contains all
harmonics and other distortions of is(t). It’s showed by the yellow graph on the Hilbert Spectrum in fig. 5(b). cis1(t)’s
amplitude is low and always below -35 dB. It has two spikes with increased frequency, that most probably is caused
by nonlinear loads, i.e. loads that draw a nonsinusoidal current from a sinusoidal voltage source [4].
100 Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
30
35
40
45
50
55
60
65
70
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
Fig. 6: Hilbert spectrum of cis2(t).
Table 3: Summary of frequency fluctuations measured at the grid-connected microgrid.
cvon6cion 6
Mean frequency 49.65 Hz 49.26 Hz
Max frequency 54.31 Hz 64.63 Hz
Min frequency 45.65 Hz 37.86 Hz
Deviation from mean frequency 9.38 % 31.18 %
is(t)’s second intrinsic mode function, cis2(t) is the blue graph located around 50 Hz. Table 2 shows that it has
considerable more variations in it’s frequency than cvs1(t). It is expected that the current is more distorted compared to
its corresponding voltage source. Both the frequency fluctuations on cis2(t) and cvs1(t) have a high periodic behavior.
4.2. Analysis of electrical waveform data collected at the grid-connected microgrid
The voltage waveform, von(t), measured at the grid-connected microgrid was decomposed into six IMFs, cvon 1
to cvon6, where cvon 6corresponds to the grid frequency. The three first IMFs, cvon 1to cvon3, were discarded as their
frequency fluctuations are higher than the band limit described in [2, p. 929]. The summary of the fluctuations in the
grid frequency is shown in table 3. The frequency variations on von(t) are 3.65 times higher than that on vs(t), with
fluctuations up to 9.37 % from the mean. From fig. 7(a) it is notable to see that the frequency has a periodic behavior,
with a new cycle every 10 ms.
The Hilbert spectrum of von(t) is shown in fig. 8(a) and shows considerable distortions. In this figure, the blue line
at the bottom is cvon6, the graph shifting between blue-green and yellow is cvon 5, and the yellow graph at the top is cvon3.
The corresponding current waveform, ion(t), was divided into seven IMFs, cion1to cion7, where the first two IMFs
were discarded due to reasons described above. ion (t)’s Hilbert spectrum is depicted in fig. 8(b). The light blue, green
and orange graphs above it corresponds to higher frequency distortions and is represented by the first six IMFs, cion1
to cion6. These have amplitudes up to -21 dB, so frequency fluctuations on ion(t) has a higher magnitude than is(t)’s.
The blue line at the bottom of the Hilbert spectrum corresponds to the 50 Hz of the current ion(t), i.e. cion 7.As
observed, cion7’s instantaneous frequency also has a periodic behavior, with frequency cycles of 10 ms, just like cvon6
(see fig. 7(b)). This is probably a cause for much of the distortions on von(t).
The observed 100 Hz instantaneous frequency is a property of the instantaneous power in single phase alternating
current systems. This eect being observed in the voltage and current might indicate a propagation of the power
oscillations on the ac side through the inverter dc bus voltage and the control feedback of the inverter. To elucidate
the nature of this instantaneous frequency transfer from the power to the voltage and current, further eorts will be
directed towards matching this measured 100 Hz instantaneous frequency with an analytical model of the votlage and
current of the inverter.
101
Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
30
35
40
45
50
55
60
65
70
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(a) Hilbert spectrum of cvon6(t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
30
35
40
45
50
55
60
65
70
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(b) Hilbert spectrum of cion6(t).
Fig. 7: Grid frequency of von(t) and ion (t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
0
200
400
600
800
1000
1200
1400
1600
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(a) Hilbert spectrum of von(t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
0
200
400
600
800
1000
1200
1400
1600
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(b) Hilbert spectrum of ion(t).
Fig. 8: Hilbert spectra of electrical waveforms measured at grid-connected microgrid.
Table 4: Summary of frequency fluctuations measured at the stand alone micromicrogrid.
cvo3cio6
Mean frequency 50.04 Hz 49.48 Hz
Max frequency 58.10 Hz 64.09 Hz
Min frequency 41.25 Hz 33.98 Hz
Deviation from mean frequency 17.56 % 31.33 %
4.3. Analysis of electrical waveform data collected at the stand-alone microgrid
The voltage waveform vo(t) measured at the stand alone microgrid was decomposed like von(t), into IMFs. Three
IMFs, cvo1to cvo3, were necessary to describe vo(t). Unlike von(t), none of vo(t)’s IMFs were discarded. The Hilbert
spectrum of vo(t) is shown in fig. 10(a). The blue line at the bottom represent the grid frequency, cvo3. The yellow
graph above it represent cvo2and the brown graph at the top is cvo1.cvo1s frequency has periodic properties with
cycles of 10 ms, and an amplitude up to -34 dB. As shown in fig. 9(a), cvo3does also have frequency fluctuations
with periods of 10 ms, but its frequency cycles are phase shifted, compared to that of cvo1s instantanious frequency.
The magnitude of the frequency fluctuations on cvo3is 1.87 and 6.83 times higher than that observed on cvon6and cvs1
respectively.
102 Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
30
35
40
45
50
55
60
65
70
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(a) Hilbert spectrum of cvo3(t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
30
35
40
45
50
55
60
65
70
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(b) Hilbert spectrum of cio6(t).
Fig. 9: Grid frequency of vo(t) and io(t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
0
200
400
600
800
1000
1200
1400
1600
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(a) Hilbert spectrum of vo(t).
time [s]
0 0.02 0.04 0.06 0.08
ω
/
2π
[
Hz
]
0
200
400
600
800
1000
1200
1400
1600
a
(
t
)[
dB
]
-50
-40
-30
-20
-10
0
(b) Hilbert spectrum of io(t).
Fig. 10: Hilbert spectra of electrical waveforms measured at the stand-alone microgrid.
The corresponding current waveform, io(t), was decomposed to six IMFs, cion1to cion 6. The Hilbert spectrum of
io(t) is shown in fig. 10(b). The first IMF cion 1is the light blue graph at the top of the Hilbert spectrum. Its amplitude
peaks at -15 dB, and the frequency has varying cycles with a period around 10 ms, that are phase shifted to cvo3’s
frequency cycles. cio2has similar frequency cycles. The last IMF, cio6, corresponds to the 50 Hz component of the
signal. Its frequency also varies with cycles of 10 ms (see fig. 9(b)).
It is remarkable how much more distorted the stand-alone grid is compared to the grid-connected one. It is also
noteworthy that also in this case there is a systematic 10 ms fluctuation on the stand alone microgrid as the one
observed in the grid connected microgrid. As explained above, this originates from the typical 100 Hz oscillations
observed in the power of single phase systems [4].
5. Discussion
Foundations for a software platform for real-time data acquisition and analysis of distorted electrical measurements
for isolated microgrids have been outlined in this paper. The HHT-EMD lies at the core of this platform by enabling
the identification of instantaneous frequencies in the monocomponents of the original data. The Empirical Mode
Decomposition divides the electrical voltage and current waveforms into useful and easy-to-analyze modes, where
each component carries information about particular aspects of the signal and the system behind the signal. Showing
that the instantaneous grid frequency is not stable with considerable fluctuations on both grids connected and stand
103
Geir Kulia et al. / Procedia Engineering 159 ( 2016 ) 94 – 103
alone microgrids displays the strength of the method, which has enabled us to identify a transfer of frequency (10 ms
Cycle) from the power to the voltage and currents of the microgrid. A similar identification was not possible to achieve
with an FFT analysis of the data. An apparent dierence that emerges from our comparison is the characteristics of
the frequency fluctuation of the synthetically generated data and the field data. The synthetic data shows periodic
characteristics with constant frequency while the field data appears to have high-frequency fluctuations. Further
eorts will be put in distinguishing this dierence more categorically by analyzing data more extensively.
From these results, we expect that measurement equipment able to acquire, analyze and detect electrical grid prob-
lems in the types of grid studied in this paper, will require information about the instantaneous values of frequencies
of the monocomponents of the signal. Our results also indicate that tools such as the EMD will provide a better under-
standing of the electrical waveforms, enabling in the future, better and more accessible microgrid control possibilities.
Acknowledgments
This research was partially supported by Ren-Peace, IUG NTNU, and Department of Electronics and Telecommu-
nications at NTNU.
We thank Norden Huang who provided insight and expertise in his methods by spending tens of hours teaching
and discussing them with us. His open-mindedness and generosity have been a tremendous source of inspiration.
The data analysis would not have been verified without the measurements preformed at RUB. It is therefore in place
to thank Tshewang Lhendupand, Cheku Dorji and my travel partner and coworker Håkon Duus for their assistance in
collecting data from the microgrids.
We would also like to acknowledge the contribution of Helge Seljeseth at Sintef AS for providing data from
Hundhammerfjellet windmill park.
The icons in fig. 4 were designed by Freepik.
References
[1] IEEE Standard 519, IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems, New York, IEEE Power
Energy Society, 2014
[2] Norden E. Huang, Zheng Shen, Steven R. Long, Manli C. Wu, Hsing H. Shih, Quanan Zheng, Nai-Chyuan Yen, Chi Chao Tung and Henry H.
Liu, The Empirical Mode Decomposition and the Hilbert Spectrum for Nonlinear and Non-Stationary Time Series Analysis, London, United
Kingdom, Royal Society, 1996
[3] Norden E. Huang, Samuel S. P. Shen Hilbert-Huang Transform and Its Applications, 2nd ed. Singapore, World Scientific publisher Co. Pte.
Ltd., 2014
[4] Hirofumi Akagi, Edson Hirokazu Watanabe, Mauricio Aredes, Instantaneous Power Theory and Applications to Power Conditioning, IEEE
Computer Society Press, New York, Wiley, 2007
[5] Mohan, Undeland, Robbins, Power electronics - Converters, Applications, and Design, 3rd ed. New York, Wiley, 2003
... Due to the penetration of the new technologies, such as non-conventional sources of renewable energies (NCSRE) in distribution networks, the harmonic distortion of current and voltage waveform is becoming an important issue [4]. Therefore, it is necessary to develop new methodologies for the analysis of signals that have a wide content of harmonics and noise from NCSRE signals [5]. ...
... The instantaneous frequency is defined by (5). ...
... In this paper we have discussed different methods of signal analysis, in order to find the most efficient strategy in terms of frequency separation for signals with high noise content, characteristic of signals with high penetration of Non-Conventional Sources of Renewable Energies [5]. In Fig. 4, it is possible to see the IMFs obtained with EMD Masking, which do not adequately break down the signal, this is caused by the high noise of the signal; this being evident in Fig. 5. ...
Conference Paper
Full-text available
This paper aims to develop a combination method for the evaluation of power quality disturbances. First, we apply the Fast Fourier Transform, Wavelet Transform and Hilbert Huang Transform on a synthetic signal that represents typical behavior in a power system with high penetration of Renewable Energies. Then, we combine the methods to extract the best of each of these and achieve a better signal decomposition. The paper seeks to generate decision criteria on the method of analysis of signals to be used according to the application.
... After an extensive study of IEC Standard 61000-4-7 measuring methods, [4] states that these methods do not produce accurate results in environments with time-varying angular frequency. Keeping the aforementioned problems of nonlinearities and time-varying quantities in mind, measurements and estimation in isolated microgrids should rather be based on instantaneous amplitude and frequency rather than the usage of average values [1,5]. With improved data acquisition-and measurement tools, the supervisory control systems in isolated microgrids may perform better actions, and earlier hidden distortions may be revealed. ...
... The notions of instantaneous amplitude and frequency for general signals are not welldefined [5,37]. For a perfect sinusoid, the instantaneous frequency will be f = 1 T . ...
... The HHT, in fact a NASA designated name, combines EMD and the aforementioned HT, and is well suited for analysis of non-stationary signals. The use of HHT has proven useful for obtaining instantaneous amplitude, frequency and power in power systems and isolated microgrids [1,5,38,39]. As will be outlined in the next subsection, the EMD decomposes signals into monocomponents/IMFs. ...
Thesis
Full-text available
Several cases with time varying frequencies have been reported in isolated electrical systems such as stand-alone microgrids and marine vessel power systems. This thesis studies the use of several types of Kalman filters (KF), Hilbert-Huang Transform (HHT) and the proposed method of merging empirical mode decomposition (EMD) and KF for the purpose of tracking instantaneous values of voltage- and current waveforms in isolated microgrids with the aforementioned challenges. Both synthetic signals and real measurements from a marine vessel power system were used to validate the methods. The algorithms and methods were implemented in Matlab and Simulink. In varying degrees, the methods did all prove to be viable options for tracking of the fundamental frequency on the marine vessel. The proposed method turned out to be particularly powerful to decompose multicomponent signals consisting of several time-varying monocomponents, and track their instantaneous amplitude and frequency.
... Frequency is an elemental descriptor of an oscillation, and one might expect different instability modes to show distinct frequency characteristics, yet the ordinary Fourier spectra may be not enough in this context. To be specific, frequency modulation (FM) effect has been reported in both control-involved waveform distortion [2,3] and harmonic oscillation [4], indicating that the instantaneous frequency (IF) [5,6] of VSC is constantly varying, rather than discrete frequency components, as is commonly recognized. Besides, the site signals can be rather complex that both the amplitude and the frequency are vary-ing with time. ...
Conference Paper
Full-text available
With the increasing penetration of voltage-source-converter (VSC) -interfaced distributed generations(DGs) in power systems, oscillation issues have been widelyconcerned whereas the root cause and nature of the oscilla-tion is sometimes not clear in real cases. This paper focuseson the instability mode recognition (IMR) based on a com-plete data-driven approach applied to the oscillation waveswhich can be obtained from the on-site recordings. To thisend, we explore the Hilbert-Huang Transform (HHT) fordiagnosing the root cause of instability, using only raw datasuch as the current and voltage waveforms which are acces-sible by operators. Special attention is paid to distinguishbetween the sub-synchronous oscillation (SSO) and the lossof synchronization (LOS) as they are two primary instabil-ity forms of grid-tied VSC which manifest with very similarwaveforms. The pros and cons of the considered signalanalysis tools in SSO and LOS recognition are discussed andnew lines of investigations are proposed. The analysis andresults presented in this paper could shed light on futuredata-driven analysis, e.g., serving as model-free or hybridmodel database for artificial intelligence-based stabilitydiagnosis and recognition. (PDF) Instability Mode Recognition of Grid-Tied Voltage Source Converters with Nonstationary Signal Analysis. Available from: https://www.researchgate.net/publication/360005412_Instability_Mode_Recognition_of_Grid-Tied_Voltage_Source_Converters_with_Nonstationary_Signal_Analysis [accessed Apr 18 2022].
... The notion of instantaneous frequency (IF) has not been previously explored in power systems, but with the arrival of new technologies such as distributed generation, nonlinear loads and electronic devices was necessary to include that concept [22]. For many years, different methods have been used for the analysis of signals in power systems. ...
Article
Full-text available
The use of Renewable Power Generation brings new challenges related to power quality issues. Furthermore, with the changing power system nature due to the presence of new components such as power electronics in large numbers and distributed generation systems, the tools used for more than a century to analyze signals in this type of systems are no longer providing accurate information with a good resolution in time and frequency domain. To contribute with a new view of the problem, this paper presents a hybrid technique for the analysis of oscillations in Low Voltage distribution systems considering photovoltaic generation. The aim is to characterize the behavior of the system in a time-frequency domain and get the different instantaneous frequencies that appear. The results obtained with this technique are compared with three well-known methods of analysis. The validation of the methodology is carried out in a real-time digital simulator of a distributed system with Photovoltaic generation.
... Geir Kulia et al. [34] developed a software platform to analyze the real-time electrical voltage and current waveforms for islanded microgrids. Hilbert Huang Transformation based Empirical Mode Decomposition (HHT-EMD) was used as a key building block for the above analysis. ...
Conference Paper
Full-text available
Highly fluctuating renewable sources create enormous stability issues in microgrids. Small signal and transient stability are the major classifications in microgrid stability. For small signal studies, eigenvalue analysis based on state space modeling is the most common method. Detailed dynamic modeling of the system is required for transient analysis. Since transient stability is related to larger disturbances, it creates power imbalance problem in microgrids. Therefore, calculation of power imbalance is an essential study for an islanded microgrid. This paper gives a review of the existing microgrid stability analysis methods. It also suggests a real-time stability monitoring method for islanded microgrids. A classification method along with feature extraction is presented to identify load disturbances based on the amount of load change by using frequency oscillation data. The method is validated using MATLAB simulations applied to a simple microgrid system.
... The new technologies, such as non-conventional sources of renewable energies (NCSRE), Non-linear loads and electronic devices, are producing critical variations in the behavior of the transmitted wave form, therefore it is necessary to develop new methodologies for the analysis of signals which have a wide range of characteristics [1]. The results with the traditional methods are not the best because the time-frequency resolution has some problems in the detection of low frequencies and small variations in the oscillations. ...
Chapter
Full-text available
This paper describes the development and implementation of a methodology for the signal analysis in non-conventional energy systems. The proposed methodology involves the Hilbert-Huang transform supported by Empirical Mode Decomposition (EMD) to decompose one signal in its intrinsic mode function (IMF). A computational tool designed in MATLAB is used to detect oscillations and different frequencies of a non-linear and non-stationary system
... Geir Kulia et al. [34] developed a software platform to analyze the real-time electrical voltage and current waveforms for islanded microgrids. Hilbert Huang Transformation based Empirical Mode Decomposition (HHT-EMD) was used as a key building block for the above analysis. ...
... The arrival of new technologies such as distributed generation, nonlinear loads and power electronic devices has increased the network complexity and caused new problems in power quality. This has called for new methodologies for analyzing signals which have different characteristics to previously studied ones [1]. One of the most common techniques used in power systems for signal analysis is the Fast Fourier Transform (FFT) with its intrinsic limitation of frequency resolution. ...
Conference Paper
Full-text available
Nonlinear and/or nonstationary properties have been observed in measurements coming from microgrids in modern power systems and biological systems. Generally, signals from these two domains are analyzed separately although they may share many features and can bene�t from the use of the same methodology. This paper explores the use of Hilbert-Huang transform (HHT) and Wavelet transform (WT) for instantaneous frequency detection in these two di�erent domains, in the search for a new adaptive algorithm that can be used to analyze signals from these domains without the need to make many a-priory adjustments. Two signals are selected for the investigation: a synthetic signal containing a time varying component and a real EEG signal obtained from The Ecole Polytechnique Federale de Lausanne. The two signals are analyzed with HHT and a discrete WT (DWT). When interpreting the results obtained with the synthetic signal, it is clear that the HHT reproduces the true components, while the DWT does not, making a meaningful interpretation of the modes more challenging. The results obtained when applying HHT to the EEG signal shows 5 modes of oscillations that appear to be well behaved Intrinsic Mode Functions (IMFs), while the results with DWT are harder to interpret in terms of modes. The DWT requires a higher level of decomposition to get closer to the results of the HHT, however multi-frequency bands may be useful depending on the application. The reconstruction of the signal from the approximation and detail coe�cients shows a good behavior and this is one application for DWT especially for removing the unwanted noise of a signal.
... For many years, Fourier-based analyses were enough to study signals in power systems. The arrival of new technologies such as distributed generation, nonlinear loads and electronic devices causes problems in power quality, and this has generated the necessity to develop new methodologies for analyzing signals which have different characteristics to previously studied (Geir et al., 2016). One the most common strategies used in power systems for signal analysis has been fast Fourier transform (FFT), but a big limitation is frequency resolution; therefore, new methods for accurate and fast disturbance detection are necessary. ...
Article
Full-text available
Purpose Nowadays, an extra consumption of electric energy in the Colombian houses is generated due to electric or electronic elements plugged into the electric network. This fact produces a cost overrun in the user’s electricity bills. To reduce this extra cost, and also with a plus of reducing greenhouse gas emission, a monitoring system for the consumption of electric energy in a household will be designed and implemented to make electricity users realize how much money and energy is being wasted due to the unnecessary electric elements plugged into the network. This paper aims to show a monitoring system that allows the client to supervise the consumption of some appliances inside his/her home, remotely. It is also considered the HMI to be able to log in, choose the intervals of data and generate reports and graphics. The monitoring system is based on the integration of several technologies that are already used and implemented in houses and buildings, such as: measuring and treatment of data electronically using microcontrollers, Wi-Fi technology and dynamic graphic interface (website). Design/methodology/approach The methodology consists of several tasks, starting from documentation of the variables, instrumentation and methods for getting to the solution; the first part of the methodology focuses on selecting the electric and/or electronic elements to be monitored, so the instrumentation is able to monitor. Then, the power stage was implemented in this stage to measure signals from the sensors while sensing the electric nodes are adjusted, so does the transmission and reception. In the third stage, the design information system was implemented; this is where the received data from the sensors are stored and managed for further organization and visualization. Activities included the following: Analysis of the model of use cases: Identification of actors and actions that are involved in the system. Server selection: Study of the different server to manage the database. Design of the database: The variables, tables, fields, profiles are determined for managing the information. Connection between sensors and database: Correct data transmission and managing to the database from the sensors. Finally, the system is validated in a rural house for a month. Findings The monitoring system satisfies the main objective of making a tracing of the behavior of some appliances inside a house, showing graphically the instant current generated while connected, the cumulated energy consumed and the cost in Colombian pesos of the energy consumed so far, in real time. Research limitations/implications The monitoring system requires the correct functioning of the sensors connected to each household appliance in the home. Practical implications The main approach in the monitoring platform is the real-time measurement of energy consumption by nodes (in each appliance) that allows the user to control the money. The innovative impact of the project will be based on the use of hardware and information systems in the measurement of electrical consumption. Social implications This research has a direct impact on the economic aspects of the low-income population by allowing them to manage their energy consumption through the proposed system. Originality/value The main approach in the monitoring platform is the real-time measurement of energy consumption by nodes (in each appliance) that allows the user to control the money.
Research Proposal
Full-text available
Aim of the project: David against Goliath: Could Small Data from single-channel or low-density EEG compete in the Big Data contest with high density EEG on equal footing or could David and Goliath join forces? Yes, they can and FlexEEG will show how. FlexEEG proposes a new concept of dry single-channel EEG with enriched information extraction that will materialize into a sensor-embedded data-driven approach to the real-time localization of brain activity. Level of impact and excellence: While a laboratory setting and research-grade electroencephalogram (EEG) equipment will ensure a controlled environment and high-quality multiple-channel EEG recording, there are situations and populations for which this is not suitable. FlexEEG aims at validating a new concept of single-channel or low-density EEG system that while being portable and relying on dry-sensor technology, will produce recordings of comparable quality to a research-grade EEG system but will surpass the capabilities and scope of conventional lab-based EEG equipment: In short, a single more intelligent EEG sensor could defeat high-density EEG. Conventional EEG is challenged by high cost, immobility of equipment and the use of inconvenient conductive gels. Ease of use and quality of information extraction are much awaited in a new EEG concept that produces recording of comparable quality to a research-grade system but that puts EEG within the reach of everyone. FlexEEG will bring that. This project will exploit methods of inverse problems, data-driven non-linear and non-stationary signal analysis 1,2,3 combined with dry-sensor technology to develop a pioneering system that will enable a single, properly localized EEG channel, to provide research-grade information comparable to and surpassing the capabilities of high density-channel EEG. Through this, the range of applications of EEG signals will be expanded from clinical diagnosis and research to healthcare, to better understanding of cognitive processes, to learning and education, and to today hidden/unknown properties behind ordinary human activity and ailments (e.g. walking, sleeping, complex cognitive activity, chronic pain, insomnia). This will be made possible by the implementation of adaptive non-linear and non-stationary data analysis tools in combination with inverse modelling to solve the brain-mapping problem.
Article
Full-text available
A new method for analysing nonlinear and non-stationary data has been developed. The key part of the method is the `empirical mode decomposition' method with which any complicated data set can be decomposed into a finite and often small number of 'intrinsic mode functions' that admit well-behaved Hilbert transforms. This decomposition method is adaptive, and, therefore, highly efficient. Since the decomposition is based on the local characteristic time scale of the data, it is applicable to nonlinear and non-stationary processes. With the Hilbert transform, the 'instrinic mode functions' yield instantaneous frequencies as functions of time that give sharp identifications of imbedded structures. The final presentation of the results is an energy-frequency-time distribution, designated as the Hilbert spectrum. In this method, the main conceptual innovations are the introduction of `intrinsic mode functions' based on local properties of the signal, which make the instantaneous frequency meaningful; and th
Article
The prelims comprise: Half Title Title Copyright Dedication Contents Preface
IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems
IEEE Standard 519, IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems, New York, IEEE Power Energy Society, 2014