ACKNOWLEDGMENTS This study grew out of data analyzed from a post-occupancysurvey. The insights of Charlie Huizenga and Steve Murray of CBE, and Tamara Dinsmore and Randy Howder of SOM, spurred this effort. The research proposal was developed jointly with Ken Roy of Armstrong World Industries. Many,colleagues at Charles M. Salter Associates suggested changes that clarified both the method and text, particularly Jeff Clukey, Jack Freytag, Harold Goldberg, Tony Nash, Michael Toy, Pamela Vold and Brenda Yee. CBE Partner representatives Kevin Kampschroer (US General Services Administration),Ken Roy (Armstrong World Industries), and David Wyon (Technical University of Denmark, formerly with Johnson Controls) offered editorial suggestions that were instrumental in finalizing the text. David Lehrer (CBE) worked tirelessly with us through many revisions, and is responsible for the report’s graphic clarity. CBE Director Ed Arens’ insight, rigor, and tireless guidance were instrumental through the entire project. The Center for the Built Environment (CBE) was established in May 1997 at the University of California, Berkeley, to provide timely unbiased information on promising new building technologies and design strategies. The Center's work is supported by the National Science Foundation and CBE's Industry Partners, a consortium of corporations and organizations committed,to improving the design and operation of commercial buildings. CBE’s Industry Partners include: Armstrong World Industries Arup California Department Of General Services California Energy Commission EHDD Architects HOK Keen Engineering NBBJ
No caption available
… 
No caption available
… 
Content may be subject to copyright.
eScholarship provides open access, scholarly publishing
services to the University of California and delivers a dynamic
research platform to scholars worldwide.
Center for the Built Environment
UC Berkeley
Title:
Case Studies of a Method for Predicting Speech Privacy in the Contemporary Workplace
Author:
Salter, C.
Powell, K.
Begault, D.
Alvarado, R.
Publication Date:
01-01-2003
Series:
Indoor Environmental Quality (IEQ)
Publication Info:
Indoor Environmental Quality (IEQ), Center for the Built Environment, Center for Environmental
Design Research, UC Berkeley
Permalink:
http://escholarship.org/uc/item/8qf0z5v4
Additional Info:
ORIGINAL CITATION: Salter, C., K. Powell, D. Begault, and R. Alvarado, 2003. Case Studies of
a Method for Predicting Speech Privacy in the Contemporary Workplace. CBE Summary Report,
January. (2MB)
Abstract:
In surveys of office environments that measure occupants’ satisfaction with their workspace,
the intrusion of unwanted sound—noise—vies with temperature as the leading source of
dissatisfaction (Harris, 1978, 1991, Sundstrom, 1994, Brill, 2001). Recent research by the Center
for the Built Environment supports this finding, with more than 40% of employees responding to
CBE’s occupant satisfaction survey reporting that workplace acoustics make it harder for them
to do their job (CBE, 2001). Moreover, an elevated level of workplace noise has been shown
to increase stress, decrease motivation and is associated with risk factors for musculoskeletal
disorder (Evans, 2000).
To improve this situation, architects, interior designers, and facilities management professionals
need to be able to translate a proposed design into a specific prediction of acoustical satisfaction
with the resulting workspace. Over the past 40 years, acoustical consultants have in fact developed
such a method. In the late 1950’s, engineers at Bolt, Beranek & Newman recognized that a
majority of acoustical complaints in offices were related to speech privacy—overhearing unwanted
conversations or feeling that one is overheard. Building on research at Bell Labs that correlated
a listener’s ability to understand words with the ratio between the loudness of a person’s voice
eScholarship provides open access, scholarly publishing
services to the University of California and delivers a dynamic
research platform to scholars worldwide.
and the loudness of the background noise, these engineers demonstrated that a listener’s inability
to understand words in a workplace setting is part of this same continuum of signal to noise.
They then showed that that a series of objective measurements can establish this ratio and
accurately predict an occupant’s satisfaction with their speech privacy (Cavanaugh 1962). Over
the past forty years, this method for predicting speech privacy satisfaction with has been simplified
(Young, 1965), adapted for use in open plan environments (Pirn, 1971) and consolidated into
worksheet formats for both open and closed office environments (Egan, 1972). Versions of this
calculation procedure have been published in leading texts on acoustical design, including ones
by Cavanaugh (1999), Egan (1988), and Salter (1998).
Designing Acoustically Successful Workplaces:
CASE STUDIES OF A METHOD FOR PREDICTING
SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
SUMMARY REPORT, JANUARY 2003
CHARLES M. SALTER ASSOCIATES INC.
CHARLES SALTER, KEVIN POWELL,
DURAND BEGAULT, ROBERT ALVARADO
CENTER FOR THE BUILT ENVIRONMENT
ACKNOWLEDGMENTS
This study grew out of data analyzed from a post-occupancy survey. The insights of Charlie
Huizenga and Steve Murray of CBE, and Tamara Dinsmore and Randy Howder of SOM,
spurred this effort. The research proposal was developed jointly with Ken Roy of Armstrong
World Industries. Many colleagues at Charles M. Salter Associates suggested changes that
clarified both the method and text, particularly Jeff Clukey, Jack Freytag, Harold Goldberg,
Tony Nash, Michael Toy, Pamela Vold and Brenda Yee. CBE Partner representatives Kevin
Kampschroer (US General Services Administration), Ken Roy (Armstrong World Industries),
and David Wyon (Technical University of Denmark, formerly with Johnson Controls) offered
editorial suggestions that were instrumental in finalizing the text. David Lehrer (CBE) worked
tirelessly with us through many revisions, and is responsible for the report’s graphic clarity.
CBE Director Ed Arens’ insight, rigor, and tireless guidance were instrumental through the
entire project.
The Center for the Built Environment (CBE) was established in May 1997 at the University
of California, Berkeley, to provide timely unbiased information on promising new building
technologies and design strategies. The Center's work is supported by the National Science
Foundation and CBE's Industry Partners, a consortium of corporations and organizations
committed to improving the design and operation of commercial buildings.
CBE’s Industry Partners include:
Armstrong World Industries
Arup
California Department Of General Services
California Energy Commission
EHDD Architects
HOK
Keen Engineering
NBBJ
Pacific Gas & Electric Co.
Skidmore Owings And Merrill, LLP
Tate Access Floors, Inc.
Taylor Engineering Team: Taylor
Engineering, The Electrical Enterprise,
Southland Industries, Swinerton Builders
Trane
U.S. Department Of Energy (DOE)
U.S. General Services Administration
(GSA)
United Technologies Corporation
Webcor Team: Webcor Builders,
Critchfield Mechanical, Rosendin Electric,
C&B Consulting Engineers
York International Corporation
© Center for the Built Environment (CBE)
A National Science Foundation Industry/University Cooperative Research Center
390 Wurster Hall #1839, Berkeley, CA 94720-1839
tel: 510.642.4950 fax: 510.643.5571
cbe@uclink.berkeley.edu www.cbe.berkeley.edu
TABLE OF CONTENTS
1.0 Introduction 1
2.0 Method 2
3.0 Open Plan Case Study Results 6
4.0 Private Office Case Study Results 14
5.0 Conference Room Case Study Results 22
6.0 Conclusions 30
Appendix 1: Detailed Method for Speech Privacy Predictor 31
Appendix 2 Construction Details for Acoustical Privacy 38
Appendix 3. Survey Methods and Results 39
Appendix 4: Testing Protocol 41
References 42
DESIGNING ACOUSTICALLY SUCCESSFUL WORKPLACES:
Case Studies of a Method for Predicting
Speech Privacy in the Contemporary Workplace
1.0 INTRODUCTION
In surveys of office environments that measure occupants’ satisfaction with their
workspace, the intrusion of unwanted sound—noise—vies with temperature as the leading
source of dissatisfaction (Harris, 1978, 1991, Sundstrom, 1994, Brill, 2001). Recent
research by the Center for the Built Environment supports this finding, with more than
40% of employees responding to CBE’s occupant satisfaction survey reporting that
workplace acoustics make it harder for them to do their job (CBE, 2001). Moreover, an
elevated level of workplace noise has been shown to increase stress, decrease motivation
and is associated with risk factors for musculoskeletal disorder (Evans, 2000).
To improve this situation, architects, interior designers, and facilities management
professionals need to be able to translate a proposed design into a specific prediction of
acoustical satisfaction with the resulting workspace. Over the past 40 years, acoustical
consultants have in fact developed such a method. In the late 1950’s, engineers at Bolt,
Beranek & Newman recognized that a majority of acoustical complaints in offices were
related to speech privacy—overhearing unwanted conversations or feeling that one is
overheard. Building on research at Bell Labs that correlated a listener’s ability to
understand words with the ratio between the loudness of a person’s voice and the loudness
of the background noise, these engineers demonstrated that a listener’s inability to
understand words in a workplace setting is part of this same continuum of signal to noise.
They then showed that that a series of objective measurements can establish this ratio and
accurately predict an occupant’s satisfaction with their speech privacy (Cavanaugh 1962).
Over the past forty years, this method for predicting speech privacy satisfaction with has
been simplified (Young, 1965), adapted for use in open plan environments (Pirn, 1971)
and consolidated into worksheet formats for both open and closed office environments
(Egan, 1972). Versions of this calculation procedure have been published in leading texts
on acoustical design, including ones by Cavanaugh (1999), Egan (1988), and Salter
(1998).
Acoustical consultants have found these speech privacy calculations useful for analyzing
design documents, evaluating full-scale prototypes and identifying problems in fully
occupied and functioning buildings. These calculation procedures have not, however,
been disseminated widely in the architectural and interior design community. Reasons
may include unfamiliar measurement units and concepts, the specialized testing
equipment required for prototype and in situ evaluations, a lack of formal testing validated
and illustrated in the context of today’s offices, and cost and aesthetics-driven decision
making which does not identify the risks of unacceptable acoustics.
2 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
This paper presents an updated, simple, easy-to-use version of a predictive methodology,
the Speech Privacy Predictor (SPP). SPP is intended to help those designing, furnishing
or retrofitting open plan and private offices. To illustrate the application of the SPP
method, nine case studies are described below. These case studies document acoustical
conditions in an office building where the Center for the Built Environment had
previously conducted an occupant survey. In layout and utilization, this building is
representative of a typical modern office—large open plan areas, ubiquitous telephones
with built-in speakerphones, distributed common areas, and widespread use of computers.
It is also typical of the acoustical shortcomings of modern offices: CBE’s occupant
satisfaction survey had detected significant occupant dissatisfaction with speech privacy.
Each case study is designed to demonstrate how the SPP calculation is performed. The
case studies evaluate the reliability of the SPP method, by comparing predicted results
with measurements of actual acoustic conditions as well as the subjective level of acoustic
dissatisfaction reported by those who had taken the CBE Survey.
Results of these comparisons show broad agreement between the predictive tool,
measured acoustic conditions, and surveyed employee dissatisfaction. The SPP method
therefore appears to be a viable tool for designing to achieve good acoustical
environments. This finding is especially noteworthy because while poor speech privacy
has been shown to reduce worker motivation, interfere with concentration and
compromise the security of meetings and confidential discussions, retrofitting office
spaces with poor acoustic performance is often an expensive and disruptive solution.
2.0 METHOD
2.1 Building Selection
To illustrate the application of the SPP method, and evaluate its effectiveness as a design
tool, a series of case studies were conducted in a building where the Center for the Built
Environment had conducted a Post Occupancy Evaluation Survey.
1
This Class-A office
building was constructed in 1980 for its current owner, and contains 650,000 gross square
feet of office space. The building’s layout is typical of the modern office: 15% of gross
space is used for enclosed private offices and conference rooms, with the remainder used
for open plan workstations, common areas, lobbies, circulation, and a variety of other
operations. Office equipment is also characteristic of the modern workplace: ubiquitous
telephones with built-in speakerphones, computers on nearly every desktop, broad
distribution of laser printers, and centrally located areas for photocopying.
While nearly two-thirds of the 687 respondents reported overall satisfaction with their
workspace, and nearly three-quarters of respondents expressed overall satisfaction with
the building, CBE’s survey had detected significant dissatisfaction with acoustical
conditions.
2
In contrast to pluralities reporting that lighting, air quality, temperature,
1
This survey was administered in January 2001, and asked occupants to rank their satisfaction with a
number of attributes of their building. Questions ranged from building-wide attributes, such as the
perceived quality of the grounds, lobby and cleanliness, to specific conditions in the occupant’s work
area, such as lighting, office equipment and thermal comfort. The survey’s protocol requires that
specific information about the building, including its owner, location and identifiable physical attributes
be kept confidential. An overview of the survey’s structure, how the survey was produced and
implemented, as well as key acoustical findings is reproduced in Appendix 3.
2
Of the nine major categories surveyed, only acoustical conditions got more votes of dissatisfaction than
satisfaction
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 3
office equipment, and furniture made it easier to get their jobs done, 46% of building
occupants reported that the overall noise level in their workspace made it harder for them
to get their job done.
3
Table 1
Summary of
Post Occupancy
Evaluation Results by
Category
This level of acoustic dissatisfaction relative to other building attributes is consistent with
nearly two-dozen similar occupant satisfaction surveys CBE has administered over the
past three years. It is nonetheless puzzling, because the surveyed building is owner-
occupied, constructed less than twenty five years ago as a headquarters building with
premium finishes and materials, and has a responsive and involved facility management
staff. Moreover, dissatisfaction is not limited to occupants working in open-plan areas:
more than a third of respondents in the enclosed private offices also expressed
dissatisfaction with their speech privacy. Nor can acoustical dissatisfaction be attributed to
unusual or specialized work processes, overcrowded conditions, rapid growth or
management turbulence: the majority of the building’s occupants are managerial and
professional workers engaged in the types of ‘knowledge work’ characteristic of many
modern business enterprises, and the building’s owner/occupant has not engaged in
expansion, acquisition or layoffs in the five years before the survey. Would the SPP
method have predicted this level of acoustic dissatisfaction?
3
Question 30.4. “Overall, does the noise level in your workspace make it easier or harder to get your job
done?”
4 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
2.2 Selection of Case Study Locations
CBE’s research protocol allowed us to filter data by floor and office type (enclosed/open
plan). We then worked with the building’s facility manager to identify floors that had a
representative range of acoustic and work conditions, and responses that tracked with the
overall building.
4
OPEN PLAN CASE STUDIES.
The facility manager noted that the physical layout of workstations in the case study floor
were representative of those distributed throughout the facility, consisting of standard 8
foot by 10-foot cubicles, enclosed by Herman Miller Action Office I, a 62-inch high
acoustical partitions.
5
The ceiling finishes were also representative of those found
throughout the building, consisting of 2-x 2-foot mineral-fiber ceiling tiles
6
with a noise
reduction coefficient (NRC) of 0.55
7
and a ceiling attenuation class (CAC) of
approximately 35.
8
Floors were finished with standard carpet tiles.
PRIVATE (ENCLOSED) OFFICE CASE STUDIES.
Although the facility manager reported that, building-wide, private offices varied more in
size than did open-plan workstations, the private offices we studied were standardized at
10 feet wide by 15 feet deep, and were located in the building core. These offices were
constructed of uninsulated steel stud partitions faced with one layer of gypsum board on
each side. A solid core wood door and a five-foot expanse of floor to ceiling glazing were
part of the corridor-facing wall. Partitions terminated at the underside of the suspended
acoustic tile ceiling. Ceiling and floor finishes were identical to open plan areas.
CONFERENCE ROOM CASE STUDIES
Narrative comments revealed frequent complaints of sound transfer between private
offices and conference rooms, and between the conference rooms themselves. We
conducted case studies in three representative conditions: between a large conference
room and a private office, between a small conference room and a private office and
between a small conference room and a large conference room. Like private offices,
conference rooms were located in the building core, and shared the same modular
geometry (large conference rooms were 15 feet by 20 feet, small conference rooms 10 feet
by 15 feet). Construction assemblies and finishes for conference rooms were nearly
4
Survey results for the selected case study locations showed a level of speech privacy dissatisfaction that
was within 10% of the building-wide average response for open plan areas and within 2% of the
building-wide average response for the private offices.
5
The building occupant has adopted a new standard of 8’ x 8’ cubes, but at the time of the survey, only
limited areas had been redesigned.
6
A portion of the private offices we studied received a higher performing ceiling as part of a 1998
redesign. This ceiling did not produce a noticeable effect in survey data. The open plan case studies
were conducted on a floor with a ceiling height of 13 feet while other floors had a 9-foot ceiling height.
Again, we were not able to detect significance in survey data.
7
NRC measures the average percentage of noise a material absorbs at four frequencies across the audible
spectrum. This key measure of absorption of general office noise is expressed as a single value
percentage.
8
CAC rates a structure's efficiency as a barrier to airborne sound at 16 speech frequencies. It is an
especially significant measure in providing acoustic privacy between adjacent work areas, where sound
can penetrate plenum spaces and carry to other spaces. CAC is stated as a minimum value; CAC
minimum 25 is acceptable in open plan offices, while a rating of minimum 35 or 40 is preferred for
closed offices. (Reference: ASTM E 1264)
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 5
identical to those found in private offices, including the same acoustic tile ceilings,
carpeted floors and walls of gypsum board on steel studs, with the corridor facing wall
including a solid core door, and an expanse of floor to ceiling glass. No sound absorbing
panels were installed on any walls.
2.3 Application of the SPP Method
To establish the ratio of intruding speech to the ambient background noise the SPP method
considers a pair of adjacent spaces, the source space, where conversation is occurring, and
the receive space, where speech privacy is being measured. The calculation procedure
simply involves subtracting isolation factors from source factors, in order to produce a
single number rating called sound excess for the receive space. Speech-privacy
satisfaction can then be plotted as a function of the single number sound excess rating, as
illustrated in Figure 2.
To illustrate the SPP method’s application and evaluate whether it would have predicted
the unsatisfactory conditions detected by the CBE survey in both open and enclosed office
settings, a SPP predictive calculation procedure was performed for each case study
location
9
. These calculations drew on the following information: workstation layout, room
surface treatments and materials, partition heights and construction, voice levels, room
sizes, and background noise. To test the reliability of the assumed values for the variables
involved in these calculations, a series of acoustical measurements and field observations
of occupant behavior were also made in each case study location. Predicted and measured
results were described in terms of the level of satisfaction predicted by the SPP method,
and congruence of these ratings with the CBE survey’s overall finding of occupant
satisfaction with speech privacy was evaluated. Table 2 provides an overview of the
research design. The worksheets and detailed description of the SPP method’s variables
and calculation method are summarized in Appendix 1.
Table 2: Overview
of Research Design
PREDICTED VALUES
(FROM DESIGN DOCUMENTS)
MEASURED VALUES
(FROM FIELD OBSERVATION
& MEASUREMENT)
SOURCE FACTORS
A. Sum Source Factors
(value) (value)
ISOLATION FACTORS
B. Sum Isolation Factors
(value) (value)
SOUND EXCESS
Source Factors minus Isolation
Factors (A-B)
(value) (value)
Predicted Level of Acceptability (value) (value)
9
Testing protocol is described in Appendix 4.
6 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
Figure 2: Levels of
Speech Privacy
Acceptability, per
Cavanaugh
SOUND EXCESS LEVEL OF
DISSATISFACTION
+3 Mild
+7 Moderate
+12 Strong
>+20 Extreme
3.0 OPEN PLAN CASE STUDY RESULTS
Three open plan case studies are described below. Overall, we found that the level of
dissatisfaction predicted by the SPP method correlated with the dissatisfaction with speech
privacy expressed in the CBE survey and with measurements of actual acoustical
conditions. There was, however, more spread between predicted and measured SPP
values than in case studies of private offices and conference rooms. We attribute this
spread largely to the greater range of conditions that the SPP procedure must account for
in an open plan environment. In this case, better than predicted noise reduction between
workstations was achieved by a combination of a partition product that performs better
than expected, a greater than usual number of absorptive surfaces, and a noisy HVAC
system in one of the three measured locations.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 7
Had these case study locations
originally been evaluated with the
SPP method, a level of background
noise too low for normal speech
privacy given the dense spacing of
cubicles would have been
predicted. Although it may seem
counter-intuitive, the most
effective way to improve speech
privacy in this condition is to
introduce background noise in a
controlled manner. This is
commonly referred to as sound
masking, and is typically achieved
by placing loudspeakers in the
ceiling plenum. These
loudspeakers produce evenly
distributed noise similar to the
sound of air coming out of an air register. Based on this finding, a sound masking system
has been installed in this area as a retrofit, and is currently being tuned and adjusted.
Initial response has been positive.
Two additional design issues would have been identified as likely to contribute to a speech
privacy problem. First, a lack of appropriately designed and distributed meeting and
conference spaces leads occupants to hold impromptu meetings in their cubicles, even
though occupants are aware that this will disturb their neighbors. The second design issue
that would have been identified is that grid-like layouts of cubicles create an extensive
network of circulation ‘streets’ where casual conversation is likely to occur and disturb
other occupants. Both of these behaviors were, in fact, observed as contributing
significantly to the speech privacy complaints in the space.
FINDING 1: In open plan settings with underfloor air distribution or traditional variable
air volume overhead ventilation systems (HVAC), the background sound level will be too
low to achieve “normal” speech privacy. In these environments the background sound can
be augmented with sound masking system. Adequate absorptive surfaces such as
acoustical ceiling and partitions and a carpeted floor will also be required.
FINDING 2: In open plan offices, there should be a distribution of enclosed ‘teaming’ and
conference spaces, located proximate to the work area, with good visual access to and
effective acoustical separation from the open plan work area to accommodate both formal
and informal group conversation.
FINDING 3: In open plan settings a ‘boulevard’ and ‘cul-de-sac’ layout should be used to
ensure that impromptu casual conversation occurs away from workstations.
8 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
3.1 Case Study 1: Open Plan Workstation to Workstation
In this case study, we observed work-related conversation occurring between two co-
workers in a cubicle adjacent to the evaluation space. Even though a nearby HVAC
supply air diffuser was mis-adjusted, creating additional background noise and improving
the signal-to-noise ratio in this workspace, the occupant commented, “I am disturbed by
conversations in adjacent cubes, it makes it difficult to concentrate”.
Plan:
Case Study 1
Although the employees in the adjacent cubicle were maintaining a respectfully quiet
conversational voice, it is difficult to accommodate any meeting activity in an open plan
workstation. Even if there were a sound masking system, this level of conversational
activity given this cubicle spacing would produce “moderate dissatisfaction.”
Narrative comments in the CBE survey offer additional insight into this condition:
We currently don't have a conference room; therefore, meetings are held next to my
cubicle. I can usually ignore that noise, but it is extremely difficult and disconcerting
to know that the people in these meetings hear my phone calls.
It is very hard to concentrate when people are talking, having meetings, in
surrounding cubes.
The other group next to us is very chatty and loud. They are not
programmers/developers so they may not need the same amount of quiet I do to
complete my job.
The biggest illusion of cubicle dwelling is the illusion of privacy. People sometimes
forget that just because they cannot be seen does not mean that they cannot be heard.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 9
Case Study 1
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level
(dBA)
Low Voice 54 Conversational 60
B. Speech Privacy
Criterion
Normal 9 Normal 9
Sum Source Factors 63 69
ISOLATION FACTORS PREDICTED OBSERVED
C. Distance:
Source to receiver
(from table)
6 feet 5 N/A
D. Barrier Noise
Reduction
(from table)
Source to barrier: 3’
Receiver to barrier: 3’
Break in line-of-sight: 1’
8 N/A
C+D Noise Reduction
(measured in situ)
13 Measured 17
E. Background Noise
(dBA, receiving
cubicle)
Typical: Open Plan
(without sound
masking system)
40 Measured
(Under HVAC
return)
42
Sum Isolation Factors 53 59
SOUND EXCESS PREDICTED OBSERVED
Source factors minus
isolation factors
+10 +10
Predicted level of
acceptability
Strong dissatisfaction Strong Dissatisfaction
.
10 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
3.2 Case Study 2: Workstation to Workstation
In this case study, we observed no unusual activities. The occupant of this cubicle and
others nearby spoke in low speech levels into their telephones. This voice level is
characteristic of the type of speech behavior that is most successfully accommodated in an
open plan environment. The very low level of background noise created unsatisfactory
speech privacy conditions. The occupant commented, “I can hear others talking but I tune
it out. No one can use a speakerphone because it would bother other people”. SPP
calculation would suggest that the introduction of 8 bBA of additional background noise
through a well-tuned sound-masking system would create acceptable acoustical conditions
for this partition system and cubicle layout, assuming the workgroup would consistently
maintain the low voice level we observed.
Plan:
Case Study 2
Narrative comments in the POE survey offer additional insight into this condition:
Some talking could be classified as productive (one can learn a lot just by overhearing
relevant conversations).
I wear hearing protectors (like the jack-hammer guys) when I really want complete
concentration. It's amazing how noisy the area can be - not the decibel level, but a
number of surrounding cubicles with conversations going on.
No private work conversations can ever be held in my work area because of the lack of
privacy.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 11
Case Study 2
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level
(dBA)
Low Voice 54 Low Voice 54
B. Speech Privacy
Criterion
Normal 9 Normal 9
Sum Source Factors 63 63
ISOLATION FACTORS PREDICTED OBSERVED
C. Distance:
Source to receiver
(from table)
6 feet 5 N/A
D. Barrier Noise
Reduction
(from table)
Source to barrier: 3’
Receiver to barrier: 3’
Break in line-of-sight: 1’
8 N/A
C+D Noise Reduction
(measured in situ)
13 Measured 17
E. Background Noise
(dBA, receiving
cubicle)
Typical: Open Plan
(without sound
masking system)
40 Measured 37
Sum Isolation Factors 53 54
SOUND EXCESS PREDICTED OBSERVED
Source factors minus
isolation factors
+10 +9
Predicted level of
acceptability
Moderate-strong dissatisfaction Moderate-strong dissatisfaction
12 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
3.3 Case Study 3: Corridor Talkers to Workstation
In this case study, we observed an informal conversation occurring between two co-
workers from a different work unit taking place in the adjoining corridor. While
conversation was occurring, a nearby employee was engaged in technical work requiring
analytic concentration. Although the corridor conversation was not loud, it was not
possible to accommodate the type of casual, informal conversation that often occurs in
circulation spaces (and which is typically one of the desired outcomes of the less formal
open space environment) adjacent to a workstation where an occupant’s job required
concentration. The occupant commented: “People talk in the corridor near my
workstation, it can be distracting.”
Plan:
Case Study 3
In this case, the introduction of increased background noise would improve but not
remedy the situation. A change in occupancy to a person not requiring speech privacy
would be recommended for this area. If redesign could be considered, segregating
‘boulevards’ of office-wide circulation from ‘cul de sacs’ offering workstation access to
employees in a given workgroup would be recommended
Three narrative comments in the POE survey offer insight into this finding:
Corridors aren't just around the elevator, etc. but throughout the work area and
people stop and talk everywhere. The sound just carries through open space.
The floor plan is arranged so all the traffic goes past the open side of the cubicles.
Better design would come up with an alternative route.
I sit near a row of offices. The managers have lots of people in and out of their offices,
as they should, but the way the offices are set up, they reflect sound out into the open
office. It's very distracting.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 13
Case Study 3
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level
(dBA)
Conversational 60 Conversational 60
B. Speech Privacy
Criterion
Normal 9 Normal 9
Sum Source Factors 69 69
ISOLATION FACTORS PREDICTED OBSERVED
C. Distance:
Source to receiver
(from table)
12’ 10 N/A
D. Barrier Noise
Reduction
(from table)
Source to barrier: 6’
Receiver to barrier: 6’
Slight break in
line-of-sight’
5 N/A
C+D Noise Reduction
(measured in situ)
15 Measured 12
E. Background Noise
(dBA, receiving
cubicle)
Typical: Open Plan
(without sound
masking system)
40 Measured
(under HVAC return)
42
Sum Isolation Factors 55 54
SOUND EXCESS PREDICTED OBSERVED
Source factors minus
isolation factors
+14 +15
Predicted level of
acceptability
Strong dissatisfaction Strong dissatisfaction
14 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
4.0 PRIVATE OFFICE CASE STUDY RESULTS
Three case studies of private offices are described below. Here, too, we found that
occupant dissatisfaction predicted by the SPP method correlated broadly with the overall
speech privacy dissatisfaction detected in the CBE survey. Moreover, predicted values
calculated from design document data corresponded well with values derived from
measurement.
Had the design originally been evaluated with the SPP method, a series of options could
have been iteratively explored. This process would have begun by identifying employees
requiring “confidential” speech privacy and those requiring “normal” speech privacy.
Construction assemblies that could achieve the required levels of speech privacy would
have then have been recommended. These assemblies would likely have included
acoustically upgraded wall construction, and details minimizing the sound transfer
between offices where the wall terminates at the underside of a continuous, suspended
ceiling. Additional acoustic details to minimize sound leaks at wall penetrations and
floor/ceiling connections, as well as
methods to minimize the ‘cross talk’ that
occurs from unlined ducts running
between offices would also have been
recommended.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 15
FINDING 1:
In standard private offices (100-200 square feet) where ‘normal’ speech
privacy is desired and speakerphone use limited, an ordinary steel stud ceiling-height wall
can be used if the A-weighted background noise level is at least 40 dB. In a contemporary
office building with carpeted floors, a suspended acoustical ceiling, and VAV or
underfloor HVAC systems, this level of background noise is likely to be achieved with the
installation of a sound masking system. Alternatively, “normal” speech privacy can be
achieved in standard private offices with an acoustically upgraded wall assembly.
FINDING 2: In a similar office setting where a where a speakerphone is frequently used, a
“confidential” level of speech privacy is required, and a more typical background noise
level of 35 dB is desired, an acoustically rated, slab-to-slab partition wall is required.
FINDING 3: Speakerphone use should be specifically considered and accommodated in
either the acoustical design of private offices or in nearby spaces such as specially
designed ‘phone booths’ and conference rooms.
‘Normal’ speech
privacy provided by
ceiling height
partition and sound-
rated ceiling
16 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
4.1 Case Study 4: Private Office to Private Office
In this case study, we observed speakerphone use in the office adjacent to the evaluation
space. The occupant using the speakerphone later told us, “walls are thin. I know my
voice carries, and I am concerned that my neighbors can hear me”. A well-known psycho-
acoustic feedback mechanism describes the tendency of people to raise their voice when
they experience difficulty comprehending the person(s) they are speaking to.
10
In an
office setting, this frequently occurs when people use speakerphones.
11
In the past, private
offices have typically been designed to provide normal to confidential speech privacy for
informal conversation between two or three people. This voice level is lower than that
typically used by speakerphone users. Because speakerphones have become increasingly
widespread in office settings in recent years, an organizational decision should be made
regarding their appropriate use. One possibility is to restrict speakerphone use to
conference rooms and/or specially designed rooms, sometimes referred to as ‘phone
booths’. Alternatively, speakerphone use within an office can be accommodated by using
an acoustically rated construction that will provide the required level of speech privacy for
this voice level.
Plan:
Case Study 4
The following narrative comments in the CBE survey offer additional insight into this
finding:
[I am dissatisfied with the noise level because] several folks use their speakerphones
rather than using a conference room.
10
It is well known that the presence of noise produces an increase in vocal levels. People's systematic
speech modifications during noise are an automatic normalization response called the "Lombard effect".
During noise, people increase their volume and reduce theirs peaking rate and change both their pitch and
articulation, especially for vowels. Lombard (1911), Junqua (1993).
11
Among the causes of poor comprehension: the lack of spatial imaging associated with a monaural
source, the overall lack of fidelity in the telephone speaker, and in the case of conference calls, typically
poor audibility of some parties to the conversation.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 17
Case Study 4
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level
(dBA)
Raised 66 Raised 66
B. Speech Privacy Criterion Confidential 15 Confidential 15
C. Effect of Source Room
(from table)
150 sq. ft. 6 150 sq. ft. 6
Sum Source Factors 87 87
ISOLATION FACTORS
PREDICTED OBSERVED
D. Partition Rating
(STC or NIC)
3 5/8” steel stud
5/8” drywall each
side, slab to ceiling
39 Measured
39
E. Effect of Receive Room
(from table)
2
NA
F. Background Noise (dBA,
receiving room)
Typ.: Private Office 35 Measured 33
Sum Isolation Factors 76 72
SOUND EXCESS
PREDICTED OBSERVED
Source factors minus
isolation factors
+11 +15
Predicted level of
acceptability
Strong dissatisfaction Strong dissatisfaction
18 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
4.2 Case Study 5: Private Office to Private Office
In this case-study, we observed no unusual activity in the adjacent office or open plan
area. The occupant of the evaluation space complained, “I have quiet neighbors, but I can
hear talking from the offices on both sides of me. It’s not that I can hear what they are
saying, but that I can hear that people are talking, and it’s distracting”. The level of
speech privacy desired by this occupant, inaudibility, is not ordinarily provided in private
offices.
Plan:
Case Study 5
It should also be noted that a private office achieves its rated speech privacy only with its
door closed. With its door open, speech privacy will be only marginally better than in the
surrounding circulation space/office areas. Exacerbating the potential for disturbance by
conversation from surrounding areas, private offices are typically designed to have a level
of background noise approximately 10dBA below open plan areas. For these reasons,
private offices have traditionally been buffered by an administrative space, or placed
within a workgroup where overheard conversation is viewed as a benefit of an ‘open door
policy’.
The following narrative comments in the CBE survey offer additional insight into this
finding:
The area is noisy and it is sometimes difficult to concentrate unless I close my door.
Closing my door contradicts my open door policy.
I can hear conversations in the surrounding offices sometimes. It is annoying.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 19
Case Study 5
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level
(dBA)
Conversational 60 Conversational 60
B. Speech Privacy Criterion
(constant)
Confidential 15 Confidential 15
C. Effect of Source Room
(from table)
150 sq. ft. 6 150 sq. ft. 6
Sum Source Factors 81 81
ISOLATION FACTORS
PREDICTED OBSERVED
D. Partition Rating
(STC or NIC)
3 5/8” steel stud
5/8” drywall each
side, slab to ceiling
39 Measured
37
E. Effect of Receive Room
(from table)
0
NA
F. Background Noise (dBA,
receiving room)
Typ.: Private Office 35 Measured 38
Sum Isolation Factors 74 75
SOUND EXCESS
PREDICTED OBSERVED
Source factors minus
isolation factors
+7 +6
Predicted level of
acceptability
Moderate dissatisfaction
Moderate dissatisfaction
20 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
4.3 Case Study 6: Private Office to Private Office
As in Case Study 5, we observed no unusual activity in the adjacent offices or open plan
areas. In contrast to Case Study 5, however, the occupant of this evaluation space
appeared substantially less sensitive to the intrusion of speech. The occupant expressed
concern, however, that sound was traveling through the HVAC vent: “I’m generally
satisfied. But sometimes I can hear conversation in adjacent offices. Sound seems to
travel through vents”
Plan:
Case Study 6
All case-study private offices and conference rooms were constructed with walls that
extend only to the underside of a continuous suspended ceiling. Although this wall
assembly is less expensive than extending the walls from slab-to-slab, the common ceiling
plenum becomes a ‘flanking path’, a way for sound to transfer into the adjacent space by
moving around the intervening partition. Other common flanking paths include electrical
outlet boxes in the common partition, recessed lighting fixtures in the ceiling, connections
at the intersection of one partition with another or with a window mullion, and through
shared, unlined ventilation ductwork. In all six case studies of private offices and
conference rooms, we found sound leaks at the connection between the ceiling and the
partition wall, and cross talk at HVAC supply and return air grills
The following narrative comment in the CBE survey offers additional insight into this
finding:
Voices magnify and sound louder in my office than they do outside my office.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 21
Case Study 6
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level
(dBA)
Conversational 60 Conversational 60
B. Speech Privacy Criterion
(constant)
Confidential 15 Confidential 15
C. Effect of Source Room
(from table)
150 sq. ft. 6 150 sq. ft. 6
Sum Source Factors 81 81
ISOLATION FACTORS PREDICTED OBSERVED
D. Partition Rating
(STC or NIC)
3 5/8” steel stud
5/8” drywall each
side, slab to ceiling
39 Measured
38
E. Effect of Receive Room
(from table)
0
NA
F. Background Noise (dBA,
receiving room)
Typ.: Private Office 35 Measured 36
Sum Isolation Factors 76 74
SOUND EXCESS
PREDICTED OBSERVED
Source factors minus
isolation factors
+7 +7
Predicted level of
acceptability
Moderate dissatisfaction Moderate dissatisfaction
22 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
5.0 CONFERENCE ROOM CASE STUDY RESULTS
In the CBE survey respondents identified the intrusion of conference room noise into
adjacent meeting spaces and private offices as a significant problem. In the three
conference room case studies described below, the source of this problem is clear: as part
of the office space’s modular design, conference rooms are fashioned from the same wall
assemblies and floor and ceiling finishes as private offices. Conference rooms, of course,
typically accommodate activities where a louder voice level is used than occurs in a
private office. Therefore, a wall assembly that is adequate for a private office is not likely
to work well for a conference space.
Had these conference room designs been evaluated with the SPP method at the design
stage, acoustically improved wall constructions would have been recommended. An
adequate acoustical design would also include details for minimizing sound leaks and the
‘cross talk’ between conference
rooms and adjacent spaces
connected by unlined ducts and
shared ceiling plenums. Sound
absorbing wall treatments and
upgraded ceilings would likely
have also been recommended to
minimize reverberation and the
build-up of sound within these
rooms.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 23
FINDING 1:
Contemporary office design emphasizes flexibility. Wall and ceiling
constructions that will provide normal speech privacy in private offices are not likely,
however, to produce acceptable results given elevated voice levels and increased privacy
requirements of a conference/meeting space.
FINDING 2: Some conference rooms are specifically designed to accommodate
teleconferencing and audio-visual presentations. These spaces must also be designed to
provide an appropriate level of acoustical privacy that allows these rooms to operate
without disturbing occupants in adjacent spaces.
Ceilings and
partitions need to
provide adequate
sound insulation for
group conversation
in conference
rooms
24 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
5.1 Case Study 7: Large Conference Room to Private Office
In this case study, we investigated the level of privacy between a large conference room
and the occupant in an adjacent office. Although we did not observe the conference room
in use, the presence of audio-visual equipment in this room suggests that the room
supports presentations to an assembled group. When speaking to a group, a presenter
typically uses a “raised” to “loud” voice level. The room itself lacked absorptive
materials on its walls, contributing to a reverberant sound field (sound reflected by the
room’s surfaces rather than being absorbed by them). Testing showed that the acoustical
performance of the wall assemblies were the same as for private offices.
Plan:
Case Study 7
The following narrative comments in the CBE survey offer additional insight into this
finding:
I often hear noise coming from other conference rooms.
Some conference rooms that have shared walls with offices carry sounds from these
offices where you can hear every conversation in the office and vice versa.
There is no sound proofing between my office and the conference room. Thus, I can
hear conversations, loud laughter, and meeting proceedings. All of this sometimes
drives me from my office.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 25
Case Study 7
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level Loud
(Presentations)
72 Loud
(Presentations)
12
72
B. Speech Privacy Criterion Confidential 15 Confidential 15
C. Effect of Source Room 300 sq. ft. 2 300 sq. ft. 2
Sum Source Factors 89 89
ISOLATION FACTORS PREDICTED OBSERVED
D. Partition:
STC or NIC
3 5/8” steel stud
5/8” drywall each
side, slab to ceiling
39 Measured
39
E. Effect of Receive Room
(from table)
5
NA
F. Background Noise (dBA,
receiving room)
Typ.: Private Office 35 Measured 38
Sum Isolation Factors
79 77
SOUND EXCESS PREDICTED OBSERVED
Source factors minus
isolation factors
+10 +12
Predicted level of
acceptability
Strong dissatisfaction Strong dissatisfaction
12
No conference was taking place, this value was predicted
26 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
5.2 Case Study 8: Small Conference Room to Private Office
In this case study, we investigated the level of privacy between a small conference room
and the occupant in an adjacent office. Although we did not observe the conference room
in use, we would predict that the room’s smaller size would encourage the use of a lower
voice level than in the larger conference room. Voice levels are still greater than those
typically used in a private office, however. Moreover, the room’s lack of absorptive
materials and use of standard ceiling height wall construction contribute to a level of
acoustical impact even greater than in the larger conference room, where a louder voice
would typically be in use. An occupant in an adjacent office confirmed this behavior: “[I]
can hear conversations from adjacent offices and from the conference room behind me.
The conference room is worse.”
Plan:
Case Study 8
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 27
Case Study 8
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level Raised 66 Raised
13
66
B. Speech Privacy Criterion Confidential 15 Confidential 15
C. Effect of Source Room 150 sq. ft. 6 150 sq. ft. 6
Sum Source Factors 87 87
ISOLATION FACTORS PREDICTED OBSERVED
D. Partition:
STC or NIC
3 5/8” steel stud
5/8” drywall each
side, slab to ceiling
39 Measured
3 ½” steel stud
5/8” drywall each side
39
E. Effect of Receive Room
(from table)
2 NA
F. Background Noise (dBA,
receiving room)
Typical: Private
Office
35 Measured 37
Sum Isolation Factors
76 76
SOUND EXCESS PREDICTED OBSERVED
Source factors minus
isolation factors
+11 +11
Predicted level of
acceptability
Strong dissatisfaction Strong dissatisfaction
13
No conference was taking place, this value was predicted.
28 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
5.3 Case Study 9: Small to Large Conference Room
In this case study, we investigated the level of privacy between a small conference room
and the adjacent large conference room. Although we did not observe either conference
room in use, we used the same prediction of a raised (but not loud) source voice level used
in Case Study 8. As was the situation in Case Study 8, the lack of absorptive material
contribute to a level of acoustical impact on the larger conference room that would, as
designed and tested, likely lead to significant complaints.
Plan:
Case Study 9
The following narrative comments in the CBE survey offer additional insight into this
finding:
Meetings in adjoining conference rooms can sometimes generate enough noise to make
concentration difficult.
Noise bleeds through all of the meeting rooms.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 29
Case Study 9
SOURCE FACTORS PREDICTED OBSERVED
A. Voice Source Level Raised 66 Raised
14
66
B. Speech Privacy Criterion Confidential 15 Confidential 15
C. Effect of Source Room 150 sq. ft. 6 150 sq. ft. 6
Sum Source Factors
87 87
ISOLATION FACTORS PREDICTED OBSERVED
D. Partition:
STC or NIC
3 5/8” steel stud
5/8” drywall each
side, slab to ceiling
39
3 5/8” steel stud 5/8”
drywall each side,
slab to ceiling
39
E. Effect of Receive Room
(from table)
3 NA
F. Background Noise (dBA,
receiving room)
Typ.: Conference
Room
32 Measured 31
Sum Isolation Factors
74 70
SOUND EXCESS PREDICTED OBSERVED
Source factors minus
isolation factors
+13 +17
Predicted level of
acceptability
Strong dissatisfaction Extreme dissatisfaction
14
No conference was taking place, this value was predicted.
30 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
6.0 CONCLUSIONS
Believing in the benefit of an open and collaborative work environment, an ever-greater
number of managers, professionals and executives are abandoning private offices and
adopting open plan areas with specialized office spaces to accommodate the casual
conversations, informal meetings and even speakerphone use that once occurred in private
offices. The poor performance of these open plan environments in occupant satisfaction
surveys appears to primarily result from their inability to provide the level of speech
privacy employees feel necessary for them to concentrate and be productive. The high
level of acoustical dissatisfaction identified in these surveys may also be working to
negate some of the presumed good will and free exchange of ideas associated with open-
plan spaces.
15
At the same time, a litigious environment and emphasis on the protection
of intellectual property mean that speech privacy is more important than ever before.
Clearly, there is a need for a reliable tool enabling building design and management
professionals to evaluate whether a given office design will provide a satisfactory level of
acoustical satisfaction.
Based on the nine case studies described above, the SPP method appears to offer an
effective framework for anticipating speech privacy problems and crafting solutions for
proposed spaces. In each case study, the level of acceptability for speech privacy
predicted by the method was broadly congruent with the level of acoustic dissatisfaction
reported by occupants of these spaces during our in-person interviews and with the
aggregated response of occupants in case studies recorded by the CBE’s post-occupancy
evaluation survey.
Use of the SPP method during the design process also promise significant cost benefits,
because acoustical upgrades are inexpensive when incorporated into the original design,
but are substantially more expensive when performed as part of an acoustical retrofit. At
the design stage, for example, the wall separating the private offices we studied could
have been upgraded to provide an acceptable level of speech privacy simply by adding a
3-inch glass fiber blanket ($0.60 per square foot), a layer of gypsum board ($1.20 per
square foot), and selecting a ceiling with a higher transmission loss rating ($1.00 per
square foot). Retrofitting these offices now, however, would involve completely
rebuilding the wall ($15 per square foot), as well as replacing the ceiling ($3.50 per square
foot), nearly ten-times the cost of the original upgrade. (See appendix 2.)
When used in open plan areas, the SPP method showed greater variability in its predicted
results. Research is underway to establish the range of this variability, and to compare
results obtained with the SPP method to those obtained with ASTM’s widely accepted
standard method for evaluating (but not predicting) speech privacy in open plan offices.
16
An important next step in disseminating the SPP method will be to develop a companion
design guide of best practices in acoustically successful office design, which will augment
the SPP method’s application among designers.
15
An extensive discussion of this phenomenon is offered in Brill (2001).
16
ASTM Method E 1130-90 (1994)
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 31
APPENDIX 1 DETAILED METHOD FOR USING
THE SPEECH PRIVACY PREDICTOR (SPP)
Introduction
The Speech Privacy Predictor (SPP) is based on research by Cavanaugh, Farrell, Hirtle
and Watters (Cavanaugh 1962). Cavanaugh found that the ratio of intruding speech to the
ambient background noise in the office was the best predictor of satisfaction with speech
privacy
17
. Cavanaugh’s rating scheme considers five variables needed to determine the
signal-to-noise ratio for a pair of adjacent office spaces. These variables are (1) how loud
the voices of people using a space typically are, (2) the level of privacy required in the
adjacent room, (3) the background noise occurring in the adjacent room (4) the effect of
the size, furnishings and finishes of the adjoining rooms in absorbing sound and (5) the
ability of the intervening partition to block sound. Cavanaugh’s calculation procedure
combines these variables into a single number rating for sound excess
18
. Cavanaugh has
demonstrated a good statistical fit between the ratings of sound excess and levels of
reported satisfaction.
Over the past 40 years, Cavanaugh’s method of predicting an occupant’s acoustic
satisfaction based on the ratio of intruding speech to the ambient background noise has
proved exceptionally durable. The Cavanaugh method underlies all leading approaches to
quantifying office acoustics in North America, including those established by the
American Society for Testing and Materials (ASTM, 1994) and the U.S. General Services
Administration (GSA, 1975). As modified by Robert W. Young (1965), who simplified
the measurement protocol, and by Rein Pirn (1971), who adapted the method for use in
open plan offices, the Cavanaugh method forms the basis for the recommended method of
evaluating office acoustics in three leading texts on acoustical design Egan (1988), Salter
et.al. (1998) and Cavanaugh (1999). SPP draws upon the calculation procedure published
in Egan (1988), Salter et.al. (1998) and Cavanaugh (1999).
Calculation Procedure
The SPP method calculates sound excess to predict the level of speech privacy
acceptability of an office space. Drawing on simple design and space programming data,
values representing ‘source’ and ‘isolation’ factors are each summed. Isolation factors are
then subtracted from the source factors. Each of these variables are described in detail
below, and the calculation procedure summarized in the worksheets shown in Figures A1
and A2. Note that the source space is the location where the occupant is speaking, and
where the confidentiality of conversation will be evaluated. The receive space conversely
is the location where the speech in the source space is intruding and can potentially be
17
This phenomenon is familiar to anyone who has dined in a crowded, noisy restaurant. Although the
people at the adjacent table may be engaged in animated conversation less than four feet away, it is
common not to be able to understand a word that they are saying. In fact, a space crowded with people
talking is a very private environment, because even when using a raised voice, only the closest, most
attentive listener can understand the speaker’s words over the background ‘din’ of conversation.
18
The authors based their work on the ‘Articulation Index’ (French and Steinberg 1947; American
National Standards Institute 1969) The Articulation Index relates physical measures of sound to predicted
levels of speech intelligibility. Intelligibility refers to the degree to which speech can be clearly
understood, and that words and sentences can be correctly identified.
32 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
overheard or will be distracting. Note also that the calculation procedure is somewhat
different for open plan and enclosed office spaces.
Calculation of Source Factors
Source factors include two variables that are shaped by occupant behavior and
expectations: speech privacy criteria and source voice level. In certain cases, overheard
conversations may aid team processes. In others, the ability to understand even partial
sentences may inhibit the ability to discuss sensitive work and personnel issues.
1. VOICE SOURCE LEVEL
Based on programming data, estimate the typical voice level associated with the loudest
likely behavior of employees in the workgroup occupying the space. Typical voice levels
are summarized in Table 1.
VOICE
SOURCE LEVEL
TYPICAL ACTIVITY CRITERIA
(dBA)
Low Telephone conversation using a low voice level 54
Conversational Casual conversation between two people in an
office setting
60
Raised Conversation of three or more people in a meeting 66
Loud Talking into a speakerphone, delivering a
presentation
72
Table 1: Source
Voice Levels
2. SPEECH PRIVACY CRITERIA
Acoustical engineers refer to three standard levels of speech privacy, which are
summarized in Table 2. Based on programming data, determine which level of privacy is
appropriate for the workgroup occupying the space.
LEVEL OF
SPEECH
PRIVACY
DESCRIPTION CRITERIA
(dBA)
Confidential Speech from adjacent space is audible but not
intelligible—the listener is aware that a conversation is
occurring, but is not able to understand individual
words
15
Normal Speech from adjacent space is audible and partially
intelligible—the listener has the ability to comprehend
an occasional word but never full sentences
9
Marginal Speech from adjacent space is largely understandable 3
Table 2: Speech
Privacy Criteria
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 33
3. EFFECT OF SOURCE ROOM
In private offices and conference spaces, voice levels in the source room are adjusted to
account for the amount of absorption provided by the furnishings and room volume.
These values are listed in Table 3.
FLOOR AREA
(SQUARE FEET)
CRITERIA
ROOM WITH 50% ABSORPTIVE
SURFACES (dBA)
19
CRITERIA
ROOM WITH LESS THAN 20%
ABSORPTIVE SURFACES (dBA)
60 +9 +15
125 +6 +12
250 +3 +9
500 0 +6
Table 3:
Adjustment for
Source Room
Effect
(Private Offices
and Conference
Rooms)
1000 -3 +3
Calculation of Isolation Factors
4. DISTANCE FROM SOURCE (OPEN PLAN AREAS)
Sound from the source workstation will attenuate as the distance between workstations
increases. Table 4 provides values for this effect. Note that these values assume
absorptive ceiling and workstation partitions and carpeted floors.
DISTANCE FROM SOURCE
WORKSTATION
TO RECEIVER WORKSTATION (FEET)
CRITERIA
(dBA)
3 0
6 5
12 10
Table 4:
Absorption (Open
Plan Offices)
24 15
5. BARRIER NOISE REDUCTION (OPEN PLAN AREAS)
This criterion accounts for the effectiveness of the partitions between workstations in both
blocking sound. Because the partitions in an open plan do not extend to the ceiling, the
noise reduction they provide is a function of STC of the partition itself, the layout of the
workstations and the amount of absorptive finishes in the space. To calculate the
effectiveness of partitions in an open plan, refer to Figure A2 and Table 5. Note that this
calculation assumes an absorptive ceiling (minimum NRC of .65), partition components
with a minimum STC of 18, and 50% of panels/wall surfaces above 3 feet having sound
absorbing materials, such as bookcases with books or acoustical panels. Note also that
partition heights in excess of 68 inches provide additional little sound reduction unless
they continue to an acoustically sealed connection at the underside of the ceiling.
19
Absorptive surfaces include absorptive wall and ceiling materials, upholstered furniture, bookcases
with books, and carpeting. Hard surfaces include gypsum board walls and/or ceilings, vinyl or concrete
floors, unupholstered furniture, bare desks.
34 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
Table 5: Barrier
Noise Reduction
(Open Plan)
CRITERIA: BARRIER HEIGHT/DISTANCE SOURCE TO BARRIER
DISTANCE:
RECEIVER TO
BARRIER
SLIGHT BREAK IN LINE
OF SIGHT
DISTANCE: SOURCE
TO BARRIER
1-FOOT BREAK IN
LINE OF SIGHT
DISTANCE: SOURCE
TO BARRIER
2-FOOT BREAK IN
LINE OF SIGHT
DISTANCE: SOURCE
TO BARRIER
3 FOOT BREAK IN
LINE OF SIGHT
DISTANCE: SOURCE
TO BARRIER
3 ft. 6 ft. 12 ft. 3 ft. 6 ft. 12 ft. 3 ft. 6 ft. 12 ft. 3 ft. 6 ft. 12 ft.
3-feet 5 5 5 8 7 7 11 10 9 13 12 12
6-feet 5 5 5 7 7 6 10 9 8 12 11 10
12-feet 5 5 5 7 6 6 9 8 8 12 10 9
6. PARTITION CONSTRUCTION (PRIVATE OFFICES AND CONFERENCE ROOMS)
This criterion accounts for the acoustic performance of the walls separating the source and
receive spaces. This value is measured in terms of the Sound Transmission Class (STC)
rating of the partition.
20
Table 6 lists STC values for standard partition types. Note that
these values assume full height (slab to slab) construction, and the use of acoustical
sealant at all penetrations and wall connections. Wall performance will be less if there are
even small gaps at floor/ceiling connections, corners, doors frames, outlet boxes, or if the
wall terminates at the underside of an un-insulated suspended ceiling.
WALL TYPE CRITERIA
(STC)
3 5/8” metal studs, 24” o.c., 1 layer 5/8” gypsum board each side 39
Same as above, with 3” glass fiber in cavity 44
Same as above, with 3” glass fiber in cavity and 2 layers 5/8” gypsum board
one side
50
Double row of 3 5/8” metal studs on separate plates, 24” o.c., 1 inch between
plates, 1 layer 5/8” gypsum board each side, 3 ½” glass fiber both sides
59
Same as above, 2 layers 5/8” gypsum board each side 63
Table 6: STC
Values of Typical
Wall Types
20
Transmission loss is typically measured in 16 one-third-octave bands and can be expressed through a
single-number rating scheme called Sound Transmission Class or STC. Higher STC values represent
better noise reduction
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 35
7. EFFECT OF RECEIVE ROOM (PRIVATE OFFICES AND CONFERENCE ROOMS)
The receive room will absorb some of the intruding sound radiating from the common
wall. Table 7 shows the values accounting for this effect.
RATIO
FLOOR AREA RECEIVE ROOM
COMMON PARTITION AREA
CRITERIA
ROOM WITH 50% ABSORPTIVE
SURFACES (dBA)
21
CRITERIA
ROOM WITH LESS THAN 20%
ABSORPTIVE SURFACES (dBA)
1 +0 -5
1.5 +2 -3
2 +3 -2
3 +5 0
4 +6 +1
5 +7 +2
6 +8 +3
Table 7:
Absorption in
Receive Room
(Private Offices
and Conference
Rooms)
10 +10 +5
8. BACKGROUND NOISE LEVEL
The level of background noise in the receive space is critical in masking speech from the
adjoining source space. Based on research summarized by Egan (1998), if intruding
speech is on average 10 dB below the background noise, satisfaction with speech privacy
approaches 100%. Conversely, if intruding speech is on average 5 dB above background
noise, dissatisfaction approaches 100%.
Although it may seem counter-intuitive, many contemporary open plan office spaces are
too quiet, and require the insertion of additional noise. This noise is called ‘sound
masking’ and represents a ‘controlled quiet’ that sounds somewhat like ventilation noise.
Sound masking differs from ‘pink’ noise (unpleasant, unnatural) and ‘white’ noise (hissy,
annoying). Sound masking needs to be specified and installed by a trained professional,
because it is specifically tuned in a given space to offer an optimum sound spectrum.
CONDITION CRITERIA
(BACKGROUND
SOUND, dBA)
Quiet ventilation system, no nearby office equipment, no traffic noise
intrusion through building façade, sound absorbing ceiling
30
Recommended limit for steady state background noise in private offices
and conference rooms
35
Constant air volume mechanical system, nearby office equipment and/or
moderate traffic intrusion, standard acoustical tile ceiling
40
Sound masking system 45
Table 8: Typical
Background Noise
Levels
Recommended limit for steady state background noise in open plan areas 50
21
Absorptive surfaces include absorptive wall and ceiling materials, upholstered furniture, bookcases
with books, and carpeting. Hard surfaces include gypsum board walls and/or ceilings, vinyl or concrete
floors, unupholstered furniture, bare desks.
36 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
FIGURE A1: SPEECH PRIVACY ANALYSIS PROCEDURE
FOR OPEN PLAN OFFICES
Adapted from Cavanaugh (1962), Young (1965), Pirn (1971) and Egan (1972).
SOURCE FACTORS
A. Voice Source Level Value from Table 1 A
B. Speech Privacy Criterion Value from Table 2 B
Sum Source Factors A+B
ISOLATION FACTORS
C. Distance from Source Value from Table 4 C
D. Barrier Noise Reduction Value from Table 5 D
E. Background Noise Value from Table 8 E
Sum Isolation Factors C+D+E
SOUND EXCESS
Sum Source Factors –
Sum Isolation Factors
(A+B) – (C+D+E)
Predicted Level of Acceptability
Value from Figure 2, pg. 6
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 37
FIGURE A2: SPEECH PRIVACY WORKSHEET
FOR ENCLOSED OFFICES
Adapted from Cavanaugh (1962), Young (1965), and Egan (1972).
SOURCE FACTORS
A. Voice Source Level Value from Table 1 A
B. Speech Privacy Criterion Value from Table 2 B
C. Effect of Source Room Value from Table 3 C
Sum Source Factors A+B+C
ISOLATION FACTORS
D. Partition STC or NIC Value from Table 6 C
E. Effect of Receive Room Table from Table 7 E
F. Background Noise
(Receive Room)
Value from Table 8 F
Sum Isolation Factors D+E+F
SOUND EXCESS
Sum Source Factors minus
Sum Isolation Factors
(A+B+C) – (D+E+F)
Predicted Level of Acceptability
Value from Figure 2, pg. 6
38 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
APPENDIX 2: CONSTRUCTION DETAILS FOR
ACOUSTICAL PRIVACY
Typical “as built”
partition for
private offices
Recommended
acoustical design
for private
offices with
‘normal’ speech
privacy
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 39
APPENDIX 3: SURVEY METHODS AND RESULTS
This report presents the results from a Post Occupancy Evaluation of a high rise
commercial office building in San Francisco, CA. The assessment took place in the form
of a web-based survey that was administered between November 27, 2000 and December
5th, 2000. Participation in the survey was voluntary and anonymous. Responses were
collected via the Internet and recorded to a database hosted at a third party vendor. The
project was sponsored jointly by CBE and the building’s owner.
Employees received an e-mail inviting them to take the survey. An additional 51
employees without an e-mail address were sent a hard copy letter inviting them to take the
survey at a series of computers at the set up for that purpose. Respondents were advised
that the purpose of the survey was to elicit quantitative information on how successful
their building was in meeting its design goals, and that this information would be used by
the building’s owners, managers, consultant team, maintenance personnel and CBE
research staff to develop scenarios for an improved building.
A total of 687 employees logged on to the survey, an overall response rate of 47%. The
resulting report contained only aggregated, anonymous results. Any information
disclosing what an individual employee said has been removed.
The survey covered twelve general areas of the work environment in a commercial office
building. Respondents were asked to evaluate their "satisfaction" with aspects of these
general areas. The survey employed a mix of yes/no questions and 7-point satisfaction
scales that range from "very satisfied" to "very dissatisfied". In most cases, respondents
who indicated "dissatisfaction" (the lowest two points on the scale) with a particular
aspect were branched to a follow up screen probing them for more information about the
nature of their dissatisfaction. Respondents who indicated higher satisfaction moved
directly to the next survey topic. Where applicable, respondents were also asked to assess
the impact of these general areas of the work environment on their effectiveness in getting
their job done.
Screen capture from
on-line survey
In order to analyze the data, responses to each satisfaction question have been counted in
three bins: "Dissatisfied", the bottom three points on the 7-point scale; "Neutral", the
middle point on the scale; and "Satisfied" the top three points on the standard scale.
Importance questions have been evaluated in a similar way with three bins: "Low
Importance", "Neutral", and "High Importance". For each question the data are displayed
as the percentage of total respondents who responded to the question in each of the three
bins. In this way the responses to various questions can be ranked and compared against
one another. Each page of the survey also included space for respondents to make
comments, including a "general comments" section at the end of the survey.
40 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
Results for Acoustics Questions
Selected survey results are illustrated in the table below.
Survey Question:
How satisfied are you
with the noise level in
your office? (noise
generated by things other
than your own work)
Survey Question:
How satisfied are you
with your sound privacy?
(ability to have
conversations without
your neighbors
overhearing and vice
versa)?
Building Systems
The building’s mechanical system is typical of the majority of Class-A office space
constructed during the past 30 years. Structurally, the building has a steel frame with
metal deck/lightweight concrete floors. Perimeter glazing is fixed. HVAC is a variable air
volume (VAV) system supplied from diffusers surrounding light fixtures. Return air is
ducted. Ceilings are 2’ x 2’ acoustical tile suspended 2-6”’ below the floor deck above. 2
x 4 ceiling fixtures with specular parabolic lenses supply direct overhead lighting. Most
open plan areas are laid out adjacent to the perimeter, with private offices, conference
rooms, circulation and service spaces in the core. Windows have horizontal blinds.
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 41
APPENDIX 4: TESTING PROTOCOL
Measurements were conducted on the Monday, February 12 and Tuesday February 13
,
2001. The facility manager characterized occupancy as typical; we observed
approximately 80% of workstations and private offices occupied.
In each case study location, occupant behavior was observed to note the location and
levels of typical speech activity. A scale drawing of the workstation, office or conference
room layout was then made, recording the typical locations of occupants in the source and
evaluation spaces and the position of office screens, desks, doors, glazing, telephones,
computers, chairs and other acoustically relevant furnishings and finishes. The height and
acoustical attributes of the office screens and the ceiling were identified, along with a
description of the floor, overhead lighting and ventilation. Digital photographs
documented the juxtaposition of workstations and the adjoining environment. When
possible, with full understanding of the confidentiality of their response, occupants were
interviewed about their expectations for and satisfaction with their speech privacy.
Field measurement of background noise and transmission loss of partitions was then
performed. Using a calibrated tape recording system, the typical background noise level
was measured at each receiver location. Background sound level was defined in terms of
the minimum A-weighted background sound pressure level (L
min
). L
min
represents the
lowest background level, independent of single-event sounds such as telephone ringing,
that can unintentionally inflate a predicted level of the effectiveness of background noise.
The microphone during the recording was slowly moved in an approximately 1-foot-
diameter circle about 4 feet above the floor. Measurements included a time period of
approximately 4 seconds at each of four positions set at 90 degree intervals in the circle.
In open plan areas, noise reduction from the source to the receiver location was measured
as follows. A calibrated loudspeaker generating pink noise was located at height and
location observed as most typical of the person(s) talking at the source location. The
sound level of the loudspeaker was then measured three feet in front of it and at location
observed as most typical of the person(s) sitting at the receive location. The sound level
of the loudspeaker was at least 10 dB more than the ambient at the receiver location.
Measurements were made following the same procedure as described for the ambient
measurement.
In private offices and conference rooms, noise reduction was measured as follows: 1-
minute space average sound level measurements were conducted in the source and then in
the receive room. In the receive room, the reverberation time was measured at five
locations.
Acoustical instrumentation used to conduct these tests consisted of the following: the
sound source was an ADS 2002 loudspeaker meeting the frequency response and sound
level variation requirements set forth in ASTM E1179 for acoustical testing in open-plan
offices. Measurements were recorded with a 1/2-inch diameter condenser microphone
fitted to a B&K 2230 sound level meter outputting a calibrated signal to a Sony TC-D5M
cassette recorder.
42 CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE
REFERENCES
American National Standards Institute (1969). “American National Standard S3.5-1969:
Methods for the Calculation of the Articulation Index”, New York: American National
Standards Institute
ASTM (1994). Method E 1130-90. . “Standard Test Method for Objective Measurement
of Speech Privacy in Open Offices Using Articulation Index”, Annual Book of ASTM
Standards 2001 Volume 4.06
Boggs, D.H. , and J.R. Simon (1968). “Differential effect of noise on tasks of varying
complexity”. Journal of Applied Psychology 52:148-153.
Brill, M., S. Margulis, et al. (1984). Using Office Design to Increase Productivity.
Buffalo, N.Y.: Workplace Design & Productivity.
Brill, M., S. Weidemann and the BOSTI Associates (2001).Disproving Widespread Myths
About Workplace Design. Kimball International, Jasper, IN
Cavanaugh, W.J., W.R. Farrell, P.W. Hirtle, and B.G. Watters, Bolt Beranek & Newman
(1962). "Speech Privacy in Buildings," Journal of the Acoustical Society of America, vol.
34, pp. 475-492
Cavanaugh, W. J. and J. A. Wilkes (1999). Architectural Acoustics. Principles and
Practice. New York, NY, Wiley.
Center for the Built Environment/Skidmore Owings and Merrill, (2001). “Post
Occupancy Evaluation Survey”. (web only resource). Berkeley, California: University of
California.
DeMarco T., and T. Lister (1987) Peopleware: Productive Projects and Teams. New
York: Dorset House Publishing.
Egan, M. D. (1972). Concepts in Architectural Acoustics. New York, NY, McGraw Hill.
Egan, M. D. (1988). Architectural Acoustics. New York, NY, McGraw Hill.
Evans, G. W. and D. Johnson (2000). Stress and Open-Office Noise. Journal of Applied
Psychology, Vol. 85, No. 5, 779-783
French, N. R. and J. C. Steinberg (1947). “Factors governing the intelligibility of speech
sounds.” Journal of the Acoustical Society of America 19(1): 90-119.
Harris, L. (1978). The Steelcase National Study of Office Environments: Do They Work?
Grand Rapids, MI , Steelcase, Inc.
Harris, L. (1991). The Office Environment Index 1991: Summary of Worldwide Findings.
New York: Louis Harris and Associates
Junqua, J.-C. (1993). “The Lombard reflex and its role on human listeners and automatic
speech recognizers.” J. Acou. Soc. America 93(1): 510-524.
Karacek, R., and T. Theorell. (1990). Healthy Work: Stress, Productivity and the
Reconstruction of Working Life. New York: Basic Books.
Lombard, E. (1911) “Le signe de l’elevation de la voix..” Ann. Maladies Oreille Larynx
37, 101--119
Pirn, Rein. (1971). Acoustical Variables in Open Planning," Journal of the Acoustical
Society of America vol. 49 (5), part 1, pp. 1339-1345
Salter, C. M. et. al. (1998). Acoustics. Architecture, Engineering, The Environment. San
Francisco, William Stout Publishers
CBE REPORT: PREDICTING SPEECH PRIVACY IN THE CONTEMPORARY WORKPLACE 43
Sundstrom, E., J.P. Town, R.W. Rice, D.P. Osborn and M. Brill (1994). “Office noise,
satisfaction, and performance”. Environment and Behavior 26(2): 195-222.
U.S. General Services Administration/Geiger & Hamme. (1975). Public Building Service
Standard Method of Test Method for the Sufficient Verification of Speech Privacy
Potential (SPP) Based on Objective Measurements. Washington, D..C PBS (PCD): PBS-
C.2
Young, Robert W (1965). “Re-Vision of the Speech-Privacy Calculation,”. Journal of the
Acoustical Society of America, vol. 38 (4), pp. 524-530
... Salter, Powell, Begault and Alvarado [12] investigate designers' point of view to the subject, which those calculation procedures are not widely used among design community. Underlying reasons are given such as unfamiliar measurement units and concepts, the specialized testing equipment required for prototype and in stu evaluations. ...
... 382) [13]. Salter, et al. [12] defines another issue about cubicle layouts, which 'streets' in between these cubicles become a natural conversation area. Croon, et al. look from a psychological perspective explaining that lack of acoustical and visual privacy in open-plan offices avoids workers to discuss personal topics [4]. ...
... 52) [9]. Salter, et al. support this idea by explaining electro-acoustical solutions for sound masking, which is placing loudspeakers in the ceiling [12]. Masking noise in office environments is called 'white noise', because it covers all frequencies in the sound spectrum, which can override disturbing components of office noise. ...
Conference Paper
The aim of this study is to find out effects of speech intelligibility on visual short-term memory performance by testing 34 interior architecture students in three different sound environments. Those sound environments were composed of real office sounds and a speech sample that are mixed to achieve varying STI levels of 'continuous noise', 'masked speech' and 'speech' sound environments. Test procedure had three steps: first questionnaire, computer based short-term memory test and second questionnaire. Results show that there is no significant difference of visual short-term memory performance between varying sound environments, however subjective results derived from questionnaires show that students were distracted most by 'speech' sound environment.
... The studies revealed that the acoustical condition of open-office spaces, and consequently, the occupant satisfaction can be increased by implementing appropriate design solutions, such as layout design, workstation design, and partition design. Salter, Powell, Begault and Alvarado (2003) supported the idea of electro-acoustical solutions for sound masking, which is placing loudspeakers in the ceiling. The masking noise in office environments is called 'white noise', and it covers all frequencies in the sound spectrum, which overrides disturbing components of office noise. ...
... Open-plan office occupants have a potential to initiate and maintain private conversations and chat between workstations. Salter, Powell, Begault and Alvarado (2003) stated that the streets in between open office cubicles become a natural conversation area. Additionally, a recent study investigated the effects of irrelevant speech on mental workloads in open-plan offices (Smith-Jackson & Klein, 2009). ...
Article
Full-text available
The aim of this study is to find out the effects of speech and speech intelligibility on computer-based task performance in open-plan offices. The research was conducted in a real open-plan office environment to include the open-office experience of subjects to the analysis. STM Bilkent Office was selected as the case, and 40 available open-office occupants were participated to the study. The experiment consists of two main phases. In the first phase, acoustical simulation of the site was done, to derive distribution graphs for speech related room acoustics parameters. In the second phase, occupants' computer-based task performances were tested under three different sound environments, which are continuous noise, speech and masked speech. According to statistical analysis of the performance test, and the acoustical properties of the case STM, suggestions for renovation were discussed. It was found that effects of intelligible speech on occupants' task performance are only psychological, because it is significant that there is no difference between results of performance test. However, all of the occupants respond to the questionnaires that speech sound environment was the most distracting one. Proposal for renovation was given to minimize the effects of intelligible speech on occupants for preventing the long-term effects on occupants' health. 1 This paper is based on the master's thesis 'Effects of Speech Intelligibility on Computer-based Task Performance in Open-Plan Offices'.
... Umumnya ada beberapa hal yang menjadi perhatian dalam proses perancangan gedung yaitu kenyamanan termal, ventilasi, pencahayaan, estetika dan hal lainnya. Namun, para desainer gedung sering kali mengabaikan kenyamanan akustik sebagai salah satu pertimbangannya (Salter, 2003). Faktor Kondisi aktual akustik dapat dievaluasi dengan melakukan pengukuran sesuai dengan prosedur yang tercantum pada ISO 3382-1:2009, Acoustic, measurements of room acoustic parameters -Part 1: Performance spaces. ...
Article
Full-text available
p class="Abstract"> During design process of auditorium, mostly, acoustics design was neglected by engineers therefore it may cause inappropriate acoustic condition. Evaluation of acoustic comfort was carried out through measurement of speech parameters such as Noise rating (NR), reverberation time and definition (D<sub>50</sub>). According to measurement result, performance of convention hall is not sufficient to perform speech activities since it has 0.4-13.7 s of reverberation time and 1.6-42.6% of D50. To improve acoustic performance, modification is applied on ceiling materials using combination of two different acoustic materials – absorber and diffusor, through simulation.. The result has shown that installment of full absorber at ceiling with high absorbtive coefficient could reduce early energy reflection which causes lower reverberation time and higher definition. Whenever ceiling are made of combination of two type of materials, the position of di on ceiling depend on diffusor orientation. Spread diffusor has better performance rather than centralized diffusor. However, the acoustic performance of convention hall remains the same. Keywords : speech, improve, modification, ceiling, simulation </p
... Pero la dificultad estriba en cuál de todos los índices de inteligibilidad es el que mejor se adecúa [22] a la función que queremos determinar [18] [4] [7] [20] [21]. Nosotros, en este trabajo vamos a seguir las ideas de Bradley y su entorno, adaptando el procedimiento a nuestra premisa original que es la determinación o evaluación de la privacidad a partir del registro de la señal MLS emitida y transmitida. ...
Conference Paper
Full-text available
Palabras Clave: privacidad acústica, escala de inteligibilidad natural, CIS, índice de articulación, AI, SNRuni32, CIS, grado de privacidad del habla, SPC, MLS. ABSTRACT. A study has been carried out on the level of privacy in different venues. For its determination we have used MLS signals. Our proposal focuses on the determination of intelligibility (Common Intelligibility Scale) trough the Speech Transmission Index calculated from the MLS signal received through the enclosures as a valuation index of privacy. Based on the existing background noises and the insulation presented by the different building systems AI was calculated for a series of standard vocal efforts. The values of the SNR32 index have been checked. The results are comparable to those presented in the literature consulted. It is noted that relatively simple "in situ" measures can objectively assess privacy. RESUMEN. Se ha realizado un estudio sobre el nivel de privacidad en distintos recintos. Para su determinación hemos usado señales MLS. Nuestra propuesta se centra en la determinación de la inteligibilidad (Common Intelligibility Scale) a partir del Speech Transmission Index calculado a partir de la señal MLS recibida a través de los cerramientos como índice de valoración de la privacidad. En función de los ruidos de fondo existentes y el aislamiento que presentaban los distintos sistemas constructivos se ha calculado el AI para una serie de esfuerzos vocales estándar. Se han contrastado los valores del índice SNR32. Los resultados son equiparables a los presentados en la literatura consultada. Se constata que medidas "in situ", relativamente sencillas, pueden de forma objetiva valorar la privacidad. 1. INTRODUCCIÓN La privacidad es un aspecto importante a tener en cuenta a la hora de diseñar despachos u otros recintos como las aulas docentes por ejemplo. Sería lógico pensar que el hablante no quiere ser escuchado y el oyente ocasional (al otro lado de la pared) no tiene interés en escucharle pues interfiere en su propia actividad o discurso, distrayéndole o produciendo molestia. Además en determinados trabajos donde se maneja información confidencial (abogados, médicos, banca, policía, etc.), su importancia es vital porque si los despachos no se
... The results of the aforementioned study showed that the populace is considerably more displeased with lack of privacy than the level of noise. Despite these results, in the majority of cases, acoustics do not take the design attention as another factor in IEQ (Salter et al., 2003). The direct and diffuse indoor sound pressure which is perceived depending on characteristics of the space such as volume of space. ...
Article
Purpose The purpose of this paper is to review the concept of occupant behavior and its relation with indoor environmental quality (IEQ) and building energy consumption. The behavior is referred to any direct or indirect action, which is selected by an occupant to manage the unpleasant indoor environmental conditions. Thermal comfort, indoor air quality, aural comfort and visual comfort are the key factors of IEQ evaluation. Human behavior significantly interacts with energy consumption in buildings. Design/methodology/approach Each IEQ parameter was reviewed separately and the overall IEQ acceptance was considered. In addition, this paper reviews the methods that were used to measure and simulate the IEQ factors, energy consumption and human behavior. Finally, the lack of knowledge in this field is based on the review demonstrated. Findings Most studies considered one or two IEQ factors to evaluate IEQ acceptance in buildings. Further, weakness of simulating all IEQ factors at the same time is the deficiency of IEQ simulation, based on reviews. In the case of occupant behavior simulation, the uncertainly of human psychological parameter is a drawback to predict behavior. Originality/value Energy consumption, occupant health and productivity are related to IEQ. Human behavior affects building energy consumption directly. Simulation software and methods can predict IEQ factors and human behavior. Therefore, reviewing the existing studies is critical to find new methods for measuring and simulating IEQ, energy consumption and human behavior in buildings.
... The results of the aforementioned study showed that the populace is considerably more displeased with lack of privacy than the level of noise. Despite these results, in the majority of cases, acoustics do not take the design attention as another factor in IEQ (Salter et al., 2003). The direct and diffuse indoor sound pressure which is perceived depending on characteristics of the space such as volume of space. ...
Conference Paper
Indoor Environmental Quality (IEQ) is an important topic which impacts on occupant health, productivity and also energy consumption in buildings. The four main parameters for IEQ evaluation are: Thermal comfort, indoor air quality, visual comfort and aural comfort. The occupant behavior in buildings defines as any direct or indirect act which an occupant selects to change the displeasure environmental condition into the comfort conditions. The selected behavior by human has a significant impact on the energy consumption in buildings. This paper reviews the methods which used to simulate IEQ parameters, energy consumption and human behavior in buildings. It aims to promote the idea of more consideration about the relation between occupant behavior and energy usage in buildings. This summary of existing studies about the importance of human behavior factor in energy simulation software helps to identify new methods and strategies for simulating IEQ, Energy and behavior.
... 7 Acoustics is an important element in creating a workable office environment, as it relates closely with human well-being by its influence on human stress level, motivation and productivity. [8][9][10][11] Acoustical environment can either enhance a person's productivity or damage it. A person's work efficiency will increase when they are working in a comfortable, distractionfree environment, which assist easy verbal communication between colleagues. ...
Article
Green building rating system outlines many requirements to be considered in order for a building to be certified as one. However, the rating tools failed at truly addressing the acoustical aspect which in turn deteriorates the acoustical quality in green buildings. As preliminary stage of this study, the objective is to assess the acoustical performance of three green office buildings in Malaysia in comparison to selected standard acceptability criteria. Four spaces containing meeting rooms and open-plan offices were selected from each green building as subjects. Assessments were limited to selected acoustical parameters of background noise level, noise criteria, reverberation time and speech transmission index. The background noise levels were found to be within acceptable criteria range despite some meeting rooms that exceeded the maximum recommended level. However, noise criteria ratings found most of the spaces to be below the acceptable noise criteria. Reverberation times data varied from satisfactory 0.7 s to unacceptable 1.5 s. Nonetheless, the background noise, noise criteria and reverberation time data collected were found to be unbiased by the volume of the space. Speech transmission indexes were found to be ample within good and fair speech intelligibility range while still maintaining its normal tendency of decreasing with distance.
...  Les travailleurs en milieu de travail bruyant déclarent souvent avoir un niveau de stress plus élevé, 10,11 et on a associé le bruit à des symptômes du stress (maux de tête, nausées, problèmes musculo-squelettiques) chez les personnes souffrant du SBM. [12][13][14] Enfin, les bruits de basse fréquence rendraient les occupants sensibles aux symptômes du SBM. 15 ...
... 8,9 • Workers in noisy office environments often selfreport increased levels of stress 10,11 and noise has been linked to stress related symptoms (headaches, nausea, musculoskeletal problems) in people suffering from "Sick Building Syndrome" (SBS). [12][13][14] Additionally, low frequency noise has been found to sensitize occupants to the symptoms of SBS. The issues outlined indicate a unique set of challenges to ensuring high indoor environmental conditions in NV buildings. ...
Book
Full-text available
Overview of primary predictors of employee performance and job satisfaction, based on BOSTI Associates data base from 1994-2000. Focuses on the implications of those factors for workplace design; not a statistically oriented booklet. (That information may be obtained from Sue Weidemann.)
Article
A field study assessed disturbance by office noise in relation to environmental satisfaction, job satisfaction, and jot performance ratings among 2,391 employees at 58 sites before and/or after office renovation. In all, 54% said they were bothered often by noise, especial!y by people talking and telephones ringing. Disturbance by noise correlated with dissatisfaction with the environment and job but not with selfor supervisor-rated performance. Quasi-experimental analysis of groups reporting increased, decreased, or unchanged disturbance by noise revealed a drop in satisfaction concurrent with increasing noise. Disturbance by office noise may reflect a variety of environmental and job characteristics and may have a role in job satisfaction through both environmental satisfaction and job characteristics. Implications are discussed.
Article
The characteristics of speech, hearing, and noise are discussed in relation to the recognition of speech sounds by the ear. It is shown that the intelligibility of these sounds is related to a quantity called articulation index which can be computed from the intensities of speech and unwanted sounds received by the ear, both as a function of frequency. Relationships developed for this purpose are presented. Results calculated from these relations are compared with the results of tests of the subjective effects on intelligibility of varying the intensity of the received speech, altering its normal intensity-frequency relations and adding noise.