Conference PaperPDF Available

Noise within a Data Center

Authors:

Abstract and Figures

Data centers with its numerous servers, network switches, routers and air conditioning equipment produce significant noise that influences work and communication of maintenance staff. Noise levels and spectrum within a data center are measured and analyzed. Daily and weekly variations of noise levels are also captured. From measured noise levels and spectrum speech intelligibility measures are calculated and communication distances within a data center are determined. The need for noise protection and methods for noise reduction are considered.
Content may be subject to copyright.
1352 MIPRO 2016/CTS
Noise within a Data Center
Dubravko Miljković
Hrvatska elektroprivreda, Zagreb, Croatia
dubravko.miljkovic@hep.hr
Abstract - Data centers with its numerous servers, network
switches, routers and air conditioning equipment produce
significant noise that influences work and communication of
maintenance staff. Noise levels and spectrum within a data
center are measured and analyzed. Daily and weekly
variations of noise levels are also captured. From measured
noise levels and spectrum speech intelligibility measures are
calculated and communication distances within a data
center are determined. The need for noise protection and
methods for noise reduction are considered.
I. INTRODUCTION
Work in a data center exposes staff to some
suboptimal working conditions. Noise, temperature and
air circulation are three of the biggest environmental
issues that data center workers face. Air-condition and
equipment cooling fans necessary for the proper operation
of IT equipment run continuously and create excessive
noise that influence comfort, poses risk to hearing and
impairs communication and concentration. With the
introduction of smaller hardware, data center is even more
densely populated and noise inside is becoming louder.
Constant humming of air-conditioners and servers within
a data center may create noise sometimes in excess of 80
dBA. Although maximum acceptable 8 hour exposure
level in most countries is set at 85 dBA, as 10% of the
level that does not show any effect (NOEL - No Observed
Effect Level), this level is far above levels prescribed for
mentally demanding work and office environment.
II. SOURCES OF DATA CENTER NOISE
Data centers consist of servers, routers, switches,
storages, tape systems, UPS and cooling equipment
(HVAC – Heat Ventilation Air Condition). Main sources
of data center noise are shown in Fig. 1. HVAC with its
supply ventilation ducts is a single main source of a data
center noise, with noise level typically about 70 dBA.
Within IT equipment main contributors to data center
noise are cooling fans installed in numerous servers,
routers, switches and storages, although some minor noise
comes from disks, tape drives, transformers and human
Figure 1. Main sources of data center noise
intervention. Individual servers produce noise levels in a
40-70 dBA range, depending on the brand and size, [1].
The sound power (not SPL) of centrifugal and axial
fans (such are used in HVAC ventilation ducts) is given
by (1), [2]:
NWW CBFIPQKL
1010 log20log10 (1)
where
LW sound power level
KW specific sound power level depending on a type
of fan (obtained from manufacturer data)
Q volume flow rate
P total pressure (inches of H2O)
BFI blade frequency increment, correction for pure
tone (obtained from the graphs)
CN efficiency correction (out of optimum flow
conditions, obtained in tables)
When there are hundreds of servers, with hundreds of
cooling fans, noise levels are considerably higher than in
the case of one server. Considering them as noise sources
that are not coherent, level difference is given by (2):
ΔL = 10 × log n (2)
where
ΔL is the level difference
n is the number of equally loud noise sources
Permissible Exposure Time for various noise levels
(according to NIOSH) may be calculated using (3), [3].
t = 480 / 2(L - 85)/3 (3)
where
t is maximum exposure duration (seconds)
L is noise exposure level (dBA)
3 is exchange rate (dBA), i.e. for noise level increase
of 3 dBA, permissible exposure time is cut in half
Permissible exposure time for noise - guidelines for
level and duration (time) are shown in Table I, [4]. Noise
exposure level/times exceeding those shown in table
require use of hearing protection. When considering
working conditions for technicians and visitors in a data
center, high noise levels influence not only hearing and
communication but negatively influence concentration
needed for performing complex cognitive tasks. Some
kind of protection may be needed, especially for workers
working long shifts to increase concentration, comfort and
TABLE I. PERMISSIBLE TIME EXPOSURE
Level, dBA 85 88 90 92 94 95 100 105 110 115
OSHA PEL 16 8 4 2 1 0,5 0,25
NIOSH REL 8 4 1 0,25
Duration (in hours) of allowable exposure based on OSHA and NIOSH
criteria. PEL = Permissible Exposure Limit; REL = Recommended
Exposure Limit
MIPRO 2016/CTS 1353
prevent undesirable extra-aural effects (influence on the
autonomous system), [5]. When noise levels exceed 85
dBA, hearing conservation programs are required. This
includes baseline audiometric testing, noise level
monitoring or dosimetry, noise hazard signage, education
and training, [6]. Once levels exceed 87 dBA (in Europe)
or 90 dBA (in the US), further measures are required like
use of hearing protection, rotation of employees, or
engineering controls must be taken, [6].
III. SPEECH COMMUNICATION UNDER NOISY
CONDITIONS
During various installation and maintenance works
communication between staff is of utter importance.
Normal conversation tends to occupy 60-70 dBA range.
Speech communication in data center is degraded by the
masking effect of the background noise and changes in
vocal effort are necessary for various background noise
levels, [7], as shown in Fig. 2, [8], and Table II.
Figure 2. Long-term spectrum of speech under various vocal efforts
(adopted from [8])
TABLE II. SPEECH LEVELS AT VARIOUS VOCAL EFFORTS
Voice Average level dB/dBA
Casual 52.0/42.0
Normal 57.0/47.0 (private speech)
Raised 64.0/57.0
Loud 73.0/62.0
Shout 85.0/72.0
Auditory masking is intrusion of unwanted sounds
that interfere with the speech signal. Masking effect of
data center noise in spectral domain is illustrated in Fig.
3-5. When the low-frequency noise is louder than the
Figure 3. Spectrogram of speech (‘Noise within a data center’)
Figure 4. Spectrogram of data center noise
Figure 5. Spectrogram speech plus data center noise combined
speech signal it effectively masks speech. At high sound
pressure levels such noise effectively masks both vowels
and consonants. High-frequency noise masks only the
consonants, and its masking effectiveness decreases as
the noise gets louder, [9]. Noise exposure levels in a data
center afford less than desired intelligibility (< 95%).
IV. DATA CENTER NOISE MEASUREMENTS
Noise measurements were performed in mid-size
corporate data center, of surface area about 170 m2. IT
equipment installed within a data center is listed in Table
III. Temperature inside a data center is kept in 21-22 °C
range with separate cabinet cooling systems blowing out
air at 18-19 °C.
TABLE III. IT EQUIPMENT WITHIN A DATA CENTER
Type Number of devices
Server (physical) 120
Storage 5
Tape subsystem 3
Routers/ Switches 15
Cabinet Cooling System 10
A. Measuring Equipment
Noise levels were measured using the CEM DR-805
Sound Meter. A-level weighting was used due to high
correlation with people’s subjective judgment of the
loudness. Noise signals were recorded at 44.1 kHz
sampling frequency and 16-bit resolution, using simple
Ednet Desktop Microphone with 30 Hz-16 kHz range, HP
ProBook 6570b laptop computer with internal audio card
and YMEC sound measurement and analyzing software.
1354 MIPRO 2016/CTS
Figure 6. Data center schematic
B. Measured Noise Levels
Noise was measured at 19 different places, 15 in a
data center and 4 in accompanying spaces (console room,
archive, operators room and at the entrance hall) shown
in data center schematic, Fig. 6. All noise measurements
were performed at the head level while in standing
position. Measurement results are shown in Table IV.
Noise level depends if it is measured in a cold or hot
aisle. The lowest level in a data center was around 70
dBA and the highest slightly above 80 dBA. Similar
values are common in data centers, [10]. Higher levels
were measured in hot aisles (where cooling air gets out of
servers). The highest level was measured near routers
with particularly noisy cooling fans. These levels are
bellow maximum acceptable levels. However repeated
exposure to noise levels between 75 and 85 dBA may
pose a small risk to some people, [11]. Being so close to
the limit and considering excess risk of long term
exposure, [4], it may be wise to take no chances and wear
some hearing protection. Noise in accompanying spaces
was much lower (under 60 dBA). Although this is much
less than in data center and staff got used to it, prolonged
stay is still quite unpleasant for unaccustomed visitors.
C. Noise Spectrum
Spectrum of data center noise is shown in Fig. 7.
Please note harmonic content at frequency range from
150 Hz up to 1.5 kHz that originates from air condition
TABLE IV. NOISE LEVELS AT VARIOUS POSITIONS
Position Description, contributing sources in aisle dBA
1 Servers, storage, cabinet cooling system 76,2
2 Servers, storage, cabinet cooling system 76,1
3 Servers, storage, cabinet cooling system 79,2
4 Servers, storage, cabinet cooling system 76,9
5 Servers, storage, cabinet cooling system 78,1
6 Servers, cabinet cooling system 79,1
7 Servers, storage, cabinet cooling system 74,2
8 Servers, cabinet cooling system 75,0
9 Servers, cabinet cooling system 74,7
10 Servers, cabinet cooling system 73,9
11 Servers, cabinet cooling system 70,9
12 Servers, cabinet cooling system 70,9
13 Routers 75,2
14 Routers 80,3
15 Fire central (alarm and dischargers) 70,7
16 Console room 57,8
17 Archive 55,6
18 Operators room 58,5
19 Entrance hall 58,3
and IT equipment cooling fans. These fans operate at
discrete frequencies, and certain frequencies like blade
passing frequency (BPF), have more power than others.
BPF is the product of the fan rotation speed and the
number of fan blades, (4), [2]:
60
BR NN
BPF (4)
where BPF is the basic frequency of fan tonal
components, NR is the fan rotation speed (rotations per
minute, RPM) and NB is the number of fan blades.
Numerous harmonics are present as multiples of BPF.
There is also a considerable noise in a frequency range of
2-7 kHz due to the turbulent air flow produced by the
fans. Above 7 kHz noise rapidly diminishes.
Figure 7. Spectrum of data center noise
D. Daily and Weekly Variations
Data centers have its temperature fluctuations that
may indirectly (due to different cooling requirements)
influence noise levels. This includes:
daily variation caused by daily swings in the IT load
and outdoor temperature
day-to-day variation caused by the weather
IT load reduction on weekends
Daily noise variations measured at position 3 in data
center schematic from Fig. 6, are shown in Fig. 8.
MIPRO 2016/CTS 1355
Figure 8. Daily noise variations (linear amplitude scale, working day)
Noise level is quite constant with occasional spikes
due to human influence (opening data center doors,
opening server cabinets, loud communication etc.). Noise
levels averaged in four hour periods are shown in Table
V. Summary of daily variations, but averaged over 5s
period are given in Table VI. Weekly noise variations of
daily averages are given in Table VII.
TABLE V. DAILY NOISE VARIATIONS
Noise level (4
hour average) dBA
0-4 4-8 8-12 12-16 16-20 20-24
79,4 79,4 79,3 79,3 79,4 79,4
TABLE VI. DAILY NOISE VARIATIONS SUMMARY
Noise level
(5s average) dBA
min max aver
78.5 88.3 79.4
TABLE VII. WEEKLY NOISE VARIATIONS SUMMARY
Noise (daily
average) dBA
Sun Mon Thu Wen Thu Fri Sat
79,3 79,3 79,4 79,5 79,4 79,4 79,4
Data center where the measurements have taken place
is working with low utilization of computing resources
and main contributor to temperature changes is the
weather alone. As can be seen from our particular case,
noise variation during a period of one day and week are
negligible. In some data centers temperature fluctuations
may be up to 9 ºC depending on the time of day, season
and the current weather. Much lower temperature
excursions (just few degrees) are common in most data
centers.
V. MEASURED NOISE LEVELS, SPEECH
INTELIGIBILLITY AND COMMUNICATION DISTANCE
Several noise metrics have evolved for assessing the
influence of noise on speech, [12].
A. Speech Interference Level (SIL)
Speech Interference Level is defined as the arithmetic
average of the sound pressure levels at 500, 1000, 2000
and 4000 Hz octave bands, (5), [12, 13].
4
400020001000500 pppp LLLL
SIL
(5)
A-weighted sound level Lpa correlate well with SIL for
most sounds in aviation, [2]. Acceptable results of SIL
values maybe derived from A-weighted noise levels by
using the following approximate expression, (6), [13]:
10pA
LSIL (6)
For data center noise spectral content shown in Fig. 7 and
put into (5), more appropriate expression would be (7):
5,12
pA
LSIL (7)
B. Articulation Index (AI)
Articulation Index (AI) is the value, between 0 and
1.0, which describes the masking of speech by
background noise. An AI of 1 means that all speech can
be understood, and 0 that no speech can be understood.
An AI < 0,05 means very poor speech intelligibility, and
an AI > 0.80 good speech intelligibility. AI is found by
evaluating the signal to noise ratio in specific frequency
bands, [12], according to (8), [14].

30
12
1
i
n
i
iSNRI
AI (8)
where
AI is the Articulation Index
Ii is the frequency importance function for band i
SNR is the Signal-to-Noise Ratio for band i
AI can be calculated from the 1/3 octave band levels
between 200 Hz and 6300 Hz center frequencies, using
the AI calculator, shown in Fig. 9, [15].
Figure 9. AI Calculator
C. Speech Intelligibility Index (SII)
The Speech Intelligibility Index (SII), [12, 16, 17], is
a standardized objective measure which is correlated with
the intelligibility of speech under a variety of adverse
listening conditions. SII is a function of the long-term
average spectrum of the speech and noise signals and is
based on the Articulation Index. SII and the AI are not
the same thing, but are quite similar. The SII, like the AI,
is a quantification of the proportion of speech information
that is both audible and usable for a listener. The SII is
computed as a product of the frequency band importance
function Ii, and the band audibility function Ai, (9).
n
i
ii AISII
1
(9)
The value of the SII varies from 0 (completely
unintelligible) to 1 (perfect intelligibility). SSI can be
determined using the SII Calculator, Fig. 10, [17].
Speech intelligibility in a data center is determined
according to mentioned intelligibility measures. Values
for SIL were determined using (5) and scaling the noise
values. In a similar way values for AI and SII were
determined using AI and SII calculator (for SII calculator
1356 MIPRO 2016/CTS
Figure 10. SII Calculator
user specified male speech spectrum normalized to 70 dB
SPL was supplied). Speech intelligibility values for
various noise levels are listed in Table VIII. At levels
within a data center, staff have to talk loudly to be heard.
D. Communication Distance
The distance between the talker and listener (i.e.
communication distance) is important when the
conversation takes place. Speech levels are reduced
typically by 6 dB for each distance doubling between the
talker and listener. Communication distances for various
values of SIL are shown in Fig. 11, [18], and for various
noise levels encountered in a data center in Table VIII.
Figure 11. Communication distance for various values of SIL
(adopted from [18])
TABLE VIII NOISE LEVELS, SPEECH INTELLIGIBILITY MEASURES AND
COMMUNICATION DISTANCES
Noise
level, dBA
Speech intelligibility1 Communication distance (m)
SIL AI SII normal speech loud speech
552 42,5 0,82 0,66 2,6 9,5
602 47,5 0,66 0,53 1,2 4,5
70 57,5 0,34 0,23 0,44 1,6
72 59,5 0,28 0,17 0,35 1,2
74 61,5 0,22 0,12 0,29 1,0
76 63,5 0,17 0,08 0,23 0,76
78 65,5 0,11 0,06 0,18 0,66
80 67,5 0,06 0,04 0,14 0,53
82 69,5 0,03 0,03 0,13 0,44
84 71,5 0,01 0,02 0,10 0,34
1normal speech, 2noise levels at accompanying spaces
VI. POSSIBLE NOISE REDUCTION SOLUTIONS
A. Passive Noise Reduction
Data center with its walls, floors and ceiling surfaces
provide little acoustic absorption. Conventional passive
acoustic absorption materials are not used because they
are highly flammable and may emit particulates that may
trigger fire detection sensors, [19]. Materials used in a
data center must be properly fire rated and fiber free.
They can be mounted on walls and suspended from
ceilings preventing reflections, reducing reverberation
and preventing noise build up. It is also possible to use
sound dampening server cabinets that use acoustic foam.
Passive noise protection headphones may be used for
tasks where no communication is needed. Conventional
hearing protection or noise protection headphones restrict
the workers ability to communicate. If communication
among workers is needed, headphones with integrated
wireless communication (like Bluetooth) could be used.
B. Active Noise Control
Noise within a data center consists of tonal and
broadband components. Tonal components originate from
HVAC fans and equipment cooling fans with pronounced
discrete spectrum. Broadband component originates from
turbulent airflow. Active Noise Control (ANC) is quite
successful at eliminating tonal components. Eliminating
these low to mid frequency components would greatly
reduce the amount of noise present in the data center.
ANC is generally not suitable for noise attenuation in
large spaces, but is mostly restricted to generating local
zones of silence. ANC over an extended region is not
possible in the data center room in general, [20]. This is
due to the random nature of the noise and the high modal
density of the room itself. If trying to suppress noise
within a large space better approach is to attenuate noise
at the source itself, like at ends of ventilation ducts.
ANC can be successfully applied for silencing HVAC
ventilation ducts, [21, 22], Fig. 12. Ventilation ducts
contain low to mid frequency tonal and broadband noise.
ANC systems for silencing ventilation ducts have been
developed decades ago, but with reduced cost of signal
processing hardware are becoming feasible for common
use. In laboratory, ANC can achieve 15-25 dB additional
noise reduction at frequency range of 50-350 Hz, [21],
and values of 10-15 dB are reported in a real world, [22].
Specially designed add-on unit can be installed at the end
of a pipe emitting or sucking air and generating noise.
ANC within servers, integrated with cooling fans, is
something to be common in a future. Such system uses a
magnetic field to generate minute vibrations in fan
blades. A microphone samples the noise and then tunes
the fan blade vibration to cancel it out, [23].
Figure 12. ANC in a ventilation duct
MIPRO 2016/CTS 1357
ANC headphones, [24], can provide greater deal of
protection, however most of ANC headphone designs are
optimized for aircraft use. Although ANC headphones are
successful at reducing noise, they also reduce the ability
to hear speech and remain aware of surroundings. Some
communication headphones combine speech enhancement
with noise suppression technology that elevates speech
and suppresses dangerous background noise so workers
can hear speech and stay protected in high noise
environments, [25]. Sometimes even situational awareness
with speech and noise direction recognition is preserved.
C. Lowering Cooling Requirements
HVAC is the main source of noise in a data center.
According to [6], 20% increase in cooling air speed
equates to a 4 dB increase in noise level. By reducing
HVAC activity it is possible to reduce noise.
Lower cooling requirements on HVAC can be
achieved by implementing higher degree of virtualization
and hence achieving higher CPU usage and the lower
number of necessary physical servers. Overall power
consumption, cooling requirements and noise levels go
down. However efficiency of power and cooling
infrastructure gets worse because of underloading, [26].
Another approach is raising target temperature within
a data center, [27]. The higher the target temperature in a
data center, the lower is the cooling requirement. HVAC
unit should not necessary run at full capacity at all times.
Increasing target temperature for just few degrees during
maintenance activities would lead to a quieter work
environment for employees. Recommendations for air
temperatures in data centers (Class 1 requirements) put
them in a range 18-27 °C (allowable 15-32 °C), [28]. As
an approximation it may be expected that 2°C increase in
data center temperatures would cause noise decrease of
3-5 dB, [6]. Server fans will, however, try to compensate
for diminished HVAC operation using the server built-in
temperature-based fan speed control, adding some noise.
VII. CONCLUSION
Measured noise levels within a data center were in
70-80 dBA range (as in other data centers). These levels
are below maximal acceptable eight hour exposure limit
but are close enough and it may be wise to use some kind
of hearing protection like noise protection headphones.
Prolonged exposure to such noise levels could produce
extra-aural health effects. High noise levels interfere with
performing cognitive tasks, influence autonomous system
and after the long-term exposure may cause behavior
modifications. Noise in a data center significantly
interferes with speech intelligibility (as reflected in
speech intelligibility measures), making communication
among personnel difficult (raising voice and reducing
communication distance). Lightweight ANC headphones
with build in wireless interphones would be beneficial.
Staff should perform as much as possible tasks remotely
from the office, using iLO console or RD connections.
Passive noise reduction with certified fire resistant
materials may be applied to data center surfaces. ANC is
suitable for HVAC ventilation ducts. During extensive
maintenance activities temperature throttling can be used.
REFERENCES
[1] TechMikeNY, Server Guide, Internet: https://techmikeny.com/
server-guide/ [February 29, 2016]
[2] Fan Noise Prediction, Internet: http://www.mne.psu.edu/
lamancusa/me458/11_fan.pdf [February 29, 2016]
[3] Noise Exposure - Permissible Level and Duration, Internet:
http://www.engineeringtoolbox.com/noise-exposure-level-duratio
n-d_717.html [February 29, 2016]
[4] Patricia T. Johnson, Noise Exposure: Explanation of OSHA and
NIOSH SafeExposure Limits and the Importance of Noise
Dosimetry, ER078114 B, Etymotic Research
[5] Sharp L. F., Swiney J. F., Dansby M. R., Hyatt S. C. & Schimmel
D. E.: Behavioral and physiological correlates of varying noise
environments, EPA-600/1-77-038, EPA, June 1977
[6] ASHRAE Publication, 2008 ASHRAE Environmental Guidelines
for Datacom Equipment, ASHRAE, 2008
[7] Pearsons K., Bennett Ricarda L. & Fidell S.: Speech levels in
various noise environments, EPA-600/1-77-025, EPA, May 1997
[8] P. H. Stypulkowski, Circuitry options, signal processing under
altered signal conditions, in Tobin, H (ed.): Practical Hearing Aid
Selection and Fitting, DIANE Publishing, 1997
[9] R. Jones, Factors That Affect Intelligibility in Sound Systems,
Meyer Sound, Internet: http://www.meyersound.com/support/
papers/speech/section2.htm [February 29, 2016]
[10] D. Alger, DC Deconstructed | Sounds of a Data Center, Cisco,
Internet: https://www.youtube.com/watch?v=EQTgpE35zSM&
nohtml5 [April 6 2015]
[11] National Standard for Occupational Noise [NOHSC: 1007(2000)],
2nd Ed., Canberra, Australia, July 2000
[12] Newman J. S. & Beattie K. R., Aviation Noise Effects, Report No.
FAA-EE-85-2, US DoT FAA, March 1985
[13] D. Miljković, J. Ivošević and T. Bucak, Psycho-acoustical
ergonomics in a light aircraft interior, Proc. of Ergonomics 2013,
pp. 111-116, 12-15 June 2013, Zadar, Croatia
[14] H. Bächler and A. Vonlanthen, Signal processing tools to support
your manner of communication, Phonak Focus 17, 1994
[15] Articulation Index, Internet: http://www.diracdelta.co.uk/science/
source/a/r/articulation%20index/source.html [February 29, 2016]
[16] American National Standard ANSI S3.5-1997, Methods for
Calculation of the Speech Intelligibility Index
[17] SII CALCULATION 1.0, A Software for ANSI S3.5-1997
[18] Transportation Safety Board of Canada (TSB), Railway
Investigation Report R98V0148, [February 29, 2016]
[19] Y. Joshi and P. Kumar (ed.), Energy Efficient Thermal
Management of Data Centers, Springer, 2012
[20] J. Daily, J. Esplin, Z. Collins and M. Shaw, Acoustical Analysis of
Active Control in the Server Room of a C7 Data Centers Colocation
Facility Feasibility Report, Brigham Young Univ., June 21, 2010
[21] M. Larsson, Active Noise Control in Ventilation Systems,
Blekinge Institute of Technology Licentiate Dissertation Series No
2008:12, Karlskrona, Sweden, 2008
[22] L. J. Gelin, Active noise control: a tutorial for HVAC designers,
ASHRAE Journal, August 1997
[23] G. Gasior, Noise-canceling Noctua CPU Cooler Coming in 2014,
The TechReport, Internet: http://techreport.com/news/24947/noise
-canceling-noctua-cpu-cooler-coming-in-2014 [February 29, 2016]
[24] C. Moy, Active Noise Reduction Headphone System, Internet:
http://cero-ruido.blogspot.com/2014/11/active-noise-reduction-hea
dphone-systems.html [February 29, 2016]
[25] Sensear, Data Center Industry Case Study, 2014
[26] Suzanne Niles, Virtualization: ooptimized power and cooling to
maximize benefits, White Paper #118, Schneider Electric, 2011
[27] To Lower the Noise Levels in Data Centers, Raise the
Temperature, Internet: http://www.itwatchdogs.com/environment
al-monitoring-news/data-center/to-lower-the-noise-levels-in-data-
centers,-raise-the-temperature-617409 [February 29, 2016]
[28] 2011 Thermal Guidelines for Data Processing Environments -
Expanded Data Center Classes and Usage Guidance, ASHRAE
TC 9.9, ASHRAE, 2011
... The minimum intensity to detect a sound clearly depends on the distance from speaker to microphone, but in our experiments we played sounds of at least 30dB. Normal conversation is on the order of 50 dB [30]. ...
... ., while conducting our experiments, we heard a misconfigured server beeping for weeks.4 Datacenter noise may exceed 85 dBA[30]. ...
Conference Paper
Full-text available
For several years researchers have used the term "network orchestration" as a metaphor. In this paper, we make the metaphor reality; we describe a novel approach to network orchestration that leverages sounds to augment or replace various network management operations. We test our Music- Defined Networking approach with both a real and a virtual network testbed, on several mechanisms and applications: from datacenter server fan failure detection to authentication, from load balancing to explicit congestion notification and detection of heavy hitter flows. Our approach can be used with and without a Software-Defined Network controller. Despite its limitations, we believe that sound-based network management has potential to be further explored as an effective and inexpensive out-of-band orchestration technique.
... The associated noise decibels and air jet speed were 63 dB and 5.2 m/s. These values are within the acceptable range for data centers and IT-rooms according to [12]. ...
Conference Paper
Full-text available
As the online frameworks and services are growing rapidly with the evolution of web-based Artificial Intelligence (AI) applications, server rooms are upgrading in computational capacity and size to keep up with these demands. Enterprise companies with their limited capacity server rooms struggle to keep up with these increasing computational demands. Hence, some of them end up outsourcing their servers to co-located facilities (Co-Lo) and the others choose to upgrade their existing server rooms. Correspondingly, the thermal load associated with such upgrades is typically tremendous. Approximately around 40% of the power consumed by datacentres is dissipated as heat. Conventional HVAC systems fail to satisfy the requirements of such server capacities. Not only do they struggle to fulfil the cooling load, but their maldistribution of cool air into the server room forms a major cause for hotspots formation. To tackle this issue, Liquid-to-Air (L2A) Coolant Distribution Units (CDUs) are being used as a liquid-based cooling solution for rack-level cooling. This type of CDUs provide efficient cooling for servers through liquid coolant that is distributed into cooling loops mounted on top of each server board. The generated heat is curried away using this liquid coolant back to the CDU, which then dissipates it into the surrounding air using dedicated pumps, fans, and heat exchanger, hence the name Liquid-to-Air. In the present work, one of the most popular liquid cooling strategies is explored based on various scenarios. the performance of a 24-kW liquid to Air (L2A) CDU is judged based on cooling effect, stability, and reliability. The study is curried out experimentally, in which a test rack with three thermal test vehicles (TTVs) are used to investigate various operation scenarios. Both liquid coolant and air sides of this experimental setup are equipped with the required instrumentations to monitor and analyse the tests. All test cases were taken in a room with limited air conditioning to resemble the environment of upgraded server rooms with conventional AC systems. Moreover, the impact of using such high-power density cooling unit on the server room environment with restricted HVAC system is also brought to light. Environmental and human comfort parameters such as noise, air velocity, and ambient temperature are measured under various operation conditions and benchmarked against their ranges for human comfort as listed in ASHREE standards. At the end of this research, recommendations for best practice are provided along with areas of enhancement for the selected system.
... The Heating, Ventilation, and Air Conditioning (HVAC) system and a single server typically produce 70 dBA and 40−70 dBA noise, respectively. The data center scale noise lies within 70 − 80dBA, with higher level observed in the hot aisle [260]. Prolonged exposure in such noisy environment impedes effective vocal communication and potentially harms the hearing of workers. ...
Article
Full-text available
Recently, the rapid growth in both data center power density and scale poses great challenges to the cooling system. On one hand, data center operators try to over provision cooling resources for fear of server failures induced by accumulated heat. On the other hand, they also want to reduce the energy cost as the cooling system takes up a significant portion of overall energy consumption. Among all available cooling solutions, air cooling dominates the data center industry due to its simpleness. However, its cooling efficiency has been questioned due to the low air density and specific heat. In this paper, we provide an overview for current endeavours to improve the air cooling efficiency. We group existing researches according to the locations where they can be applied from the perspective of air flow cycle. We also discuss the thermal measurement issues. We hope this paper can help researchers and engineers to design and control their data center air cooling systems.
Conference Paper
Full-text available
Noise levels in light aircraft interiors, particularly during take-off and climb phases of flight, often exceed acceptable values. Communication between a pilot, copilot and an Air Traffic Control (ATC) staff, as well as among passengers, is severe disrupted in such noisy environments. Based on noise measurements in a typical representative of a light aircraft, its spectral content and corresponding noise levels, parameters relevant to speech intelligibility are calculated. Speech Interference Level (SIL), Articulation Index (AI) and maximum communication distances are determined for various flight phases and vocal efforts.
Conference Paper
In this article, active noise reduction system has been described. The ANR system was made on basis of finite impulse response filter and realised algorithms LMS or NLMS. The algorithms were implemented on the dSPACE card with floating-point processor TMS320C31. Researches were performed in the anechoic chamber and in the enclosure of dimension 4.4 x 3.05 x 3.2 m and reverberation time T = 0.53 s. White noise filtered by third and octave filter with mid-band frequency 125 Hz was used for the experiments. The ANR system working in free field conditions (in the anechoic chamber) allowed to obtain the average acoustic pressure level reduction ranging from 9.1 to 24.1 dB For octave, and 14.7 to 23.1 dB for third octave. Measurements carried out in natural acoustics conditions in a selected room allowed to obtain the following values of average acoustic pressure level reduction: For octave Prom 2.2 to 14.2 dB, and for third octave from 6.4 to 19.8 dB. The result of experiments proved that the convergence time of NLMS algorithm was several times shorter than convergence time of LMS algorithm.
Book
Energy Efficient Thermal Management of Data Centers examines energy flow in today's data centers. Particular focus is given to the state-of-the-art thermal management and thermal design approaches now being implemented across the multiple length scales involved. The impact of future trends in information technology hardware, and emerging software paradigms such as cloud computing and virtualization, on thermal management are also addressed. The book explores computational and experimental characterization approaches for determining temperature and air flow patterns within data centers. Thermodynamic analyses using the second law to improve energy efficiency are introduced and used in proposing improvements in cooling methodologies. Reduced-order modeling and robust multi-objective design of next generation data centers are discussed. © 2012 Springer Science+Business Media, LLC. All rights reserved.
Article
This article will identify the capabilities and limitations of ANC in its application to HVAC noise control. ANC can be used in ducted HVAC systems to cancel ductborne, low-frequency fan noise by injecting sound waves of equal amplitude and opposite phase into an air duct, as close as possible to the source of the unwanted noise. Destructive interference of the fan noise and injected noise results in sound cancellation. The noise problems that it solves are typically described as rumble, roar or throb, all of which are difficult to address using traditional noise control methods. This article will also contrast the use of active against passive noise control techniques. The main differences between the two noise control measures are acoustic performance, energy consumption, and design flexibility. The article will first present the fundamentals and basic physics of ANC. The application to real HVAC systems will follow.
Article
This report summarizes the effects of aviation noise in many areas, ranging from human annoyance to impact on real estate values. It also synthesizes the findings of literature on several topics. Included in the literature were many original studies carried out under FAA and other Federal funding over the past two decades. Efforts have been made to present the critical findings and conclusions of pertinent research, providing, when possible, a bottom line conclusion, criterion or perspective. Issues related to aviation noise are highlighted, and current policy is presented. Specific topic addressed include: annoyance; Hearing and hearing loss; noise metrics; human response to noise; speech interference; sleep interference; non-auditory health effects of noise; effects of noise on wild and domesticated animals; low frequency acoustical energy; impulsive noise; time of day weightings; noise contours; land use compatibility; and real estate values. This document is designed for a variety of users, from the individual completely unfamiliar with aviation noise to experts in the field.
Article
In many kinds of buildings, the ventilation is handled by a mechanical ventilation system. Such ventilation systems constitute a well known source of broadband noise. As awareness of the negative effects that subjection to low frequency noise can have on human well-being has increased, so too has the requirement for quieter ventilation installations. Traditionally, duct born noise is attenuated using passive resistive silencers. These passive silencers are valued for their ability to produce a high level of attenuation over a broad frequency range, however they tend to become large and bulky if designed for low frequency attenuation. The active noise control (ANC) technique is known for its ability to produce high levels of attenuation in the low frequency range even with a relatively moderate sized ANC system. On the other hand, ANC normally tends to be ineffective for higher frequencies. Accordingly, a combination of active- and passive techniques, i.e. the construction of a hybrid active/passive silencer, provides a duct silencer solution of manageable size which also covers the low frequency range. The ANC systems controller normally relies on adaptive digital signal processing. Even so, adequate levels of attenuation are not likely to be obtained if the installation of the ANC system is not designed to account for the physical factors that may degrade its performance. This thesis focuses on applying ANC in ventilation systems, with particular emphasis on analysis and installation design, for the purpose of reducing the influence of some of these degrading physical factors. The degrading factors which are of particular interest include: flow induced noise in the microphone signals, acoustic feedback between the control loudspeaker and reference microphone, and standing waves inside the ducts. With respect to installation design, focus is also placed upon industry requests on the ANC system. Taking this into consideration has led to a module based approach, in which the microphones and the loudspeaker are installed in separate modules based on standard duct parts. This thesis comprises four parts. The first describes initial investigations of potential microphone installations intended to reduce flow induced noise. The second part analyzes the influence of flow induced noise on the digital controller and presents further investigations of microphone modules. Further, results of measurements conducted in an acoustic laboratory according to an ISO-standard are presented. The attenuation produced by the ANC system was approximately 15-25 dB between 50-315 Hz even for airflow speeds up to 20 m/s. The third part of this thesis focuses on the possibility of using the passive silencer with which the ANC system is combined, to reduce acoustic feedback and standing waves. The fourth and final part investigates the possibility of using a passive silencer to reduce standing waves in the duct when the ANC system is not installed near the duct outlet.
Internet: https://techmikeny.com/ server-guide
  • Server Techmikeny
  • Guide
TechMikeNY, Server Guide, Internet: https://techmikeny.com/ server-guide/ [February 29, 2016]
Speech levels in various noise environments, EPA-600
  • K Pearsons
  • L Bennett Ricarda
  • S Fidell
Pearsons K., Bennett Ricarda L. & Fidell S.: Speech levels in various noise environments, EPA-600/1-77-025, EPA, May 1997
  • Sensear
Sensear, Data Center Industry Case Study, 2014
Acoustical Analysis of Active Control in the Server Room of a C7 Data Centers Colocation Facility Feasibility Report
  • J Daily
  • J Esplin
  • Z Collins
  • M Shaw
J. Daily, J. Esplin, Z. Collins and M. Shaw, Acoustical Analysis of Active Control in the Server Room of a C7 Data Centers Colocation Facility Feasibility Report, Brigham Young Univ., June 21, 2010