Content uploaded by Faruk Aras
Author content
All content in this area was uploaded by Faruk Aras on Oct 12, 2015
Content may be subject to copyright.
EMP 33(12) #64353 [EIC ID No. 6817]
Electric Power Components and Systems, 33:1385–1402, 2005
Copyright © Taylor & Francis Inc.
ISSN: 1532-5008 print/1532-5016 online
DOI: 10.1080/15325000590964425
An Assessment of the Methods for Calculating
Ampacity of Underground Power Cables
FARUK ARAS
Kocaeli University
Technical Education Faculty
Department of Electrical Education
Kocaeli, Turkey
CÜNEYT OYSU
Kocaeli University
Engineering Faculty
Mechatronics Engineering
Kocaeli, Turkey
GÜNE¸S YILMAZ
Uluda
˘
g University
Engineering Faculty
Electronics Engineering
Bursa, Turkey
Endurance of an insulation material to high temperatures determines the maximum
current-carrying capacity (ampacity) of an underground power cable. Cable ampacity
is calculated conventionally using the installation conditions and maximum steady-
state operation temperature according to IEC-60287 standard. In this article, finite
element method results are compared with IEC-60287. A further verification has
also been made with experiments. In this work, ampacity analyzes of 154 kV high
voltage XLPE underground power cable are made using ANSYS 5.61 finite element
analysis software. An experimental set-up is developed to measure conductor and
surface temperature of the cable in underground conditions. The results of experiments
and numerical calculations are compared to the IEC-60287 standard. Additionally,
the thermal regions of three cables in flat installation are investigated to show the
versatility of the finite element method. The effects of insulation thickness and external
thermal source on ampacity are also analyzed using the finite element method.
Keywords ampacity, finite element, thermal rating, underground power cables
Manuscript received in final form on 17 March 2005.
Address correspondence to Dr. Faruk Aras, Kocaeli University, Dept. of Electrical Education,
Anitpark, Izmit, Kocaeli, TR-41100, Turkey. E-mail: arasfa@kou.edu.tr
1385
1386 F. Aras et al.
Introduction
Underground power cables are more expensive to install and maintain than overhead lines.
The greater cost of underground installation reflects the high cost of materials, equipment,
labor, and time necessary to manufacture and install the cable. The large capital cost
investment makes it necessary to use their full capacity. On the other hand, conductor
temperature of a power cable limits its ampacity (i.e., maximum allowable temperature
for XLPE insulated cables is 90
◦
C). Also, the operating temperature adversely affects the
useful working life of a cable. Excessive conductor temperature may irreversibly damage
the cable insulation and jacket.
A successful model was proposed for calculating ampacity of underground cable by
Neher-McGrath in 1957 [1]. The Neher-McGrath Model has been widely accepted for
over 40 years. Today, the greater majority of utilities and cable manufacturers have been
using the IEC-60287 standard [2]. This method employs a lot of simplifications and has
its limitations. Thus, it is not reliable for the analysis of complex configurations.
The finite element method (FEM) is more powerful and precise in terms of geomet-
rical modeling complexity. The finite element method solves problems that are described
by partial differential equations, using numerical techniques. A domain to be analyzed is
represented as an assembly of finite elements. Approximating functions in finite elements
are defined in terms of nodal values of a physical field. A continuous physical problem
is transformed into a discretized finite element problem with unknown nodal values. For
linear problems, developed system of linear algebraic equations are solved numerically.
Values inside finite elements can be obtained using nodal solutions.
Although the idea of dividing a continuum into small finite pieces had been first
suggested by Courant in 1943 [3], the development of the finite element method coin-
cided with major advances in computers technology and programming languages. Under
operation circumstances, the measurement of the conductor temperature of the HV un-
derground cable is very difficult. Thus, the usual conditions of installation and operation
can be simulated in laboratory environment. A heating test bed according to IEC62067,
which is an extension of IEC60840 for higher voltages, is set up to measure temperature
distribution. The cable loaded with various currents can be investigated. Consequently,
the thermal rating of the cable can be determined.
Ampacity analysis of cables with FEM has been studied by many researchers [4–7].
Lately, an IEC technical report, namely IEC TR 62095 [8], has been published for
current ratings calculation using the finite element method when IEC 60287 [2] can-
not be applied. Nahman and Tanaskovic [9] have measured and modeled thermal re-
gions outside the cable using FEM. Even if they used linear triangular elements in the
FEM analysis, their results were in good agreement with their measurements. If they
had used quadratic quadrilateral elements in their method, improved results could be
obtained.
In this project, current rating calculations for power cables in steady-state conditions
were performed using IEC 60287, finite element method and experiments. The models
developed for the finite element analysis were verified with IEC 60287 and experiments.
A numerically efficient finite element model is obtained with sensitivity analysis. Since
the domain under the cable is not an isotherm, the control volume to be analyzed is very
effective in the degree of accuracy of the analysis. Fundamental terms and boundary
conditions in the FEM analysis were clearly identified in the results section, which can
help engineers to develop their models for ratings calculations.
An Assessment of the Methods for Ampacity 1387
Ampacity Calculation
The ampacity calculation of a power cable using IEC 60287 formulation can be written
in the following form:
I =
θ
c
− θ
a
− θ
d
(T
1
+ (1 + λ
1
)(T
3
+ T
4
))R
ac
(1)
where
θ
c
maximum operating conductor temperature
◦
K
θ
a
ambient temperature
◦
K
θ
d
temperature rise due to dielectric loss
◦
K
λ
1
sheath loss factor
R
ac
AC resistance of conductor at temperature θ
c
T
1
, T
3
, T
4
thermal resistances of insulation, covering and soil (
◦
Km/W), respectively.
The external thermal resistance T
4
, depends on the diameter of the cable, the depth of
laying, the thermal characteristics of the soil, mode of installation and on temperature
rise generated by neighboring cables.
Finite Element Method
A basic equation of heat transfer for an isotropic body with temperature dependent heat
transfer has the following form:
−
∂q
x
∂x
+
∂q
y
∂y
+ Q = ρc
∂θ
∂t
(2)
where q
x
and q
y
are components of heat flow through the unit area; Q is the inner heat
generation rate; q is density; c is thermal heat capacity; θ is temperature, and t is time.
Fourier’s law describes the heat flow equations as
q
x
=−k
∂θ
∂x
,q
y
=−k
∂θ
∂y
(3)
Here k denotes the thermal coefficient of the material. Substitution of the above relations
gives
∂
∂x
k
∂θ
∂x
+
∂
∂y
k
∂θ
∂y
+ Q = ρc
∂θ
∂t
(4)
Then the variation of the temperature and temperature gradients inside an element can
be expressed in terms of nodal temperatures using shape functions N
i
as
{θ}=[N]{θ
e
} (5)
1388 F. Aras et al.
Differentiation of the temperature field gives
∂θ
∂x
=
∂N
∂x
{θ
e
} (6)
where θ
e
are the nodal temperatures for the eth element. N represents the quadratic shape
functions for 8-node quadrilateral elements (serendipity elements)
While shape functions are expressed through the local coordinates ξ,η, the matrix
contains derivatives in respect to the global coordinates x,y. Derivatives can be easily
converted from one coordinate system to the other by means of the chain rule of partial
differentiation:
∂N
i
∂ξ
∂N
i
∂η
=
∂x
∂ξ
∂x
∂η
∂y
∂ξ
∂y
∂η
(7)
Using Galerkin method, we can rewrite Eq. (4) in the following form:
=
1
2
{θ
n
}
T
k
∂
2
[N]
T
∂x
2
∂
2
[N]
∂x
2
+
∂
2
[N]
T
∂y
2
∂
2
[N]
∂y
2
{θ
n
}−
{θ
n
}
T
[N]
T
q
dxdy (8)
Equations are rearranged to give stiffness matrix of [K] and force vector of {f } as
[K]=
∂
2
[N]
T
∂x
2
∂
2
[N]
∂x
2
+
∂
2
[N]
T
∂y
2
∂
2
[N]
∂y
2
kdxdy (9)
{f }=
[N]
T
qdxdy (10)
FEM equations are found by minimization of functional in terms of nodal temperatures.
∂
∂θ
n
= 0 and [K]{θ
n
}={f } (11)
Stiffness matrix [K] and force vector {f } integrals are calculated on each element numer-
ically (using Gaussian quadrature), and then total stiffness matrix is set up by summation
of each equation system. The total equation system is then solved for each node.
Numerical and Experimental Work
154 kV underground cable in single installation is analyzed using FEM and IEC-60287.
These results are used for determining the insulation thickness representing the soil’s
thermal resistance in a thermal rating experiment. Further further loading cycles are then
applied to the test cable, and the values obtained from a full heating of a cycle is compared
with FEM and IEC 60287 results. The effects of insulation thickness on current ratings
An Assessment of the Methods for Ampacity 1389
were also analyzed using both methods. Another current rating calculation defined in
IEC 60287, three cables in flat formation, were also analyzed and compared with FEM
analysis. A further application of this problem in the case of a heat pipe installed parallel
to the cable was studied as well.
154 kV Single Underground Cable Analysis with FEM and IEC
The ampacity of the underground cable, whose sectional view is illustrated in Figure 1,
is analyzed using the finite element method. Under the operation conditions, the amount
of heat generated from the cable should be calculated to determine ampacity. Since the
limiting operation temperature of XLPE cables is 90
◦
C, the heat generated from the
charged cable should be transferred to the environment to reside under this temperature.
That’s why the correct calculation of heat transfer from the cable affects the ampacity
analysis directly. The soil temperature is 20
◦
C for northern Turkey. 1.2 m is the depth
the underground cables are normally buried under. However, the temperature and thermal
properties of soil depend on various parameters like the moisture content, the seasonal
variations and cable depth. These were reported by Brakelmann [10]. In steady-state oper-
ation conditions, moisture around the cable can be ignored since the heat generation from
the cable dry out the moisture nearby. IEC-60287 standard assumes that the properties
of soil and boundary conditions for the calculations are constant. Using these conditions,
and assuming the soil is homogenous, heat transfer and ampacity are calculated both by
IEC-60287 and the finite element method. The boundary conditions for FEM analysis is
shown in Figure 2.
The steady-state calculation of the heat transfer gives general operating ampere ca-
pacity. For shorter times, this current can be exceeded under cable manufacturer’s limiting
values. In this analysis, transient effects are not considered, thus time is not a parameter.
Since the heat transfer coefficients of XLPE and the semi-conductor material are
very close to each other, they are assumed to be same and are considered as a single
layer. The effects of coating layers and very thin metallic screens are omitted as their
thermal resistivities are very small and have very little effect on the results. Generalized
Figure 1. Sectional view of the cable.
1390 F. Aras et al.
Figure 2. The layout position of the 154 kV cable is given above.
layer dimensions of a 154 kV underground cable and the dielectric losses generated on
XLPE are as follows:
D
Conductor
= 37.7mm
D
XLPE+Semi Conductor
= 81.7mm
D
Screen
= 98.7mm
D
Cover
= 106.7mm
h
depth
= 1200 mm
q
dielectric
= 3.57 W/m
k
soil
= 1.2 W/Km
k
XLPE
= 0.2857 W/Km
k
screen
= 384.6 W/Km
For the underground cables, the earth surface can be assumed as isotherm as described
in IEC 62095. The domain under the cable is earth, which is an infinite medium. The
soil temperature also increases gradually as it gets deeper underneath the earth’s surface.
However, the soil temperature below 5 meters converges to a certain value and does not
fluctuate seasonally [10]. That’s why earth underneath the cable can also be taken as
isotherm at a certain depth. This effective control volume can be found using sensitivity
analysis. Various control volume sizes are analyzed, and heat transfer rates for the half of
the region are shown in Figure 3. At the depth of approximately 10 meters, heat transfer
rate converges to a value within the 1% range. Heat dissipation increases by 0.6% if the
region to be discretized is increased from 5m to 10 m in depth. Thus, a control volume
of 10 m depth and 18 m width is taken for all other cases as well.
The insulation thickness of a cable affects the permissible maximum current and heat
transfer from the cable. Higher insulation thickness also blocks the heat generated in the
conductor. Various insulation thicknesses for a 154 kV underground cable are analyzed
An Assessment of the Methods for Ampacity 1391
Figure 3. Sensitivity analysis between the control volume depth and heat dissipation.
in this example. For each cable, the heat flux is applied on the conductor found by an
iterative approach. The heat flux is increased gradually until a maximum temperature
of 90
◦
C on the conductor is achieved. For the cable with 22 mm XLPE insulation, the
thermal flux generated on the conductor surface is found to be 0.585 W/m
2
.
Since the model is symmetrical about y-axis, only half of the domain is modeled. As
a general rule of finite element method, element shapes are kept close to an aspect ratio of
unity. Heat generation by dielectric losses is applied on the XLPE domain. 1074 elements
are found to be dense enough for the final calculation. FEM analyzes with different mesh
densities, such as the number of elements 557, 690, 1074, and 1486, have shown that
the total heat transfer on the conductor converges to a certain value by increasing mesh
density. This sensitivity analysis regarding mesh density is necessary for evaluating the
correctness of the FEM analysis as described in IEC TR 62095. The mesh chosen after
the sensitivity analysis are shown in Figures 4 and 5.
Figure 6 show that the ampacity for the cable has a difference of around 1% be-
tween the FEM and IEC 60287 models. The results also illustrated that the reduction in
the insulation thickness by 22% (from 22 to 17 mm) has an effect of 2.9% increase in
the ampacity. Since the heat transfer mechanism is conduction, and this is directly pro-
portional to the contacting surface area, reduction in the diameter reduce both thermal
barrier and contacting surface.
Thermal Rating of 154 kV XLPE Power Cable
The experiment conditions are devised to comply with IEC-62067, which is an extension
of IEC-60840 for higher voltages section 12.4.7 on power cable systems [11, 12]. Thermal
rating standards involve a series of heating cycles by conductor current and cooling cycles
with natural cooling. In a heating cycle range from approximately 310 K to 380 K,
conductor and shield temperatures measured on experiments can be compared to the
FEM and IEC-60287 results to observe the performance of the both methods.
For this purpose, a 15 m of 154 kV XLPE power cable is used in the experiments.
A heating system is devised using thermocouples and thermal insulators for the temper-
ature measurements on the conductor and shield of the cable. Thermal resistance of the
soil is represented with a paper layer which has a thermal conductivity of 0.475 W/Km.
1392 F. Aras et al.
Figure 4. FEM mesh around the cable.
Figure 5. The mesh modeling both the cable and the surrounding soil with 1074 elements.
An Assessment of the Methods for Ampacity 1393
Figure 6. The ampacities for different insulation thickness by both FEM and IEC 60287 model.
The thickness of the paper layer wrapped on the cable is found by a trial and error
technique. In steady-state conditions at 363 K conductor temperature, the shield tem-
perature was measured and compared to the analytical values while the paper thickness
increased gradually. As the same values of conductor and shield temperatures are ob-
tained from both analytical calculations and experiments, the wrapped paper thickness
gives the thermal resistance of the soil. Three thermocouples are used to measure con-
ductor temperature. One is located at the center and two others are located at a distance
of one meter from the ends. A precise temperature measurement is achieved by drilling
the cables till 3 mm in conductors, as shown in Figure 7. The space at the tip of the
thermocouple and the conductor is filled with a highly conductive material.
Figure 7. Experimental layout.
1394 F. Aras et al.
Table 1
Experimental results
Cycle 10 Cycle 11
T-conductor (
◦
K) T-shield (
◦
K) T-conductor (
◦
K) T-shield (
◦
K)
319 298 327 304
321 300 330 307
335 313 339 316
351 322 355 324
369 330 365 329
381 337 375 332
382 338 377 333
382 338.5 377 333
377 333
Four thermocouples are positioned evenly in length on the outer surface of the
cable. All of the thermocouples are connected to a temperature recorder (Siemens-
Kompensograph C1015).
Both ends of the cable are connected to secondary probes of the voltage transformer.
Then the cable is placed as the secondary winding of a heating transformer. The cable
is gradually heated up in steps and awaited in each step until the difference between
each conductor thermocouples are less than 1
◦
K. Each experimental cycle took at least
8 hours to reach maximum temperature. Twenty experiments are performed consequently.
The experimental results in 10th and 11th cycles, when stable periodic conditions were
achieved, are given in Table 1.
The results from two cycles construct a continuous path, even if the recorded con-
ductor temperatures are different in each experiment. The heat dissipation from the cable
is calculated from the measured conductor and shield temperatures.
While the experimental setup was calibrated with analytical calculations at 363 K,
the heating experiments ranged from 320 K to 383 K. Consequently the comparison
of the FEM and IEC-60287 with experiments gives an indication about both methods’
performances. The currents necessary to generate the heat versus conductor temperature
are plotted on Figure 8. There is a difference between the FEM and experiment results
at lower temperatures. Since the speed of the heating is too high at the beginning of the
experiment, the converged temperature values have not been reached. However on the
rest of the graph, experimental results are very close to FEM results.
At the beginning of the experiment, the current was increased so much that cal-
culations under steady-state conditions would not be expected to conform. The heating
process after 340
◦
K became more stable and the ratio changed linearly. FEM and IEC-
60287 analysis were performed using homogenous and isotropic material properties.
Nonhomogenous effects in cable layers, like the screen and filling materials, deteriorate
the analysis conditions. Therefore, small differences between the results are very obvious.
Analysis of 154 kV Three Cables in Flat Installation Using FEM
In the analysis of three cables in flat installation, the distances between the cables are
considered to be twice the cable’s diameter, as given in IEC-60287. Thermal and geo-
An Assessment of the Methods for Ampacity 1395
Figure 8. Conductor temperature while current increases.
metrical properties of the cable are as given in single cable layout analysis with 22 mm
XLPE insulation. The cable installation is shown in Figure 9. The earth is assumed to
be homogenous and isotropic for the FEM analysis.
The heat generation boundary conditions are applied at each conductor and increased
gradually until the center conductor temperature reaches 90
◦
C. The heat transfer is
44.4 W/m while the conductor temperature at the center is 90
◦
C and at the sides are
85.08
◦
C. Besides the thermal boundary conditions applied on the cable, the dielectric
losses are also estimated (wd = 3.57 W/m) and applied as a thermal source over the
XLPE.
Figure 9. 154 kV cable installed in flat configuration.
1396 F. Aras et al.
Figure 10. FEM model and boundary conditions.
Cable layout in Figure 9 shows that the domain to be considered is symmetrical
in y-axis. Utilization of symmetrical boundary conditions as shown in Figure 10 on the
analysis saves modeling and computation time significantly, especially in large problems.
Symmetric boundary condition can be used by assuming the heat transfer on the symmetry
lines are adiabatic. The mesh around the three cable installations are shown in Figures 11
and 12.
Thermal contours of the region nearby the cables are given in Figures 13 and 14.
These figures illustrate that the heat transfer from the cable at the center is lower than the
others. Thus, the ampacity analysis should be made for the center cable, as it is the most
critical one. IEC-60287 also considers the center cable as the significant cable on its cal-
culations. In the IEC calculations, the ampacity is 2.4% less than the numerical analysis.
Heat transfer from the cables and the ampacity values estimated using two methods
are given below.
Heat transfer (IEC-60287) Q
AN
= 42.35 W/m
Heat transfer (finite element method) Q
FEM
= 44.4 W/m
Ampacity (analytical) I
AN
= 1296 A
Ampacity (finite element method) I
FEM
= 1327 A
An Assessment of the Methods for Ampacity 1397
Figure 11. FEM model with 948 elements and 3001 nodes.
Figure 12. Mapped mesh around the cables.
1398 F. Aras et al.
Figure 13. Temperature distribution between the cable and surrounding.
Analysis of 154 kV Cable by a Heat Source
In many cases, cable routes cross other cables or steam pipes. Due to the thermal in-
terference in the crossing region, the cable ampacities can be decreased noticeably [13].
Analytical methods give poor results because of the geometrical complexity. However,
FEM can easily analyze this kind of problem. In this numerical analysis, a heat pipe with
insulation buried 600 mm below the surface is considered as shown in Figure 15. The
steam temperature is normally higher than 100
◦
C, and under steady-state conditions, the
temperature on the surface of insulation is assumed to be a 60
◦
C isotherm. Cable and
pipe crossing at an angle involves a three-dimensional analysis. However, the worst case
occurs when they are run in parallel in a trench. That’s why the cable properties and
installation dimensions are as given in the three cables installation case previously. The
heat generation on the conductor is again estimated by increasing the heat generation
Figure 14. Temperature distribution around the cable.
An Assessment of the Methods for Ampacity 1399
Figure 15. Cables parallel to steam pipe with boundary conditions.
gradually, until 90
◦
C conductor temperature is reached. The mesh for FEM analysis is
given in Figure 16.
When three cables are installed parallel to a heat pipe at 60 cm distance, the ampacity
of the cable becomes 1236 A. Three cable installations without steam pipes have an
ampacity of 1327 A, and a derating factor is necessary for application of crossing heat
sources. For this case, the derating factor is 0.92. When the same boundary conditions
given in the Finite Element Method section is applied to the case with steam pipe, a
temperature rise of 9.4
◦
C on the conductor is observed. Figure 17 shows the temperature
distribution after the FEM analysis.
Ampacity of 154 kV cable with 22 mm XLPE insulation under different conditions
are calculated by FEM as:
FEM (A) Analytical (A) % difference
Single cable 1657 1635 1.3
Three cables 1327 1296 2.4
Three cables and heat source 1236 1130 9.4
1400 F. Aras et al.
Figure 16. FEM mesh with 1215 elements.
Figure 17. Temperature distribution around the cables and steam pipe.
An Assessment of the Methods for Ampacity 1401
Conclusions
The analytical modeling of heat transfer mechanism by IEC-60287 works well in simple
cable installations. However, simplifying assumptions and empirical correlation to obtain
the analytical method can be significant in complex installations like crossing cable
ducts, cables on trays, cables near buildings, cable splices, etc., thus making the solution
become impossible. Today’s computer technology gives finite element method a capability
to solve any of these cases with very complex geometrical configuration. It can solve
complex installations in any environment and subjected to any type of load condition
together with transient analysis efficiently. When the cable surrounding is composed of
various materials with different thermal resistivities, IEC-60287 formulation fails to get
an acceptable result.
The numerical solutions for the underground cables showed that the finite element
method gives a solution in any domain free from any geometrical complexities. Conse-
quently, an improved calculation of ampacity saves the investment and operation expenses
considerably. Currently, used power cables can be operated with higher capacity. In three
cable installation analysis using FEM, the temperature distribution inside and around the
cable is also determined, which is not possible using the analytical approximations. This
is useful when the temperature field and specific isotherms around the cable are to be
found out. The difference in the ampacity analysis using FEM and analytic solution of
single cable increases in the three cable layout case.
Cables installed near the other heat sources have to be treated carefully. FEM results
showed that the ampacity should be decreased by 8%. Derating factors of 0.92 found
empirically could be used in crossing cable cases. However, FEM gives almost exact
solutions to these kinds of problems. The mutual heating of the cables are more accurately
handled in FEM.
In this study, FEM and IEC methods are assessed for some common problems. The
boundary conditions and control volume determined are similar for a wide range of
problems. Models for the problems with more geometric complexity can be developed
using the similar approach given in this publication. Additionally the various soil thermal
properties depending on the moisture content can be easily analyzed by FEM.
References
1. J. H. Neher and M. H. McGrath, “The calculation of the temperature rise and load capability
of cable systems,” AIEE Trans., vol. 76, pp. 752–772, 1957.
2. IEC Publication 60287, Calculation of the Continuous Current Ratings of Cables, 1982.
3. R. Courant, “Variational methods for the solution of problems of equilibrium and vibration,”
Bulletin of American Mathematical Society, vol. 49, pp. 1–43, 1943.
4. G. J. Anders, Rating of Electric Power Cables, New York: McGraw Hill, pp. 295–311, 1997.
5. C. C. Hwang, J. J. Chang, and H. Y. Chen, “Calculation of ampacities for cables in trays using
finite elements,” Electric Power Systems Research, vol. 54, pp. 75–81, 2000.
6. M. Chaban and J. Leduc, “Using the finite element method for complex cable ampacity cal-
culations: A more accurate and much more flexible alternative to the conventional analytical
methods,” Proc. of the 5th Int. Conf. on Insulated Power Cables, Paris, France, p. A6.3, 20–24
June 1999.
7. R. C. Kemp, K. W. Barber, G. D. Barnewall, M. Jansen, M. Muxworthy, R. Piechota, and
Y. Soetopo, “A finite element computer program for the thermal analysis, design and monitoring
of underground and aerial high and medium voltage insulated cable systems,” Proc. of the 5th
Int. Conf. on Insulated Power Cables, Paris, France, p. A6.5, 20–24 June 1999.
1402 F. Aras et al.
8. IEC Technical report TR-62095, Electric Cables—Calculations for Current Ratings—Finite
Element Method, 2003.
9. J. Nahman and M. Tanaskovic, “Determination of the current carrying capacity of cables using
the finite element method,” Electric Power Systems Research, vol. 61, pp. 109–117, 2002.
10. H. Brakelmann, “Physical principles and calculation methods of moisture and heat transfer in
cable trenches,” Report No. AK 411.0.3 K, Universitat Duisburg, September 1993.
11. IEC Publication 62067, Power Cables with Extruded Insulation and their Accessories for Rated
Voltage above 150 kV up to 500 kV—Test Methods and Requirements, 2001.
12. IEC Publication 60840, Power Cables with Extruded Insulation and their Accessories for Rated
Voltage above 30 kV up to 150 kV—Test Methods and Requirements, 2004.
13. G. Anders and H. Brakelmann, “Cable crossing—Derating consideration,” IEEE Trans. Power
Delivery, vol. 14, pp. 709–720, July 1999.