This paper presents a technique for retrofitting nonseismically reinforced concrete (RC) masonry-infilled frames with textile-reinforced mortar (TRM) jacketing. In the present study the application of TRM is examined on nearly full-scale, as-built and retrofitted, three-story frames, subjected to in-plane cyclic loading. The results of testing a 2∶3 scale, as-built frame representing typical structures with nonseismic design and detailing characteristics and of a companion frame retrofitted via TRM jacketing are presented and compared in terms of the efficiency of the proposed technique to enhance the strength and deformation characteristics of substandard infilled frames. Online version: http://ascelibrary.org/doi/abs/10.1061/%28ASCE%29CC.1943-5614.0000507
Content may be subject to copyright.
This is the version of the paper submitted to ASCE after peer review and prior to copyediting or
other ASCE production activities.
You can find the final, copyedited (online) version of the published paper here:
http://ascelibrary.org/doi/abs/10.1061/%28ASCE%29CC.1943-5614.0000507
You can cite this paper as:
Koutas, L., Bousias, S., and Triantafillou, T. (2014). "Seismic Strengthening of Masonry-Infilled RC Frames with
TRM: Experimental Study." J. Compos. Constr., 10.1061/(ASCE)CC.1943-5614.0000507, 04014048.
Seismic Strengthening of Masonry Infilled RC Frames with Textile-
Reinforced Mortar: Experimental Study
L. Koutas
1
; S. N. Bousias, M. ASCE
2
;
and T. C. Triantafillou, M. ASCE
3
1
Graduate student, Dept. of Civil Engrg., Univ. of Patras, Patras GR-26500, Greece. Email:
koutasciv@upatras.gr
2
Associate Professor, Dept. of Civil Engrg., Univ. of Patras, Patras GR-26500, Greece. Email:
sbousias@upatras.gr
3
Professor, Dept. of Civil Engrg., Univ. of Patras, Patras GR-26500, Greece. Email: ttriant@upatras.gr
Abstract:
The paper presents a technique for retrofitting non-seismically reinforced concrete (RC)
masonry-infilled frames with textile-reinforced mortar (TRM) jacketing. In the present study
the application of TRM is examined on nearly full-scale, as-built and retrofitted, three-storey
frames, subjected to in-plane cyclic loading. The results of testing a 2:3 scale, as-built frame
representing typical structures with non-seismic design and detailing characteristics and of a
companion frame retrofitted via TRM jacketing are presented and compared in terms of the
efficiency of the proposed technique to enhance the strength and deformation characteristics
of sub-standard infilled frames.
Keywords: advanced composites; infilled frame; masonry infill; reinforced concrete;
seismic retrofitting; strengthening; textile anchors; textile-reinforced mortar (TRM).
Introduction and Background
The effect of masonry infills over the entire response curve of existing reinforced concrete
(RC) structures subjected to earthquake loading is significant, both before separation of the
infill from the surrounding frame occurs as encountered during frequent earthquakes and
during large cycles of imposed deformations near collapse. As reported in the literature, the
most common beneficial contribution of the infills is the increase in, both, the global lateral
stiffness and shear strength of infilled frames, and their contribution to the global energy
dissipation capacity (e.g. Mehrabi et al. 1996, Fardis 1997). Nevertheless, the presence of
infills induces or aggravates potential adverse effects, with the most critical one being the
potential brittle shear failure of columns due to the additional shear demand in the column
end-region where the, so-called, “diagonal strutof the infilling is in contact with the frame
members. In addition, regarding multistorey infilled RC buildings, there is a concern about
the tendency for concentration of interstorey drift demand and damage within the 1
st
storey,
ultimately leading to the development of a soft-storey mechanism (Fardis 2000).
Strengthening of frame structures usually aims at increasing the resistance and deformation
capacity of the frame itself, for the structure to comply with the code-prescribed levels of
performance. A worth-examining alternative route to improve the performance of existing
structures and avoid the excessive economic consequences of infill failure, is the effort of
converting infilling to a more reliable source of resistance over the whole spectrum of
structural response, through a guaranteed and quantifiable contribution to building’s
strength/stiffness. Several strengthening techniques have been proposed along this direction,
with the application of sprayable ductile-fiber reinforced cementitious composites (e.g.
Kyriakides and Billington 2008), and fiber-reinforced polymer (FRP) sheets (Ozcebe et al.
2003, Saatcioglu et al. 2005, Yuksel et al. 2006, Almusallam and Al-Salloum 2007, Altin et
al. 2008, Akin et al. 2009, Ozden et al. 2011), being the most recent ones.
In the present study the very promising technique of application of textile-reinforced
mortar (TRM) as externally bonded reinforcement, is for the first time employed to existing,
masonry infilled, reinforced concrete frames. The effectiveness of this non-conventional,
environmentally friendly material that combines advanced fibers, in the form of textiles, with
inorganic matrices (e.g. cement-based mortars) for strengthening reinforced concrete
structures has been reported less than a decade ago by Triantafillou et al. (2006), Triantafillou
and Papanicolaou (2006) and Bournas et al. (2007); and more recently by D’Ambrisi and
Focacci (2011), Al-Salloum et al. (2011, 2012) and Loreto et al. (2014). Tests on masonry
sub-assemblies and wallettes have provided experimental evidence that TRM is effective in
strengthening masonry structures too, as it enhances both the in-plane and out-of-plane
strength (Papanicolaou et al. 2007, Papanicolaou et al. 2008, Harajli et al. 2010, Augenti et al.
2011, Papanicolaou et al. 2011, Babaeidarabad et al. 2013), as well as the strength in diagonal
compression (Prota et al. 2006, Babaeidarabad et al. 2014). Nonetheless, in all these studies
individual, single storey wall-type masonry specimens were employed, without considering
the frame-wall interaction in multistorey structures.
The concept of TRM-strengthening masonry infilled RC frames has been described in
the past by Koutas et al. (2014), who, as part of a broader experimental campaign, presented a
first successful attempt to develop different infill-frame connection methods employing small-
scale sub-assemblies. Key objective of the present study is the experimental investigation of
the effectiveness of this new strengthening technique when employed in retrofitting
multistorey, non-seismically designed masonry infilled frames.
Experimental Program
The single-storey, single-bay infilled frame test setup has been the configuration of preference
in the majority of experimental studies investigating the response of infilled frames (either as-
built or after retrofitting), not only due to its simplicity but also because it facilitates the
calibration of relevant numerical models. However, stress redistribution occurring in
multistorey frames in which the load-bearing capacity of certain members is exceeded, cannot
be represented by such test configuration. To draw conclusions on the response of actual
systems, a 3-storey frame representing a full-height internal bay of an existing non-ductile
building built in Southern Europe in the ‘60s, was considered in the present study. The test
specimens comprise a 2:3 scale model of the prototype frame.
Test Specimens
Two identical infilled frames were designed and built: the first (Specimen #1) was tested as
built and served as the control specimen, whereas the second (Specimen #2) was strengthened
via TRM before been tested to failure. In addition to all parameters being kept identical
between the two frames, construction of the infills by the same craftsmen and use of a
common loading protocol, allow for the direct assessment of the effectiveness of the
retrofitting method.
The geometry of the test frames is shown in Figure 1. For the 2:3 model-to-prototype
scale selected, each storey resulted 2.0 m in height (3.0 m in the prototype) and 2.5 m between
column centerlines (3.75 m in the prototype), yielding a length-to-height aspect ratio of 1.36
for the infill wall.
The columns were of rectangular cross-section 170x230 mm (with the long side parallel
to the plane of the frame), whereas beams were of T-section, to account for the effective
width of the slab (Fig. 2). The column longitudinal reinforcement consisted of deformed bars,
lap-spliced only at the base of the first storey (connection to the foundation); a 60-bar-
diameter splicing length was adopted to preclude splice failure prior to yielding of the
longitudinal reinforcement. The transverse reinforcement for all concrete members consisted
of plain bars with 90-deg hooks at the ends. As typical of sub-standard structures, the
thickness of the cover concrete to stirrups was low (10 mm). To represent the actual three-
dimensional nature of column-beam joints, short transverse beams were constructed at all
joints.
The average cylinder compressive strength of concrete on the day of testing for the
foundation beam and each storey (average values from three specimens) was 27.8 MPa for
Specimen #1 and 27.2 MPa for Specimen #2. The values of reinforcing steel yield stress were
equal to 270 MPa and 550 MPa for the plain steel stirrups and for the rest (deformed)
reinforcement, respectively.
Each 3-storey frame was cast in-situ in four stages, allowing for a 10-day period of
construction and curing for each storey. The infills, which were constructed by perforated,
fired clay bricks (185x85x55 mm) laid with the perforations running parallel to the unit’s
length, comprised two individual wythes separated by a 60 mm gap (Fig.3a). In total, the wall
final thickness resulted equal to the width of the columns (170 mm). The 11.3 MPa mean
compressive strength of the bricks perpendicular to the perforations was obtained as average
of three tests on bricks capped with rapid-hardening sulfur mortar. The thickness of the bed
and the head mortar joints was approximately 10 mm. The cement:lime:sand proportion in the
mortar used to bind the bricks was 1:1:5. The flexural and compressive strength of the mortar
was obtained according to EN-1015-11 (1993), as average of nine specimens. The
compressive strength on the day of testing was 12.6 MPa (Specimen #1) and 13.3 MPa
(Specimen #2), and the flexural strength was 2.6 MPa (Specimen #1) and 2.6 MPa (Specimen
#2).
The construction of the masonry infilling commenced few weeks after completing the
concrete frame and was implemented in two stages: all rows of masonry units in each bay
were built, but the last one. The space left below the beam soffit was filled after a period of
seven days, thus allowing for the development of substantial part of mortar shrinkage. To
guarantee a minimum level of confinement to the masonry and represent the common practice
in the 60s, the last row of bricks was completed with the units being laid at slope (Fig.3b),
pressing each one against the previous.
Strengthening Scheme
The selection of the strengthening scheme for Specimen #2 was dictated by the performance
of the control specimen and was assisted by the results obtained from tests on small-scale
specimens (Koutas et al. 2014) as well as by analytical calculations. In view of the shear
failure of one of the columns of the as-built specimen (see results further on), the scheme for
retrofitting Specimen #2 was based on the triptych: column strengthening to suppress the
shear failure evidenced in the control specimen, strengthening of the infill walls via two-sided
application of layers of TRM externally bonded on the faces of the infills, and provision for
adequate anchorage of the TRM jacket around its perimeter via textile-based anchors and
bond length.
In particular, the process for retrofitting Specimen #2 comprised the following steps:
Strengthening the ends of columns at the first and second stories with three and two
layers of TRM, respectively, fully wrapped around the member to form a closed jacket
over a height of 420 mm (one-quarter of the clear column height). The number of layers
of TRM was determined by the need to provide for column capacity in shear higher than
the respective demand (obtained from Specimen #1). The need to guarantee the
performance of the columns in shear opted for the solution of a fully closed jacket over
the, easier to construct, open three-sided jacket, and despite the fact that in actual
retrofitting projects a fully closed jacket would require partial demolition of the
neighboring masonry. The fact that columns in non-ductile structures suffer a severe lack
of shear resistance along with additional local distress at column ends induced by the
infills, leads to the adoption of closed jackets as a more reliable strengthening approach
for this case.
Attachment of layers of TRM on both sides of the masonry infills, completely covering
vertically the storey clear height (top of slab of lower storey to slab soffit of upper storey)
and horizontally the area between the extremities of the bounding columns. The number
of layers of TRM was determined on the basis of the response and damage observed in
Specimen #1, as well as by analytical modeling of the infilled frame. As a result, the first
storey received two layers of TRM, whereas the second and third storeys received one
layer. Details on the exact sequence of application are provided subsequently.
Insertion of textile-based anchors to provide composite action of the jacket at the slab-
infill interfaces of the first and second storey, on both sides of the infill panels. In total 11
and 8 anchors per side were placed at equal spaces along these interfaces, at the 1
st
and
2
nd
storey, respectively. The corresponding spacing between the anchors was 200 mm and
300 mm for the 1
st
and 2
nd
storey, respectively. An extra textile patch was placed at the
top frame-infill interface of the 1
st
and 2
nd
storey in order to enhance the interaction
between the infill panel and the concrete beam at that level. These textile patches were
placed on both sides of the second storey infill panel, but only on the back side of the first
storey infill panel. On the top front side of the infill panel on the first storey the back-side
patches were substituted by six 400 mm-spaced textile-based anchors, for the sake of
comparison. Details on the anchors configuration are presented in Fig. 4.
The closed TRM jackets at the column ends of the first and second storey were based on
a commercial carbon-fiber textile with equal quantity of fibers in two orthogonal directions.
The mesh size and the weight of that textile were 10x10 mm and 348 g/m
2
, respectively. For
the application of the TRM layers on the faces of the infills a commercial polymer-coated E-
glass textile (of 25x25 mm mesh size and 405 g/m
2
weight), also with equal quantity of fibers
in two orthogonal directions, was used. The anchors used in this study were custom-made
from a commercial textile made of uncoated basalt fiber rovings knitted in two orthogonal
directions, with equal quantity of fibers in each direction. The mesh size and the weight of
that textile were 25x25 mm and 192 g/m
2
, respectively. The properties of the textiles, either
provided by the manufacturers or derived analytically (where full data are not available), are
summarized in Table 1.
The mortar used as the binding material of the textile and the substrate was a
commercial fiber-reinforced cement-based mortar (with water-to-cementitious material ratio
equal to 0.22 by weight) mixed with re-dispersible polymers. Strength properties were
obtained through flexural and compressive testing, as in the case of the mortar used for the
construction of brick wallettes. The mean values of compressive and flexural strength
(average values from 5 specimens) on the day of Specimen #2 testing were equal to 18.9 MPa
and 4.3 MPa, respectively.
TRM was characterized through tension testing of coupons with dumbbell geometry
(Fig. 5a). In total, twelve coupons were fabricated and tested after 28 days. Six of the coupons
comprised one layer of glass fibers textile (see 2
nd
column of Table 1) while the rest six
comprised two layers of the same textile. All TRM coupons were subjected to uniaxial
tension, introduced by specially designed steel flanges fitting exactly the curved parts of the
specimens (Fig. 5b). The behavior of all specimens was characterized by multiple cracking
within the gauge length (Fig. 5c) and failure due to the rupture of fibers. From the obtained
results, the tensile strength of TRM (average value from six specimens) was obtained: 47.6
kN/m and 78.7 kN/m for one and two textile layers, respectively. These values correspond to
41.4% and 34.2% of the tensile strength of the textile given by the manufacturer.
Details on the development of the textile-based anchors used in this study and the
verification through testing can be found in Koutas et al. (2014). The anchors placed along the
slab-infill interfaces on both sides of 1
st
and 2
nd
storey (denoted as W400-L350) were formed
from a 400 mm-wide basalt textile sheet: a length of 100 mm of the textile was twisted to
form a stub, while the rest 350 mm was opened to form a fan (Fig. 4). The series of anchors
placed along the infill-slab soffit interface on only the front side of 1
st
storey (denoted as
W600-L500) were formed from a 600 mm-wide basalt textile sheet shaped in straight and fan-
shaped parts of 100 mm and 500 mm, respectively. The angle of the fan was kept constant for
all anchors and equal to 45
o
(Fig. 4).
For the impregnation of the straight part of each anchor a commercial low viscosity,
two-part epoxy resin adhesive was used during the anchor fabrication stage, with tensile
strength and elastic modulus of 72.4 MPa and 3.2 GPa, respectively (as provided by the
manufacturer). The adhesive used for impregnating the dry fibers in the central area of the
anchors (a procedure employed during the strengthening stage) was a special type
commercial, low viscosity, two-part epoxy resin, which can harden under high humidity
conditions, as those encountered in the fresh mortar of the TRM system. The tensile strength
and the elastic modulus of this adhesive were equal to 20 MPa and 3 GPa, respectively (as
provided by the manufacturer).
Application of Strengthening Scheme
Strengthening of Specimen #2 was performed with the aid of experienced workers and is
illustrated in Fig. 6. Strengthening the 1
st
and 2
nd
storey column ends with closed TRM-
jackets preceded the infilling of the RC frame bays (Fig. 6b), to avoid demolishing the
masonry infilling adjacent to the column ends. All concrete surfaces where mortar was to be
applied were brushed clean and dampened. A thin layer of mortar was applied first on the
dampened surfaces and then the textile sheet was wrapped by hand pressure around the
chamfer-cornered column section (Fig. 7a). Mortar was applied in-between the layers of
textile while the previous layer of mortar was in a fresh state, as well as on top of the last
textile layer. The thickness of each layer was approximately 3 mm, yielding a closed jacket of
approximate thickness of 9 mm and 6 mm for the 1
st
and 2
nd
storey, respectively.
Following the construction of the infills (Fig. 6c), the two-day long procedure for
strengthening the infill panels commenced. Each of the six faces of the infills was
strengthened independently, following the same guidelines and the procedure described
previously. In all cases, the first step was the application of the first TRM layer along both
faces of the infill and around the bounding frame members (Fig. 6d, e). Due to its limited
width (equal to 1500 mm), the textile was applied with an overlap of about 300 mm along the
entire length of each bay, near the bottom part of each storey. The next step (involving only
the 1
st
and 2
nd
storeys) comprised the application of the textile-based anchors and the extra
textile patches in the corresponding regions (Fig. 6f). The straight parts of the anchors were
inserted into pre-drilled 12 mm-diameter holes filled with injected epoxy resin, while the
fanned parts were bonded by hand pressure on the top of the first TRM layer (Fig. 7b, c). The
extra textile-patches were simply placed in the appropriate regions and bonded by pressure
against the first TRM layer. Installation of the anchors was preceded by local impregnation of
the dry fibers region with epoxy adhesive. The third step included the application of the
second TRM layer on the faces of the 1
st
storey infill and the surrounding frame members
(Fig. 6g, h). Here too, the textile was applied with an overlap of 300 mm, near the top part of
each storey, so that the two overlapping regions would be located at different levels. The final
step included wrapping of the overhanging textile parts around the chamfered corners of the
column section and their bonding on the side faces of the columns (Fig. 6i).
The final thickness of the jacket on each side was equal to 12.5 mm and 7.5 mm for the
1
st
and 2
nd
/3
rd
storeys, respectively; these values are the average of several measurements at
the mid- height of each storey. It is noted that in the regions of the 1
st
and 2
nd
storey columns
ends, the total thickness of the externally bonded composite material was equal to 20 mm and
12.5 mm, respectively, including the TRM jacket thickness. Figure 8 presents a general view
of Specimen #2 during different phases of retrofitting.
Test Setup and Procedure
Both specimens (control and retrofitted) were subjected to a sequence of quasi-static cycles of
a predefined force pattern. A history of imposed cycles of displacements was defined to be
applied at the top, while maintaining an inverted-triangular distribution of forces to all three
floor levels until failure (in terms of global response) occurred. The displacement history of
the 3
rd
storey is shown in Fig. 9. Except for an initial low-amplitude cycle of 1mm, a total of 5
and 7 cycles were finally applied to the unretrofitted and the retrofitted specimens,
respectively. The number of cycles imposed on the two specimens was determined on the
basis of achieving at least the conventionally defined failure threshold of 20% drop in the
peak load.
A general view of the test set-up is shown in Fig. 10. Three servo-hydraulic actuators
were mounted on the specimen, one per storey. The strong foundation beam was fixed to the
laboratory strong floor via 16 prestressing rods to provide specimen full clamping. Special
care was taken in order to exclude any out-of-plane specimen deformation resulting from
eventual geometrical eccentricities. A system of 2 steel trusses with 2 transverse steel arms
per storey was used to provide out-of-plane support to the specimen, leaving the in-plane
behavior unaffected.
Gravity loading of 80 kN per storey was considered to represent the fraction of
permanent loads concurrent to the lateral loading action. This load, mainly shared by the two
columns of the frame, was realized through a set of 4 prestressing rods per storey. The use of
different sets of prestressing bars per storey allowed heightwise non-uniform distribution of
the axial load to be achieved, matching that obtained analytically (120 kN, 80 kN and 40 kN
for the 1
st
, 2
nd
and 3
rd
storey, respectively). Thus, the varying confining conditions actually
existing in each infill panel, as reported in Chrisafulli (1997), are represented effectively. In
addition, the adopted configuration for the application of gravity loads respects the
observations (Chrisafulli 1997) that in the lower stories of multistorey infilled frames the
gravity loads are resisted mainly by the columns.
The instrumentation layout included:
A network of 72 potentiometers at selected locations, monitoring: (a) the separation and
sliding at the interfaces of the infills to the surrounding frame members, (b) the
deformations of the diagonals of the infill panels, and (c) the deformation along 7
consecutive zones on the outer faces of the columns.
A total of 24 strain gages, monitoring: (a) strains in the longitudinal reinforcement of 1
st
storey columns; 2 strain gages at 3 different levels along the height of each column, and (b)
strains of the threaded bars used for applying the axial load in the columns.
3 highly accurate sensors (2 μm) to monitor/control the horizontal displacements at each
storey level.
Experimental Results and Discussion
Specimen #1
The progressive cracking which developed in the 1
st
storey masonry panel of Specimen #1 is
shown in Figure 11a, for 1
st
, 3
rd
and 5
th
cycles of loading. The first cracks developed already
during the first cycle in the positive direction of loading, at a top displacement of
approximately 6 mm (0.1% top drift ratio); two step-type cracks formed at the 1
st
storey,
running in parallel to the diagonal, but not progressing much lower than the mid-height of the
panel. This behavior is in agreement with the observation (Chrisafulli 1997) that if the
horizontal projection of the length of a fully-developed step-cracking pattern is smaller than
the horizontal dimension of the infill panel, then the step-type cracking forms away from the
diagonal and is accompanied by horizontal sliding-type cracking (the latter was observed
during the 3
rd
cycle in the present tests). The step-wise cracking pattern was observed in the
direction of the opposite diagonal, after load reversal. Previously opened cracks re-opened,
became wider and propagated in the body of the infill during the 2
nd
cycle of loading,
resulting in a marked decrease of the overall lateral stiffness of the frame. The cracking
pattern was completed during the subsequent cycle with the formation of two sliding cracks,
one at top of the infill (soffit of inclined bricks) and the other slightly lower than mid-height
that joined the tips of the step-type cracks of the previous cycle. The maximum base shear
force was attained during the 3
rd
cycle of loading; for the two directions of loading a
maximum base shear of 264 kN/-252 kN was recorded at corresponding top displacement of
25 mm/-24 mm (1
st
storey drift ratio of 0.77%/-0.68%, Fig. 12b). During the same cycle the
minor shear cracks that had opened at the top of both first storey columns became wider,
especially at the top of the east-bound column. It is worth-mentioning that diagonal cracks in
the 2
nd
storey infill panel appeared first during the 2
nd
cycle of loading, but their formation
and evolution was not critical to the subsequent specimen performance.
The post-peak behavior of the specimen was non-symmetric (Fig. 12) with a rather
softer descending branch of the envelope curve in the direction of positive loading (Fig.12a)
compared to that of negative loading. For the positive direction of loading the post peak
behavior reflects the progressive corner crushing failure of the strut in the 1
st
storey infill
panel, due to high compressive stresses. In contrast, the post peak behavior in the opposite
direction of loading reflects the shear failure at the top of the 1
st
storey east-bound column
(shown in Fig. 13a), which occurred at an interstorey drift ratio as low as 0.7%. The test was
intentionally terminated at the end of the 5
th
loading cycle. Figure 13b shows the damage in
the masonry panel and at the top of the east-bound 1
st
storey column, upon test completion.
As mentioned earlier, separation of the infill from the surrounding frame members was
monitored in the perimeter of the infill via a network of potentiometers. The general
observations regarding the corresponding measurements are summarized below:
Frame-infill separation occurred at the very early stages of loading; most of the sensors
captured the opening of a gap even during the 1
st
cycle of loading (drift ratio 0.1%).
The recordings of sensors in the 2
nd
/3
rd
storeys revealed infinitesimal frame-infill
separation, with the size of the opening following the pattern of imposed cycles of loading.
In contrast, recordings of relevant sensors at 1
st
storey deviate from that pattern, due to the
presence of areas with high local deformations at the points of sensor attachment.
The interfaces between the columns and the infill exhibited larger gap opening as
compared to those at bottom slab-infill and top beam-infill interfaces, except for the
bottom slab-infill interface of the 2
nd
and 3
rd
storey; in these cases the gap opening was of
the same magnitude as the ones at the column-infill interfaces. The interfaces with
practically zero gap opening were the bottom slab-infill interface of 1
st
storey, and the top
beam-infill interfaces of 2
nd
and 3
rd
storey.
The peak values of the measured gap opening were: (a) 2.0 mm for the 1
st
storey (at the
column-infill panel interface), (b) 1.5 mm for the 2
nd
storey (at the bottom slab-infill panel
interface), and (c) 0.7 mm for the 3
rd
storey (at the bottom slab-infill panel interface).
Measurement of slippage along the top/bottom frame-infill interface showed the existence
of considerable relative deformation which occurred either at exactly along the interface,
or as in the case of the beam soffit at both first and second storey below the first row of
inclined masonry units at the top of each panel.
Specimen #2
Compared to control Specimen #1, the retrofitted specimen (Specimen #2) exhibited
initial cracking at essentially the same displacement level as in the control specimen (1
st
cycle); minor cracks appeared on the external face of the TRM jacket at the lower-left quarter
of the 1
st
storey infill panel (Fig. 11b). Similar cracking was observed at the mirror region,
upon load reversal. During the subsequent cycles of loading a more dense - compared to
Specimen #1 - cracking pattern developed, composed of inclined cracks (close to the corners
of the infill panel) and of sliding-type cracks (mostly at the central region of the panel). Infill
panel separation from columns and few cracks parallel to the diagonal developed on the 2
nd
storey infill panel (Fig. 14a, b) this pattern remained unaltered for the rest of testing. No
signs of distress of the infill panel of the 3
rd
storey were observed, except for a vertical crack
separating the panel from the west-bound column.
The response of the retrofitted specimen in terms of lateral force-top displacement is
compared in Fig. 12 to that of the control specimen. The maximum base shear force of +407
kN/-395 kN recorded in the former in the positive/negative direction of loading, respectively,
constitutes a 56% increase over that of the unretrofitted specimen and was attained during the
4
th
cycle. The top storey displacement at the instance of maximum base shear was
approximately 40 mm, corresponding to 0.67% top drift or ±1.0% 1
st
storey drift (Fig. 12).
The gradually decreasing lateral strength that followed the 4
th
cycle was the result of two
combined phenomena; complete debonding of the TRM from the beam surface on the back
side of the 1
st
storey (Fig. 13c) and gradual disintegration of the 1
st
storey infill at the two
upper ends neighboring the columns (local crushing). In the subsequent loading cycles, very
large strains were induced in the TRM at these two corner regions on the back side of the
specimen (the one without anchors at the top of the 1
st
storey), leading to rupture of fibers
(Fig.13c). An important observation regarding the post peak-strength behavior of the
specimen was that the anchors placed at the top of the front side-1
st
storey infill were actually
activated and contributed in delaying the debonding of the TRM; debonding in this case
occurred during the 6
th
cycle of loading and all six anchors fractured during the 7
th
cycle. The
different behavior of the TRM between the top front and the top back sides of 1
st
storey
clearly indicates that the extra textile placed at this region was not as effective as the
provision of anchors. Nevertheless, the demand for improved anchoring conditions of the
TRM at the upper stories of the specimen was limited and the absence of anchors did not lead
to debonding of the TRM. Regarding the anchorage of the TRM layers to the frame columns
it was observed that debonding of the TRM only occurred at the mid-height of the 1
st
storey
columns following the completion of the 5
th
loading cycle. At these regions the TRM layers
were simply extended from the infill and bonded to the surface of the surrounding columns,
whereas at the column end regions the textiles were turned around the column corner and
proved effective to prevent debonding. At the upper stories no debonding of the TRM
appeared along the interface to the columns. The anchors placed at the base of the 1
st
and 2
nd
storey infill panels did not exhibit any type of distress.
The TRM jackets which were applied at the ends of the 1
st
and 2
nd
storey columns
successfully prevented pre-emptive shear failure of the type observed in the un-retrofitted
specimen, while also providing the necessary confinement for the columns to go unscathed
through high levels of drift. Figure 13d depicts the damage at the 1
st
storey after test
completion.
Measurements from the sensors placed at the frame-infill interface to record eventual
opening of the interface or relative slippage at the interface were not much different in the two
specimens. They, however, definitely indicate that frame-infill separation was not avoided or
eliminated after applying the textile layers and the response of the frame-infill system was far
from monolithic.
Evaluation of the TRM strengthening technique
The application of the selected strengthening approach resulted in an improved response of
the 3-storey masonry infilled RC frame. The improvement was not only achieved in terms of
increased lateral resistance (reaching a 56% increased at peak resistance), but also in terms of
stiffness. The lateral (secant) stiffness, as obtained for the 1
st
storey from the storey shear-
interstorey drift loops, is shown in Fig. 15 for different levels of the interstorey drift ratio. The
retrofitted specimen displayed higher lateral stiffness compared to the control specimen,
especially at the first storey and at low interstorey drift ratio (less than 0.5%). This is
attributed to the presence of the layers of high strength cementitious mortar used as matrix for
the textile the layers were thicker than at the rest stories, as two layers of TRM were
employed at the 1
st
storey. At the initial loading cycle in which the cementitious mortar was
uncracked and the frame-infill-TRM system behaved as integral, the retrofitted specimen
exhibited an almost twofold increase in stiffness compared to the as-built specimen. At
increasing interstorey drift ratio the lateral stiffness is shown to degrade progressively in both
specimens, almost following a hyperbola. The cementitious mortar could not sustain the large
drift demands following the post-peak strength cycles, and thus failed in shear and
disintegrated. The local failure of the mortar enabled the textile to deform independently from
the masonry substrate (see Fig. 16 revealing the appreciable shear distortion of the textile at
the region enclosed between two horizontal sliding interfaces) and a new load-transfer
mechanism was formed in which the - free to distort - textile assumed the role of bridging the
regions across a sliding interface. These localized phenomena at the retrofitting material level
ultimately led to a slowly progressive degradation of strength and stiffness at the level of
global response. This constitutes a further advantageous characteristic of the TRM system: the
structural integrity of the textile is maintained, rendering it capable of containing the masonry
infill and reducing the risk of out-of-plane collapse or of becoming dangerous to users. In this
respect, the superior response of the anchors employed at the top front side of the 1
st
storey
compared to detachment of the simple patch used in the respective area on the back side,
cannot be overlooked.
The contribution of retrofitting in modifying the height-wise distribution of lateral
deformation is shown in Fig. 17. While the response of the control specimen points more
towards that of formation of soft-storey mechanism (due to the damage of one of the 1
st
storey
columns), lateral deformations in the retrofitted specimen are more evenly distributed along
height, for at least up to 0.64% top drift ratio (4
th
cycle of loading). Nevertheless, in the post-
peak region of response the strengthened specimen did not manage to retain the favourable
distribution of lateral deformations and the ensuing damage of the masonry at the 1
st
storey
led to increasing deformation demands at this level. This is evidenced in Fig. 18, showing the
condition of the masonry at 1
st
storey after-test, in which not only a much more dispersed
damage in the infilling of the retrofitted specimen is noted, but also inclined cracks at mid-
height of 1
st
storey columns are revealed. This clearly indicates initiation of shear failure in
the unretrofitted part of the columns owing to fracturing of the masonry regions in contact to
the columns and points to the suggestion that, to avoid eventual shear failure after masonry
has failed, columns should be strengthened in shear along their full height.
The progressive cracking of the cementitious mortar of the strengthening scheme and
the eventual activation of the textile at higher levels of deformation provided for an effective
dispersion of deformation demands over a broader area of the masonry infilling. Calculation
of the cumulative hysteretic energy based on the base-shear versus top-storey displacement
hysteretic loops (expressed by the area enclosed within the loops), shows that by the end of
the 5
th
loading cycle (0.87% drift ratio) the retrofitted specimen had dissipated 22.5% more
energy compared to the unretrofitted one. This reflects the contribution of the strengthening
material in consuming energy, mainly due to the multi-cracking mechanism and the
redistribution of the shear stresses on the body of the masonry infill. It should be noted that
the capacity of a textile to distort in shear depends directly on its shear stiffness which, in the
case of uncoated textiles, is practically zero and increases as the coating becomes heavier and
the mesh size smaller (assuming the same stitching technique that was used for the fabrication
of the textile). Hence, the geometry and the type of textile used for strengthening masonry
infills should be considered as parameters necessitating further investigation.
A point to be addressed regarding the proposed strengthening technique is that the
resulting increased base shear force (see Fig. 12a) imposes higher demands on the foundation
system. In the present tests, the foundation element was dimensioned for the increased
force/moment actions at the base; in actual applications, this issue will need to be particularly
considered and the capacity of the foundation element should be verified against the expected
increase in actions.
Conclusions
This paper presents an experimental study on the seismic retrofitting of nearly full-scale 3-
storey masonry infilled frames employing non-conventional materials and techniques. The
application of textile-reinforced mortar (TRM) as externally bonded reinforcement in
combination with special anchorage details was examined on an as-built and a retrofitted 3-
storey RC frame, subjected to in-plane loading. The results of testing a 2:3 scale, as-built
frame representing typical non-seismically designed and detailed structures and of a
companion frame retrofitted via TRM are presented and the efficiency of the proposed
technique is discussed in detail. The main conclusions drawn are summarized as follows:
The integrated retrofitting scheme resulted in an enhanced global response of the infilled
frame both in terms of lateral strength and deformation capacity; an approximately 56%
increase in the lateral strength was observed, accompanied with a 52% higher
deformation capacity at the top of the structure at ultimate strength state. This point
should receive the particular attention of designers, due to the increased moment that will
need to be resisted by the foundation element and the strengthening this might imply.
The retrofitted specimen dissipated 22.5% more energy compared to the control one, for
the same loading history. The effect of retrofitting on the lateral stiffness of the 1
st
storey
is an almost twofold increase for low drift levels (up to 0.5%), becoming less pronounced
at higher drift levels.
The height-wise distribution of the lateral storey displacements was drastically modified
in the retrofitted specimen, as column shear capacity enhancement by TRM wrapping
supressed pre-emptive column shear failure caused in the control specimen by the lack of
adequate transverse reinforcement and the concentration of high shear demands at
column end regions induced by the so-called “diagonal strut”.
The application of TRM over the entire surface of infills should be supplemented with an
adequate infill-frame connection, if a reliable resisting system is to be obtained. This
conclusion is drawn, mainly, from the behavior of the TRM at regions beyond the frame-
infill boundaries. The presence of custom-fabricated textile-based anchors was proved to
be particularly effective in delaying or even precluding the debonding of TRM.
Textile-reinforced mortar jacketing proved to be effective in withstanding large shear
deformations through the development of a multi-crack pattern and by introducing an
efficient load transferring mechanism at the local level. This mechanism is enabled by the
capability of the textile itself to distort in shear, while retaining at the same time its
structural integrity.
The present study is a first attempt to investigate TRM jacketing as a means of
retrofitting infill walls in non-seismically reinforced, multi-storey concrete structures. Future
research effort could be directed towards optimizing the materials in the TRM system and
investigating out-of-plane loading effects.
Acknowledgements
This research has been co-financed by the European Union (European Social Fund ESF)
and Greek national funds through the Operational Program "Education and Lifelong
Learning" of the National Strategic Reference Framework (NSRF) - Research Funding
Program HERACLEITUS II - Investing in knowledge society through the European Social
Fund. The assistance of graduate student Anil Basnet and undergraduate students Eleni
Pagoni, Giannis Triantafillou, Dimitris Tsitsokas and Stelios Kallioras in separate parts of the
experimental program is also acknowledged.
References
Almusallam, T. H., and Al-Salloum, Y. A. (2007). “Behavior of FRP strengthened infill walls
under in-plane seismic loading.” J. Comp. Constr., 11(3), 308-318.
Al-Salloum, Y. A., Siddiqui, N. A., Elsanadedy, H. M., Abadel, A. A., and Aqel, M. A.
(2011). “Textile-reinforced mortar versus FRP as strengthening material for seismically
deficient RC beam-column joints. J. Compos. Constr., 15(6), 920-933.
Al-Salloum, Y. A., Elsanadedy, H. M., Alsayed, S. H., and Iqbal, R. A. (2012). “Experimental
and numerical study for the shear strengthening of reinforced concrete beams using
textile-reinforced mortar.” J. Compos. Constr., 16(1), 74-90.
Altin, S., Anil, Ö., Kara, E. M. and Kaya, M. (2008). “An experimental study on
strengthening of masonry infilled RC frames using diagonal CFRP strips.” Composites:
Part B, 39(4), 680-693.
Akin, E., Ozcebe, G., and Ersoy, U. (2009). “Strengthening of brick infilled RC frames with
CFRP sheets.” Seismic risk assessment and retrofitting with emphasis on existing low rise
structures, 367386, A. Ilki, Karadogan. F., Pala S., Yuksel E., (eds.), Springer,
Dordrecht.
Augenti, N., Parisi, F., Prota, A., and Manfredi, G. (2011). “In-plane lateral response of a full-
scale masonry subassemblage with and without an inorganic matrix-grid strengthening
system.” J. Compos. Constr., 15(4), 578-590.
Babaeidarabad, S., Caso, F., and Nanni, A. (2013). Out-of-plane behavior of URM walls
strengthened with fabric-reinforced cementitious matrix composite. J. Compos. Constr.,
10.1061/(ASCE)CC.1943-5614.0000457, 04013057.
Babaeidarabad, S., De Caso, F., and Nanni, A. (2014). “URM walls strengthened with fabric-
reinforced cementitious matrix composite subjected to diagonal compression.J. Comp.
Constr., doi: 10.1061/(ASCE)CC.1943-5614.0000441.
Bournas, D., Lontou, P., Papanicolaou, C. G., and Triantafillou, T. C. (2007). Textile-
reinforced Mortar (TRM) versus FRP confinement in reinforced concrete columns.ACI
Struct. J., 104(6), 740-748.
Crisafulli, F. J. (1997). Seismic Behavior of Reinforced Concrete Structures with Masonry
Infills. PhD Dissertation, University of Canterbury, New Zeland.
D’Ambrisi, A., and Focacci, F. (2011). “Flexural strengthening of RC beams with cement-
based composites.J. Compos. Constr., 15(5), 707-720.
EN 1015-11 (1993). Methods of test for mortar for masonry Part 11: Determination of
flexural and compressive strength of hardened mortar, European Committee for
Standardization, Brussels.
Fardis, M. N., and Panagiotakos, T. B. (1997). “Seismic design and response of bare and
infilled reinforced concrete buildings Part II: Infilled structures.” J. Earthquake Eng.,
1(3), 473-503.
Fardis, M. N. (2000). Design provisions for masonry-infilled RC frames.” Proc.12
th
World
Conf. Earthq. Engrg., Auckland, New Zeland.
Harajli, M., ElKhatib, H., and Tomas San-Jose, J. (2010). “Static and cyclic out-of-plane
response of masonry walls strengthened using textile-mortar system.” J. Mater. Civ. Eng.,
22(11), 1171-1180.
Koutas, L., Pitytzogia, A., Triantafillou, T. C., and Bousias, S. N. (2014). “Strengthening of
infilled reinforced concrete frames with textile-reinforced mortar (TRM): Study on the
development and testing of textile-based anchors.” J. Comp. Constr.,
doi:10.1061/(ASCE)CC.1943-5614.0000390.
Kyriakides, M. A., and Billington, S. L. (2008). “Seismic retrofit of masonry-infilled non-
ductile reinforced concrete frames using sprayable ductile fiber-reinforced cementitious
composites.” Proc. 14
th
World Conf. Earthq. Engrg., Beijing, China.
Loreto, G., Leardini, L., Arboleda, D., and Nanni, A. (2014). “Performance of RC slab-type
elements strengthened with fabric-reinforced cementitious-matrix composites.” J.
Compos. Constr., doi: 10.1061/(ASCE)CC.1943-5614.0000415.
Mehrabi, A. B., Shing P. B., Schuller, M. P., and Noland, J. L. (1996). “Experimental
evaluation of masonry-infilled RC frames.” J. Struct. Eng., 122(3), 228-237.
Ozcebe, G., Ersoy, U., Tankut, T., Erduran, E., Keskin, O., and Mertol. C. (2003).
“Strengthening of brick-infilled RC frames with CFRP. TUBITAK Structural
Engineering Research Unit Report No. 2003-1, METU, Ankara, Turkey.
Ozden, S., Akguzel, U., and Ozturan T. (2011). “Seismic strengthening of infilled reinforced
concrete frames with composite materials.ACI Struct. J., 108(4), 414-422.
Papanicolaou, C. G., Triantafillou, T. C., Karlos, K., and Papathanasiou, M. (2007). “Textile-
reinforced mortar (TRM) versus FRP as strengthening material of URM walls: in-plane
cyclic loading.” Mater. Struct., 40(10), 1081-1097.
Papanicolaou, C. G., Triantafillou, T. C., Papathanasiou, M., and Karlos, K. (2008). “Textile-
reinforced mortar (TRM) versus FRP as strengthening material of URM walls: out-of-
plane cyclic loading.” Mater. Struct., 41(1), 143-157.
Papanicolaou, C. G., Triantafillou, T.C., and Lekka, M. (2011). “Externally bonded grids as
strengthening and seismic retrofitting materials of masonry panels.” Constr. Build.
Mater., 25(2), 505-514.
Prota, A., Marcari, G., Fabbrocino, G., Manfredi, G., and Aldea, C. (2006). Experimental in-
plane behavior of tuff masonry strengthened with cementitious matrix–grid composites.”
J. Compos. Constr., 10(3), 223233.
Saatcioglu, M., Serrato, F., and Foo, S. (2005). “Seismic performance of masonry infill walls
retrofitted with CFRP sheets.” SP-230: 7th International Symposium on Fiber-Reinforced
(FRP) Polymer Reinforcement for Concrete Structures, Paper 20, 341-354, Shield C.,
Busel J., Walkup S., Gremel D., (eds.), American Concrete Institute, Farmington Hills.
Triantafillou, T. C., Papanicolaou, C. G., Zisimopoulos, P., and Laourdekis, T. (2006).
“Concrete confinement with textile reinforced mortar (TRM) jackets”, ACI Struct. J.,
103(1), 28-37.
Triantafillou, T. C., and Papanicolaou, C. G. (2006). “Shear strengthening of RC members
with textile reinforced mortar (TRM) jackets”, Mater. Struct., 39(1), 85-93.
Yuksel, E., Ilki, A., Erol, G., Demir, C., and Karadogan, H. F. (2006). “Seismic retrofitting of
infilled reinforced concrete frames with CFRP composites.” Advances in earthquake
engineering for urban risk reduction, 285-300, Wasti T., Ozcebe G., (eds.), Springer,
Dordrecht.
List of Figures
Fig. 1 Geometry of the bare frame: (a) front view; (b) side view.
Fig. 2 Sections of rectangular RC columns and T-shaped RC beams (all dimensions in
mm).
Fig. 3 (a) Building of masonry infill wall; (b) detail of the last row of bricks.
Fig. 4 Configuration and dimensions (in mm) of textile anchors and textile patch.
Fig. 5 Tensile testing of TRM coupons: (a) coupons geometry; (b) test set-up; and (c)
typical crack pattern (all dimensions in mm).
Fig. 6 Strengthening scheme Application steps: (a) bare frame; (b) shear strengthening of
1
st
and 2
nd
storey columns at shear-critical regions; (c) infilling with masonry; (d)
application of 1
st
TRM layer on the face of masonry infills, bottom part of the textile;
(e) application of 1
st
TRM layer on the face of masonry infills, top part of the textile;
(f) application of textile anchors and extra textile patches on the front and back side
of the specimen, respectively; (g) application of 2
nd
TRM layer on the faces of 1
st
storey masonry infill, bottom part of the textile; (h) application of 2
nd
TRM layer on
the faces of 1
st
storey masonry infill, top part of the textile; (i) wrapping of the
overhanging textile parts around the column corner.
Fig. 7 Application of: (a) the TRM jacket at a column’s end; (b) a textile anchor at the base
of the infill; (c) a textile anchor at the top of the beam.
Fig. 8 Stages of Specimen #2 construction: (a) after strengthening of 1
st
and 2
nd
storey
columns with TRM closed jackets; (b) after infilling with masonry walls; (c) after
strengthening with TRM; (d) after completion of instrumentation.
Fig. 9 Displacement history at 3
rd
floor (Specimen #1 up to the 5
th
cycle and Specimen #2
up to 7
th
cycle).
Fig. 10 Test set-up: (a) front side; (b) back side.
Fig. 11 Crack patterns of 1
st
storey at selected peak displacements of: (a) Specimen #1; (b)
Specimen #2.
Fig. 12 Comparative response curves for the two specimens in terms of base shear versus: (a)
top drift ratio; (b) 1
st
storey drift ratio.
Fig. 13 (a) Shear failure at the top of 1
st
storey’s column Specimen #1; (b) damage of 1
st
storey after the end of the test Specimen #1; (c) rupture of fibers at the top end of
1
st
storey’s column, on the back side; (d) damage of 1
st
storey after the end of the test
Specimen #2.
Fig. 14 Crack pattern of 2
nd
storey at 4
th
cycle’s maximum and minimum peak displacements
of Specimen #2.
Fig. 15 Lateral stiffness of each storey versus interstorey drift ratio for both specimens.
Fig. 16 Textile under large shear deformations.
Fig. 17 Displacement profiles at peak displacements for both specimens (up to the 5
th
loading cycle).
Fig. 18 Damage of the 1
st
storey’s infill panel of the retrofitted specimen after the completion
of the test: (a) picture after demolishing the front wythe of the wall; (b) schematic
representation of the damage in the columns and of the wall’s disintegrated area.
Table 1. Properties of Textiles
Property
Uncoated
carbon fibers
Polymer-coated
E-glass fibers
Uncoated basalt
fibers
(used in anchors)
Mesh size
(mid-roving to mid-
roving grid spacing)
10x10 mm
25x25 mm
25x25 mm
Net grid spacing
7 mm
21 mm
23 mm
Weight
348 g/m
2
405 g/m
2
192 g/m
2
Tensile strength per
running meter
157 kN/m
*
115 kN/m
**
66 kN/m
**
Rupture strain
1.5 %
2.5 %
3.15 %
Modulus of elasticity
225 GPa
73 GPa
89 GPa
Fiber density
1.8 g/cm
3
2.6 g/cm
3
2.66 g/cm
3
*
Calculated using nominal value of thickness (obtained from the equivalent smeared
distribution of fibers);
**
taken from data sheets of the manufacturer.
Figures
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11
Fig. 12
Fig. 13
Fig. 14
Fig. 15
Fig. 16
Fig. 17
Fig. 18
... Therefore, it is considered a promising composite material for strengthening RC components, masonry walls, and for constructing slender, lightweight, modular, and freeform structures. Various studies have explored the application of the FRCM system in diverse contexts such as flexural strengthening [29][30][31][32][33], shear strengthening [34][35][36][37][38], confinement of axially loaded concrete [39][40][41][42][43][44], seismic retrofitting of RC members [45][46][47], and masonry infilled RC frames [48][49][50][51][52]. ...
... Results indicated that FRCM jackets effectively enhanced the cyclic deformation capacity and energy dissipation of poorly detailed RC columns, delaying bar buckling and preventing splitting bond failures in columns with lap-spliced rebars. Additionally, Koutas et al [48] explored the use of FRCM for retrofitting a three-story reinforced concrete frame filled with masonry under seismic loading conditions. The study revealed a 56% increase in lateral load-carrying capacity and a 52% improvement in deformation capacity corresponding to ultimate load in the retrofitted frame compared to the non-retrofitted one. ...
Article
Full-text available
In recent years, fabric-reinforced cementitious mortar (FRCM) has emerged as a popular choice for strengthening reinforced concrete and masonry structures due to several advantages over conventional fiber-reinforced polymer (FRP) composites. Particularly, the enhancement of Reinforced Concrete (RC) columns using FRCM composites has garnered significant attention. While experimental investigations are crucial for assessing the effectiveness of FRCM, physical experiments are often resource-intensive and time-consuming. Therefore, this study seeks to investigate the impact of various design parameters on the performance of RC columns strengthened with FRCM under low-amplitude cyclic loads simulating earthquakes through Finite Element (FE) analysis. The FE model, incorporating columns and FRCM strengthening materials, was developed using the DIANA 10.5 program. To assess the reliability of the model, analytical results were compared with experimental findings from a previous study, focusing on lateral strength, hysteresis behavior, and failure modes. The validation outcomes demonstrated a reasonable correlation between the test and numerical results. Subsequently, a sensitivity analysis was conducted to explore the influence of input parameters, such as concrete compressive strength, fabric reinforcement quantity, longitudinal reinforcement ratio of the columns, and pre-axial loading levels, on the seismic performance of RC columns reinforced with FRCM. The findings of the sensitivity analysis were discussed in detail.
... Considering these advantages, researchers have increased the use of TRM in developing strengthening/retrofitting details in the last ten years. Strengthening with TRM was also applied to reinforced concrete frame with masonry infill wall, and positive results were obtained (Koutas et al. 2014). ...
... load capacity of the specimens decreased by 15% was accepted as the failure point (Anıl and Altın 2007;Altın et al. 2008aAltın et al. , b, c, 2012Altın et al. , 2010Makou 2021;Koutas et al. 2014;Mercuri et al. 2023;Vailati et al. 2021Vailati et al. , 2023aAngiolilli et al. 2020;Mojsilović 2022;Zhang et al. 2022;Kaya et al. 2018). The other displacement value used in calculating the displacement ductility ratio was determined as the displacement of the peak point of the first loading cycle where the horizontal movement started in the load-displacement graph of the specimens. ...
Article
Full-text available
Adding a reinforced stucco layer to the masonry infill walls is a preferred method for strengthening RC frame system structures with an easy-to-apply method that does not require a long time, is economical, and does not require detailed and extensive workmanship. However, no research has been discovered as a result of the extensive literature review that investigates the effects of masonry-infilled RC frames strengthened with a reinforced stucco layer on the seismic performance of openings that must be due to architectural requirements such as doors, windows, installations, and similar ventilation systems. As a result, an experimental study was planned to investigate the effects of the dimensions and location of the opening in the masonry infill walls on the performance of the strengthening method with the reinforced stucco layer. The applied strengthening method increased the ultimate load capacity, initial stiffness, and energy dissipation capacity values of reinforced concrete frames with masonry infill walls by 83%, 226%, and 62%, respectively, but resulted in a 38% decrease in displacement-ductility ratios. The study found that the openings in the masonry infill walls harm the performance of the strengthening technique by adding a rebar-reinforced stucco layer and decreasing the success level. When the opening size increased, and the opening was located at the corner of the masonry wall, the performance of the applied strengthening technique was negatively affected and decreased. Furthermore, nonlinear numerical analyses of the experiments conducted as part of the study were performed using ABAQUS finite element software. The numerical analysis results were compared to the experimental results. It has been determined whether numerical analysis models are compatible with experimental results.
... These methods take one of two approaches. The first approach involves increasing the strength of the constituents via several additives, such as engineered cementitious composites (ECC) [51,52], precast concrete panels [53,54], textile-reinforced mortar (TRM) [55], fiber-reinforced polymers (FRP) [56][57][58], and mesh-reinforced plaster. ...
Article
Full-text available
In urban construction, reinforced concrete (RC) with masonry infill predominates, though traditional masonry's brittle nature poses significant seismic vulnerabilities. This study introduces a novel approach using Ductile Lightweight Fiber-Reinforced Concrete (DLFC) as an infill to address these challenges. Composed of cement, water, expanded polystyrene (EPS), ultra-fine filler, and combined polyvinyl alcohol (PVA) and polypropylene (PPF) fibers, DLFC aims to enhance ductility, minimize damage, and amplify energy absorption in seismic events. Three RC frames, with height-to-span ratios of 0.77, 1.00, and 1.28, were designed and experimentally tested under simultaneous vertical and lateral cyclic loading to evaluate DLFC's seismic response. Results illustrated that DLFC-infilled RC frames boast impressive ductility, an 8% drift at complete failure, minimal out-of-plane behavior, and elevated damping ratios. Remarkably, DLFC's low in-plane stiffness led to reduced frame stiffness compared to traditional masonry. An empirical equation, closely aligning with experimental outcomes, was formulated to estimate the lateral strength of the infill wall, and a comparison with the bare frame was made, though it necessitates additional validation through further testing.
... Since these limitations are mainly related to the organic binder, substituting the epoxy resin with an inorganic cementitious matrix seemed to be an effective solution, and a new composite material called Textile-Reinforced Mortar (TRM) has been recently proposed [17,18]. It was found that the application of TRM overlays resulted in a considerable improvement in the in-plane shear strength and ductility of the strengthened panels [19][20][21][22]. ...
Article
Full-text available
This paper presents the outcomes of a comprehensive experimental investigation aimed at characterizing the in-plane shear strength of Unreinforced Masonry (URM) wallettes subjected to diagonal compression. The study focuses on the strengthening of these wallettes using precast Ultra-High Performance Concrete (UHPC) diagonal strips, externally bonded onto the wall substrates through high-strength epoxy mortar. Twenty-three wallettes, each measuring 1000 mm × 1000 mm × 70 mm, were meticulously constructed and subjected to in-plane diagonal compression. Among these, eighteen wallettes underwent strengthening utilizing various configurations of UHPC, with a key emphasis on variables such as UHPC strip width and thickness, substrate nature, and corner confinement with enlarged UHPC rectangular plates. Findings from the experimental program highlighted the significant influence of UHPC retrofit parameters on the wallettes performance. Notably, corner confinement emerged as an effective strategy against premature toe crushing failure, enhancing the wallettes ability to withstand higher in-plane compressive loads. While UHPC strip width exhibited moderate impact, UHPC strip thickness emerged as a dominant factor. Increasing strip width from 100 to 250 mm yielded an approximate 8% shear strength improvement, whereas doubling strip thickness from 10 to 20 mm led to a substantial 27% enhancement. Notably, enhanced strip width demonstrated pronounced benefits in terms of ductility and energy dissipation capacity. Excessive UHPC retrofit thickness induced brittle failure despite escalating shear strength. Conversely, thinner UHPC retrofits achieved a favorable balance between strength, ductility, and energy dissipation. Wallettes retrofitted with 5 mm UHPC exhibited an impressive 2.36-fold shear strength increase compared to reference walls, while those with 10 mm and 20 mm UHPC retrofits experienced 2.14 and 2.78-fold improvements, respectively. Furthermore, the manner of UHPC application significantly influenced the strengthening system's behaviour. For identical strengthening layouts, the direct bonding of UHPC onto masonry substrates resulted in a 25% increase in shear strength compared to UHPC bonding onto plaster overlays.
... One way to improve the seismic performance of existing NEBs is structural strengthening. Various materials and methods of strengthening, including the use of carbon fiberreinforced polymer (CFRP) [5][6][7][8], glass fiber-reinforced polymer (GFRP) [9][10][11], aramid fiber-reinforced polymer (AFRP) [5], textile-reinforced mortar (TRM) [12][13][14][15], and steel plates [16][17][18], can be employed in such cases. Some of these materials have been used to strengthen joints and improve the seismic performance of reinforced-concrete structures. ...
Article
Full-text available
Non-engineered buildings (NEBs) are prone to earthquake damage. One type of damage that often occurs in NEBs is the separation of beam and column elements owing to joint failures. Strengthening joints with steel plates is expected to improve the seismic performance of this type of building. Strengthening with steel plates is cheap and easy to apply, so it will be a preferable choice in preventing damage to the NEB due to earthquake loads. This study investigated the seismic performance of reinforced concrete frames, representing an NEB whose beam–column joints were strengthened with L-shaped steel plates. Two widths of L-shaped steel plates were proposed: 75 mm (NEB-075) and 100 mm (NEB-100). An NEB without strengthening (NEB-000) was used as a control. Both experimental and numerical investigations were performed to determine the seismic performance of NEBs. The results showed that damage to the NEB-000 and NEB-075 models occurred at the joints, but less damage was observed in NEB-075 than in NEB-000. Furthermore, damage in the NEB-100 model occurred at the column. The undamaged limit levels of the NEB-000, NEB-075, and NEB-100 models were 56.49, 81.54, and 82.46%, respectively. These results show that strengthening the NEB with steel plates effectively improves its seismic performance. According to an analysis of the performance of the tested models, the NEB-100 model exhibited the best seismic performance.
... With a few exceptions, most commercially available open mesh textiles are composed of fiber rovings of the same material in two orthogonal directions with a 50%-50% weight distribution in the warp and weft directions. These balanced textiles could be suitable for applications where structural members are subjected to biaxial stresses and both directions are effectively utilized, such as unreinforced masonry walls, masonry infill walls in RC frames, or two-way RC slabs (e.g., Koutas et al. 2014;Bournas 2017, 2019). However, for applications where the fibers work in one of the directions, for instance, in beams or columns that are subjected to bending and shear, such a design becomes uneconomical because the warp and the weft fibers will not contribute equally to the additional capacity that is offered by the TRM overlay. ...
Conference Paper
p>Masonry walls are often regarded as non-load-bearing components in most steel or concrete- framed buildings which effectively increases the total system's strength and stiffness when subjected to horizontal forces. This paper will discuss the experiment using reversed quasi-static cyclic sinusoidal displacement-controlled loading on the masonry infill wall and explains the outstanding ductility capability of masonry infills in Reinforced Concrete (RC) frames, as seen during cyclic experimental testing on wall specimens. The study's primary aim was to describe how the rectangular brick infill panels on RC frames behave during earthquakes. The results regarding in- plane force-displacement responses, damage evolution and energy dissipation capacity will be presented. Ultimately, the experimental tests were simulated in the software ABAQUS through a simplified modelling approach and validated against the experimental results.</p
Article
Full-text available
The effectiveness of textile-reinforced mortar (TRM) jackets as a means of confining reinforced concrete (RC) columns with limited capacity due to buckling of the longitudinal bars is experimentally investigated in this study. Comparisons with fiber-reinforced polymer (FRP) jackets of equal stiffness and strength allow for the evaluation of the effectiveness of TRM versus FRP. Tests were carried out both on short prisms under concentric compression and on nearly full-scale, nonseismically detailed, RC columns subjected to cyclic uniaxial flexure under constant axial load. The compression tests on 15 RC prisms show that TRM jackets provide a substantial gain in compressive strength and deformation capacity by delaying buckling of the longitudinal bars; this gain increases with the volumetric ratio of the jacket. Compared with their FRP counter-parts, TRM jackets used in this study are slightly less effective in terms of increasing strength and deformation capacity by approximately 10%. Tests on nearly full-scale columns under cyclic uniaxial flexure show that TRM jacketing is very effective (and equally to its FRP counterpart) as a means of increasing the cyclic deformation capacity and the energy dissipation of old-lype RC columns with poor detailing by delaying bar buckling. The test results presented in this study indicate that TRM jacketing is an extremely promising solution for the confinement of RC columns, including poorly detailed ones in seismic regions.
Article
Full-text available
The application of textile reinforced mortar (TRM) as a means of increasing the shear resistance of reinforced concrete members is investigated in this study. TRM may be considered as an alternative to fiber reinforced polymers (FRP), providing solutions to many of the problems associated with application of the latter without compromising much the performance of strengthened members. Based on the experimental response of reinforced concrete members strengthened in shear it is concluded that textile-mortar jacketing provides substantial gain in shear resistance; this gain is higher as the number of layers increases and, depending on the number of layers, is sufficient to transform shear-type failure to flexural failure. TRM jackets were provided in this study either by conventional wrapping of fabrics or by helically applied strips. Both systems resulted in excellent results in terms of increasing the shear resistance. However, compared with their resin-impregnated counterparts, mortar-impregnated textiles may result in reduced effectiveness. Modelling of reinforced concrete members strengthened in shear with TRM jackets instead of FRP ones is presented by the authors as a rather straightforward procedure by the proper introduction of experimentally derived jacket effectiveness coefficients. From the limited results obtained in this study it is believed that TRM jacketing is an extremely promising solution for increasing the shear resistance of reinforced concrete members.
Article
Full-text available
The application of textile-reinforced mortars (TRMs) as a means of increasing the axial capacity of concrete through confinement is investigated experimentally in this study. TRM may be thought of as an alternative to fiber-reinforced polymers (FRPs), addressing many of the problems associated with application of the latter without compromising performance by a significant degree. Based on the response of confined cylinders and short rectangular columns, it is concluded that textile-mortar jacketing provides a substantial gain in compressive strength and deformability; this gain is higher as the number of confining layers increases and depends on the tensile strength of the mortar. Compared with their resin-impregnated counterparts, mortar-impregnated textiles may result in reduced effectiveness. This reduction was more pronounced in cylindrical specimens but rather insignificant in rectangular ones. Favorable confinement characteristics on rectangular columns were also obtained by using helically applied unbonded strips with end anchorages - an interesting concept that deserves further investigation. Modeling of concrete confined with jackets other than resin-impregnated ones is presented by the authors as a rather straight-forward procedure through the proper introduction of experimentally derived jacket effectiveness coefficients. From the results obtained in this study, it is believed that TRM jacketing is an extremely promising solution for the confinement of reinforced concrete.
Article
Full-text available
In this paper, the effectiveness of textile-reinforced mortars (TRMs), as a means of increasing the shear resistance of reinforced concrete beams, is experimentally and numerically investigated. Textiles comprise of fabric meshes made of long woven, knitted or even unwoven fiber rovings in at least two (typically orthogonal) directions. Mortars-serving as binders-may (or may not) contain polymeric additives usually used to have improved strength properties. These TRMs may be considered as an alternative to fiber-reinforced polymers (FRP), providing solutions to many of the problems associated with application of the latter without compromising much of the performance of strengthened members. In the present study, a new type of textile (basalt-based textile) was used as strengthening material. Two different mortar types' viz. cementitious and polymer-modified cementitious mortars were used as binding material for the textile sheets. The studied parameters also included the number of textile layers as well as the orientation of the textile material. The experimental program comprises of testing two control beams which were intentionally designed to be deficient in shear, in addition to testing eight beams which were externally upgraded by TRM sheets for enhancing their shear capacity. On the basis of the experimental response of reinforced concrete members strengthened in shear, it is concluded that textile-mortar composite provides substantial gain in shear resistance; this gain is higher as the number of layers increases. With higher number of layers, textile with 45 orientation along with polymer-modified cementitious mortar provides the highest shear strength enhancement. Nonlinear finite-element (FE) analysis was also carried out on the tested beams using LSDYNA, which is transient nonlinear dynamic analysis software. The numerical analysis carried out involved case studies for TRM modeled, with and without mortar. Good agreement was achieved between the experimental and numerical results especially for the ultimate load carrying capacity for the case of FE models incorporating mortar. The study was extended numerically to include additional cases of TRM-strengthened specimens with more number of TRM layers as well as a case of FRP-strengthened specimen. DOI:10.1061/(ASCE)CC.19435614.0000239. (C) 2012 American Society of Civil Engineers.
Article
Full-text available
The use of unreinforced masonry (URM) walls is common practice in different types of construction, such as interior or exterior walls. URM walls are typically deficient in flexural capacity when subjected to out-of-plane loading caused by high wind pressure or earthquakes. Retrofitting masonry walls with novel materials, such as fiber-reinforced polymer (FRP) composites, has shown enhancement of the flexural capacity and pseudoductility. This study evaluates the feasibility of fabric-reinforced cementitious matrix (FRCM) as an alternative external strengthening technology to improve out-of-plane behavior of URM walls. This paper reports experimental results on flexural capacity of nine clay brick walls of which six were strengthened with two different amounts of FRCM, namely one and four reinforcement fabrics. Experimental evidence shows significant improvements in the structural performance in terms of flexural capacity and stiffness of the strengthened walls. An analysis, disregarding arching effect, is conducted, and its results are compared with the experimental database. From here, the design limits are discussed. Finally, experimental data from other research programs using FRP are reported to show that when flexural capacity is related to a calibrated reinforcement ratio, the two technologies are equivalent.
Article
Full-text available
Unreinforced masonry (URM) walls have been constructed for the past millennia and are still widely used today. URM walls have proven to have low shear strength and are prone to brittle failure when subjected to in-plane loads caused by earthquake or wind. Retrofitting URM walls is accomplished internally and externally using current techniques, such as placing steel bars in the cavities and grouting, post-tensioning with steel tendons, stitching, and adhering fiber-reinforced polymers (FRP) to increase capacity and enhance pseudoductility. In this study, a fabric-reinforced cementitious matrix (FRCM) system is applied to URM walls to determine its feasibility as an alternative external strengthening technology. The experimental program consists of testing a total of nine clay brick walls under diagonal compression. Two FRCM strengthening reinforcement schemes are applied, namely, one and four reinforcement fabrics. An analytical model is used to calculate the shear capacity of strengthened URM walls and compare its results with the experimental database. The effect of limitations in design approach on shear capacity of strengthened walls is discussed.
Article
Full-text available
The repair and retrofit/rehabilitation of existing concrete and masonry structures have traditionally been accomplished with ex-ternally bonded fiber-reinforced polymer (FRP) systems, steel plates, reinforced concrete (RC) overlays, and posttensioning, just to name some of the many techniques presently available. Fabric-reinforced cementitious-matrix (FRCM) composites have recently emerged as an additional strengthening technology. FRCM is a composite material consisting of a sequence of one or more layers of cement-based matrix reinforced with dry-fiber fabric. This paper has three objectives: (1) to review existing guidelines for tensile testing and calculation of FRCM material properties to be used in analysis; (2) to report on some of the results of an experimental program intended to characterize the tensile behavior of FRCM coupons; and (3) to discuss the performance and analysis of concrete RC slab-type elements strengthened with FRCM. The laboratory results demonstrate the technical viability of this new composite material system for strengthening flexural RC members.
Article
The overall performance of hollow clay tile infilled reinforced concrete (RC) frames strengthened with carbon fiber-reinforced polymer (CFRP) materials is experimentally investigated in this paper. For this purpose, five one-third scale, one-bay, two-story specimens were constructed with common deficiencies (that is, low concrete strength, insufficient lap splice length, poor confinement, and lack of joint reinforcement) observed in existing RC frames and tested under reversed cyclic lateral loading. The test results indicated that the investigated strengthening schemes yielded a significant enhancement in both the response and the load capacity. It is also seen that the effectiveness of the strengthening strongly depends on the composite action of the infill panel, ensuring that the surface-bonded fiber-reinforced polymer (FRP) is provided with a sufficient anchorage development length to the surrounding frames. Results and discussions are presented on the basis of the observed global performance and local failure mechanisms along with the detailed comparisons of similar studies. Conclusions are also' drawn to provide tentative retrofit FRP scheme recommendations.
Article
A full-scale unreinforced masonry (URM) wall with an opening was tested under in-plane lateral loading. The wall was first subjected to monotonically increasing displacements until a moderate damage level was reached. The damaged specimen was then cyclically tested up to almost the same maximum drift attained during the monotonic test to investigate the effects of previous damage on its nonlinear response. Finally, the masonry wall was repaired with inorganic matrix-grid (IMG) composites and subjected to a cyclic displacement-controlled test up to a near-collapse state. Most of the observed damage developed in the spandrel panel affecting both lateral resistance and strength degradation. Rocking of piers governed lateral stiffness and hysteretic response, which was characterized by low residual displacements and recentering behavior. The comparison between the experimental force-displacement curves demonstrated that the IMG strengthening system was able to provide energy dissipation capacity to the spandrel panel, restoring load-bearing capacity of the as-built wall, and delaying strength degradation that was indeed observed at larger displacements. Bilinear idealizations of force-displacement curves allowed the identification of displacement ductility, global overstrength, and strength reduction factor of the tested wall systems. DOI: 10.1061/(ASCE)CC.1943-5614.0000193. (C) 2011 American Society of Civil Engineers.
Article
In this paper, the effectiveness of fiber-reinforced cementitious matrix (FRCM) materials for the strengthening of reinforced concrete (RC) beams is experimentally investigated. Bending tests on RC beams strengthened with different FRCM materials, made out of (1) carbon fiber nets; and (2) poliparafenilenbenzobisoxazole (PBO) fiber nets embedded in cement-based matrix, are performed. For case (2), different net shapes, cementitious matrices, and a number of net layers were considered. Depending on the type of fibers and matrix, different flexural debonding failure modes are identified. The fiber strain at debonding is evaluated by comparing the experimental results with those obtained with two different theoretical models. The results obtained in this study confirm the effectiveness of FRCM materials for the strengthening of RC structures and encourage further experimental and theoretical work on the topic. A better understanding of the debonding phenomenon is crucial for an optimal design of the strengthening material. The way in which the nature of fibers and matrices and the number of layers control the performance of the strengthened members is also investigated in the present paper. DOI: 10.1061/(ASCE)CC.1943-5614.0000218. (C) 2011 American Society of Civil Engineers.