Research on Fire Endurance of Tempered Glass based on Infrared Imaging Technology

Authors:

Abstract

The tempered glass is widely used in the buildings because of its good transparence and fire endurance under the protection of the sprinkler. The fire backdraft may occur under the good ventilation condition after the tempered glasses fall apart in fire, which can endanger the human evacuation and fire rescue. By the testing of the surface temperature of the tempered glass exposed to the building fire, the critical temperature of the glass fracture can be acquired and the basis for the prediction and prevention of the fracture of the tempered glass then can be provided, which is useful for the performance-based design of the fire safety. The infrared imaging equipment is firstly used in China for the research on the fire endurance of the tempered glass.
Procedia Engineering 84 ( 2014 ) 553 557
Available online at www.sciencedirect.com
1877-7058 © 2014 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/3.0/).
Peer-review under responsibility of scientific committee of Beijing Institute of Technology
doi: 10.1016/j.proeng.2014.10.467
ScienceDirect
2014ISSST”, 2014 International Symposium on Safety Science and Technology
Research on fire endurance of tempered glass based on infrared
imaging technology
LI Mingxuan
*
, LU Guojian, HU Zhongri, MEI Xiujuan, LI Le,WANG Liping
Sichuan Fire Research Institute of MPS, Chengdu, 610039, China
Abstract
The tempered glass is widely used in the buildings because of its good transparence and fire endurance under the protection of
the sprinkler.The fire backdraft may occur under the good ventilation condition after the tempered glasses fall apart in fire, which
can endanger the human evacuation and fire rescue. By the testing of the surface temperature of the tempered glass exposed to
the building fire, the critical temperature of the glass fracture can be acquired and the basis for the prediction and prevention of
the fracture of the tempered glass then can be provided, which is useful for the performance-based design of the fire safety. The
infrared imaging equipment is firstly used in China for the research on the fire endurance of the tempered glass.
© 2014 The Authors. Published by Elsevier Ltd.
Peer-review under responsibility of scientific committee of Beijing Institute of Technology.
Keywords: tempered glass; fire endurance; infrared imaging technology; critical temperature
1. Introduction
With the emergence of diversity of new architectural styles, new materials, and large volume buildings, the
visual translucency and continuity are required in more and more buildings. So the traditional fire compartment,
such as firewalls and fire-resistant rolling shutters are unable to meet such requirements, and more and more
tempered glass are used in the doors, windows and fire compartment. The poor ventilation condition in the
combustion chamber and the lack of oxygen may cause the extinguishing or smoldering of fire, however the good
ventilation condition caused by the fractured glass may form the fire backdraft, which can endanger the fire fighters
and occupants in the building. During the performance-based design of fire safety, the time and possibility of the
* Corresponding author. Tel.: +0-086-028-875-11960; fax: +0-086-028-875-11960.
E-mail address: robustlee@sohu.com
© 2014 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/3.0/).
Peer-review under responsibility of scientific committee of Beijing Institute of Technology
554 Li Mingxuan et al. / Procedia Engineering 84 ( 2014 ) 553 – 557
glass fracture will greatly influence the smoke spread. Many researches on glass fracture have been done at home
and abroad, but the fire fuel are almost the oil , the fire load is also low, and the glasses used in the test are almost in
small size, which do not comply with the real building fire conditions. Thus, a mathematical algorithm for glass
breakage prediction in the FDS is needed [1], and the full-scale test with the tempered glass is used to analyze the
fire endurance of the tempered glass.
Many tests of the fire endurance of the tempered glass with the sprinkler protection have been conducted in China
[2,3], in which the integrity of the tempered glass can maintain for a long time. However, the tests for the fire
endurance of the tempered glass without the protection of the sprinkler have seldom been done, and the efficiency of
the protection of the sprinkler for the tempered glass needs to be further validated.
2. Experimental setup
The testing room with the size of 10 m(L)× 10 m(W)× 5 m(H) for the full-scale test of the fire endurance of the
tempered glass is located at the large-space testing building in Dujiangyan City. The two walls of the testing room
are constructed of concrete block of 20cm thickness, the other two walls are formed by the tempered glass assembly
with the aluminum columns, which is shown in Fig. 1. The facade A is composed of 5 aluminum columns and 4
tempered glass panes with the size of 2.5m(L)×5m(W)×0.012m(T). The facade B is composed of 6 aluminum
frames and 5 tempered glass panes with the size of 2m(L)×5m(W)×0.012m(T). Each of the tempered glasses of
facade B is protected by the window sprinklers installed at top of the tempered glass, and the activation temperature
of the sprinkler is 68 @.The space between the tempered glass and the frame is filled with the fire sealant. The tests
for the fire endurance of the tempered glass with or without the protection of the window sprinkler are analyzed
respectively. And the mechanical ventilation system with the ventilation volume of 60m3/m2.h is used in the
combustion chamber, which complies with China’s codes for building fire protection. The fresh air can be supplied
into the combustion chamber through the door.
At the center of the combustion chamber and near each of the tempered glass, the thermocouples are positioned at
the height of 1.8 m, 3.5 m and 4.8 m from the ground separately, so the temperature of the gas, the tempered glass
and the glass edges can be measured, which is shown in Fig. 2. Two infrared (IR) cameras are positioned 11 m away
from the front of facade A, so the temperature distribution on both sides of the tempered glass can be recorded. For
the better application, the highest Heat Release Rate(HRR) satisfies the requirements for the ordinary places, such as
shopping mall, etc. with the reference to Technical Specification for Building Smoke Control[1]. The maximum
fire load of the shopping mall with sprinkler protection can reach 4MW, while the fire load of public hall without
any sprinkler protection can reach 8 MW. The fire sources are wood cribs, which have been calibrated by the cone
calorimeter according to ISO9705 and SBI before the test [2].
Fig. 1. Testing room. Fig. 2. Tempered glass of Façade A.
3. Data analysis
3.1. Fire scenario I
For the wood crib fire test of 4 MW, Fig. 3 shows the temperature rise of the tempered glass of façade A at 10
555
Li Mingxuan et al. / Procedia Engineering 84 ( 2014 ) 553 – 557
minutes after the ignition, in which the temperature is about 100 @ at 3 m height, and about 40 @ at 1m height. Fig.
4 shows the temperature rise of the tempered glass of façade A at 20 minutes after the ignition, in which the
temperature is about 180 @ at 3 m height, and about 80 @ at 1m height. The temperature difference between the
upper part and the lower part is great because of the smoke stratification. The gas temperature of the upper part is
higher than that of the lower part, because the fresh air comes in from the outside, and the convection between the
different smoke layers causes the different temperature distribution on the tempered glass. Fig. 5 shows the time-
dependent temperature of the tempered glass of façade A at 0.5 m1.5 m2.5 m and 3.5 m height during the test,
and the temperature difference between the upper part and the lower part is not over than 100 @. Fig. 6 shows the
temperature of the 4 points in the horizontal direction for façade A at 3 m height. It shows clearly that the
temperature difference in the horizontal direction is not over than 20 @. It is shown in Fig. 3 and Fig. 4 that the
surface temperature of the tempered glass exposed to the fire source is not obviously higher than that of the other
part of the tempered glass [3], which demonstrates that the radiation is not the dominant factor for the temperature
rise of the tempered glass. The integrity of the tempered glass maintains well during the test, and no glass fracture or
collapse happens [4].
Fig. 3. Temperature distribution on glass 2 and glass 3 at 10 minutes. Fig. 4. Temperature distribution on glass 2 and glass3 at 20 minutes.
Fig. 5. Time-dependent temperature of glass 2 at 4 different heights. Fig. 6. Time-dependent temperature of 4 points of glass 2.
3.2. Fire scenario
C
For the wood crib fire test of 8 MW, Fig. 7 shows that the left upper part of the tempered glass 2 breaks at 540
seconds after the ignition, when the highest temperature on the unexposed side is 300@ and the highest temperature
on the exposed side reach 700 @,which are recorded by the thermocouples. The right upper part of the tempered
glass 3 breaks at 660 seconds after the ignition, when the highest temperature on the unexposed side reaches 335 @
and the highest temperature on the exposed side reaches 650 @, which are recorded by the thermocouples. Fig. 8
shows that the lower part of the tempered glass 2 breaks at 680 seconds after the ignition, when the fracture
temperature of the upper part on the unexposed side is 350 @ and the lower part temperature is 100 @, while the
highest temperature of the upper part on the exposed side reaches 620 @, and the lower part temperature is 150 @,
which shows the great temperature difference between the exposed side and the unexposed side. Fig. 9 shows the
556 Li Mingxuan et al. / Procedia Engineering 84 ( 2014 ) 553 – 557
time-dependent temperature of the tempered glass 2 at 0.5 m, 1.5 m, 2.5 m and 3.5 m height, and the temperature
difference between the upper part and the lower part is around 200 @. Fig. 10 shows the time-dependent
temperature of the tempered glassof 4 points in the horizontal direction at the 3m height, which clearly shows that
the temperature difference in the horizontal direction is narrow.
4. Results
Through the full-scaled fire tests of 4 MW and 8 MW, the integrity of the tempered glass used in the shopping
malls and public buildings without any protection of window sprinkler is studied, the temperature distribution on the
tempered glass is measured, the different temperatures of the glass fracture are recorded and the following results are
included:
(1) The infrared camera(IR) can be used to record the surface temperature of the tempered glass during the whole
test, so the thermocouple installation may be reduced, but the calibration with the thermocouple shall be carried out
before the test.
(2) The temperature of the upper part of the tempered glass is higher than that of the lower part because of the
smoke stratification [5], which shows that the convection has more influence on the temperature rise than the
radiation. Because the tempered glass has no good heat conductivity, the strain caused by the temperature difference
is the key factor leading to the glass breakage.
(3) The tempered glass maintains good integrity in the wood crib fire test of 4 MW, which demonstrates that the
tempered glass used as the compartment item is reliable in the shopping mall under the sprinkler protection[6].
(4) The tempered glass does not maintain the integrity well in the wood crib fire testof 8MW without any
sprinkler protection, and the temperature difference between the exposed side and the unexposed side when the
tempered glass cracks, is about 300 @. So the tempered glass can be used as fire compartment item only when the
reliable window sprinkler is used.
(5) The tempered glass of facade B maintains good integrity in the tests, which demonstrates the effectiveness of
the sprinkler protection.
Fig. 7. Temperature distribution on glass 2 and glass 3 at 540 seconds. Fig. 8. Temperature distribution on glass 2 and glass 3 at 680 seconds.
Fig. 9. Time-dependent temperature of glass 2 at 4 different heights. Fig. 10. Time-dependent temperature of 4 horizontal points on glass 2.
557
Li Mingxuan et al. / Procedia Engineering 84 ( 2014 ) 553 – 557
5. Conclusions and future works
The traditional fire compartment items such as fire wall, fire-resistant rolling shutter, etc. are not characterized
with transparence, which can’t meet the needs of the building designers and owners. The testing results show that the
tempered glass can be used as the fire compartment item under the sprinkler protection. However, the relationship
between the temperature difference and the thermal strain of the heated tempered glass should be studied in the
future research to set up the mathematical model for the prediction of the tempered glass breakage in the building
fire.
Acknowledgement
This research project is funded by “Twelfth Five-Year” National Science and Technology Research Program
(Grant No.2011BAK03B01).
References
[1] Li Mingxuan, Lu Guojian. Full-scale experimental study on tempered glass endurance under fire exposure. Fire Science and Technology,
2013, 32(5): 493-496.
[2] Mei Xiujuan, Zhang Zejiang. Experiment study on single tempered glass with protection of sprinkler as fire compartmentation item. Fire
science and technology, 2007, 26(5): 500-502.
[3] N.D. Pope, C.G. Bailey. Development of a Gaussian glass breakage model within a re eld model. Fire Safety Journal, 2007, 42(7):366376.
[4] Li Jianhua, Zheng Huanghua. Study on Break behavior of common window glass. Fire Science. 1999, 3(8): 21-23.
[5] Sarah Mladenka, Walter Romero,ChrisYeldell,Ofodike, Ezekoye, MichaelE. Cournoyer. Chemical hood glass failure under thermal loading
associated with fire. Journal of Chemical Health&Safety, 2012: 11-13.
[6] Chan-Wei Wu, Ta-Hui Lin. Full-scale evaluations on heat resistance of glass panes incorporated with water film or sprinkler in a room fire.
Building and Environment, 2007, 42(8): 32773284.
... These differences in turn help with the identification of defects. Due to its powerful functions, infrared (IR) thermography has been applied to evaluate mechanical defects and elastic deformations in glass sheets, as well as corrosion defect characterization [84][85][86]. ...
Article
Full-text available
Aluminum windows are crucial components of building envelopes since they connect the indoor space to the external environment. Various external causes degrade or harm the functioning of aluminum windows. In this regard, inspecting the performance of aluminum windows is a necessary task to keep buildings healthy. This review illustrates the deterioration mechanisms of aluminum windows under various environmental conditions with an intention to provide comprehensive information for developing damage protection and inspection technologies. The illustrations reveal that moisture and chloride ions have the most detrimental effect on deteriorating aluminum windows in the long run, while mechanical loads can damage aluminum windows in a sudden manner. In addition, multiple advanced inspection techniques potential to benefit assessing aluminum window health state are discussed in order to help tackle the efficiency problem of traditional visual inspection. The comparison among those techniques demonstrates that infrared thermography can help acquire a preliminary defect profile of inspected windows, whereas ultrasonic phased arrays technology demonstrates a high level of competency in analyzing comprehensive defect information. This review also discusses the challenges in the scarcity of nanoscale corrosion information for insightful understandings of aluminum window corrosion and reliable window inspection tools for lifespan prediction. In this regard, molecular dynamics simulation and artificial intelligence technology are recommended as promising tools for better revealing the deterioration mechanisms and advancing inspection techniques, respectively, for future directions. It is envisioned that this paper will help upgrade the aluminum window inspection scheme and contribute to driving the construction of intelligent and safe cities.
... This process is called annealing phenomenon of tempered glass. And the attenuation rate of surface stress will gradually increase with the increase of heating temperature [5,6]. Therefore, how to maintain the surface stress at a high level on the premise of ensuring the sealing quality is a difficult point in the sealing technology of TVG [7]. ...
Article
In this paper, the safe sealing temperature range of tempered glass was determined to be no more than 300 °C by experiments. On this basis, the feasibility of silver oxide system low melting solder (SOSLMS) used in tempered vacuum glazing (TVG) sealing was explored by sealing strength experiment, scanning electron microscope (SEM), energy dispersive spectrometer (EDS), X-ray diffraction (XRD) and other test methods. The results of sealing strength experiment showed that the bonding strength of the sealing layer was inversely proportional to the sealing temperature. The bonding strength of the sealing layer in the range of 260 °C–290 °C met the standard requirements (not less than 0.6 MPa) except for the failure of the sample sealing at 300 °C. The observation results of SEM showed that when the sealing temperature was 260 °C and 270 °C, the solder layer had uniform fusion and dense structure, and the sealing layer was tightly bonded. With the increase of sealing temperature, the solder layer began to produce large holes, and there was obvious open gap between solder layer and glass substrate after stretching. The analysis results of EDS showed that the Ag and V elements all diffused into the glass at each sealing temperature, the difference of diffusion concentration and distribution was not significant. The analysis results of XRD showed that when the sealing temperature was in the range of 260 °C–270 °C, there was no crystallization phenomenon in the SOSLMS. When the sealing temperature was in the range of 280 °C–300 °C, Ag2VO2PO4 crystals began to precipitate, and with the increase of temperature, the higher the crystallinity was, the greater the crystal content was. In conclusion, in the range of 260 °C–270 °C, the SOSLMS showed good sealing performance, which was suitable for TVG sealing.
... Klassen et al. [29] adopted radiant sources to heat multipane tempered glazing to study the radiant transmission and its breakage characteristics. Li et al. [30] adopted the infrared imaging technology to obtain the critical temperature of the tempered glass fracture. These studies are primarily validation study of specific façades without repeated tests for statistical analysis. ...
Article
Tempered glass is substituting float glass and extensively employed in glass façades and some structural members. However, previous studies primarily focus on float glazing, little is known about the statistical characteristics of tempered glazing fallout in a compartment fire. In particular, the correlation between critical parameters and fallout time of tempered glass is still unknown. Based on the previous experimental data in open literature of 11 tempered glass panels in a compartment model, a comparative analysis was performed to optimize the statistical methods of the breakage behaviour for tempered glazing. The parameters from the previous Wang et al.’s research, such as tempered glass fallout time, the temperature at the center of tempered glass surface, the temperature at the edge of tempered glass surface, the temperature difference between fire exposed and frame covered areas, and total heat flux at tempered glass fallout, were analyzed by 7 different statistical functions, including the Normal, Lognormal, 2-parameter Weibull, 3-parameter Weibull, Exponential, Gamma and Logistic distributions. The results suggested that the most appropriate distributions for tempered glass fallout time, the temperature at the center of tempered glass surface, the temperature at the edge of tempered glass surface, the temperature difference between fire exposed and frame covered areas, and total heat flux at tempered glass fallout are respectively Lognormal, 3-parameter Weibull, 2-parameter Weibull, 3-parameter Weibull, and 3-parameter Weibull distributions. Overall, the 3-parameter Weibull distribution is more suitable for the statistical analysis of fallout behavior of tempered glazing in fires. For critical parameters of tempered glass fallout, the 50th percentile is close to the most probable percentile. To avoid the fallout of 6 mm thick tempered glazing, the temperature difference between fire exposed and frame covered areas as well as heat flux should be controlled under 319 °C and 38.5 kW/m². From the correlation analysis between fallout time and each critical parameter, it was established that the surface temperature may give more reliable prediction than total heat flux for tempered glass fallout.
... To map the natural heating of the different materials on stained-glass windows, it is necessary to use infrared (IR) thermography, a portable technique capable of measuring in situ the temperature on different areas and over time. This technique has been applied to evaluate the thermal efficiency of different windows systems [21,22], as well as, to evaluate glasses with different industrial purposes [23][24][25][26], to research fire endurance of tempered glass [27], to study the mechanical defects and the elastic deformations on glass sheets [28][29][30][31][32], and to analyze the efficiency of solar cells [33,34]. The application of IRthermography on historical glasses is scarce [20,32,33]; nevertheless, these studies proved to be a useful tool to evaluate the conservation of historical stained-glass windows [35,36]. ...
Article
Full-text available
This work presents the results of the evaluation of two Art Nouveau glass windows from the Casa-Museu Dr. Anastácio Gonçalves (Lisbon, Portugal) with IR-thermography during the summer solstice. According to the measurements, the surface temperature of glass depended on the outdoor environmental temperature and, mainly, on the direct solar radiation. Colored glasses presented a higher surface temperature due to the absorption of their chromophores at near-IR wavelengths. Enamels and grisailles showed higher surface temperatures than their support glasses due to both their chemical composition and color. The protective glazing, with small slits in one of the window panels, induced a hot-air pocket in its upper part due to the insufficient ventilation.
... Moreover, the high reflectance of glasses, mainly at incidence angles higher than 45 degrees, can produce erroneous temperature estimations [36,37]. Nevertheless, IR thermography has been applied successfully to evaluate windows for industrial purposes [38][39][40][41], to research fire endurance of tempered glass [42], to study the mechanical defects and the elastic deformations on glass sheets [43][44][45][46][47], to analyze the efficiency of solar cells [37,48] and to detect damages on fiber optics [49,50]. ...
Article
This paper reports the analyses of infrared thermography images of two stained‐glass windows with the objective of the in‐situ characterization of this type of artworks. The analyses were carried out by active thermography. The observations revealed that glasses absorbed the long‐wave IR radiation emitted by the halogen lamps and their apparent surface temperature progressively increased. After switching the spotlight off, they experienced a progressive decrease of temperature. Silver stained glasses presented the same thermographic behavior than uncolored glasses because silver nanoparticles were too small or the yellow layer was too thin to produce a different response than the base glass with the IR radiation. The apparent surface temperature of enamels and grisailles depended on their thickness and color. Lead cames maintained an almost constant surface apparent temperature, except those painted that behave in a similar way than enamels. Metallic tin–lead welds experienced the most important variation of the surface apparent temperature in reflection mode due to the energy reflected by the surface of the weld. Glass defects such as big bubbles were also observed. This article is protected by copyright. All rights reserved.
Article
Purpose The purpose of this paper is to conduct a comprehensive study on building, fire and evacuation, so as to effectively improve the efficiency of building fire evacuation and the management level of fire evacuation site. Make up for the difficulties of BIM technology in effectively connecting building information and fire data. Design/methodology/approach First, this paper establishes a fire model and an evacuation model based on BIM information. Then, the safety index (SI) is introduced as a comprehensive index, and the IRI is established by integrating the SI function to evaluate the safety of evacuation routes. Based on these two indices, the IRI-based fire evacuation model is established. Findings This study offers an Improved Risk Index (IRI)-based fire evacuation model, which may achieve effective evacuation in fire scenes. And the model is verified by taking the fire evacuation of a shopping center building as an example. Originality/value This paper proposes a fire evacuation principle based on IRI, so that the relevant personnel can comprehensively consider the fire factors and evacuation factors to achieve the optimization of building design, thereby improving the fire safety of buildings.
Article
This study aims at improving the grinding quality and efficiency of the grinding edges on tempered glass using electroplated diamond abrasive belts. Firstly, the most suitable diamond type and composition of metal coating were selected in the first experiment. Secondly, the structure parameters of abrasive belts, such as diamond grain size (dgs), chip clearance (chc), matrix thickness (mt), and coating thickness ratio (ctr), were optimized through an L 9 (3 ⁴ ) orthogonal experiment. Finally, the influences of the process parameters on the grinding effect were investigated, which are optimized by an L 9 (3 ³ ) orthogonal experiment. The results show the following: (1) the abrasive belt with the diamond type of SMD40 and metal coating of 90 % nickel, 5 % cobalt, 5 % copper (Ni90%-Co5%-Cu5%) weight percentage (wt.%) of the total weight of the coating metal possesses the best grinding performance for the grinding edges on tempered glass. (2) The best grinding quality can be achieved under the conditions of the 230/270 US mesh (63-53 μm) in dgs, 1.5 mm in chc, 1.2 mm in mt, and 2/3 in ctr. (3) The roughness decreases first and then increases with the increase of dgs and ctr, decreases with the increase of chc, and increases with the increase of mt. (4) With the increase of the grinding pressure (gp), the roughness increases, and the material removal rate increases first and then decreases; with the increase of belt linear velocity (blv), the roughness first descends and then tends to stability, and the material removal rate increases first and then decreases; with the increase of the belt tensioning force (btf), the roughness decreases, and the material removal rate increases first and then tends to be stable. (5) The best grinding performance can be achieved under gp of 18 N, blv of 30 m/s, and btf of 55 N.
Article
The laboratory chemical hood is the primary engineering control when using toxic and flammable chemicals in the laboratory. A sustained fire in a chemical hood can be large safety risk because of its potential to affect the chemical hood's containment integrity. Under certain conditions when the glass is exposed to thermal loading, the glass fails under a brittle fast facture. The details of the thermal loading on the glass are important to the overall stability of the glass. To better understand how fire in a compartment influences the thermal history and cracking of its glass windows, a computational and experimental study was undertaken. The gas and glass temperatures were modeled with the computational fluid dynamics code Fire Dynamics Simulator (FDS). Small-scale fires are simulated by adjusting the heat release rate to that used in the experiments. FDS models allow results from simulations on small-scale tests of window heating and deformation to be applied to a large-scale chemical hood fire. Collecting images throughout the experiment with the IR camera, showed similar trends in heating as the simulations. It was found that temperature gradients develop due to varying rates of heating between exposed and unexposed (protected by frame) glass. The correlation of simulation results with experimental data can be particularly useful in gaining insight into the underlying physics of the fire. Studies of this type can be helpful in identifying the mechanisms for glass failure and designing mitigating features to eliminate glass failure modes during a chemical hood fire. In this paper, simulation data to better understand the effects of fire on thermal loading and glass failure in a chemical hood are discussed.
Article
In this study, a full-scale room (573cm×420cm×330cm) fire test was developed to investigate the performance and the variations of the absorption of convection heat and the resistance of radiation by using either the water film or the closed-pendent-type sprinkler onto the non-heat-resistant fireproof glass panes. The results showed that in the initial stage of the fire, the water film could completely restrain the surface temperature of the glass, and when the fire induced the flashover and further proceeded to the intense burning, the surface temperature of the glass could still be controlled around 100°C. Although the flow rate of the sprinkler system was 3 times of the water film system, the effective heat resistance was only a third to a half that of the water film system only. Thus, for situations where the available amount of water flow is limited, by using a layer of uniform down-flowing water film with appropriate thickness and velocity, reducing the temperature of the glass surface could be achieved effectively. The usage of the water film onto the glass pane to assure the fire insulation and fire integrity of the glass pane has been proven workable, through a series test using small-scale [Wu CW, Lin TH, Lei MY, Chung TH, Huang CH, Chiang WT. Fire test on a non-heat-resistant fireproof glass with down-flowing water film. Proceedings of the eighth international symposium on fire safety science, 2005. p. 327–39], full-scale [Wu CW, Lin TH. Fire resistance tests of a glass pane with down-flowing water film. Technical Report, Safety Technology Co., Ltd., Taiwan, ROC, 2005; based on ISO 834-1] and real-scale (this study) fire.
Article
A glass breakage model has been implemented within the existing FDS fire field model. The field model allows the prediction of radiative and convective heating to solid-phase objects. This is utilised by filtering, within the code, the objects to be modelled as glass, and then linking a one-dimensional heat transfer across those objects to a Gaussian spread of breaking temperatures across panes within the compartment being modelled. The gas- and solid-phase heat transfer methods are described along with the implemented glass breakage model. A case study is then presented involving the modelling of a large-scale compartment fire in a building with a high degree of glazing. A key factor in the severity of the atmospheric conditions, and the variations in temperature prediction, comes as a result of the different breaking patterns of glass around the compartment. The Gaussian glass breakage model emphasises this, and equivalently high local temperatures are not predicted when the typically adopted method of solid-object removal is used, or when the assumption of an ‘open’ compartment condition, where all the glazing is removed, is modelled. Changing ventilation patterns from a Gaussian breakage model are thus shown to produce markedly different gas temperature predictions than other methods. The new glass brakeage model presented in this paper can be implemented into any existing CFD fire field model and is not exclusive to FDS.
Full-scale experimental study on tempered glass endurance under fire exposure
  • Li Mingxuan
  • Lu Guojian
Li Mingxuan, Lu Guojian. Full-scale experimental study on tempered glass endurance under fire exposure. Fire Science and Technology, 2013, 32(5): 493-496.
Experiment study on single tempered glass with protection of sprinkler as fire compartmentation item. Fire science and technology
  • Mei Xiujuan
  • Zhang Zejiang
Mei Xiujuan, Zhang Zejiang. Experiment study on single tempered glass with protection of sprinkler as fire compartmentation item. Fire science and technology, 2007, 26(5): 500-502.
Study on Break behavior of common window glass. Fire Science
  • Li Jianhua
  • Zheng Huanghua
Li Jianhua, Zheng Huanghua. Study on Break behavior of common window glass. Fire Science. 1999, 3(8): 21-23.