Research of energy efficiency direct-heating systems with
sequential connection of space heaters with different
methods of heat consumption regulation
Maxim N. Morozov
a
and Pavel A. Strizhak
National Research Tomsk Polytechnic University, 634050 Tomsk, Russia
Abstract. A model of the building heating system, consisting of energy source, a
distributed automatic control system, elements of individual heating unit and heating system
is designed. Application Simulink of mathematical package Matlab is selected as a platform
for the model. There are the specialized application Simscape libraries in aggregate with a
wide range of Matlab mathematical tools allow to apply the “acausal” modeling concept.
The conducted research of single-pipe heating system configuration and automatic control
system allowed comparing the integral parameters of the systems with local and individual
regulation. The results of research of thermal condition premises, situated in the extreme
movement direction of the coolant are given. The conclusions about the possibility of
increasing the operational efficiency of single-pipe heating system configuration in the
implementation of distributed control systems are presented.
1. Introduction
In recent years issues of energy conservation, improving energy and resource efficiency are considered
decisive in many countries [1, 2].
Particular attention, as a rule, is given to activities aimed at improving the energy efficiency of
administrative and industrial purposes buildings and facilities [3–9].
There are several active requirements for a modern heating system. On the one hand it is necessary to
maintain the microclimate parameters at a comfortable level and on the other – it is required increasing
energy efficiency of engineering building life support systems.
The aim of this work is to investigate a single-pipe building heating system in case of local regulation
in heating unit and also in the case of individual regulators.
2. Simulation object
As a simulation object, a district heating system of a typical administrative building (for Russia) has
been selected. The system consists of the individual heating unit (IHU), mainline inlet and outlet pipes,
a
Corresponding author: tpu_chm@tpu.ru
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits
unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Article available at http://www.epj-conferences.org or http://dx.doi.org/10.1051/epjconf/20158201047
EPJ Web of Conferences
Figure 1. A schematic diagram of a single-pipe building heating system by a vertical configuration: 1 – water pipe,
2 – heating appliance.
risers, heating appliance and control valve. Heat supply of the building is provided by the central heating
unit at t he temperature chart 95/70
◦
C.
Entry heat supply system into the building carried out through heat metering point of IHU. The IHU
has been designed under the “independent scheme” using pump circulation and mixing the coolant from
the return pipeline to the feed [10, 11]. The building heating system’s feature is the availability of both
single- and double-pipe configurations.
As modeling object a vertical single-pipe configuration with overhead coolant distribution
and heating appliances, connected in sequential groups, has been selected in this research work
(Fig. 1).
The system is a combined (heating appliances installed on the upper floors provided with a bypass,
the lower floor – flow system).
3. Model of the building district heating system
The thermal model of the building has been developed to evaluate the energy efficiency of pipe heating
systems with different methods of regulation.
The application Simulink of t he mathematical package Matlab [12] has been selected as a platform
for a model. An extension package Simscape, which implements a “physical” simulation concept [13],
has also been applied to develop the model.
Model implementation in the Matlab package is based on representing of each individual functional
component [12, 13] in the form of s-functions and subsystems blocks (Figs. 2, 3).
The law of energy conservation for a typical premise is at the basis of the thermal model of the
building heating system [14].
To simulate different mechanisms of heat transfer between model components laws Fourier,
describing the mechanism of conductivity heat transfer and the Newton-Richman (convective heat
transfer) has been applied [14].
The model universality allows applying it for a variety of purposes: energy efficiency evaluation of
various configurations heating systems, methods of heat consumption regulation, as well as research
problems of reliability of energy supply systems and emergency situations forecasting of heat networks.
01047-p.2
Thermophysical Basis of Energy Technologies
Figure 2. The main thermal model blocks of the building district heating system.
Figure 3. A part of premise model.
In this context the model can be used as a tool at the technical-and-economic assessment
development of energy management systems in accordance with ISO 50001:2011 “Energy management
systems – Requirements with guidance for use” [15].
An example of applied problem is realization of an individual building thermal mode [16–19]. This
assumes implementation of low heat demand mode, where the temperature of indoor air is reduced to
an allowable parameters “heat-humidity” mode, regulatory documents, as well as economic reasons.
4. Modelling results
To achieve the set purpose of investigations, a series of numerical experiments has been carried out,
aimed to analyze the influence of the external disturbing factor (outside temperature Tout) on premises
thermal mode, containing the heating system:
1) with individual regulation;
2) with local regulation in IHU without individual.
01047-p.3
EPJ Web of Conferences
Table 1. Results of system reaction at the external disturbing factor influence.
Outdoor temperature
Regulation time treg, s ×10
4
T
out
,
◦
C Premise 3rd floor (No 3) Premise 2nd floor (No 2) Premise 1st floor (No 1)
5 ...0 0,0608 0,0776 0,2655
0 ...− 5 0,0628 0,1296 0,2661
−5 ...− 10 0,0621 0,1284 0,2243
−10 ...− 15 0,0623 0,0872 5,9
−15 ...− 20 0,0598 0,0867 4,55
−20 ...− 25 0,0585 0,088 4,58
−25 ...− 30 0,0582 0,0925 4,6
−30 ...− 35 0,067 0,1067 4,63
−35 ...− 40 0,0532 0,1607 4,117
Table 2. Results of building thermal mode research in case of local regulation with weather compensator at the
external disturbing factor influence.
Outdoor temperature
Indoor temperature T
in
,
◦
C
T
out
,
◦
C Premise 3rd floor (No 3) Premise 2nd floor (No 2) Premise 1st floor (No 1)
5 26,37 24,68 22,51
0 25,68 23,92 21,64
−5 25,49 23,49 20,87
−10 25,32 23,05 20,04
−15 25,15 22,61 19,24
−20 24,97 22,18 18,45
−25 24,79 21,75 17,66
−30 24,59 21,32 16,89
−35 24,59 21,06 16,27
In each series of experiments three rooms located on different floors of the building (Fig. 1) has been
considered: vertical single-pipe configuration with sequential connections of heating appliances. As an
external disturbing factor outside air temperature T
out
has been accepted. Temperature change has been
set in the range [−40;5]
◦
C with increments of 5
◦
C.
Comparative analysis of the first series modeling results showed that individual control of heating
appliances provides stabilization of the controlled parameter – indoor air temperature T
in
.
Estimation of the transient processes quality has been conducted by the regulation time treg. After
modeling the specified temperature range of the external disturbing factor Tout obtained data have been
processed. Results of this process are summarized in Table 1.
Analysis of data (Table 1) leads to the conclusion about the regulation time increasing for the 1st
floor premise. The latter is explained by lack of coolant temperature at t he inlet to the heating appliances.
The individual (distributed) automatic control system cannot cope with its main objective – stabilizing
indoor room temperature.
Comparative analysis of the second series modeling results showed that under the considered
weather conditions the absence of individual regulation does not allow the heating system to maintain
optimal thermal conditions of the premises (Table 2).
Also, the analysis shows that the 3rd floor indoor air temperature T
in
is inflated in the whole range
of external disturbing factor influence Tout during the entire heating season.
On the contrary, the 1st floor premise is characterized by a scarce heat supply. Thus the heating
system does not satisfy normative values of microclimate parameters and causes extra heat loss due to
inflated indoor air temperature T
in
.
01047-p.4
Thermophysical Basis of Energy Technologies
Uneven coolant distribution at heating appliances is the most important disadvantage of single-pipe
heating systems. This problem cannot be solved even in case of installation modern controller with
weather compensator (“weather-dependent” algorithm) in IHU.
Research has been shown that total modernization of heat supply system by installing individual
regulators of heat consumption (distributed system) in addition to centralized controller allows getting
qualitatively new opportunities. In this case, it becomes available to maintain the individual premises
thermal modes, precise control i n accordance with the PID, PD or PI-laws exclude overruns heat, which
caused by inflated indoor air temperature T
in
.
In this case there is an automatic coolant redistribution between heating appliances. Functioning of
the considered system becomes the most optimal (in the hydraulic balance term) i n the implementation
of automatic balancing valves, which compensate the negative influence of individual regulators.
5. Conclusions
A model of the building district heating system, which allows investigating the problems of widespread
single-pipe heating systems in closed to reality operating conditions has been developed.
The conducted researches provide an opportunity to evaluate the efficiency of various heating
systems and its regulation variants: centralized in IHU using “weather-dependent” algorithm separately
and also combined with individual regulation of heat consumption.
It is shown that even a single-pipe heating system configuration allows maintaining the building
indoor climate parameters in the optimal range with less power consumption only in case of
implementation of distributed control system (a combination of local regulation in IHU and individual
– in each premise).
The reported study is supported by the Ministry of Education and Science of the Russian Federation Grant (project
2.1321.2014).
References
[1] V. Roshchanka, M. Evans, Playing hot and cold: how can Russian heat policy find its way toward
energy efficiency (Pacific Northwest National Laboratory, Washington, 2012)
[2] G. Keikkala, A. Kask, J. Dahl, V. Malyshev, V. Kotomkin, Energ. Policy B 35, 1452 (2007)
[3] A. Korppo, N. Korobova, Energ. Policy B 42, 213 (2012)
[4] A. Boute, Pace Envtl. L. Rev. B 29, 746 (2012)
[5] Z. Wang, Y. Ding, G. Geng, N. Zhu, Energy Convers. Manage. B 77, 233 (2014)
[6] G. Dall’O, L. Sarto, Energy and Build. B 67, 298 (2013)
[7] G. Mustafaraj, D. Marini, A. Costa, M. Keane, Appl. Energy B 130, 72 ( 2014)
[8] T. Berger, C. Amann, H. Formayer, A. Korjenic, B. Pospischal, C. Neururer, R. Smutny, Energy
and Build. B 80, 517 (2014)
[9] M.D. Moldovan, I. Visa, M. Neagoe, B.G. Burduhos, Energy Procedia B 48, 924 (2014)
[10] M. Zago, A. Casalegno, R. Marchesi, F. Rinaldi, Energies B 4, 2115 (2011)
[11] O. Ibrahim, F. Fardoun, R. Younes, H. Louahlia-Gualous, Build. Environ. B 72, 259 (2014)
[12] M. Kiyan, E. Bingöl, M. Melikoglu, A. Albostan, Energy Convers. Manage. B 72, 147 (2013)
[13] D. Broman, P. Fritzson, Proceedings of the 2nd International workshop on equation-based object-
oriented languages and tools, 59 (Paphos, Cyprus, 2008)
[14] P. Lauenburg, J. Wollerstrand, Proceedings of the 11th International Building Performance
Simulation Association Conference, 150 (Glasgow, 2009)
01047-p.5
EPJ Web of Conferences
[15] C. Eccleston, F. March, T. Cohen, Inside Energy: The Handbook for Implementing an ISO 50001
Energy Management Systems (CRC Press, 2011)
[16] M. Wallace, R. McBride, S. Aumi, P. Mhaskar, J. House, T. Salsbury, Chem. Eng. Sci. B 69,45
(2012)
[17] S. Privara, Z. Vana, E. Zacekova, Energy and Build. B 55, 341 (2012)
[18] M. Maasoumy, M. Razmara, M. Shahbakhti, A. Sangiovanni Vincentelli, Energy and Build. B 77,
377 (2014)
[19] H.F. Scherer, M. Pasamontes, J.L. Guzman, J.D. Alvarez, E. Camponogara, J.E. Normey-Rico, J.
Process Control, B 24, 740 (2014)
01047-p.6