Introduction We breathe about 13 cubic meters of air each day, and many of the particles in the air deposit in our lungs. Hundreds of studies worldwide have documented increases in morbidity and mortality associated with increases in particle levels outdoors. However, people spend almost 90% of their time indoors, and indoor air has its own list of sources that may be as bad or worse than outdoors—for example, cigarette smoke. Therefore much interest lies in developing ways to clean indoor air. One way to improve indoor air quality is to use an air cleaner. Air cleaners have been sold for many years, but it is important to evaluate their effectiveness in reducing pollutants in the home. Therefore Health Canada has sponsored this review of the effectiveness of air cleaners in homes. Although pollutants include gases as well as particles, this review concentrates on particle air cleaners.
Content may be subject to copyright.
1
Effectiveness of Home Air Cleaners in
Reducing Indoor Levels of Particles
Final Report
Health Canada Contract # 4500172935
Lance Wallace
March 12, 2008
2
Introduction
We breathe about 13 cubic meters of air each day, and many of the particles in the air deposit in
our lungs. Hundreds of studies worldwide have documented increases in morbidity and
mortality associated with increases in particle levels outdoors. However, people spend almost
90% of their time indoors, and indoor air has its own list of sources that may be as bad or worse
than outdoors—for example, cigarette smoke. Therefore much interest lies in developing ways
to clean indoor air. One way to improve indoor air quality is to use an air cleaner. Air cleaners
have been sold for many years, but it is important to evaluate their effectiveness in reducing
pollutants in the home. Therefore Health Canada has sponsored this review of the effectiveness
of air cleaners in homes. Although pollutants include gases as well as particles, this review
concentrates on particle air cleaners.
Background
There are several ways to obtain cleaner indoor air in homes. The most effective way is to
remove the source. For certain powerful sources, such as smoking in the home or allergen-
producing pets, removal may be the only effective strategy. A second way to obtain cleaner air
is by ventilation. For indoor sources, increased ventilation will reduce their concentration in
indoor air. However, if outdoor sources are important, increased ventilation will worsen the
situation. Filtering the air, however, can reduce concentrations from both outdoor and indoor
sources. Therefore air filters have been a popular mode of cleaning indoor air, and the associated
industry is in the neighborhood of several hundred million dollars per year.
Types of air cleaners
Air cleaners employing filters are of two general types. Portable air cleaners are self-contained
devices that can be placed in a room, such as the bedroom of an allergic child, and operated there
to reduce particle levels in the room. In-duct air cleaners are installed in the ductwork of a home
with central forced air, and are designed to reduce particle levels throughout the house. This
review will deal with both types.
Types of filters
Filters are of two general typesmechanical and electrical. The mechanical filter simply
intercepts particles in the air passing through the filter. The ordinary furnace filter represents the
3
most common type of filter: the fibrous filter. Fibrous filters consist of layers of fibers, criss-
crossed in more or less random ways so as to allow air molecules to find a tortuous path through
the filter, while at the same time removing particles that intercept the fibers. The thicker or more
tightly weaved the filter, the more success it will have in removing particles. However,
increased thickness or tightness of the weave requires more energy to move the air through the
filter, so there is an economic cost in going to more efficient mechanical filters.
The second type of filter employs electrical charge to enhance collection of particles. For
example, the fibers can be permanently charged. This type of filter is often called an electret.
Since some air particles are charged, they will be attracted to charges of opposite polarity on the
filter. Even for uncharged particles, the existence of a charge on a nearby fiber will induce a
dipole moment (pushing like charges to the back of the particle and unlike charges to the front,
as seen from the fiber) and the net result is an attraction to the fiber. Since the electric charge on
the filter doesn’t affect the pressure drop, there is no energy penalty. Electrets are widely used in
automobiles to filter air coming in to the passenger compartment.
Another way to use electric charge is to actively add charge to the incoming particles by passing
them through a strong electric field created by multiple wires. The particles are driven to a
number of collecting plates. These air cleaners are called electrostatic precipitators (ESPs).
A third approach using electric charge is to send out large quantities of charged particles (ions)
into a room. The ions collide with particles and stick, thereby charging them and causing them
to be attracted to grounded surfaces such as walls and floors. Such devices are called ion
generators or ionizers.
There can also be hybrid filters. For example, some electrets may also have a continuous electric
field applied to them, in an attempt to reduce the loss of charge over time that has been noted for
electret fibers.
These categories and some subcategories are listed in Table 1. Panel filters are flat filters, often
about 1 inch deep, designed typically for insertion into furnaces. They are mainly designed to
protect the furnace from large debris and have virtually no air cleaning capacity for respirable
particles.
Pleated or extended surface filters attain better efficiencies by presenting much more surface
area to the particles as they pass through the filter. For a given depth, there are more fibers and
therefore more chance to intercept particles. These filters are often much thicker, 4-6 inches, and
may require cutting sheet metal in the ductwork to install.
HEPA (High Efficiency Particulate Arrestors) filters were originally developed for worker
protection against radioactive elements encountered in certain workplaces. They consist usually
of extremely densely packed fiberglass. To obtain the designation HEPA, they must filter out
99.97% of particles 0.3 μm in diameter. This particle size is normally the hardest to filter, so the
4
efficiency should be even greater than 99.97% for all other sizes. “HEPA-type” filters meet a
less stringent standard of 95% efficiency for 0.3 μm particles.
Table 1. Types of filters.
Type
Name
Composition
Comments
Mechanical
Panel
Cotton, polyester,
fiberglass, many others
Ordinary furnace
filter
Pleated
HEPA
>99.97% efficient
“HEPA-type”
>95% efficient
Electrical
Electret
Permanently charged
fibers
Electrostatic
precipitator
Wires at high voltage;
collecting metal plates
Ionizer
Corona discharge
needle(s)
The Association of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) has
developed standard tests for classifying and ranking efficiencies of filters. The tests are described
below in the section “Rating filters” and in more detailed fashion in Appendix B.
5
Effectiveness of air cleaners
The basic question for any air cleaner is “How well does it work?” For many years, there was no
standardized test procedure to answer this question. Eventually, in about 1985, such a test
procedure was developed, but only for portable air cleaners. There is still no standardized
procedure for in-duct air cleaners.
We must first distinguish between two measures: efficiency and effectiveness. The efficiency of
an air cleaner is the fraction of particles that it removes in a single pass through the system. This
is easily measured by measuring the concentration of particles just upstream and just
downstream from the filter. A typical furnace filter has an efficiency well below 10%, whereas
an ESP (when clean) will typically have an efficiency better than 90% for all particle sizes.
Efficiency alone is not enough, however, to characterize an air cleaner. It could have very high
efficiency, but a very low air flow. In that case, it would not be delivering very much clean air.
One must multiply the efficiency by the air flow through the filter to determine how much clean
air it can deliver: the clean air delivery rate, or CADR. The CADR is usually presented as a
volume of clean air delivered per time unit, such as cubic feet per minute (cfm) or cubic meters
per hour (m3/h).
The standardized test procedure mentioned above results in a measure of the CADR for a given
portable air cleaner. The procedure is administered or overseen by the Association of Home
Appliance Manufacturers (AHAM). AHAM certifies those air cleaners that have undergone the
test (AHAM 1988), and maintains a Website listing all brands and models (presently >150) with
their associated CADRs. This is the single most valuable resource for consumers wishing to buy
an air cleaner.
The entire list can be searched online at
http://www.cadr.org/consumer-certified.htm
The link has search capabilities allowing quick identification of the companies and products
meeting the user’s specifications. For example, a search for air cleaners exceeding a CADR for
tobacco smoke of 400 cfm identified 10 air cleaners sold by 4 companies. This is extremely
valuable for consumers wishing to cut through the cloudy descriptions of advertisers. The same
search also returned the maximum size room for which the air cleaner would be deemed
effective—in this case, a large room of >679 square feet. Rooms up to this size would, in theory,
have their particle concentrations reduced by 80% or more. However, this would not be true if
the door was open to other rooms in the house, or if the window in the room was open, or if the
house air exchange rate was higher than average.
6
Very recently, AHAM has added a second criterion to its testwhether or not the air cleaner can
meet a standard for ozone generation. The standard is maintained by the Underwriters
Laboratory (UL) and is UL Standard for Safety 867. The standard specifies that the air cleaner be
operated for at least 8 hours and up to 24 hours (to achieve a steady-state concentration) in a
stainless steel chamber (approximately 10' X 10' X 10' or about 28 m3). The ozone level is
measured at a point about 2 inches from the main outlet (highest ozone emission rate) of the air
cleaner, and must be < 50 parts per billion (ppb).
However, the AHAM certification program is voluntary. Manufacturers need not participate. In
fact, manufacturers of inefficient air cleaners may not wish to participate. Therefore independent
testing of such instruments is also useful. Such testing is done by consumer organizations and
reported in publications such as Consumer Reports Magazine or associated websites.
Even the CADR, however, is not the last word on air cleaners. For one thing, it applies only to
new units. As air cleaners are used, their efficiency may change in different ways. But also the
CADR applies only to the air passing through the filter. Air that reaches the person before
passing through the filter will be unaffected.
Therefore we define effectiveness as the ability of the filter to remove particles from a room or
from the breathing zone of a person. Since all homes have cracks allowing particles to enter,
there is always a fresh supply of particles, some of which will not pass through the filter before
encountering the person. Indoor sources of particles, such as cooking or vacuuming, will add
even more particles that may reach the person before going through the filter. Therefore the
effectiveness of a filter is always less than its efficiency. Effectiveness, like efficiency, may be
reported as a fraction or a percentage of the particles that are removed before reaching the
person. It may also be reported as an effective air change rate, or the number of house volumes
or room volumes of clean air that it can provide in an hour. Effectiveness is much more difficult
to measure than efficiency. However, under certain conditions, effectiveness has a well-
understood mathematical form and can be determined in homes or test houses.
A more mathematical description of efficiency and effectiveness is provided in Appendix A.
The focus of this report is on actual effectiveness of air cleaners as used in homes. The literature
search specified “home” or “residence” as a key word along with “filter” and “air cleaner” or “air
purifier.” Since filters help persons with allergies, we included terms such as “allergy” and
“asthma”; also since studies of effectiveness often use the term “intervention” we included that
as a search term
We believe the literature search is fairly complete for air cleaners used in homes. The earliest
uses of air cleaners may have been by physicians for treatment of acute hay fever or asthmatic
episodes. Some of these air cleaners were set up in hospital rooms or wards, but they have been
included in our report.
7
We have also identified a number of reports on laboratory or chamber tests of air cleaners.
These are valuable for identifying the upper limit of the effectiveness of an air cleaner, and for
indicating the relative efficiency or clean air delivery rates for a series of filters of different
composition. For example, if a chamber test shows that a furnace filter has an efficiency of 5%,
this is useful information—we don’t need to worry about its ultimate effectiveness, since we
know it will be close to zero once all the other factors such as infiltration and indoor sources
come into play. For this reason, we also provide a summary of the chamber tests that we have
found. We think this summary is also fairly complete.
Air cleaners used in homes
The results of the literature review are summarized in Table 2 (see associated Excel file: Table 2
Residences.xlsx). Many of the early reports were by physicians treating acute asthma or hay
fever. The first we have found is from a Dutch physician (van Leeuwen 1924). He erected a 50-
foot high pipe to sample air from well above the rooftops and bring it to a room for his patients
to breathe. Leopold and Leopold (1925) constructed a room in the Hospital of the University of
Pennsylvania with filtered air. Cohen (1926, 1927a,b, 1928) constructed a portable window-
mounted mechanical filter with a pump pulling 140 cfm (later 250 cfm) into the room. He noted
this made sealing the room unnecessary since the positive pressure would force other dust and
pollen out the cracks in the room. Cohen reported improvement in all 10 of his refractory asthma
patients after spending 12-15 hours per day in the room with the filter. All of these physicians
reported nearly complete relief from symptoms within some period of time ranging from a few to
18 hours. Reported effectiveness of the filters, as determined by counting pollen grains on glass
slides, was very high at better than 95% reduction.
A drawback of the Cohen mechanism was a filter that got clogged after a time in the heavy
ragweed season and was difficult to remove. Peshkin and Beck (1930) improved on this by
developing a device with an easily removable pleated filter (surface area 8 square feet). Since
the ragweed season lasts for some weeks, they noted that their filter needed changing several
times over that period. Their device had a fan capable of pulling 400 cfm at the highest setting.
This would be sufficient to provide a complete air change to a 2000 cubic foot room (14’ X 14’
X 10’) in five minutes. Peshkin and Beck claimed that the device removed 100% of ragweed
pollen as measured by counting grains on a slide downstream of the filter.
Three more articles appeared in 1932-33, each reporting on large numbers of patients treated for
asthma by staying in hospital rooms with filtered air. Beck (1932) reported on 54 patients;
Nelson et al., (1933) on 76; Rappaport et al., (1932) on 105.
8
The first use of an electrostatic precipitator for patients with asthma was reported by Criep and
Green (1936). The ESP had only just been developed as a prototype model a few years earlier
by Westinghouse. Criep and Green reported >99% effectiveness in removing pollen from their
ESP-equipped hospital room. Improvement in nearly all of their 53 patients was reported within
4-9 hours of entering the room.
Friedlander and Friedlander (1954) studied the clinical effect of a portable ESP on 30 patients.
For most, the ESP was installed in a room of their home. “Excellent” improvement was noted for
12 of 30 patients; no improvement for 7. Earlier tests of the ESP in an empty room showed
better than 90% removal of pollen grains, based on comparisons with a similar room without the
ESP. Lefcoe and Inculet (1971) studied the effect of an ESP installed in the HVAC system of a
20,000 ft3 home with 6 inhabitants. This was also the first to report effectiveness using a
measure other than pollen counts. Lefcoe reported 80-86% reductions in three sizes of respirable
particles between 0.3 and 2 μm, using hourly measures over a 3-day period.
The first report on a HEPA filter, and the first comparing a HEPA filter with an ESP, was
presented by King et al., (1973). He reported reductions of particle concentrations from 106
particles/ft3 to 6000 /ft3 using the HEPA filter, and to 34000 /ft3 using the ESP. He also noted a
decline in the ESP efficiency over only 4 days.
An early study of a negative ion generator found no further reduction of pollen, mold, and
bacterial counts beyond the reduction provided by an air conditioning unit (Spiegelman et al.,
1961). Later, Repace (1983) used a very powerful multi-needle device mounted on the ceiling
and obtained a 96% reduction in environmental tobacco smoke (ETS). Nogrady and Furnass
(1983) tested an ionizer for its effect on bronchial asthma in 20 adults. Sham or active ionizers
were placed in subjects’ bedrooms for two 8-week periods separated by a 4-week “washout”
period. Although the ionizers produced 100-fold increases in ion density, no effects were seen in
lung function, symptoms, or medication use. A decade later, Warner et al., (1993) performed a
similar double blind placebo controlled study on 20 adults, with one difference being the use of
two ionizers, one in the bedroom and one in the living room. Once again there was a major
increase in ion density but no effect on lung function, symptoms, or medication use.
About ten studies have investigated the effect of air cleaners on fungal spores and mold, with
reported effectiveness ranging from 0 (Nelson et al., 1991) to 94% (Richardson, 2000). These
studies include Cheong et al., 2004, Huang 1993, Huang et al., 1995, Jacobs et al., 1989, Li et al.,
1995, Loo et al., 1996, Perraud et al., 1992, Rhame et al., 1984, and Takatori et al., 2001.
Since radioactive radon daughters can attach to particles and be drawn deep into the lungs, an air
cleaner could reduce risk. Several studies investigated this, with general agreement that
exposures could be reduced by substantial amounts (30-60%; Hopke 1993, 1994, 1995a,b; Miles
et al., 1980; Rajala et al., 1984; Wasiolek et al., 1993), but that radioactive dose would be less
9
affected, partly because although the attached fraction would be reduced, the unattached fraction
(which can also penetrate deep into the lung) would increase.
An idea for increasing the effectiveness of air cleaners by mounting it on the headboard and
blowing the cleaned air directly over sleepers’ heads was tested in several studies (Villaveces et
al., 1977, Zwemer and Karibo, 1973). Although very high effectiveness was claimed in some of
these studies (Verrall et al., 1988, Morris et al., 2006), funding was sometimes supplied by
manufacturers and some authors (Morris et al., 2006, Hacker and Sparrow, 2005) were affiliated
with the companies that manufactured the device. There was also poor study design (no
blinding, no placebo) in some of these studies.
A serious problem in hospitals, particularly in those being renovated, is aspergillosis, an often-
fatal disease striking immunocompromised patients. The renovation disturbs spores of the
common fungus Aspergillus. Intensive filtration procedures are necessary to protect patients, and
several papers have recounted successes and failures in these attempts (Opal et al., 1986, Marieu
& Nelson, 1993, Mahieu et al., 2000, Engelhart et al., 2003). The recent resurgence of
tuberculosis has also sparked interest in filtration to protect against Mycobacterium tuberculosis
(Rutala et al., 1995, Miller-Leiden et al., 1996).
Following the early mostly anecdotal studies of hay fever and pollen allergies, a series of studies,
some with more stringent design (double blind, placebo controlled) were applied to study the
effect of air cleaners on asthmatic and allergic patients (Reisman et al., 1990, Reisman 2001,
Scherr and Peck, 1977, Schwartz et al., 1973). The allergens studied included dust mite
(Antonicelli et al., 1991, Harving et al., 1991, 1993, 1994, Shapiro et al., 1999, Thiam et al.,
1999, van der Heide et al., 1997, 1999, 2000, Warner et al., 1993); cat allergen (Boquete et al.,
1997, Custovic et al., 1998, de Blay et al., 1991, Eggleston et al., 2005, Gore et al., 2003a,b,
Luczynska et al., 1990, Pahdi et al., 1997, Swanson et al., 1985, and Wood et al., 1993, 1997,
1998); and dog allergen (Green et al., 1999). Mixed results ensued. Sometimes the air cleaner
was unsuccessful in reducing allergen levels. Sometimes it did reduce levels considerably, but
symptoms were unaffected. In only a small number of studies were both allergen and symptom
reductions significant (Bascom et al., 1996, Li et al., 1995, van der Heide et al., 1999).
Because of the importance of any treatment that could reduce allergic symptoms, these studies
have been periodically reviewed by committees of physicians and official reports issued by their
associations (e.g., American Lung Association (ALA 1997), American Thoracic Society (1990,
1997), Nelson et al., 1988, National Academy of Sciences (NAS 1993)). The invariable
conclusion has been that there is little to no evidence that air cleaners are effective in reducing
symptoms, and that they cannot be recommended to patients except as additional aids to more
basic strategies such as source removal, isolation of the bedroom from the pet or other source,
encapsulating of bed material in the case of dust mites, etc.
10
With the recognition of childhood asthma as a fast-growing and serious problem, several large-
scale studies were launched in recent years that included simultaneous approaches toward
reducing allergens: supply of HEPA air filters, HEPA vacuums, impermeable bedding, pest
management procedures, etc. The largest of these studies was the Inner-City Asthma Study
(ICAS), which took place over 3 years in 937 homes in poor neighborhoods in 7 US cities
(Morgan et al., 2004). A cost-benefit analysis of this study concluded that the benefits in
increased symptom-free days, reduced use of inhalers, and fewer unscheduled clinic visits
outweighed the substantial cost of $1469 per family (Kattan et al., 2005). Since the intervention
methods were simultaneous, it is not possible to attribute the benefits to any one of them, but the
HEPA air cleaners were an important part of the strategy. A second study taking this approach of
multiple simultaneous actions, one of which included a HEPA air cleaner in every child’s
bedroom, also resulted in significant improvements (Eggleston et al., 2005).
Beyond asthma, two groups of illnesses have been shown to be exacerbated by particles: chronic
obstructive pulmonary disease (COPD) and cardiovascular disease. Since particles are a mixture
of many elements and chemical compounds, it may be that certain components of the particles
are more toxic than others. Suspicion has focused in the past on combustion particles, and more
recently on ultrafine particles, which are more numerous than larger particles and may be more
toxic on an equal-mass basis (Oberdorster et al., 2005). A recent study employed filtration of
ultrafines to detect an effect of auto exhaust on oxidative stress of 29 healthy subjects (Bräuner et
al., 2007). The subjects were exposed in a chamber in random order for 24 hours to unfiltered
air and for 24 hours to filtered air from a nearby street with traffic. The HEPA filter reduced
ultrafine particle levels by 97.7%. The unfiltered air exposures resulted in significantly elevated
levels of oxidative stress as measured by DNA damage. Bräuner et al. (2008) extended these
studies to a set of 42 elderly healthy subjects, who were exposed to filtered and unfiltered air for
48 hours. The HEPA filter reduced the ultrafine particle number by about 68%, and the fine
particle mass by 63%. There was a significant 8% improvement in microvascular function
following exposure to the filtered air. However, in this study, the fine particle mass was more
highly associated with damage than the ultrafine particle number.
Long-term studies of air cleaners used in homes
A second question for the prospective buyer of an air cleaner after “How well does it work?” is
“How long will it work?” A weakness of the AHAM certification program is that it applies only
to new air cleaners. Therefore we searched for studies looking at long-term use within a home.
The Canadian Mortgage and Housing Corporation (CMHC) has provided a valuable series of
studies on filters as used in homes (CMHC 1998, 1999, 2001, 2005, 2007; Bowser et al., 1999;
Bowser and Fugler 2002; Fugler et al., 2000; Fugler and Bowser 2002). These studies have
looked at the effectiveness of portable filters, in-duct filters, and various determinants of particle
11
levels such as penetration factors, effects of floor cleaning, etc. In many cases, the CMHC has
looked at the effectiveness of the filter as actually used and with varying lengths of use. The
results from one study of five homes with in-duct ESPs is particularly relevant to the question
above, and returned rather disturbing answers. In several cases, leaks or gaps allowing air to
avoid the filter were present. In most cases, the filter performance degenerated within days after
cleaning. The best-performing filter averaged about 80% efficiency, but others were as low as
35% or 40%. These efficiencies would translate to even lower effectiveness, as determined by
measurements of actual indoor concentration reductions.
In several long-term studies in a home, Wallace et al. (2002, 2004) and Howard-Reed et al.
(2003) documented the behavior of an ESP and a good-quality mechanical filter over 6 months
to a year of continual use in a forced-air system that was nearly always on. Since this is almost
the only study documenting long-term (up to one year) behavior in a real-life situation, the
results of the study will be examined in detail. The ESP was installed in the return air duct of the
forced-air system. Probes were inserted upstream and downstream and particle levels measured
every minute using Climet monitors with 6 size categories: 0.3-0.5 μm, 0.5-1, 1-2.5, 2.5-5, 5-10,
and > 10 μm. Monitor results were automatically logged and inspected periodically. Thus the
changing efficiency over time could be monitored. The ESP when new was extremely efficient
for all particle sizes: 98-99% for the three largest sizes (2.5-10 mm), and 95-98% for the smallest
sizes (0.3-2.5 mm). However, after several weeks constant use, the efficiency for the smallest
sizes began to decline. The manufacturer recommended cleaning every month or two by soaking
in dishwasher detergent. This was done, and resulted in restoring the very high efficiency for the
coarse particles, but the efficiency for the fine particles reached about 95%, not the 95-98% that
had been achieved before. Therefore each of the 20 or so collector plates was wiped with a
sponge to remove collected dust. This resulted in bringing the efficiency back to the high levels
observed before. The sponge-wiping step was added to the cleaning routine from then on. (It has
subsequently been learned that the reason for the falloff in efficiency of ESPs is probably due not
to deposition of dust on the collector plates, but rather to the wires themselves being coated with
a silicon-based molecule (Chen and Davidson, 1999; Davidson and McKinney, 1998), perhaps
from household use of deodorants or other products; the reason for the positive effect of the
sponge wiping was probably that the narrowness of the opening between plates meant that each
wire was cleaned by the sponge at the same time the associated plate was being cleaned.) Over
the course of almost a year, the ESP was cleaned five times (approximately every 2 months).
The results of these long-term efficiency tests for the ESP and mechanical filter are provided in
Figures 1 & 2. Figure 1 documents the repeated declines and restoration of the ESP efficiency
for both fine and coarse particles provided by the cleaning routine. Although the ESP was
operating at reduced efficiency much of the time, overall it was providing a major air cleaning
benefit for both fine (65% reduction) and coarse (75%) particles. An even greater benefit would
have been obtained had the cleaning been done more often (every 3 weeks or so, instead of the
actual rate of every 6 weeks or so.)
12
Figure 1. Long-term Efficiency of the Electrostatic Precipitator (ESP). Over nearly one year of
constant air flow (2400 cfm) over the ESP, the average efficiency for fine particles was about 65%,
a reduction of particle concentrations by a factor of 3. For coarse particles the reduction averaged
about 75% (a factor of 4). After a month or two without cleaning, however, the efficiency was
reduced from > 90% to about 20-50%. The five cleanings over the year restored the efficiency to
>90% for both fine and coarse particles.
13
Figure 2 shows the long-term performance of the mechanical filter. A great contrast is seen
between its efficiency for coarse particles (80%) and that for fine respirable particles (near zero).
As dust collected on the filter, the efficiency for the coarse particles showed a slight
improvement, but the near-zero efficiency for fine particles was unchanged.
Figure 2. Long-term Efficiency of the Mechanical Filter. The mechanical filter increased its
efficiency for coarse particles (>2.5 μm) from less than 60% to nearly 80% over the course of 1600
hours of operation. However, the efficiency for fine particles hovered near 0 at all times.
14
Howard-Reed et al. (2003) extended these results to look at the overall effectiveness of both
filters by calculating the increase in deposition rate when the filter was on compared to when it
was off. The effective decay rate produced by the ESP was several times the natural decay rate
due to air exchange and deposition, indicating an effectiveness of better than 60% for both fine
and coarse particles (0.3-10 μm). The mechanical filter had somewhat smaller effectiveness for
the coarse particles and was ineffective for the fine particles.
Wallace et al. (2004) extended the results further to the realm of ultrafine particles. Figure 3
shows the increase in decay rates for the entire range of particle sizes provided by the ESP
compared to the mechanical filter, the furnace filter, and no filtration. It should be noted that the
large increases in the decay rates provided by the ESP is an average over all periods including
those when its efficiency was impaired. As an aid to estimating the effectiveness associated with
these decay rates, one can take the ratio of the decay rate with a filter to that with no filtration. A
ratio of 2:1 means the filter is reducing particles twice as fast as no filtration: a reduction of 50%.
A ratio of 3:1 corresponds to an effectiveness of 2/3 (about 67%), 4:1 an effectiveness of ¾
(75%), and 5:1 corresponds to an effectiveness of 4/5 (80%). The latter 80% figure is the figure
used by AHAM in calculating the size of the room that can be cleaned by a given portable air
cleaner. This figure is much more difficult to attain in a whole-house situation, where the
volume to be cleaned may be an order of magnitude larger than a room, and the number of
infiltration locations and indoor sources another order of magnitude larger. Nonetheless, it is
possible to estimate that the overall effectiveness across all particle sizes of the ESP in this real-
life situation was better than 50%. Theoretical calculations (Riley et al., 2002) suggest that a
whole-house effectiveness of about 65% could be expected for a well-performing and well-
maintained in-duct ESP.
A recent study of long-term (2 months) filter performance was carried out by Batterman et al.,
(2005). Four single-family homes with cigarette smokers were equipped with portable HEPA
filter units (CADR rating of 330 cfm). Over the course of the study, the airflow dropped by 7-
14%, largely due to particle accumulation on the prefilters. The effectiveness of the filters
ranged from 30-70%. Presumably this could be improved by a few percent with more frequent
changeout of the prefilters.
Shaughnessy et al. (1993) tested two filters (HEPA and ESP) for 800 hours over a 6-month
period. The HEPA was tested in a nonsmoking bedroom, the ESP in an office with smoking.
Both filters lost efficiency, with the CADR reduced by 25% for the HEPA filter and 38% for the
ESP. The difference might not be significant, since the ESP no doubt dealt with much greater
particle loadings.
15
Figure 3. Effectiveness of an ESP compared to a good-quality mechanical filter, a furnace filter,
and no filtration. In the 0.1 to 1 μm range (where most particle mass resides) the ESP outperforms
the other filters by a ratio of about 3:1, corresponding to a reduction of particle levels by about
67%.
0.1
1
10
0.01 0.1 110
k (h-1)
Particle diameter (
m)
ESP filter
Mech filter
Fan on, no filter
Fan off
SMPS
APS
16
Chamber studies
Laboratory or chamber studies of air cleaners can provide precise measurements of their
efficiencies and clean air delivery rates. They are most valuable in providing relative rankings of
different air cleaners. They can also be used to rule out all air cleaners below some desired clean
air delivery rate. For this purpose, the AHAM web site is the most useful and up-to-date
compilation of air cleaner CADRs.
However, earlier chamber studies also have their uses. For example, the detailed information on
efficiency, flow rates, and clean air delivery rates allows a calculation not only of the cost of
buying and maintaining any air cleaner tested, but also of calculating the cost of the clean air
provided and comparing that value across different air cleaners.
Therefore we also include in this report the chamber studies that were identified by our literature
search (Table 3; see associated Excel file:table 3—chamber studies.xls).
One of the earliest and most influential chamber studies was provided by Offermann et al.,
(1985). He studied 10 air cleaners including all major types (panel filters, pleated filters, HEPA
filters, ESPs and ionizers). A room in a test house operated by Lawrence Berkeley National
Laboratory provided excellent control over all important environmental variables. To compare
the devices on a single metric, Offerman developed the concept of the Effective Cleaning Rate
(ECR), which was later adopted by AHAM and renamed the Clean Air Delivery Rate (CADR).
(Offermann was a consultant to AHAM when they developed their test method.) For most of the
air cleaners mentioned, the CADR is the product of the air flow through the device and its
efficiency. For example, if the device pulls air at 300 cubic feet per minute across the filter, and
the filter has an efficiency of 50%, the device will produce clean air at the rate of 150 cubic feet
per minute: a CADR of 150 cfm. The units of CADRs are normally either cfm or m3/h.
The study of 10 air cleaners showed that the HEPA filter (ECR about 300 m3/h) and the two
ESPs (about 200 m3/h each) were by far the best performers. The ion generators, panel filters,
and electrets ranged between 0 and about 50 m3/h, while the combination extended surface
electret/ionizer attained about 100 m3/h cleaning rate. Shortly thereafter, Humphreys (1987)
tested 3 HEPAs, two ESPs and one ionizer, with similar results: the HEPAs and ESPs ranged
from about 30-120 cfm of clean air whereas the ionizer provided only 30 cfm. In Sweden,
Olander et al., (1987, 1988) tested all 31 brands of air cleaners on the Swedish market, again
showing ESPs near the top and ionizers at the bottom of the rankings.
The first test of a duct-mounted filter, an ESP, seems to have been performed by Hanley et al.,
(1990). The device was tested for eight size fractions at three flow rates (250, 500, 1000 cfm)
with efficiencies ranging from 70-90% at low flow and 45-90% at high rates. The higher
17
efficiency at lower flow rates is expected, since the particles spend longer in the region affected
by the electric field and have more time to deposit. However, Hanley also suspected that some
particles might flow through areas unaffected by the electric field (“sneakage”). By masking the
extremities of the device, he was able to improve the efficiency even at high flow to 60-100%.
Offermann et al., (1991, 1992) then extended the in-duct testing to six air cleaners, including two
panel filters, one pleated filter, a HEPA filter, and two ESPs. Testing was done in a 3-room test
house at LBNL. The HEPA filter, pleated filter and one of the two ESPs accounted for the
highest clean air delivery rates (400-600 cfm) compared to a range of only 14-24 cfm for the
other three filters. Offermann calculated the cost of clean air delivery (taking into account both
retail cost and upkeep) and found it was 28-30 cents per cfm for the ESP and pleated filter, and
56 cents per cfm for the HEPA filter, but $4-7 per cfm for the other three in-duct filters.
Hanley et al., (1994) summarized tests at Research Triangle Institute on 12 in-duct air cleaners.
The best performers were ESPs (80-90% efficient at lower face velocities, 70% at higher
velocities); and ASHRAE 95% “pocket filters” (70-98% new; > 95% loaded). The furnace filter
had an efficiency of about 2% and a “self-charging” filter an efficiency of about 60%.
Shaughnessy et al., (1993, 1994) summarized experiments on 12 air cleaners in his test chamber
at Tulsa University. The rank order was ESP >HEPA >extended surface (electrets) >ionizers
>ozone generators. A more recent review is Shaughnessy and Sextro (2005, 2006).
In an extensive study at the 3M company, Kinzer and Moreno (1997) measured the efficiency of
27 air cleaners, including panel filters, pleated filters, “washable/reusable” filters, “deep” pleated
filters, and ESPs. Of them all, only the ESPs were able to achieve better than 50% efficiency
(range of 44-94%).
One chamber study (Faulkner et al., 1999) dealt with a “personal air supply system” designed for
use in offices. This is an attempt to deliver filtered air directly to the breathing zone of the
worker, thus avoiding the common problem of pollutants contaminating the filtered air before it
reaches the worker. The particular system tested appeared capable of reducing particle levels by
a substantial amount, thus reducing the amount of outdoor air necessary to bring in by 23-47%;
this would account for a major saving in the expense of conditioning the outdoor air.
Office studies
Although we did not seek studies of filtration in offices or other buildings, a number of such
studies showed up in our literature search. These studies are listed in Table 4 (see associated
Excel file:table 4--offices.xls). The list is not complete, but does serve to give an indication of
the type of filtration studies that have been performed in offices, schools, day care centers, and
18
similar buildings. Over the past two decades, a series of studies by a group in Denmark
(Wargocki et al., 2002, 2004, Wyon 1992, 2004) have concentrated on the effects of ventilation
on productivity, with fairly consistent indications that productivity is often improved by 6-9%
when conditions are improved (e.g., newer or better filters are installed). Only one study in
schools has been carried out (Wargocki and Wyon, 2007) but it showed a similar improvement in
objective performance on tests of various types when ventilation was increased (but no effect of
replacing an old filter with a new one was seen). However, the old filter had seen little use so the
difference between filters was small.
Fisk et al. (1987, 2000, 2002, 2003) have concentrated on performance and cost of air filtration
technologies. Clausen (2004), Clausen et al., (2002a,b) and Hytinnen et al., (2002, 2003a,b,
2006) have focused on the effects of used filters on odor and health. Seppanen and Fisk (2002,
2004), Seppanen et al. (2006), and Jaakola et al. (1991) have investigated the role of filters in
worker performance and the Sick Building Syndrome. Hänninen et al. (2005) investigated the
reduction potential of mortality risk attributed to filtration. A specific study of the effect of ESPs
on airborne dust and health of employees was carried out by Skyberg et al. (2000, 2003) and
Skulberg et al. (2005). The ESPs succeeded in reducing particle levels by 46% but improvements
in symptom prevalence were not significant.
Combinations of measurement and models have been used by Emmerich and Nabinger (2001),
and Jamriska et al., (2000, 2002, 2003) to determine the impact of air filtration in buildings.
“Personalized” ventilation systems (individual supply of filtered air contained in or attached to
the desks of office works) have been investigated by Hedge (1993), Kaczmarczyk (2002 a,b,
2004), Melikov (2000, 2002), and Zeng et al., (2002). In most cases, these systems succeed in
providing considerable reductions of particle exposures as long as people remain at their desks.
Ionizers
Special attention to ionizers may be warranted. As mentioned above, most comparative studies
show poor results from ionizers, with CADRs typically ranging between 0 and 50 cfm. In a
highly visible controversy, Sharper Image, Inc sued Consumer Reports over their low rating of
the Ionic Breeze, a best-selling ionizer. The courts supported the Consumer Reports testing
methods and conclusions. (And in February 2008, in the face of several class actions brought
against Sharper Image regarding the Ionic Breeze, and sharply declining sales of the Ionic
Breeze, Sharper Image declared bankruptcy.) However, several studies such as Repace et al.,
(1983) and a series of studies from the laboratory of Sergei Grinshpun (Lee et al., 2004a,b;
Grishpun et al., 2005) have shown excellent results from ionizers. This apparent contradiction
may simply be due to the relative strength of the ionizers tested. The ceiling-mounted system
19
Repace tested and the series of ionizers tested in the Grinshpun chamber (funded by Wein
Products, a manufacturer of ionizers) are apparently much stronger than those typically available
to the consumer. A major reason for this is that the ionizers produce ozone, and the stronger
ionizers produce more ozone. Several tests indicate that a medium-strength ionizer will produce
ozone at levels sufficient to exceed the 50 ppb level that is a recommended upper limit (Britigan
et al., 2006, Mullen et al., 2005, Niu et al., 2001a,b, Shaughnessy and Oatman, 1991, Phillips et
al., 1999). Therefore most ionizers available to the public are rather weak, and probably unable
to maintain high levels of ions throughout a medium-sized room. In addition, the Grishpun tests
are done in a sealed chamber with no air change and therefore no constant supply of particles to
be charged; Mayya et al., (2004) showed that such a supply of particles very quickly reduced the
efficiency of the ionizers tested.
Both ionizers and ESPs produce ozone as a byproduct. Several studies have documented the
amount of ozone produced (Table 5; see associated Excel file:table 5—ozone.xls). In some
cases, the resulting ozone levels would exceed various standards such as the FDA standard of 50
ppb. Most existing studies of ozone production have looked at ozone generators and ionizers.
Whether ESPs would have equivalent ozone production rates is not well known. One study of
five Canadian homes with duct-mounted ESPs showed an average ozone increase of 9 ppb
(CMHC 2007). While well below the FDA standard, this could add to existing ozone levels to
cause concentrations exceeding the standard in some cases.
Ozone can react with some organic gases to produce ultrafine particles (Liu et al., 2004, Mullen
et al., 2005, Siegel et al., 2006, Tung et al., 2005, Waring et al., 2007, 2008). The most
productive reactions are with terpenes, including alpha-pinene (the pine scent) and limonene
(lemon scent), common constituents of many consumer products. Therefore most homes with
ozone levels indoors will have some ultrafine particles produced when these consumer products
are used.
Another problem with some of the ionizer studies are that results are not reported as CADRs,
which are comparable across different room volumes and ventilation rates. However, in her
Master’s thesis, Yu was able to use reported results to calculate CADRs for all of these cases
(Yu, 2005). (Her calculations are included in Table 3). The CADRs in general range from about
10 to about 70 m3/h, which puts nearly all of the ionizers studied near the bottom of the
effectiveness ratings. Considering that even these values were obtained under conditions of no
supply of new particles, it is clear that the effectiveness of ionizers will be even lower under
realistic conditions.
20
Ozone generators
Ozone generators have been marketed to the public as both air cleaning devices and mood
elevators. However, ozone has generally deleterious effects on organisms (it can kill microbes at
high concentrations) and few if any positive effects. The state of California has recently passed
legislation to stop the sale of ozone generators and other products that will create ozone in excess
of 50 parts per billion (ppb) according to a standardized test (Underwriters Laboratory Standard
for Safety 867).
Cost Considerations
A few studies have provided data on the cost of the air cleaners studied. Offermann et al., (1985,
1992) detailed the cost of 10 portable air cleaners (and one circulating fan) in 1985, and did the
same for 6 in-duct air cleaners in 1991-92. We have applied Offermann’s cost figures and his
calculations of the CADR for these 16 air cleaners to calculate the cost per cubic meter per hour
of clean air supplied (Table 6). We have also calculated the effectiveness of the air cleaners for a
50 m3 room and a 350 m3 house, using several assumptions regarding air movement within
homes and air change rates for Canadian homes.
21
Table 6. The Cost of Clean Air
Air cleaner type
a
Cost
(unit) Filter
replacement d Power
CADR
(m3/h)
b Cost
per
m3/h
c
Effectiveness
Portable air cleaners
HEPA-type
395
77
12
306
0.36
0.87
ESP 1 (metal plates)
370
0
12
207
0.15
0.82
ESP 2 (foam pad)
395
0
12
197
0.16
0.81
Electret-ionizer
pleated
295
16
12
97
0.44
0.68
Electret-ionizer flat
150
12
12
12
2.63
0.21
Electret 1
35
5
12
5
3.75
0.10
Electret 2
40
6
12
5
4.00
0.10
Circulating fan
52
0
12
2
7.30
0.04
Ionizer (residential)
80
0
12
2
8.00
0.04
Flat filter
30
4
12
0
0.00
In-duct air cleaners
pleated bag filter
450
50
90
991
0.16
0.83
ESP 1 (metal plates)
780
0
125
928
0.18
0.82
HEPA
481
131
80
712
0.33
0.77
ESP 2 (foam pad)
300
0
102
43
2.75
0.17
panel
2
2
90
41
2.26
0.16
electret
40
0
90
24
3.87
0.10
no filter
0
0
90
24
3.78
0.10
a Cost figures for portable air cleaners from Offermann (1985); for in-duct air cleaners from
Offermann (1992)
b Cost per m3/h calculated over 20-year period with one filter change per year
c Effectiveness calculated by (CADR/V)/(CADR/V + a + k), where
a (room) = 0.5 h
-1
k (PM
2.5
) = 0.4 h
-1
V (room) = 50 m
3
a (house) = 0.2 h
-1
V (house) = 350 m
3
d For in-duct cleaners, includes cost of running the central fan at all times during the year
22
The results on effectiveness are in complete agreement with the findings of Offermann et al.,
(1985, 1992), Shaughnessy et al., (1994), Kinzer and Moreno (1997), and Hanley et al., (1994)—
that is, the best air cleaners, whether portable or in-duct, are the ESP and HEPA devices.
However, considering cost in addition, the ESPs have a distinct advantage over the HEPA
devices, because they require no changes in filters (which can cost nearly $100 for the HEPA
cleaners) and do not increase the electric bill in the way that HEPA devices do. Most of the
mechanical filters tested do well on coarse particles but not on the fine particles that may have
more serious health effects. Many of the electrets lose efficiency for reasons that are not fully
known, but may relate to shielding of the fibers by the collected particles. And most of the
ionizers have low CADRs to begin with, while those with stronger ion generation powers have
other undesirable attributes such as unacceptable ozone production.
However, it is not possible to wholeheartedly recommend the ESPs either. For one thing, they
require a commitment on the part of the homeowner to keep a regular maintenance schedule.
The evidence suggests that monthly cleaning is required. Although the cleaning regimen is not
very demanding (soaking in detergent, cleaning each wire and plate with a sponge, and hosing
off), if neglected it will not be long before the efficiency dips well below 50%. Therefore the
prospective buyer should be honest with himself about how well he can maintain a regular
maintenance schedule.
Secondly, there is sobering evidence from the CMHC study of five homes with installed in-duct
ESPs that the installation process itself may often be unsatisfactory. For the ESP to work
properly, it needs to be tightly fitted into the duct to avoid bypass. The installation problem
extends to all in-duct air cleaners, but is perhaps worst for the HEPA filters, since they present
the greatest resistance to air flow. This means the air is even more likely to find small defects or
openings in the fitted housing and be diverted around the filter. There are engineering
approaches to finding and filling these cracks, with liquid-based sealant, but this may often be
beyond the ability of the homeowner himself to carry out.
Often a family with an allergic child will consider an air cleaner for the child’s room. They
might be swayed by the argument that a less powerful air cleaner will be sufficient for a small
room. However, there are several problems here. For one thing, the allergen may not be
confined to the child’s room. If the allergy is to cockroaches or furry pets, the allergen will be
found throughout the house. Secondly, the less powerful air cleaner, supposedly suited to the
room, will not perform as well if the room door is open much of the time. In that case, there will
be considerable air exchange with the rest of the house, reducing the effectiveness of the air
cleaner. (Even if the door is closed, if there is a forced-air system, it will bring in air from other
parts of the house unless care is taken to close the register in the room.) Finally, most allergens,
23
such as dust mite fecal allergen, are contained in relatively large particles and are mostly found
in bedding and house dust, which the air cleaner cannot clean.
The high-efficiency in-duct pleated filter tested by Offermann et al., (1991, 1992) did about as
well as the ESP and HEPA filter. These filters have advantages as well. They require little or no
maintenance, unlike the ESP, and they don’t have the energy penalty of the HEPA filter. They
could be a good choice for the homeowner who does not wish to bother with the maintenance of
the ESP. However, care would need to be exercised regarding the rating of the filter. An
ASHRAE Dust Spot Efficiency rating of 80% to >95% or a MERV rating of 13-16 would be
required to clean the air effectively over the entire house.
In summary, the CADR is a controlling factor determining the upper limits of the cleaning ability
of a portable filter. But other factors, including particularly the tightness of the house and
whether interior doors are open or closed will affect the degree of cleaning the portable filter can
provide. For in-duct filters, no CADR test is available, so the buyer needs to determine the
rating of the filter to make an informed decision. This is the subject of the next section of this
report.
Rating filters
Before the CADR was developed, filters were rated by a standardized test—in the U.S., this test
was known as ASHRAE Standard 52.1 (ASHRAE 1992). A test dust was introduced to the filter
at a certain spot and the amount of dust intercepted was measured by the color of the spot (the
Dust Spot rating, on a percentage scale from <20% to > 95%). A second test measured the
fraction (by weight) of the test dust that came through the filter after a given amount of exposure
time (the Arrestance rating, also on a percentage scale, from <65% to >98%). However, these
tests had major deficiencies. First, the test dust was not very similar to the type of dust that is
found in modern-day outdoor air. Secondly, measuring by weight of the dust trapped gave high
values for larger particles (which weigh more)yet research indicates that the smaller particles,
which can penetrate deep into the lung, may be more harmful. Thirdly, these tests did not
provide an indication of how well the filter worked for different sizes of particles, since only a
total amount was considered. Fourthly, the tests did not have some of the practical problems of
installing filters in homes, such as fitting the filter tightly into its assigned space to eliminate
24
bypass. Fifthly, these short-term tests gave no indication of how the filter would perform over an
extended period of time.
Therefore ASHRAE sponsored research to get a better idea of how filters actually worked with
different sizes and compositions of particles (Hanley 1993a,b). In general terms, there are two
processes at work: diffusion and interception/impaction. In diffusion, or Brownian motion, the
particle moves in random directions as it is hit by molecules of air. The smaller the particle, the
farther and faster it will move in these random directions, and the more likely it is to hit and be
trapped by a fiber on the filter. A large particle has more inertia, and as the airstream changes
direction to get through the cross-hatchings of the filter, the large particle keeps right on going
and impacts (or is intercepted by) the fiber. Therefore in very general terms, it must be that
filters are most effective for the smallest and largest particles, and will reach a minimum at some
intermediate size. This size turned out to be in the neighborhood of 0.1-0.5 µm .
With this knowledge, it was realized that a useful indicator of the efficiency of a filter would be
its efficiency at this minimum level. Therefore ASHRAE Standard 52.2 was developed, and
ranks filters according to their minimum efficiencies (MERV, for Minimum Efficiency Rated
Value) (ASHRAE , 2007). There are 20 categories within the MERV appellation, with MERV-1
being the least and MERV-20 the most efficient. ASHRAE Standard 52.2 did not replace
Standard 52.1, so that filter ratings may use either the newer MERV scale or the older ASHRAE
Dust Spot Efficiency and/or Arrestance ratings. The relationship between these three systems is
shown in Table 7.
The MERV 17-20 ratings apply to HEPA and ultra-low penetration air (ULPA) filters used in
clean rooms, hospital surgery rooms, laboratories dealing with radioactive materials, etc. MERV
13 -16 rated filters are also used mainly in commercial locations requiring very low particle
levels, such as hospital inpatient rooms, general surgery, smoking lounges, and high-end
commercial buildings.
Residences were classified according to their filter materials in an Appendix to ASHRAE
Standard 52.2 as “superior” (MERV 9-12), or “better” (MERV 5-8).
A more detailed discussion of the history of the ASHRAE filter tests is provided in Appendix B.
25
Table 7. MERV ratings from ASHRAE Standard 52.2 compared to the ASHRAE
Standard 52.1 Dust Spot Efficiency and Arrestance Tests
MERV rating
ASHRAE Dust Spot Efficiency
Arrestance
1
<20%
<65%
2
<20%
65-70%
3
<20%
70-75%
4
<20%
75-80%
5
<20%
80-85%
6
<20%
85-90%
7
25-30%
>90%
8
30-35%
>90%
9
40-45%
>90%
10
50-55%
>95%
11
60-65%
>95%
12
70-75%
>95%
13
80-90%
>98%
14
90-95%
n/a
15
>95%
n/a
16
n/a
n/a
17
n/a
n/a
18
n/a
n/a
19
n/a
n/a
20
n/a
n/a
26
Recommendations on Choosing Air Cleaners
About 60% of Canadian homes have central forced air systems (CMHC 1999). For homes with
forced air, Consumers Union recommends whole-house (in-duct) air cleaners as the “only
sensible” choice (ConsumerReports.org 2008). Within that category, they state that electrostatic
precipitators (ESPs) “have worked best overall and restricted airflow least among whole-house
models.” They also state that although ESPs may cost more at first than mechanical filters, they
may cost less overall because of the need to replace the filters every one to three months.
Although they also note that ESPs emit small amounts of ozone, the seven models that were
rated in 2008 all produced less than the 50 ppb that is the FDA guideline. Finally, they state that
the top-performing models that they tested had a MERV rating between 11 and 13. These
recommendations are in general agreement with the scientific studies reviewed in this report.
However, as the CMHC study of 5 homes with existing in-duct ESPs makes clear, they often
perform at a much lower effectiveness than expected. One suspected cause of this is faulty
installation. If a gap exists, some of the air will not pass through the working parts of the ESP
and will not be cleaned. Even if it appears that no gap exists, some researchers have noted that
the air can avoid the best cleaning zone (“sneakage”) and reduce the effectiveness of the air
cleaner. These researchers masked the outer perimeter of the air cleaner, forcing the air through
the central regions, and measured improved efficiency.
The problem of faulty installation is not restricted to ESPs. In fact, HEPA or “HEPA-type
filters have even more of a problem, since the increased resistance of the filter makes it more
likely that the air will find a way to avoid going through. For filter-based in-duct systems, there
is a need to determine whether the system is matched to the existing air handling unit capacity,
both at the expected pressure drop for a clean filter and the higher manufacturer-specified
pressure drop for a used filter. This means that the buyer must have his system capacity checked
before making a final decision on the filter-based system to buy. Because installation is so
important, a careful investigation of the reputation of the installer, including references from
other customers or appearance on lists of high-quality performers would be important.
Assuming that the filter-based system is properly matched to the existing forced-air system, and
has been properly installed, and has an efficiency equivalent to a MERV 13-16 rating, such a
system should give good performance. The homeowner will have to remember to change filters
every few months.
For all in-duct systems, ESP and filter-based alike, there remains the problem of testing whether
the installed system is working as designed. A possible way for the homeowner to test whether
his in-duct system is working properly is to place a mechanical filter behind it. The mechanical
27
filter should remain perfectly clean for a long time if the in-duct filter is working. Often the in-
duct system is installed in the return air duct, leaving a space for the furnace filter, so this space
could be utilized for the “test” filter.
For portable units, as described above, the AHAM website is always kept up-to-date and its
searchability makes it the most convenient and efficient way to compare all models by the single
best unit of comparison, the CADR. Therefore the first step in buying a portable air cleaner is to
determine the size of the space for which cleaning is desired. If the space is open to other areas
in the home, or if it has a door that will sometimes be open, the homeowner should multiply the
volume by some factor greater than 1 and look for a portable air cleaner rated for that size on the
AHAM Website. This will provide a list of air cleaner manufacturers and the model numbers
that will meet these specifications. A reasonable second step is to investigate the Consumer
Reports ratings of air cleaners. Consumer Reports.org maintains a website that provides access
to all previous ratings reports from the magazine. (This requires a subscription.) These reports
provide information on aspects other than the CADR, such as unit cost, annual energy cost,
replacement filter costs, noise of operation, ozone emission rates, and an overall rating. These
two objective sources of information should provide a trustworthy guide to obtaining the
portable air cleaner suited to the homeowner’s needs.
Summary
Air cleaners have been employed for more than 80 years. The first practitioners (in the 1920s
and 1930s) were doctors seeking to alleviate acute hay fever and pollen asthma in their patients.
They often created their filters and fan units themselves, or depended on local engineers to do
that for them. They were imaginative about the design and quick to incorporate improvements.
For example, one of the first air cleaners diagrammed already took advantage of the idea of
pleating the filter to increase the surface area within a limited space. Almost concurrently with
the development of the electrostatic precipitator for industrial use, doctors were adapting it for
use with their patients in hospital wards and in the patients’ bedrooms. Within 3 years of
developing a prototype for use in a hospital room, one air cleaner began to be marketed
commercially.
The early articles written by these doctors often included tests of the air cleaners, generally by
exposing glass slides and counting pollen grains, either artificially generated or naturally
occurring outside the room with the air cleaner. These tests often showed excellent results, since
even the simplest filters are in fact highly effective at trapping large particles such as pollen
grains. The physicians could also note very satisfactory results in many of their patients, since
the acute hay fever or pollen allergy is often quickly relieved by removal from the source.
28
However, the physicians also reported more stubborn cases, usually in persons with chronic non-
seasonal allergy. Often 20% or so of patients would show little or no improvement.
What we would in these days consider good study design was not done in these early years.
None of the physicians considered sham approaches (non-working air cleaners) to guard against
the placebo effect. None used a control population. No statistical tests of significance were
employed. However, there is little doubt that these early studies (about 10 articles between 1924
and 1936) were a powerful argument for the effect of air pollution on health, and the benefits of
reducing exposure.
After the ESP, the next advance in filter design was the HEPA filter, which was developed in the
1940s to protect radiation workers from exposure to inhalable radioactive particles. No new
principle was involved in the development of the HEPA filter—only a recognition that
increasing the twists and turns that air was forced to go through as it passed through the filter
would eventually succeed in trapping nearly all particles in the air. This was accomplished by
vastly increasing the density of fibers in the matrix and adding many layers of material. The
drawback to this approach is the much greater pressure drop that resulted. Since the amount of
power is proportional to the amount of pressure drop to overcome, the power requirements for
the HEPA filter have often been the reason it is not as popular as it could be.
A number of articles were published dealing with the effects on radiation exposure and dose of
these new filters. For the first time, it became important to deal with ultrafine particles, because
the “unattached fraction” of the radioactive particles consists of clusters of particles smaller than
a few nanometers (nm). When the air cleaner reduces particle levels, it changes the balance
between the unattached and attached fractions. Since the unattached fraction can be breathed
deeper into the lungs, it has a higher ultimate dose. Thus the air cleaner can reduce total
exposure but does not reduce total dose as much. Since most measurement techniques were
unable to deal with ultrafine particles, new methods and equipment needed to be developed, as
outlined by Hopke and others in a series of articles.
A new wave of articles dealing with more difficult allergies than hay fever or pollen began in the
1980s. Allergies to cats, dogs, dust mites, and cockroaches were recognized at this time, and
asthma began increase in prevalence and severity. The authors of these articles recognized the
importance of
a) guarding against the placebo effect,
b) running single-blind or double-blind studies to preserve objectivity,
c) using a control group with no treatment or else a crossover design in which all persons receive
treatment or no treatment first (randomly selected) and then the other of the two choices (thus
each person is his own control), and
29
d) treating results statistically with tests to determine significance.
This new wave of articles began in about 1980 and has continued to date. As it became clear that
asthma was far more complicated and resistant to treatment than the hay fever and pollen
allergies of earlier years, it was recognized that a multifactorial strategy would need to be
developed. This strategy included such things as instruction on better cleaning techniques,
HEPA vacuum cleaners, HEPA air cleaners, impermeable bedding, and pest removal techniques.
The largest and most complete of these studies eventually resulted in a clear indication of
benefits outweighing the cost, even though the cost was high (>$1000 per household).
There has also been a focus on the possible benefits of negative ions, at first according to a belief
on the part of some that negative ions had a beneficial effect on mood. This idea has not been
generally accepted, although there are still proponents. A second approach has been to consider
the effect of negative ions on particle removal. Several studies using quite powerful ion
generators have showed reasonable removal capabilities. However, these powerful ion
generators are not acceptable for residential use, partly because of undesirable effects on static
electricity in the home and partly because of generating ozone at an unacceptable rate.
Finally, there was also a period when ozone generators were sold in the belief that ozone acted to
kill bacteria and viruses as well as having beneficial effect on mood. However, the adverse
health effects of ozone have been well documented, and there is general recognition that ozone
generators are not desirable. California has banned the sale of appliances that can increase the
level of ozone in homes to 50 ppb.
There is no question that some air cleaners can perform a valuable service in lowering particle
levels in homes. Fortunately, there are three important sources of objective information that
homeowners can use to select suitable air cleaners—the AHAM and ConsumerReports.org
Websites described above, and the newest ASHRAE ratings of filters (the MERV scale described
above). However, there is one important gap in our knowledge concerning whole-house air
cleaners: the quality of the installation process. There is evidence that faulty installation can
sharply reduce the effectiveness of a whole-house air cleaner. Therefore selection of an installer
must be done with great care.
30
Appendix A. Measuring efficiency and effectiveness
The theory of filtration effectiveness has recently been presented by Nazaroff (2000). The
following discussion follows that presentation closely.
We first define a single-pass efficiency as the fraction of particles removed when air passes
through a filter. Assuming we measure a particle concentration immediately upstream and
downstream of the filter, the single-pass efficiency is:
up down
sp up
CC
C
ε
=
[1]
If the total air flow per unit time through the filter is F, then the rate of delivery of “clean air”
(Clean Air Delivery Rate, or CADR) is
sp
CADR F
ε
=
[2]
The CADR is a crucial ingredient in determining the effectiveness of portable air cleaners.
However, it is not the only ingredient. There are other considerations in determining the total
effectiveness E of air cleaners, by which we mean the ability to reduce the average concentration
in a room from an initial equilibrium concentration C0 to a final equilibrium concentration Cf:
0
0
f
CC
EC
=
[3]
The effectiveness ranges from 0 to 1, with 1 standing for perfect cleaning of the air.
The general equation governing indoor air concentrations as a function of outdoor air levels and
indoor sources is called the mass balance equation. Although the equation can be complicated if
all processes are considered (Nazaroff and Cass, 1989), for our purposes we can consider only
five major processes: infiltration (particles entering from outdoors), exfiltration (particles leaving
the house), deposition (particles depositing on surfaces), filtration (particles removed by an air
cleaner), and generation (particles created by indoor sources). The differential form of the mass
balance equation can then be written as the sum of these 5 processes:
in out in in in
dC
dm V PQC QC kVC CADRC S
dt dt
= −− − +
[4]
31
where
m = mass of all airborne particles in the volume V
V = volume of space considered (e.g., a room or an entire residence)
Cin = concentration indoors
P = penetration factor (a dimensionless quantity between 0 and 1 describing the fraction of
outdoor airborne particles able to penetrate the building envelope)
Q = the air flow rate entering the building
Cout = concentration outdoors
k = deposition rate
S = source generation rate
It should be noted that this equation rests on the well-mixed assumption: that is, perfect
instantaneous mixing of the particles throughout the entire volume such that the concentration
Cin is identical at every point. Although this seems to be a stringent assumption, and is not true
when there are rapid changes of the source generation term, it is surprisingly valid for many
situations.
Another aspect of this equation is that parameters such as the penetration coefficient, deposition
rate, and generation rate depend strongly on particle size. Therefore the equation applies to
particles of any size, but the parameter values must be changed for each size category
considered.
Since the outdoor concentration, the air flow rate, and the source generation rate are generally
unknown functions of time, the differential equation cannot be solved for the general case.
However, we can consider several widely applicable cases with simple solutions.
Steady-state solution
In this case, the outdoor concentration is constant over time, as are the airflow entering the
building, the source generation rate, the penetration factor, and the deposition rate. The resulting
indoor concentration C0 before turning on the air cleaner is
0out
C PQ S
CQ kV
+
=+
[5]
32
After turning on the air cleaner (and waiting for a sufficient length of time for the unit to pass
enough air through it to fully clean the air), the final indoor air concentration Cf is
out
fC PQ S
CQ kV CADR
+
=++
[6]
The effectiveness of the air cleaner is then given (after some tedious algebra) by
CADR
ECADR Q kV
=++
[7]
From this equation, one can see that the effectiveness is greater when CADR increases. Also, if
one were to tighten up the house (i.e., reduce the airflow Q), the effectiveness is increased. It is
interesting to see that the source term S has no effect on the effectiveness of the air cleaner.
To help familiarize ourselves with the practical meaning of this equation, we can consider an
example:
Suppose first of all that no indoor source is active. Then the indoor-outdoor ratio before the air
cleaner is turned on is given by
0
out
CPQ
C Q kV
=+
[8]
To remove the size of the room or house from this equation, divide top and bottom of the
equation by the house volume V:
0
out
CPa
C ak
=+
[9]
where a is the air exchange rate: Q/V. The air exchange rate is the number of house volumes of
air entering the house per unit time. Usually the air exchange rate is measured in air changes per
hour (ach) or inverse hours (h-1). Several thousand measurements of air change rate have been
made in US homes, and studies show that the rates may vary from about 0.1 h-1 for a very tight
house to about 2 h-1 for a house with windows wide open, with a typical value in the
neighborhood of 0.5-0.75 h-1. Recent measurements in Canadian homes suggest rather tight
homes in general, with typical values around 0.2 h-1 (Wheeler et al., unpublished)
33
The indoor-outdoor ratio in equation [9] is called the infiltration factor. It is a crucial descriptor
of the penetration of outdoor air particles into a home. If the air exchange rate is the average rate
over a year for the home, then the infiltration factor tells us what percent of the outdoor air
particles, on average, will penetrate the home. A recent study of 37 North Carolina homes
showed that annual average infiltration factors in this one small area ranged from about 0.27 to
about 0.81. That is, the amount of outdoor air particles entering those homes varied by a factor
of 3. Since epidemiological studies relating outdoor air concentrations to health effects assume
identical exposures for a given outdoor air concentration, we can see that actual exposures to
outdoor air will be widely different for persons living in a tight vs. loose home, and thus there
will be considerable misclassification of subjects in these studies.
Several studies of human exposure and indoor air quality have shown that a typical infiltration
factor for particle mass is on the order of 0.5-0.6—that is, about half of outdoor air particles
remain airborne after penetrating the home envelope. By insulating the house, adding storm
windows, etc., this fraction can be reduced, but not eliminated. (If the air exchange rate were
reduced to zero, we would suffocate!)
In fact, many studies have shown that a certain minimum air exchange rate is required for health.
This rate has been set at about 0.35 h-1 in ASHRAE Standard 62 (ASHRAE 2004). Since new
homes are often designed to be energy efficient, having tight construction with low air change
rates on the order of 0.1 h-1, there may be a need for additional ventilation to assure adequate
fresh air for breathing.
The other parameters entering into the infiltration factor are the penetration coefficient P and the
deposition rate k. The penetration coefficient is particularly difficult to measure, and actual
values in existing homes are not known well. One large study of 178 California homes indicated
that the penetration factor for inhalable particles (< 10 μm in diameter) was unity (Őzkaynak et
al., 1996). This is a somewhat surprising result at first, since one imagines that most particles
will bang up against the house walls. However, these particles are extremely small, invisible in
fact, and follow the streamlines of the air as it enters the house through windows, door openings,
electrical and plumbing entries, and cracks. To a 10-μm particle, a crack the width of a human
hair (100 μm) looks like a vast open area that the particle can easily traverse. Smaller particles
have even easier access, until we reach the smallest (ultrafine) sizes, where Brownian motion
34
comes into play, and the particles are tossed about by molecular collisions and can get thrown
into the sides of the crack before they get through it.
The deposition rate k is only slightly easier to measure than the penetration coefficient, and is
also not well known in a practical sense. The same California study (Ozkaynak 1996) resulted in
an estimate for k of 0.39 (+ 0.16) h-1 for fine particles (<2.5 μm) and 0.65 (+ 0.28) h-1 for
inhalable particles (<10 μm).
Putting these estimates together, (say, P = 1, a = 0.5, k = 0.4) we can see that a typical infiltration
factor for fine particles might be (1)(0.5)/(0.5+0.4) = 5/9 = 0.55. This was in fact close to the
infiltration factors of 0.55 to 0.61 found for three PM10 studies (Ott et al., 2000).
With these values for a and k we can now interpret the fundamental equation [7] for the
effectiveness of an air cleaner. The average volume of a US home around 2000 was more than
350 cubic meters (m3). For an air change rate of 0.5 h-1, this translates to an air flow rate Q of
175 m3/h. Then the effectiveness of an air cleaner in cleaning an entire home would be given by
175 140
CADR CADR
ECADR Q kV CADR
= =
++ + +
[10]
To achieve an effectiveness of 50%, we can see that the CADR must be 315 m3/h. To get to an
increased effectiveness of, say, 2/3 (67%), the CADR would have to double to 630 m3/h. This
example shows that attempts to increase effectiveness run into a steeply increasing CADR
requirement. In fact, CADRs above 800 m3/h are not generally found in existing portable air
cleaners (The AHAM list cuts off at 450 cfm, or 765 m3/h). Therefore for homes of average size
and larger, achieving an effectiveness better than 50% would require either multiple portable air
cleaners or else an efficient in-duct air cleaner.
Short-term indoor source (smoking, cooking)
The second case we will consider is the common situation of a short-term indoor source, such as
baking a potato. (Both electric and gas stoves emit very large numbers of ultrafine particles
from the stovetop or oven.) In this case, a solution of the differential equation can be found by
assuming a constant rate of production while the source is on, followed by no emission when it is
off. The resulting concentration takes the form of a “shark fin”, with a sharp initial rise followed
by a slowing increase and then a sharp initial decrease that also then slows down as it approaches
35
zero (Figure A-1). The solution can be plotted for the two cases with the air cleaner off and on.
Then the difference will show the effect of the air cleaner. We can see that during the initial
moments, the air cleaner provides no help at all. This is because the particles need to pass
through the air cleaner before reaching the person, and when the person is close to the source,
this does not happen. However, it can be shown that the air cleaner will reduce the average
particle concentration by exactly the same amount as in the steady-state case.
Figure A-1. Particle concentration during and after an indoor source is on for one houreffect of an air
cleaner with an effectiveness of 50%. The effectiveness is less than 50% while the source is on, but better than
50% after an hour or so, so that the average effectiveness is 50%.
0
1
2
3
4
5
6
7
0 0.5 1 1.5 2 2.5
Concentration (arbitrary units)
Time (hours)
Air cleaner
No air cleaner
36
Appendix B. Testing and Ranking Filters
For many years, the standard method of testing filters in the US was Standard 52 (later 52.1)
developed by ASHRAE. This method employs a standardized mixture of particles and a
standardized measure of the effect of the filter. The efficiency of the filter is estimated by
calculating the mass of particles encountering the filter and comparing to the mass collected
downstream. The resulting ratio is transformed into an efficiency rating in percent—for
example, a 65% filter would be expected to collect about 65% of the total mass of particles
impinging on the filter.
Method 52.1 was recognized to have several defects. Since most of the mass of the particles is
contained in the larger (nonrespirable) particles, the test results overestimated the effect of the
filter on respirable particles. Also, the standardized mixture contained about 15% black carbon
(soot), perhaps 5 times as much as is normally found in ambient air. Since black carbon is highly
conductive, testing ESPs with this mixture was impossible since the particles quickly short out
the ESP. Also, the test was unable to estimate accurately the effect of loading the filter over
time.
Therefore ASHRAE contracted with Research Triangle Institute to develop an improved test.
RTI built a testing system and experimented with different mixtures of particles for suitability in
a standard test (Ensor 1988a,b, 1991, 1997; Hanley et al., 1990, 1993a,b, 1994, 1995a,b, 1999,
2000; Hanley 2001, 2002; Hanley and Owen, 2003; Owen et al., 1992 a,b) . One innovation was
to employ monitors capable of measuring multiple particle sizes, to determine efficiency as a
function of particle size. Instead of a single number characterizing a filter (such as a 65%
ASHRAE rating), this would result in multiple efficiencies for different size particles for each
filter tested. A reasonable choice was then to rank the filter by the minimum efficiency observed
for some particle size category. Figure B-1 shows the results of the new test on several filters
with their ASHRAE ratings. As can be seen, all the filters showed a characteristic “U”-shaped
curve, with minimum efficiencies occurring near the 0.3 μm size range, and improved
efficiencies for particles larger and smaller than that. (Smaller particles have increased Brownian
random motions and are more likely to collide with the filter elements; larger particles have more
inertia and cannot follow the air streamlines and therefore collide with the filter elements more
readily.)
37
Figure B-1. Size-resolved efficiencies of filters with a range of ASHRAE Dust Spot
Efficiency ratings (Hanley et al., 1994).
This test eventually achieved the status of an official standard test (Method 52.2). Since the
particle mixture employed had much smaller black carbon content, it was suitable for testing
ESPs as well as other filters. There was also a new procedure developed of loading filters to
simulate extended use. A new system of ranking filters was also developed, based on the
minimum efficiencies established by Method 52.2. These rankings are called Minimum
Efficiency Rating Values (MERV) and range from MERV-1 to MERV-20 in order of increasing
efficiency.
However, some of the other deficiencies, such as not testing long-term efficiency, or actual real-
world effectiveness, still remain. Research is ongoing to fill some of these gaps. For example,
testing the effectiveness and lifetime of the electric charge on electret filters is being
investigated. To determine the effectiveness of the electric charge itself, as distinct from the
effectiveness due to the mechanical interception provided by the fibers, it is necessary to
somehow remove the electric charge (which is designed to be permanent or at least
semipermanent) from the filter for testing while not affecting the characteristics of the uncharged
fibers. Then it is necessary to see how the electric charge is reduced as a function of time and
the characteristics (composition, electrical distribution, etc.) of the dust loadings.
38
As another example, it has recently been found that the decline in efficiency over time observed
in electrostatic precipitators is not so much because of the dust deposited on the collector plates,
but rather silicon compounds deposited on the corona wires. Therefore a proper test of the ESPs
would involve exposure to silicon vapor in the test chamber to determine the rate of decline of
efficiency, as well as the proper mode and ease of cleaning the wires. (The source of silicon
vapor in homes is also a subject for further research—apparently several cosmetic preparations
contain silicon.)
International standard methods of ranking filters also exist. These are based on somewhat
different tests that are standardized for one country (e.g., Britain) or for several allied countries
(Europe). The European rankings run from EU-1 to EU-8—most filters used in European
buildings are EU-7 or EU-8. The European test comparable to ASHRAE Standards 52.1 and
52.2 is known as EN779 (1993).
Increased attention has been paid to protecting buildings from biological or chemical attack.
Because particle behavior in air is governed almost entirely by size, viruses, bacteria, and pollen
will behave very much like nonliving particles of the same size. For example, most pollen grains
are > 5 μm and are easily trapped by even the least efficient filters. A test for effectiveness
against biological aerosols, based on determining the viability of those aerosols penetrating the
filter, has been developed, again at RTI (Foarde et al., 1999a,b). However, no accepted standard
test for biological aerosols has been established.
After the anthrax attack in the US in 2001, the US Post Office sponsored at least one study
testing the effectiveness of the filtration system at three of the processing centers (Martin et al.,
2006). All three had identical high-efficiency filters (MERV-14 followed by a HEPA filter).
However, only two achieved the 99.97% or better efficiency required for a HEPA filter. The
filters were reinstalled with attention paid to blocking bypass leaks, and were brought up to
proper performance in the next test. (One of the three buildings also tested a new filter system at
that time, and the new system also failed the first test but passed the second after repairs.) This
experience underlines the need to consider installation as a serious variable possibly affecting
efficiency even before the filter system comes on line.
With the increasing importance of ultrafine particles, a question arises of how efficient filters
will be for the full range of ultrafines from 1-100 nm. The tests of Hanley et al., (1994) stopped
at 10 nm (see Figure B-1) because that was the limit of the instrumentation available. Some
theoretical and experimental studies have indicated that perhaps the efficiency does not continue
to improve as sizes decrease from 10 nm due to possible new processes (“thermal rebound”)
coming into play (Ichitsubo et al., 1996; Wang and Kasper 1991). However, a recent study by
Kim et al., (2008) shows consistent monotonic increase in efficiency down to the lowest size (3
nm) studied. Therefore it is expected that all ultrafines will be more efficiently filtered than
larger submicron particles by all mechanical filters.
39
References
Abraham, J. L., G. Siwinski, and A. Hunt. 2002. Ultrafine particulate exposures in indoor,
outdoor, personal and mobile environments: Effects of diesel, traffic, pottery kiln, cooking and
HEPA filtration on micro-environmental particle number concentration. Ann Occup Hyg 46
Suppl. 1: 406-11.
Abraham, M. E. 1999. Microanalysis of indoor aerosols and the impact of a compact high-
efficiency particulate Air (HEPA) filter system. Indoor Air 9(1): 33-40.
Agranovski, I. E., Braddock, R.D., and Myojo, T. 1999. Removal of aerosols by bubbling
through porous media. Aerosol Sci Tech 31(4): 249-57.
Agranovski, I. E., Braddock, R.D., and Myojo, T. 2001. Comparative study of the performance
of nine filters utilized in filtration of aerosols by bubbling. Aerosol Sci Tech 35(4): 852-59.
Agranovski, I. E., Huang, R., Pyankov, O.V., Altman, I.S., and Grinshpun S.A. 2006.
Enhancement of the performance of low-efficiency HVAC filters due to continuous unipolar ion
emission. Aerosol Sci Tech 40(11): 963-68.
Agranovski, V. 1999. evaluation of electrostatic precipitator performance for submicron particle
size range. Indoor Air 99: Proceedings of the 8th International Conference on Indoor Air Quality
and Climate. Edinburgh, Scotland 8-13 August 1999. 2: 653-658.
AHAM. 1988. American national standard method for measuring performance of portable
household electric cord-connected room air cleaners. ANSI/AHAM AC-1-1988. Chicago, IL:
Association of Home Appliance Manufacturers.
ALA. 1997. Residential air cleaning devices: types, effectiveness, and health impact. American
Lung Association, Washington, DC.
Alderman SL, Nagel BA, Parsons MS, Rogers DM, Hogancamp KU, Waggoner CA. 2006.
Evaluation of glass fiber HEPA filters as a function of media velocity. Mississippi State
University, Institute for Clean Energy Technology, 205 Research Boulevard, Starkville, MS p.
511-518.
Alford G. 2005. The buzz on room air cleaners: How effective are they for management of
allergies and asthma? Asthma Magazine 10(1):27-9.
American Thoracic Society. 1990. Environmental controls and lung disease. Am Rev of Resp
Dis 142:915-939.
40
American Thoracic Society. 1997. Achieving healthy indoor air: report of the ATS workshop.
1997. Santa Fe, New Mexico, November 16–19, 1995. American Journal of Respiratory and
Critical Care Medicine 156: S33-S64.
Antonicelli L, Bilo MB, Pucci S, Schou C, Bonifazi F. 1991. Efficacy of an air-cleaning device
equipped with a high efficiency particulate air filter in house dust mite respiratory allergy.
Allergy 46:594-600.
Asgharian, Bahman, and Yung Sung Cheng. 2002. The filtration of fibrous aerosols. Aerosol
Science and Technology 36, no. 1: 10-17.
ASHRAE 1992. Standard 52.1 – 1992. Gravimetric and dust-spot procedures for testing air-
cleaning devices used in general ventilation for removing particulate matter. Atlanta, GA:
American Society of Heating, Refrigerating, and Air-Conditioning Engineers.
ASHRAE 2007. Standard 52.2 – 2007. Method of testing general ventilation air-cleaning devices
for removal efficiency by particle size. Atlanta, GA: American Society of Heating, Refrigerating,
and Air-Conditioning Engineers.
ASHRAE 2004. Standard 62.1 – 2004. Ventilation for acceptable indoor air quality. Atlanta,
GA: American Society of Heating, Refrigerating, and Air-Conditioning Engineers.
ASHRAE 1996. 1996 ASHRAE Handbook, HVAC Systems and Equipment. American Society
of Heating, Refrigerating, and Air Conditioning Engineers, Atlanta, GA.
Barrett LW, Rousseau AD. 1998. Aerosol loading performance of electret filter media. Am Ind
Hyg Assoc J 59:532–539.
Bascom R, Fitzgerald TK, Kesavanathan J, Swift DL. 1996. A portable air cleaner partially
reduces the upper respiratory response to sidestream tobacco smoke. Appl Occup Environ Hyg
11(6):553-559.
Batterman, S., Burge, H. 1995. HVAC systems as emission sources affecting indoor air quality: a
critical review. International Journal of Heating, Ventilating, Air-Conditioning and
Refrigerating Research, 1:61-80.
Batterman, S., Godwin, C., and Jia, C. 2005. Long duration tests of room air filters in cigarette
smokers’ homes. Environ Sci Tech 39:7260-7268.
Baumgartner, H.P. and Löffler, F. 1986 The collection performance of electrets filters in the
particle size range 10 nm10 μm, J. Aerosol Sci., 17, 438–445.
Beck, I. 1932. The treatment of hay fever and pollen asthma with pollen free air. MJ& Rec 136:
90 (Aug).
41
Bekö , G., Clausen, G., Weschler, C.J. 2006. Further studies of oxidation processes on filter
surfaces: evidence of oxidation products and the influence of time in service. Atmos Environ 41:
5202-12.
Bekö , G., Halás, O., Clausen, G., Weschler, C.J. 2006. Initial studies of oxidation processes on
filter surfaces and their impact on perceived air quality. Indoor Air 16, 56–64.
Bekö , G., Tamas, G., Halás, O., Clausen, G., Weschler, C. 2005. Ultra-fine particles as
indicators of the generation of oxidized products on the surface of used air filters. Proceedings of
Indoor Air’05, the 10th International Conference on Indoor Air Quality and Climate II, Beijing,
China, pp. 1521–1525.
Bémer, D., and Callé, S. 2000. evolution of the efficiency and pressure drop of a filter media
with loading. Aerosol Science and Technology 33, no. 5: 427-39.
Bernstein, J. A., L. Levin, M. S. Crandall, A. Perez, and B. Lanphear. 2005. A pilot study to
investigate the effects of combined dehumidification and HEPA filtration on dew point and
airborne mold spore counts in day care centers. Indoor Air 15, no. 6: 402-7.
Bigu, J 1983. On the effect of a negative ion generator and a mixing fan on the plate-out of radon
decay products in a radon box. Health Phys 44:259-266.
Berry D, Mainelis G, Fennell D. 2007. Effect of an ionic air cleaner on indoor/outdoor particle
ratios in a residential environment. Aerosol Science and Technology 41(3):315-28.
Bjornsdottir US Jakobinudottir S. Runarsdottir B., and Juliusson S. 2003. The effect of reducing
levels of cat allergen (Fel d 1) on clinical symptoms in patients with cat allergy. Annals of
Allergy, Asthma, and Immunoology 91(2):189-194.
Boeniger MF. 1995. Use of ozone generating devices to improve indoor air quality. Am Ind Hyg
Assoc J 56:590-598.
Boleman WT. 2000. A look at indoor allergen environmental control. Pediatric Asthma, Allergy
and Immunology 14(4):301-5.
BOMA 2002. Emergency preparedness. Washington, DC: Building Owners and Managers
Association International, p.170.
Boquete M, Cortada Macias JM, Gonzalez JJG, Ibero M, Cocera CM. 1997 Effectiveness of air
purification with HEPA filter in domestic environmental control. Eficacia de unpurificador de
aire con filtro HEPA en el control ambinetal domicilario. Revista Espanola de Alergologia e
Inmunologia Clinica 12(4):258-64.
Bowler, SD Mitchell CA Miles J. 1985. House dust control and asthma: a placebo-controlled
trial of cleaning air filtration. Ann Allergy 55:498.
42
Bowser, D. and Fugler, D., 2002. Indoor ozone and electronic air cleaners. Proceedings, 9th
International Conference on Indoor Air Quality and Climate, Monterey, CA June 30-July 5,
2002. Vol. II, 670-674.
Bowser, D., Fugler, D., Salares, V. 1999. The effects of improved residential filtration on
particulate exposure; Proceedings of Indoor Air 99: Edinburgh, Scotland, August 8-13, 1999.
Bräuner, E.V., Forchhammer, L., Møller, P., Simonsen, J., Glasius, M., Wåhlin, P., Raaschou-
Nielsen, O., Loft, S. 2007. Exposure to ultrafine particles from ambient air and oxidative stress–
induced DNA damage. Environ. Health Persp., 115:1177-1182.
Bräuner, E.V., Forchhammer, L., Møller, P., Barregard, L.,Gunnarsen, L., Afshari, A., Wåhlin,
P., Glasius, M., Dragsted, L.O., Basu, S., Raaschou-Nielsen, O., Loft, S. 2008. Indoor particles
affect vascular function in the aged: an air filtration–based intervention study. Am. J. Resp. Crit.
Care Med. 177: 419-25.
Brehler R, tting B, Biel K, Luger T. 2003. Positive effects of a fresh air filtration system on
hay fever symptoms. International Archives of Allergy and Immunology 130(1):60-5.
Britigan, N., Alshawa, A., Nizkorodov, S.A. 2006. Quantification of ozone levels in indoor
environments generated by ionization and ozonolysis air purifiers. Journal of the Air & Waste
Management Association 56, 601-610.
Brown RC, Wake D, Gray R, Blackford DB, Bostock GJ [1988]. Effect of industrial aerosols on
the performance of electrically charged filter material. Ann Occup Hyg 32(3):271–294.
Brown, S.K.; Sim, M.R.; Abramson, M.J.; Gray, C.N. Indoor Air 1994 (4):123-134.
Brown, S.K. 1999. Assessing the performance of room air cleaners using a room environmental
chamber. In: Proceedings of Indoor Air ’99: the 8th International Conference on Indoor Air
quality and Climate. August 8-13, Edinburgh, Scotland. Vol. 2, pp. 647-652. International
Society of Indoor Air Quality, Espoo, Finland.
Burge HA. and Ko G. 2004. Performance of a silent electrostatic air cleaner for eliminating
culturable aerosols, J Allergy and Clinical Immunology. 113 (2, Supplement 1): S224-S224.
Burr ML, St. Leger AS, Neale E. 1976. Anti-mite measures in mite-sensitive adult asthma. A
controlled trial. Lancet 1976 1:333-335.
Burroughs, H.E. Kinzer, K.E., Gonsoulin, T. 1998. Improved filtration and the residential
environment: an intervention research project to determine the relevancy and efficacy of
particulate filtration in improving air quality conditions in residences. IAQ and Energy 98: Using
ASHRAE Standards 62 and 90.1 Conference. Louisiana.
Burroughs H. E., Kinzer K.E. 1998. Improved filtration in residential environments. ASHRAE
Journal, 40 (6), 47-51.
43
Burton NC, Grinshpun SA, Reponen T. 2007. Physical collection efficiency of filter materials
for bacteria and viruses. Ann Occup Hyg 51(2):143-51.
Byeon, JH, Hwang J, Park JH, Yoon KY, Ko BJ and Ji JH. 2006. Collection of submicron
particles by an electrostatic precipitator using a dielectric barrier discharge. J Aerosol Sci
37:1618-1628.
California Air Resources Board. 2007. Survey of the use of ozone generating air cleaners by the
California public. Thomas Piazza. University of California, Berkeley, 05-301.
California EPA 1997. Health effects of exposure to environmental tobacco smoke, final report
September 1997, California Environmental Protection Agency, Sacramento, CA.
Calizaya F, Mousset-Jones P. 1995. Use of HEPA filters to control ionizing radiation. Mackay
Sch of Mines, Reno, United States. 628-30.
Carter MC, Pewrzanowski MS Raymond A., and Platts-Mills, TA. 2001. Home intervention in
the treatment of asthma among inner-city children. J Allergy & Clin Immun 108(5):732-737.
Chan MY, Cheng BN. 2006. Performance evaluation of domestic ionizer type air cleaners.
Architectural Science Review 49(4):357-62.
Chen H., and Davidson J.H. 1999. Effect of silicone concentration on deposition of silicon-
dioxide in the corona discharge of electrostatic air cleaners, Proceedings of the 1999 Fall Topical
Conference, pp 203-210, American Filtration and Separations Society.
Cheng, Y.S., Lu, J.C. and Chen, T.R. 1998. Efficiency of a portable indoor air cleaner in
removing pollens and fungal spores, Aerosol Sci. Technol., 29, 92–101.
Cheong CD, Neumeister-Kemp HG, Dingle PW, Hardy GS. 2004. Intervention study of airborne
fungal spora in homes with portable HEPA filtration units. Journal of Environmental Monitoring
6(11):866-73.
Chessor E. 1998. Case studies: testing of ozone-generating air-purifying devices. Appl. Occup.
Environ. Hyg. 13(3):141-143.
Choi, K.J. 2005. Current and recent trend of HVAC filters for indoor air quality. Proceedings,
10th International Conference on Indoor Air Quality and Climate, Beijing, China, Sept. 4-9,
2005. 1228-1230.
Clausen, G. 2004. Ventilation filters and indoor air quality: a review of research from the
International Centre for Indoor Environment and Energy. Indoor Air 14, (Suppl)7: 202-7.
Clausen, G., Alm, O. and Fanger, P.O. 2002. Sensory source strength of used ventilation filters.
Proceedings, 9th International Conference on Indoor Air Quality and Climate, Monterey, CA
June 30-July 5, 2002. Vol. I, 344-348.
44
Clausen, G., Alm, O., and Fanger, P.O. 2002. The impact of air pollution from used ventilation
filters on human comfort and health. Proceedings, 9th International Conference on Indoor Air
Quality and Climate, Monterey, CA June 30-July 5, 2002. Vol. I, 338-34.
CMHC 1998. The effect of improving the home environment on asthma: a pilot study. Canada
Mortgage and Housing Corporation. Ottawa, Ontario.
CMHC 1999. Evaluation of residential furnace filters. Canada Mortgage and Housing
Corporation. Ottawa, Ontario.
CMHC 1999. Evaluation of residential furnace filters. Appendices. Canada Mortgage and
Housing Corporation. Ottawa, Ontario.
CMHC 2001. A guide to mechanical equipment for healthy indoor environments. Canada
Mortgage and Housing Corporation. Ottawa, Ontario.
CMHC 2005. Réduction générale des particules dans les maisons où les occupants souffrent de
maladies respiratoires. Canada Mortgage and Housing Corporation. Ottawa, Ontario.
CMHC 2007. Investigation of the performance of residential electronic filters in actual use.
Research Highlight Technical Series 07-117. Canada Mortgage and Housing Corporation.
Ottawa, Ontario.
Cohen, M.B. 1926. A pollen filter: preliminary report of the treatment of hay fever in rooms
made pollen free by a new filter. M. J. & Rec 123:322 (March 3) 1926.
Cohen, M.B. 1927a. The prophylaxis and treatment of hay-fever and asthma by means of pollen
filters. Clin Med & Surg 34: 276 (April) 1927.
Cohen, M.B. 1927b. The prophylaxis and treatment of hay fever and asthma in rooms made
pollen and dust free by means of mechanical filters. J Lab & Clin Med 13: 59 (Oct) 1927.
Cohen, M.B. 1928. Further observations on the use of filtered air in the diagnosis and treatment
of allergic conditions. J Lab & Clin Med 13: 963 (July) 1928.
ConsumerReports.org. 2008. Ratings of household air cleaners.
http://www.consumerreports.org/cro/appliances/heating-cooling-and-air/air-cleaners/air-
purifiers-sub/room-air-purifiers/latest-ratings/ratings-air-purifiers.htm ; accessed March 2008.
Cooper, D.W. 1980. Mechanisms for electrostatic enhancement of fabric filter performance.
Filtration and Separation 17(6):520–523.
Criep LH and Greeen MA. 1936. Air cleaning as an aid in the treatment of hay fever and
bronchial asthma. J Allergy 7:120.
45
Croxford, B., K. W. Tham, A. Young, T. Oreszczyn1, and D. Wyon. 2000. A study of local
electrostatic filtration and main pre-filtration on airborne and surface dust levels in air-
conditioned office premises. Indoor Air 10, no. 3: 170-177.
Custovic A, Simpson A, Pahdi H, Green RM, Chapman M, Woodcock A. 1998. Distribution,
aerodynamic characteristics, and removal of the major cat allergen Fel d 1 in British homes.
Thorax 53(1):33-38.
Daniell,W., Camp, J., and Horstman, S. 1991. Trial of a negative ion generator device in
remediating problems related to indoor air quality. J. Occup.Med. 6:681–7.
Darlington, A., M. Chan, D. Malloch, C. Pilger, and M. A. Dixon. 2000. The biofiltration of
indoor air: implications for air quality. Indoor Air 10, no. 1: 39-46.
Davidson J. H. and McKinney P. J. 1998. Chemical vapor deposition in the corona discharge of
electrostatic air cleaners. aerosol Science and Technology, 29:2.
De Blay F, Casel S, Colas F, Spirlet F, Pauli G. 2000. Eviction of airborne allergens for the
household environment. Revue des Maladies Respiratoires 17(1):29-39.
De Blay F, Colas F, Richard MC, et al. 1997. Air cleaners and airborne allergens. Journal of
Investigational Allergology and Clinical Immunology 7(5):335-7.
De Blay, F., Chapman, M.D., and Platts-Mills, TAE. 1991. Airborne cat allergen (Fel d 1)
environmental control with the cat in situ. Am Rev Respir Dis 143:1334-1339.
De Koster JA, Thorne PS. 1995. Bioaerosol concentrations in noncomplaint, complaint, and
intervention homes in the Midwest. American Industrial Hygiene Association Journal 56(6):573-
80.
Dee SA, Deen J, Cano JP, Batista L, Pijoan C. 2006. Further evaluation of alternative air-
filtration systems for reducing the transmission of Porcine reproductive and respiratory
syndrome virus by aerosol. Can J Vet Res 70(3):168-75.
Demasi J, Mauriello P, Georgitis J, Davis G, Reisman R. 1998. Double-blind study of the
effectiveness of a high-efficiency particulate air hepa filter in patients with perennial allergic
rhinitis and asthma. Forty-fourth annual meeting of the American Academy of Allergy and
Immunology, Anaheim, California, USA, March 11-16, 1988, p. 323.
Eggleston PA, Butz A, Rand C, Curtin-Brosnan J, Kanchanaraksa S, Swartz L, et al. 2005. Home
environmental intervention in inner-city asthma: A randomized controlled clinical trial. Annals
of Allergy, Asthma and Immunology 95(6):518-24.
Emenius, G., Egmar, A.C. and Wickman, M. 1998. Mechanical ventilation protects one-storey
single-dwelling houses against increased air humidity, domestic mite allergens and indoor
pollutants in a cold climate region, Clin. Exp. Allergy, 28:1389–1396.
46
Emenius, G., Svartengren, M., Korsgaard, J., Nordvall, L., Pershagen, G. and Wickman, M.
(2004) Building characteristics, indoor air quality and recurrent wheezing in very young
children(BAMSE), Indoor Air, 14, 34–42.
Emmerich, S.J. and Nabinger, S.J. 2001. Measurement and simulation of the IAQ impact of
particle air cleaners in a single-zone building, ASHRAE HVAC & R Research Journal, 7, 223–
244.
EN 779:1993. Particulate air filters for general ventilation - Requirements, testing, marking.
CEN European Committee for Standardization, Brussels 1993, 37 pages.
Engelhart S, Exner M. 2002. Air-cleaning devices and indoor allergens. Allergologie 25(3):147-
56.
Engelhart S., Hanfland J., Glasmacher A., Krizek L., Schmidt-Wolf IG. and Exner M. 2003.
Impact of portable air filtration units on exposure of haematology-oncology patients to airborne
Aspergillus fumigatus spores under field conditions, The Journal of Hospital Infection. 54 (4):
300-304.
Engvall K, Norrby C, Norback D. 2003. Ocular, nasal, dermal and respiratory symptoms in
relation to heating, ventilation, energy conservation, and reconstruction of older multi-family
houses. Indoor Air 13(3):206-11.
Engvall K, Wickman P, Norback D. 2005. Sick building syndrome and perceived indoor
environment in relation to energy saving by reduced ventilation flow during heating season: a 1
year intervention study in dwellings. Indoor Air 15(2):120-6.
Ensor D S., Hanley J T. Sparks L E. 1988a. Air filter particle size efficiency testing for diameters
greater than 1 micrometer. ASHRAE Trans, 1988, vol 94, part 2, 1859-1865.
Ensor DS, Viner AS, Hanley JT, Lawless PA, Ramanathan K, Owen MK, Yamamoto T, Sparks
LE. 1988b. Air cleaner technologies for indoor air pollution. In: Engineering solutions to indoor
air problems. Proceedings of the ASHRAE conference IAQ'88, April 11-13, 1988, Atlanta, GA.
Atlanta, GA: American Society of Heating, Refrigerating and Air-conditioning Engineers, Inc.
pp.111-129.
Ensor DS, Hanley JT, Sparks LE 1991. Particle-size-dependent efficiency of air cleaners.
Washington D.C.: IAQ 1991, Healthy Buildings/IAQ, pp. 334–336.
Ensor, D.S., Hanley, J.T. 1997. Recent advances in particulate air filter testing: quality assurance
framework. Winter 1997 issue of Air Media. National Air Filtration Association.
file:///C:/Documents%20and%20Settings/lance/My%20Documents/filter%20basic%20testing%2
0Ensor%20N%20Air%20Filt%20Assoc%201999.htm . Accessed 11/11/07.
47
EPA 1999. General ventilation filters. Research Triangle Institute, Research Triangle Park, NC.
EPA Cooperative Agreement No. CR 822870-01. U.S. Environmental Protection Agency
Research Triangle Park, NC.
EUROVENT 4/9 Method of testing air filters used in general ventilation for determination of
fractional efficiency. EUROVENT Technical Secretariat, 1997, 38 pages.
EUROVENT recommendation (REC 06) January 1999. Air Filters for Better Indoor Air
Quality.
Fanger, O. P. 2006. What is IAQ? Indoor Air 16, no. 5: 328-34.
Faulkner D, Fisk WJ, Walton JT. 1996. Energy savings in cleanrooms from demand-controlled
filtration. Journal of the Institute of Environmental Sciences 39(6):21-7.
Faulkner, David, William J. Fisk, Douglas P. Sullivan, and David P. Wyon. 1999. Ventilation
efficiencies of desk-mounted task/ambient conditioning systems. Indoor Air 9, no. 4: 273-81.
Federspiel, C. C., W. J. Fisk, P. N. Price, G. Liu, D. Faulkner, D. L. Dibartolomeo, D. P.
Sullivan, and M. Lahiff. 2004. Worker performance and ventilation in a call center: analyses of
work performance data for registered nurses. Indoor Air 14, no. s8: 41-50.
Ferguson BJ.1995. Environmental controls part 1: Air cleaners. Ear Nose Throat J 74(4).
Fernandez-Caldas E, Trudeau WL, Ledford DK. 1994. Environmental control of indoor biologic
agents. Journal of Allergy and Clinical Immunology 94(2 II SUPPL.):404-12.
Fishman, D.S. 1981. Subjective comfort associated with negative air ions. Heat. & Vent. Engin.
Oct., 13-15.
Fisk WJ, Spencer RK, Grimsrud DT, Offermann FJ, Pedersen B, Sextro R. 1987. Indoor air
quality control techniques: radon, formaldehyde, combustion products. Park Ridge, NJ: Noyes
Data Corporation.
Fisk WJ, Faulkner D, Sullivan D, Mendell MJ. 2000. Particle concentrations and sizes with
normal and high efficiency air filtration in a sealed air-conditioned office building. Aerosol
Science and Technology 32(6):527-44.
Fisk WJ, Faulkner D, Palonen J, and Seppänen O. 2002. Performance and cost of particle air
filtration technologies. Indoor Air 12(4): 223-234.
Fisk WJ, Faulkner D, Palonen J, Seppänen O. 2003. Particle air filtration in HVAC supply-air
streams. HPAC Heating, Piping, Air Conditioning Engineering 75(7):24-28.
48
Foarde, K.K., Hanley, J.T., Ensor, D.S. and Roessler, P. 1999a. Development of a method for
measuring single-pass bioaerosol removal efficiencies of a room air cleaner, Aerosol Sci.
Technol., 30, 223– 234.
Foarde, K.K., Myers, E.A., Hanley, J.T., Ensor, D.S. and Roessler, P.F. 1999b. Methodology to
perform clean air delivery rate type determinations with microbiological aerosols, Aerosol Sci.
Technol., 30, 235–245.
Fox RW. 1994. Air cleaners: a review. J Allergy Clin Immunol 94:413-6.
Francis H, Fletcher G, Anthony C, Pickering C, Oldham L, Hadley E, et al. 2003. Clinical effects
of air filters in homes of asthmatic adults sensitized and exposed to pet allergens. Clin Exp
Allergy 33:101–105.
Franke, D.L., Ensor, D.S., Hanley, J.T., and Sparks, L.E. 2002. Testing indoor air products: one
approach to developing widely accepted protocols. Proceedings, 9th International Conference on
Indoor Air Quality and Climate, Monterey, CA June 30-July 5, 2002. Vol. III, 172-177.
Friedlander S. and Friedlander, AS. 1954. Effectiveness of a portable electrostatic precipitator in
elimination of environmental allergens and control of allergic symptoms. Ann Allergy 1954
12:419.
Fugler, D., Bowser, D., Kwan, W. 2000. The effects of improved residential furnace filtration on
airborne particles. ASHRAE Transactions 106: 317-326.
Fugler, D. and Bowser, D. 2002. Reducing particulate levels in houses. Proceedings, 9th
International Conference on Indoor Air Quality and Climate, Monterey, CA June 30-July 5,
2002. I:868-872.
Ginestet, A., Pugnet, D. 1997. The fractional efficiency of air filters used in general ventilation.
J Aerosol Sci 28 S1 S293-94.
Godwin, C. C. , S. A. Batterman, S. P. Sahni, and C. Y. Peng. 2003. Indoor environment quality
in dental clinics: Potential concerns from particulate matter. Am J Dent 16: 260-266.
Goel, R. 2008. Whole-house air cleaners: effect on HVAC system performance. Ashrae J 50
(3):51-59.
Goodman N and Hughes JF. 2002. The effect of corona discharge on der p I. Clin Exp Allergy
32:515-519.
Goodman N, Hughes JF. 2002. Long-range destruction of Der p 1 using experimental and
commercially available ionizers. Clinical and Experimental Allergy 32(11):1613-9.
Gore C, Custovic A. 2004. Can we prevent allergy? Allergy 59(2):151-61.
49
Gore R. 2002. Allergen avoidance: the attraction of charge. Clin Exp Allergy 32(4):483-5.
Gore RB, Bishop S, Durrell B, Curbishley L, Woodcock A, Custovic A. 2003a. Air filtration
units in homes with cats: Can they reduce personal exposure to cat allergen? Clinical and
Experimental Allergy 33(6):765-9.
Gore RB, Durrell B, Bishop S, Curbishley L, Woodcock A, Custovic A. 2003b. High-efficiency
particulate arrest-filter vacuum cleaners increase personal cat allergen exposure in homes with
cats. Journal of Allergy and Clinical Immunology 111(4):784-7.
Grabarczyk Z. 2001. Effectiveness of indoor air cleaning with corona ionizers. Journal of
Electrostatics 51-52(1-4):278-83.
Green, R., Simpson, A., Custovic, A., Faragher, B., Chapman, M. and Woodcock, A. 1999. The
effect of air filtration on airborne dog allergen, Allergy, 54, 484–488.
Grinshpun, S. A., G. Mainelis, M. Trunov, A. Adhikari, T. Reponen, and K. Willeke. 2005.
Evaluation of ionic air purifiers for reducing aerosol exposure in confined indoor spaces. Indoor
Air 15, no. 4: 235-45.
Grinshpun, S.A., Adhikari, A., Honda, T., Kim, K.Y., Toivola, M., Rao, K.S.R., Reponen, T.,
2007. Control of aerosol contaminants in indoor air: Combining the particle concentration
reduction with microbial inactivation. Environmental Science and Technology 41, 606-612.
Gustavsson, J. 1999. Can we trust air filters?
http://www.cfa.harvard.edu/~thunter/manuals/secure/trustair.html . Accessed 11/17/2007.
Gustavsson, J. 1999. How can air filters contribute to better IAQ? Filtration & Separation March
1999, 20-25.
Gustavsson, J. 2007. Air filters for better indoor air quality. Review EUROVENT-CECOMAF
April 2007 No. 96.
Hacker DW, Sparrow EM. 2005. Use of air-cleaning devices to create airborne particle-free
spaces intended to alleviate allergic rhinitis and asthma during sleep. Indoor Air 15(6):420-31.
Hanley J.T., Smith D.D., Lawless P.A., Ensor D.S., and Sparks L.E. 1990. A fundamental
evaluation of an electronic air cleaner, Proceedings of the 5th International Conference on Indoor
Air Quality and Climate - Indoor Air 90, Vol. 3, pp. 145-150, Toronto: Indoor Air ‘90.
Hanley, J.T., Smith, D.D., Ensor, D.S. 1993a. Define a fractional efficiency test method that is
compatible with particulate removal air cleaners used in general ventilation, Final Report,
ASHRAE Research Project 671-RP.
50
Hanley J.T., Ensor D.S., Smith D.D., and Sparks L.E. 1993b. Fractional aerosol filtration
efficiency of in-duct ventilation air cleaners, Proceedings of the 6th International Conference on
Indoor Air Quality and Climate - Indoor Air 93, Vol. 4, pp. 169-178, Helsinki: Indoor Air ‘93.
Hanley JT, Ensor DS, Smith DD, Sparks LE. (1994). Fractional aerosol filtration efficiency of
in-duct ventilation air cleaners. Indoor Air 4(3):169-178.
Hanley, J.T., Smith, D., Ensor, D.S. 1995a. A fractional aerosol filtration efficiency test method
for ventilation air cleaners. ASHRAE Trans., 1995, Vol.101, Part 1, Paper number 3842, 97-
110, 5 figs, 5 tabs, refs
Hanley J T., Smith D., Ensor D S. 1995b. A fractional aerosol filtration efficiency test method
for ventilation air cleaners. ASHRAE Trans., 1995, Vol.101, Part 1, Paper number 3842, 97-110.
Hanley, J.T., Ensor, D.S., Foarde, K.K. and Sparks, L.E. (1999) Effect of loading dust type on
the filtration efficiency of electrostatically charged filters. In: Proceedings of the 8th
International Conference on Indoor Air Quality and Climate, Vol. 1. Edinburgh, UK, 73–78,
Construction Research Communications Ltd, London, UK.
Hanley J. T. 2001. Development of test methods for electronic air cleaners. Presented at the
Electronic Air Cleaners Stakeholders Meeting, Environmental Technology Verification Program,
held at Research Triangle Institute, October 25, 2001. (Meeting minutes available at
http://etv.rti.org/iap/aircleaner/index.cfm ).
Hanley, JT, Franke, DL, Owen, MK, Ensor, DS, and Sparks, LE. 2002. Improved test methods
for electronic air cleaners. Proceedings, 9th International Conference on Indoor Air Quality and
Climate, Monterey, CA June 30-July 5, 2002. II:664-670.
Hanley, J.T. 2002. Improved test methods for electronic air cleaners. Fall 2002 issue of Air
Media. National Air Filtration Association.
file:///C:/Documents%20and%20Settings/lance/My%20Documents/filter%20Hanley%20Nat%2
0Air%20Filt%20Assoc%20--%20Indoor%20Air%202002.htm Accessed 11/11/07.
Hanley, J.T. and Owen, M.K. 2003. Develop a new loading dust and dust loading procedure for
the ASHRAE filter test standards 52.1 and 52.2, Final Report, ASHRAE Research Project 1190-
RP.
Hänninen, O. O., J. Palonen, J. T. Tuomisto, T. Yli-Tuomi, O. Seppanen, and M. J. Jantunen.
2005. Reduction potential of urban PM2.5 mortality risk using modern ventilation systems in
buildings. Indoor Air 15: 246-56.
Harving H, Hansen LG, Korsgaard J, Nielsen PA, Olsen OF, Romer J, et al. 1991. House dust
mite allergy and anti-mite measures in the indoor environment. Allergy 46(Suppl 11):33-8.
Harving H, Korsgaard J, Dahl R. 1993. House-dust mites and associated environmental
conditions in Danish homes. Allergy 48(2):106-9.
51
Harving H, Korsgaard J, Dahl R. 1994. House-dust mite exposure reduction in specially
designed, mechanically ventilated "healthy" homes. Allergy 49(9):713-8.
Hawkins, L.H. 1981. J Environ Psych 1:279-292.
Hawkins, L.H., Morris, L. 1984. Air ions and the Sick Building Syndrome. Proceedings of the
3rd International Conference on Indoor Air. August 20-24, 1984. Stockholm, Sweden. Vol. 3, pp.
197-201.
Health Canada 1999. Health Canada warns the public about air cleaners designed to
intentionally generate ozone (Ozone generators). Warning 1999-62, Ottawa, Ontario. April 13.
Hedge, A., Mitchell, G.E., McCarthy, J.F., and Ludwig, J. 1993. effects of a furniture-integrated
breathing-zone filtration system on indoor air quality, Sick Building Syndrome, and productivity.
Indoor Air 3, no. 4: 328-36.
Henderson DA 1998. Bioterrorism as a public health threat. Emerging Infectious Diseases
4(3):1–7.
Henderson DA 1999. The looming threat of bioterrorism. Science 283:1279–1282.
Henderson DE, Milford JB, Miller SL. 2005. Prescribed burns and wildfires in Colorado:
impacts of mitigation measures on indoor air particulate matter. Journal of the Air & Waste
Management Association 55(10):1516-26.
Hering, S. V., M. M. Lunden, T. L. Thatcher, T. W. Kirchstetter, and N. J. Brown. 2007. Using
regional data and building leakage to assess indoor concentrations of particles of outdoor origin.
Aerosol Science and Technology 41, no. 7: 639-54.
Hines, Cynthia J., Donald K. Milton, Lennart Larsson, Martin R. Petersen, William J. Fisk, and
Mark J. Mendell. 2000. Characterization and variability of endotoxin and 3-hydroxy fatty acids
in an office building during a particle intervention study. Indoor Air 10, no. 1: 2-12.
Holcátová, I., Lajčíková, A., Mathauserová, Z. 2000. Using and evaluating household air-
cleaners. Proceedings of Healthy Buildings 2000, Vol. 2, 73-78.
Holmquist L, Weiner J, Vesterberg O. 2001. Airborne birch and grass pollen allergens in street-
level shops. Indoor Air 11(4):241-5.
Hopke, P.K., Montassier, N., Wasiolek, P. 1993. Evaluation of the effectiveness of several air
cleaners for reducing the hazard from indoor radon progeny. Aerosol Sci Tech 19:268-278.
Hopke PK., Jensen B., Montassier N. and Wasiolek P. 1994. Evaluation of room air cleaners for
the reduction of exposure and dose to indoor radon progeny, Radiat Prot Dosimetry. 56 (1-4):
55-60.
52
Hopke, P.K., Jensen, B., Li, C-S, Montassier, N., Wasiolek, P., Cavallo, A.J., Gatsby, K. Scolow,
R.H., James, A.C. 1995a. Assessment of the exposure to and dose from radon decay products in
normally occupied homes. Environ Sci Tech 29(5):1359-64.
Hopke, P.K., Jensen, B., Sextro, R., Xu, M. and Nematollahi, M. 1995b. Evaluation of an
electrostatic air cleaner for particle and radon-decay product removal from indoor air, Indoor Air
An Integrated Approach, 351-354 (1995). Editors L. Morawska, N.D. Bofinger, M. Maroni.
Elsevier Science, Inc., Tarrytown, NY.
Hopke, P.K. 1996. Studies of the performance of room air cleaners and their optimal reduction
of dose from radon progeny. Final Report on Cooperative Agreement CR-820470 October 5,
1992 to December 1, 1996. US EPA, Washington, DC.
Howard Reed, C., L. A. Wallace, and S. J. Emmerich. 2003. Effect of ventilation systems and air
filters on decay rates of particles produced by indoor sources in an occupied townhouse. Atmos
Env 37: 5295-306.
Huang S-W, Kimbrough JW 1995.. Effect of air cleaners on mold count in the air and on the
symptoms of perennial rhinitis. Pediatric Asthma Allergy & Immunology 9(4):205-11.
Huang, S.W. 1993. The effects of an air cleaner in the homes of children with perennial allergic
rhinitis, Pediatr. Asthma Allergy Immunol., 7, 111–117.
Hubbard, H.F., Coleman, B.K., Sarwar, G. and Corsi, R.L. 2005. Effects of an ozone-generating
air purifier on indoor secondary particles in three residential dwellings. Indoor Air 15, 432-444.
Humphreys MP. 1987. Performance testing of residential indoor air cleaning devices. Presented
at the 1987 EPA/APCA Symposium on Measurement of Toxic and Related Air Pollutants,
Research Triangle Park, NC, May 3-6, 1987.
Humphries, W., J. J. Madden, and M. Miceli. 1984. The effect of particle precharging on the
performance of a fabric filter collecting lead smelter dust. Aerosol Science and Technology 3, no.
4: 381-95.
Hytinnen, M., Pasanen, P. and Kallkokoski, P. 2002. VOC emissions from dusty air filters.
Proceedings, 9th International Conference on Indoor Air Quality and Climate, Monterey, CA
June 30-July 5, 2002. I:368-372.
Hyttinen, M., Pasanen, P., Salo, J., Björkroth, M., Vartiainen, M., Kalliokoski, P. 2003a.
Reactions of ozone on ventilation filters. Indoor and Built Environment 12 (3), 151–158.
Hyttinen, M., Pasanen, P., Björkroth, M., and Kalliokoski, P. 2003b. Odors and volatile organic
compounds released from ventilation filters. Atmos Environ 41: 4029-39.
Hyttinen, M., Pasanen, P., Kalliokoski, P. 2006. Removal of ozone on clean, dusty and sooty
supply air filters. Atmospheric Environment 40, 315–325.
53
Ichitsubo H., Hashimoto, T., Alonso, M., Kousaka, Y. 1996. Penetration of ultrafine particles
and ion clusters through wire screens. Aerosol Sci. Technol. 24, 119–127.
Institute of Environmental Sciences. 1986. Recommended practice for HEPA filters. IES RP-
CC-001-86. Mt. Prospect, IL: Institute of Environmental Sciences.
Iwashita, Go, and Ken-ichi Kimura. 1993. method for evaluating efficiency in removing
perceived air pollutants by air cleaners. Indoor Air 3, no. 4: 315-21.
Jaakkola, Jouni J. K., Olli P. Heinoneon, and Olli Seppanen. 1991. Mechanical ventilation in
office buildings and the Sick Building Syndrome: an experimental and epidemiological study.
Indoor Air 1, no. 2: 111-21.
Jacobs RL, Andrews CP, Jacobs FO. 1989. Hypersensitivity pneumonitis treated with an
electrostatic dust filter. Ann Intern Med 15;110(2):115-8.
Jaisinghani R A. et al 1989. Effectiveness of air cleaners using an environmental tobacco smoke
material balance model. Proceedings IAQ 89 San Diego, California, April 1989, ASHRAE, 38-
45. ISBN 0 910110 59 X,
Jamieson, S.S. and Colvile, R.N. 2005. Efficiency of portable air cleaners: a review and
evaluation with a microenvironmental approach. Proceedings, 10th International Conference on
Indoor Air Quality and Climate, Beijing, China, Sept. 4-9, 2005. 554-560.
Jamriska, M. , L. Morawska, and B. A. Clark. 2000. Effect of ventilation and filtration on
submicrometer particles in an indoor environment. Indoor Air 10: 19–26.
Jamriska, MK., Morawska, L. and Nathanson, T. 2002. Characterisation of filter performance in
relation to outdoor air quality. Proceedings, 9th International Conference on Indoor Air Quality
and Climate, Monterey, CA June 30-July 5, 2002. I:197-202.
Jamriska, M., L. Morawska, and D. S. Ensor. 2003. Control strategies for sub-micrometer
particles indoors: model study of air filtration and ventilation. Indoor Air 13, no. 2: 96-105.
Ji, JH, Gae, GN, Kang, SH, Hwang, J. 2003. Effect of particle loading on the collection
performance of an electret cabin air filter for submicron aerosols. J Aerosol Sci 34:1493-1504.
Johanson, J.H.P. 2000. Impact of room air cleaners on the indoor particle concentration.
Proceedings of Healthy Buildings 2000 2:59-60. SIY Indoor Air Information Oy, Helsinki,
Finland.
Johnson AE, Brown RC. 1998. Measurement of the performance of air cleaners against the
particulate element of Rosin-based solder flux fume. Annals of Occupational Hygiene 42(8):511-
9.
54
Kaczmarczyk, J., Zeng, Q., Melikov, A. and Fanger, P.O. 2002a. The effect of personalized
ventilation system on air quality perception, SBS symptoms, and occupant’s performance. In:
Proceedings of Indoor Air _02, Monterey, CA, 4, 1042–1047.
Kaczmarczyk, J., Zeng, Q., Melikov, A. and Fanger, P.O. 2002b. Individual control and people’s
preferences in an experiment with a personalized ventilation system, Proceedings of Roomvent
02, Copenhagen, Denmark, 57–60.
Kaczmarczyk J, Melikov A, Fanger PO. 2004. Human response to personalized ventilation and
mixing ventilation. Indoor Air 14(Suppl 8):17-29.
Kao JN, Tardos GI, Pfeffer R. 1987. Dust deposition in electrostatically enhanced fibrous filters.
IEEE Transactions on Industry Applications IA-23(3):464-473.
Kattan, M., Stearns S, Crain E, Stout J, Gergen P, Evans R, et al. 2005. Cost-effectiveness of a
home-based environmental intervention for inner-city children with asthma. J Allergy Clin
Immunol 116(5):1058–1063.
Kawabata N. and Kawato S. 1998. Removal of airborne bacteria by filtration using a composite
microporous membrane made of a pyridinium-type polymer showing strong affinity with
microbial cells, epidemiology and infection. 121 (2): 349-356.
Kawada Y., Kaneko T., Ito T. and Chang J. 2002. Simultaneous removal of aerosol particles,
NOx and SO2, from incense smokes by a DC electrostatic precipitator with dielectric barrier
discharge prechargers, Journal of Physics D - Applied Physics. 35 (16): 1961-1967.
Kawamoto S, Oshita M, Fukuoka N, Shigeta S, Aki T, Hayashi T, et al. 2006. Decrease in the
allergenicity of Japanese cedar pollen allergen by treatment with positive and negative cluster
ions. Int Arch Allergy Immunol 141(4):313-21.
Keeler, G. J.; Dvonch, T.; Yip, F.; Parker, E. A.; Israel, B. A.; Marsik, F. J.; Morishita, M.;
Barres, J. A.; Robins, T. G.; Brakefield-Caldwell, W.; Sam, M. 2002. Assessment of personal
exposures to particulate matter (PM) among children with asthma in Detroit, MI as part of
Community Action Against Asthma (CAAA). Environ. Health Perspect. 110, 2, 173-181.
Kemp, P. C., Dingle, P. and Heike G. Neumeister, H.G. 1998. Particulate matter intervention
study: a causal factor of building-related symptoms in an older building. Indoor Air 8, no. 3:
153-71.
Kemp, S.J., Kuehn, T.H., Pui D, Y.H. et al. 1995. Filter collection efficiency and growth of
microorganisms on filters loaded with outdoor air. ASHRAE Trans., Vol.101, Part 1, Paper
number 3853 (RP-625), 228-238,
Kilburn S, Lasserson TJ, McKean M. 2003. Pet allergen control measures for allergic asthma in
children and adults. The Cochrane Database Sys Rev 1:CD002989.
55
Kim, S.C., Harrington, M.S., and Pui, D.Y.H. 2008. Experimental study of nanoparticle
penetration through commercial filter media. J Nanoparticle Research (2007) 9:117–125
Kim, S., Sioutas, C, and Chang, M. 2000. Electrostatic enhancement of the collection efficiency
of stainless steel fiber filters. Aerosol Science and Technology 32, no. 3: 197-213.
King, J.G. 1973. Air for living. Respir Care 18:160.
Kinney PL, Northridge ME, Chew GL, Gronning E, Joseph E, Correa JC, et al. 2002. On the
front lines: an environmental asthma intervention in New York City. Am J Public Health
92(1):24-6.
Kinzer, KE and Moreno CR 1997. Performance comparison of residential in-duct air cleaning
devices. American Filtration Society.
Kissel, JC 1993. Potential impact of deliberately introduced ozone on indoor air quality. J
Expos Anal Environ Epidemiol 3(2):155-164.
Klepeis, Neil E., and William W. Nazaroff. 2006. Mitigating residential exposure to secondhand
tobacco smoke. Atmos Env 40: 4408-22.
Kokotti, H., Kujanpaa, L., Halonen, R., Keskikuru, T., and Reiman, M. 2002. Operation time of
the ventilation system as a cause of microbial contamination of the infiltration filter.
Proceedings, Healthy Buildings 2003, 7th International Conference, Singapore, December 7-11
2003. I:350-355.
Kooistra, JB, Pasch R, and Reed CE. 1978. The effects of air cleaners on hay fever symptoms in
air-conditioned homes. J Allergy Clin Immunol 1978 61:315.
Kort HS, Koers WJ, Van Nes AM, Young E, Vorenkamp J, Wolfs BG, et al. 1993. Clinical
improvement after unusual avoidance measures in the home of an atopic dermatitis patient.
Allergy (Cph ) 48(6):468-71.
Kowalski WJ, Bahnfleth WP, Whittam TS. Filtration of airborne microorganisms: Modeling and
prediction. Pennsylvania State Univ, University Park, United States. 1999.
Kowalski WJ, Bahnfleth WP. 2002. Airborne-microbe filtration in indoor environments. HPAC
Heating, Piping, Air Conditioning Engineering 74(1):57-69.
Kranz P. 1963. Indoor air cleaning for allergy purposes. J. Allergy 34:155.
Krieger J and Takaro T. 2008. Housing and asthma: interventions and strategies from Seattle.
AM J Public Health In press.
56
Kujundzic, E., Zander, D.A., Hernandez, M., Angenent, L.T., Henderson, D.E., and Miller, S.
2005. Effects of ceiling-mounted HEPA-UV air filters on airborne bacteria concentrations in an
indoor therapy pool building. J. Air & Waste Manage. Assoc. 55:210–218.
Kulmala, I., Taipale, A., Heinonen, K., Jalonen, T. and Makipaa, V. 2003. Development of an
advanced supply air filter. Proceedings, 9th International Conference on Indoor Air Quality and
Climate, Monterey, CA June 30-July 5, 2002.
Kulmala, M., A. Asmia , and I. Pirjola. 1999. Indoor air aerosol model: the effect of outdoor air ,
filtration and ventilation on indoor concentrations. Atmos Env 33: 2133-44.
Lam, K. S., F. S. Chan, W. Y. Fung, B. S. S. Lui, and L. W. L. Lau. 2006. Achieving 'excellent'
indoor air quality in commercial offices equipped with air-handling unit - respirable suspended
particulate. Indoor Air 16, no. 2: 86-97.
Lamb, George E. R. 1995. Use of ambient aerosols for measuring filter efficiencies. Aerosol
Science and Technology 23, no. 2: 250-252.
Lawless PA, Viver AS, Ensor DS, Sparks LE. 1990. Computations on the performance of
particle filters and electronic air cleaners. Proceedings of Indoor Air '90: Fifth International
Conference on Indoor Air Quality and Climate 3:187-192.
Lawless, P.A.; Sparks, L.E. 1984. A review of mathematical models for ESPs and comparison of
their successes, in Proceedings of Second International Conference on Electrostatic Precipitation,
Kyoto, Japan, 513-522.
Laws, C.A. 1982. Air ions in the working environment. Heat. & Vent. Engin. May, 18-20.
Lebret, E.; Boleij, J.; Brunekreef, B. 1990. home ventilation under normal living conditions. In
Indoor Air ’90: Proceedings of the 5th International Conference on Indoor Air Quality and
Climate, Toronto, Canada Vol. 4, pp 413–418.
Lee, B.U., Yermakov, M., and Grinshpun, S. A. 2004b. Unipolar ion emission enhances
respiratory protection against fine and ultrafine particles, J. Aerosol Sci. 35(11):1359–1368.
Lee, B.U., Yermakov, M., Grinshpun, S.A. 2004a. Removal of fine and ultrafine particles from
indoor air environments by unipolar ion emission. Atmospheric Environment 38, 4815-4823.
Lee, Jae-Keun, Seong-Chan Kim, Jin-Hyouk Shin, Jung-Eun Lee, Jae-Hyun Ku, and Hee-Soo
Shin. 2001. Performance evaluation of electrostatically augmented air filters coupled with a
corona precharger. Aerosol Science and Technology 35, no. 4: 785-91.
Lee JK, Ock JH, Kim SC, Noh HS, Ahn YC, Hwang YJ, et al. 2004. Design and performance
evaluation of plasma air cleaning systems for removing yellow sand dust. Korean Journal of
Chemical Engineering 21(1):177-81.
57
Lee KW, Liu BYH 1980. On the minimum efficiency and the most penetrating particle size for
fibrous filters. J Air Pollut Control Assoc 30:377–381.
Lee KW, Liu BYH 1981. Experimental study of aerosol filtration by fibrous filters. Aerosol Sci
Technol 1(1):35–46.
Lee KW, Liu BYH 1982. Theoretical study of aerosol filtration by fibrous filters. Aerosol Sci
Technol 1(2):147–162.
Lee, K.W.; Chen, H.; Gieseke, J.A. 1984. Log-normally preserving size distribution for
Brownian coagulation in the free molecule regime, Aerosol Sci. Technol. 3:53-62.
Lefcoe NM, Inculet II. 1971. Particulates in domestic premises. I. Ambient levels and central air
filtration. Arch Environ Health 22:230.
Leopold S.S. and Leopold, C.S. 1925. Bronchial asthma and allied allergic disorders.
Preliminary report of a study under controlled conditions of environment, temperature, and
humidity. JAMA 84:731.
Levetin E, Shaughnessy R, Sublette K. 1992. Portable indoor air cleaners a comparison of
cleaning technologies. Forty-Eighth Annual Meeting of the American Academy of Allergy and
Immunology, Orlando, Florida, USA, March 6-11, 1992, p. 257.
Li, D-W., Kendrick, B. 1995. Indoor aeromycota in relation to residential characteristics and
allergic symptoms. Mycopathologia 131:149-157.
Li, C.S., Hsu, C.W., Tai, M.L. 1997. Indoor pollution and Sick Building Synddrome symptoms
among workers in day-care centers. Archives of Enviromental Health 52(3):200-207.
Li, C. S., and P. K. Hopke. 1992. Air filtration and radon decay product mitigation. Indoor Air 2:
84-100.
Li W and Hopke PK 1993. Initial size distributions and hygroscopicity of indoor combustion
aerosol particles Aerosol Sci Tech 119:305-16.
Lindgren, T. , and D. Norback. 2002. Cabin air quality: indoor pollutants and climate during
intercontinental flights with and without tobacco smoking. Indoor Air 12: 263-72.
Lindgren, T., and D. Norback. 2005. Health and perception of cabin air quality among Swedish
commercial airline crew. Indoor Air 15, no. s10: 65-72.
Liu BYH, Pui DYH, Rubow KL 1983. Characteristics of air sampling filter media. In: Marple
VA, Liu BYH, eds. Aerosols in the mining and industrial work environments. Ann Arbor, MI:
Ann Arbor Science 3:989–1038.
58
Liu RT, Huza MA. 1995. Filtration and indoor air quality: a practical approach. ASHRAE
Journal 37(2):18-23.
Liu, D.-L. and Nazaroff, W. W. 2003. Particle penetration through building cracks. Aerosol
Science and Technology, Vol. 37, pp. 565-573.
Liu, D.L., Nazaroff, W.W., 2001. Modeling pollutant penetration across building envelopes.
Atmospheric Environment 35, 4451–4462.
Liu, L.M., Guo, J.F., Li, J., Sheng, L.X., 2000. The effect of wire heating and configuration on
ozone emission in a negative ion generator. Journal of Electrostatics 48, 81-91.
Liu, X., Mason, M., Krebs, K. and Sparks, L. 2004. Full-scale chamber investigation and
simulation of air freshener emissions in the presence of ozone. ES&T 38: 2802-2812.
Loo VG, Bertrand, C., Dixon, C. et al. 1996. Control of construction-associated nosocomial
aspergillosis in an antiquated hematology unit. Infect Control Hosp Epidemiol 17: 191-197.
Luczynska CM, Li Y, Chapman MD, Platts-Mills TAE. 1990. Airborne concentrations and
particle size distribution of allergen derived from domestic cats (Felis domesticus). Am Rev
Resp Dis 141:361-367.
Mahieu LM, De Dooy, JJ, Van Laer, FA, Jansens H, Leven MM. 2000. A prospective study on
factors influencing aspergillus spore load in the air during renovation works in a neonatal
intensive care unit. J Hosp Infect 45: 191-197.
Marier RL, Nelson T. 1993. A ventilation-filtration unit for respiratory isolation. Infect Control
Hosp Epidemiol 14(12):700-5.
Martin SB, Beamer BR, Moyer ES. 2006. Evaluation of a high-efficiency, filter-bank system. J
Occup Environ Hyg 3(4):204-13.
Masuda S., Hosokawa S., Tu X-L., Tsutsumi M., Ohtani T., Tsukahara T., and Matsuda N. 1993.
The performance of an integrated air purifier for control of aerosol, microbial, and odor, IEEE
Transactions on Industry Applications. 29(4): 774-780.
Mattsson, M. and Hygge, S. 2005. Effect of particulate air cleaning on perceived health and
cognitive performance in school children during pollen season. Proceedings, 10th International
Conference on Indoor Air Quality and Climate, Beijing, China, Sept. 4-9, 2005. 1111-1115.
Maus, R., and H. Umhauer. 1996. Determination of the fractional efficiencies of fibrous filter
media by optical in situ measurements. Aerosol Science and Technology 24, no. 3: 161-73.
Maus, R., and H. Umhauer. 1997. Collection efficiencies of coarse and fine dust filter media for
airborne biological particles. J Aerosol Sci 28:401-415.
59
Mayya, Y.S., Sapra, B.K., Khan, A., Sunny, F., 2004. Aerosol removal by unipolar ionization in
indoor environments. Journal of Aerosol Science 35, 923–941.
McDonald E, Cook D, Newman T, Burr ML. 2003. The benefits of residential air filters remain
uncertain for people with asthma. Evidence-Based Healthcare 7(2):102-3.
McDonald E, Cook D, Newman T, Griffith L, Cox G, Guyatt G. 2002. Effect of air filtration
systems on asthma: A systematic review of randomized trials. Chest 122(5):1535-42.
McLarnon N, Burrow G, MacLaren W, Aidoo K, Hepher M. 2003.The use of an air filtration
system in podiatry clinics. International Journal of Environmental Health Research 13(2):215-21.
Meckler M., Janssen J E. 1988. Use of air cleaners to reduce outdoor air requirements.
Proceedings ASHRAE Conference, IAQ 88, Engineering Solutions to Indoor Air Problems, 11-
13 April 1988, Atlanta, Georgia, 130-147. ISBN 0-910110-53-0
Melikov, A.K., Cermak, R. and Mayer, M. 2002. Personalized ventilation: evaluation of different
air terminal devices, Energy Build., 34, 829–836.
Melikov, A.K., Kaczmarczyk, J. and Cygan, L. 2000. Indoor air quality assessment by a
breathing thermal manikin, Proc. Roomvent, 1, 101–106.
Menzies D, Pasztor J, Nunes F, Leduc J, Chan CH. 1997. Effect of a new ventilation system on
health and well-being of office workers. Arch Environ Health 52(5):360-7.
Miles JCH, Davies BL, Algar RA, and Cliff KD. 1980. The effects of domestic air treatment
equipment on the concentration of radon-222 daughters in a sealed room. J Roy Soc Health 100:
82-85.
Miller JD 2002. Defensive filtration. ASHRAE Journal 44(12):18–23.
Miller-Leiden, S.; Lobascio, C.; Nazaroff, W.W.; Macher, J.M. 1996. Effectiveness of in-room
air filtration and dilution ventilation for tuberculosis infection control; J. Air & Waste Manage.
Assoc.46, 869-882.
Mitchell EA and Elliott RB. 1980. Controlled trial of an electrostatic precipitator in childhood
asthma. Lancet 1980 2:559.
Molk L. 1974. HEPA-filter effects of intractable asthma Ann Allergy 33:299-304.
Montassier, N., Hopke,P.K., Shi, Y. and Wasiolek, P, 1992. Evaluation of the effectiveness of
several types of air cleaners in reducing the hazards of indoor radon decay products,
Measurements of Toxic and Related Air Pollutants, A&WMA Publication VIP-25, Pittsburgh,
PA, 77-82 (1992).
60
Morawska, L. 2000. Control of particles indoors—state of the art. Proceedings of Healthy
Buildings 2000 2:9-20. SIY Indoor Air Information Oy, Helskinki, Finland.
Morawska, L., V. Agranovski, Z. Ristovski, and M. Jamriska. 2002. Effect of face velocity and
the nature of aerosol on the collection of submicrometer particles by electrostatic precipitator.
Indoor Air 12, no. 2: 129-37.
Morgan WJ, Crain EF, Gruchalla RS, O’Connor GT, Kattan M, Evans R III, et al. 2004. Results
of a home-based environmental intervention among urban children with asthma. N Engl J Med
351:1068–1080.
Morris RJ, Helm TJ, Schmid W, Hacker D. 2006. A novel air filtration delivery system improves
seasonal allergic rhinitis. Allergy and Asthma Proceedings 27(1):63-7.
Moyer ES, Commodore MA, Hayes JL, Fotta SA, Berardinelli SPJ. 2007. Real-time evaluation
of ventilation filter-bank systems. J Occup Environ Hyg 4(1):58-69.
Mullen, N., Yu, X., Zhao, P., Corsi, R.L., Siegel, J.A., 2005. Experimental characterization of
portable ion generators. Indoor Air 2005: Proceedings of the 10th International Conference on
IAQ and Climate, 2957-2961.
Muller CO, England WG. 1995. Achieving your indoor air quality goals: which filtration system
works best? ASHRAE Journal 37(2).
NAFA 1997. Installation, operation, and maintenance of air filtration systems. Washington, DC:
National Air Filtration Association.
NAFA 2001a. Guide to air filtration. Washington, DC: National Air Filtration Association.
Naguwa SM, Gershwin ME. 2001. The influence of a central vacuum system on quality life in
patients with house dust-associated allergic rhinitis. J Investig Allergol Clin Immunol 11(4):290-
4.
NAS. 1981. Indoor pollutants.: National Academy of Sciences, National Academy Press.
Washington, DC.
NAS 1993. Indoor allergens: assessing and controlling adverse health effects, Pope, A.M.,
Patterson, R., and Burge, H. editors. Committee on Health Effects of Indoor Allergens. National
Academy of Sciences, National Academy Press, Washington, D.C.
NAS 2000. Clearing the Air: Asthma and Indoor Air Exposures, Committee on Assessment of
Asthma and Indoor Air Institute of Medicine, National Academy of Sciences, National Academy
Press, Washington, DC.
NAS. 2004. Damp Indoor Spaces and Health. Institute of Medicine, National Academy of
Sciences, National Academy Press, Washington, DC.
61
National Heart, Lung, and Blood Institute. 1995. Global strategy for asthma management and
prevention, NHLBI/WHO workshop report. NIH Publication No. 96-3659A.
Nazaroff, W.W. 2000. Effectiveness of air cleaning technologies. Proceedings of Healthy
Buildings 2000 2:49-72. SIY Indoor Air Information Oy, Helsinki, Finland.
Nazaroff, W.W. and Cass, G.R. 1989. Mathematical modeling of indoor aerosol dynamics.
Environ. Sci. Tech. 23:157-166.
Nelson HS, Hirsch SR, Ohman JL, Platts-Mills TAE, Reed CE, Solomon WR. 1988.
Recommendations for the use of residential air-cleaning devices in the treatment of allergic
respiratory diseases. J Allergy Clin Immunol 82:661-9.
Nelson HS, Skufca RM. 1991. Double-blind study of suppression of indoor fungi and bacteria by
the PuriDyne biogenic air purifier. Ann Allergy 66(3):263-6.
Nelson,T, Rappaport BZ and Walker, WH. 1933. The effect of air filtration in hay fever and
pollen asthma. Further studies. JAMA 100:1385.
NIOSH 2003. Guidance for filtration and air-cleaning systems to protect building environments
from airborne chemical, biological, or radiological attacks. Department of Health and Human
Services, Centers for Disease Control and Prevention, National Institute for Occupational Safety
and Health, Atlanta, GA. DHHS (NIOSH) Publication No. 2002–139
Niu JL., Tung TCW and Burnett J. 2001. Quantification of dust removal and ozone emission of
ionizer air cleaners by chamber testing. J Electrostatics 51(1):20-24.
Niu, J., Tung, T.C.W., and Burnett, J. 2001. Ozone emission rate testing and ranking method
using environmental chamber. Atmos Environ 35:2143-51.
Nogrady SG, Furnass SB 1983. Ionisers in the management of bronchial asthma. Thorax
38:919-922.
Nordtest 1997. Electret filters: determination of the electrostatic enhancement factor of filter
media. Nordtest Method NT VVS 117. Nordtest Tekniikantie 12 FIN-02150 Espoo FINLAND.
Oberdörster G, Oberdörster E, and Oberdörster J. 2005. Nanotoxicology: an emerging discipline
evolving from studies of ultrafine particles. Environ. Health Perspect., 113:823–839.
O’Connor GT. 2005. Allergen avoidance in asthma: What do we do now? Journal of Allergy and
Clinical Immunology 116(1):26-30.
Offermann, F.J., Sextro, R.G., Fisk, W.J., Grimsrud, D.T., Nazaroff, W.W., Nero, A.V., Revzan,
K.L., Yater, J., 1985. Control of respirable particles in indoor air with portable air cleaners.
Atmospheric Environment 19, 1761-1771.
62
Offermann F J., Loiselle S A., Sextro R G. 1991. Performance comparisons of six different air
cleaners installed in a residential forced-air ventilation system. IAQ 91 - Healthy buildings,
ASHRAE Washington DC, September 4-8, 1991, 342-350.
Offermann F J., Loiselle S A., Sextro R G. 1992. Performance of air cleaners in a residential
forced air system. ASHRAE Journal, July 1992, vol.34, no.7, 51-57. ISSN-0001-2491.
Olander L, Johansson J, Johansson R. 1987. Air cleaners for tobacco smoke. In: Seifert B, et al.,
eds. Indoor air '87. Proceedings of the 4th Conference on Indoor Air Quality and Climate, West
Berlin, August 17-21, 1987. Vol. 2. Berlin: Institute for Water, Soil and Air Hygiene. pp. 39-43.
Olander L, Johansson J, Johansson R. 1988. Tobacco smoke removal with room air cleaners.
Scand J Work Environ Health 14(6):390-7.
Opal SM, Asp AA, Cannady Jr PB, Morse PL, Burton LJ, Hammer 2nd PG. 1986. Efficacy of
infection control measures during a nosocomial outbreak of disseminated aspergillosis associated
with hospital construction. J Infect Dis 153: 634-637.
Ott, W., Wallace, L. and Mage D. 2000. Predicting Particulate (PM10) Personal exposure
distributions using a random component superposition statistical model, J Air Waste Manage
Assoc 50: 1390-1406.
Owen, M. K., Ensor, D. S., and Sparks, L. E. 1992a. Airborne particle sizes and sources found in
indoor air, Atmospheric Environment 26A(12):2149 2162.
Owen, M. K., Ensor, D. S., Lawless, P. A., Hanley, J. T., and Sparks, L. E. 1992b. Relating air
cleaner efficiency to indoor air quality, Proceedings of IAQ 92 , pp. 397-402, ASHRAE,
Atlanta, GA. ISBN 0 910110 94 8.
Ozis, F., M. Singh, J. Devinny, and C. Sioutas. 2004. Removal of ultrafine and fine particulate
matter from air by a granular bed filter. J Air Waste Man Assoc 54: 935-40.
Özkaynak, H., Xue, J., Spengler, J.D., Wallace, L.A., Pellizzari, E.D. and Jenkins, P. 1996.
Personal exposure to airborne particles and metals: results from the Particle TEAM study in
Riverside, CA. J. Exposure Analysis and Environmental Epidemiology 6:57-78.
Pahdi HS, Simpson A, Custovic A, Woodcock A. 1997. The effect of high efficiency particulate
air cleaner on airborne cat allergen. Thorax 52(SUPPL. 6).
Partti-Pellinen, K., O. Marttila, A. Ahonen, O. Suominen, and T. Haahtela. 2000. Penetration of
nitrogen oxides and particles from outdoor into indoor air and removal of the pollutants through
filtration of incoming air. Indoor Air 10: 126-32.
Pejtersen, Jan, Henrik Brohus, Carl Erik Hyldgaard, Jan Bach Nielsen, Ole Valbjorn, Pernille
Hauschildt, Soren K. Kjaergaard, and Peder Wolkoff. 2001. Effect of renovating an office
building on occupants' comfort and health. Indoor Air 11, no. 1: 10-25.
63
Pejtersen, Jan. 1996. Sensory pollution and microbial contamination of ventilation filters. Indoor
Air 6, no. 4: 239-48.
Perraud, M., Nicolle, MC Chiarello, E., Tisso Guerraz F, Cetre JC Sepetjan M. 1992. Air
filtation and prevention of aspergillary pneumopathies. Nouv Rev Fr Hematol 34: 295-299.
Persily, A. 2002. The revision of standard 62: what a difference a decade makes. Proceedings, 9th
International Conference on Indoor Air Quality and Climate, Monterey, CA June 30-July 5,
2002. III:328-332.
Peshkin, M.M. & Beck, I. 1930. A new and simplified mechanical air filter in the treatment of
hay fever and pollen asthma. J Lab & Clin Med 15:643.
Phillips TJ, Bloudoff DP, Jenkins PL, Stroud KR. 1999. Ozone emissions from a "personal air
purifier". J Expo Anal Environ Epidemiol 9(6):594-601.
Pierce, W. M.; Janczewski, J. N.; Roethlisberger, B.; Pelton, M.; Kunstel, K. 1996. Effectiveness
of auxiliary air cleaners in reducing ETS components in offices. ASHRAE J. 51-57.
Pollart S, Chapman MD, Platts Mills TAE. 1988. House dust mite and dust control. Clinical
Reviews in Allergy 6(1):23-33.
Rajala M, Janka K, Graeffe G, Kulmala V. 1984. Laboratory measurements of the influence of
air treatment devices on radon daughters. In: Berglund B, Lindvall T, Sundell J, eds. Proceedings
of the 3rd International Conference on Indoor Air Quality and Climate, Stockholm, August 20-
24, 1984. Vol. 5. Stockholm: Swedish Council for Building Research. pp. 117-122.
Rappaport BZ, Nelson T and Walker WH. 1932. Effect of air filtration in hay fever and pollen
asthma. JAMA 98:1861.
Raynor, Peter C. 2002. Flow Field and Drag for Elliptical Filter Fibers. Aerosol Science and
Technology 36, no. 12: 1118-27.
Raynor, P. C. and Chae, S. J. 2003. Dust loading on electrostatically charged filters in a standard
test and a real HVAC system. Filtration and Separation, Vol. 40, pp. 35-39.
Raynor, P.C. and Chae, S.J. 2004. The long-term performance of electrically charged filters in a
ventilation system, J. Occup. Environ. Hyg., 1, 463–471.
Raynor, P. C., Kim, B.G., Ramachandran, G., STrommen, M.R., Horns, J.H. and Streifel, A.J.
2007. Collection of biological and non-biological particles by new and use filters made from
glass and electrostatically charged synthetic fibers. Indoor Air in press.
Reisman RE, Mauriello PM, Davis GB, Georgitis JW, DeMasi JM. 1990. A double-blind study
of the effectiveness of a high-efficiency particulate air (HEPA) filter in the treatment of patients
with perennial allergic rhinitis and asthma. J Allergy Clinical Immunology 85:1050-7.
64
Reisman RE. 2001. Do air cleaners make a difference in treating allergic disease in homes?
Annals of Allergy, Asthma and Immunology 87(6 Suppl. 3):41-3.
Repace JL, Seba DB, Lowrey AH, Gregory TW. 1983. Effect of negative ion generators on
ambient tobacco smoke. J Clinical Ecology 2(2): 90-94.
Rhame FS, Streifel, AJ Kersey Jr. JH, McGlave PB. 1984. Extrinsic risk factors for pneumonia
in the patient at high risk of infection. Am J Med 76:42-52.
Richardson G, Harwood DJ, Eick SA, Dobbs F, Rosén KG. 2001. Reduction of fine airborne
particulates (PM3) in a small city centre office, by altering electrostatic forces. Science of the
Total Environment 269(1-3):145-55.
Richardson MD Rennie S., Marshal, I., et al. 2000. Fungal surveillance of an open haematology
ward. J Hosp Infect 45: 288-292.
Riley, W.J., McKone, T.E., Lai, A.C.K., and Nazaroff, W.W., 2002. Indoor particulate matter of
outdoor origin: Importance of size-dependent removal mechanisms, Environmental Science and
Technology, 36, 200-207.
Rivers R D. 1988. Interpretation and use of air filter particle size efficiency data for general
ventilation applications. ASHRAE Trans, 94, part 2: 1835-1849.
Robinson TJ, Quellet AE. 1999. Filters and filtration. ASHRAE Journal 41(4):65-70.
Romay, Francisco J., Benjamin Y. H. Liu, and Soo-Jae Chae. 1998. Experimental study of
electrostatic capture mechanisms in commercial electret filters. Aerosol Science and Technology
28, no. 3: 224-34.
Roncarolo D, Mistrello G, Centanni S, Diano P, Ottoboni F, Gentili M, et al. 1997. Air cleaners
can reduce the risk of allergic sensitization. Aerobiologia 13(3):185-9.
Rosén KG, Richardson G. 1999. Would removing indoor air particulates in children's
environments reduce rate of absenteeism - A hypothesis. Sci Total Environ 234(1-3):87-93.
Rudnick, S.N., Hinds, W.C., Maher, E.F., and First, M.W. 1983. Effect of plateout, air motion
and dust removal on radon decay product concentration in a simulated residence, Health Phys.
45:463-470.
Rudnick, S. N. 2004. Optimizing the design of room air filters for the removal of submicrometer
particles. Aerosol Sci Tech 38: 861-69.
Rudnick, S. N., and D. K. Milton. 2003. Risk of indoor airborne infection transmission estimated
from carbon dioxide concentration. Indoor Air 13, no. 3: 237-45.
65
Russell, M. Sherman, M. and Rudd, A. (2007) Review of residential ventilation technologies,
HVAC&R Research 13:325-348.
RutalaWA, Jones SM Worhington JM Reist PC Weber DJ. 1995. Efficacy of portable filtration
unts in reducing aerosolized particles in the size range of Mycobacterium tuberculosis. Infect
Contrl Hosp Epidemiol 16: 391-398.
Sarsfield JK, Gowland G Roy R et al. 1974. Mite-sensitive asthma of childhood: trial of
avoidance measures. Arch Dis Child 49:716-721.
Scherr MS Peck LW. 1977. The effects of high efficiency air filtration system on nighttime
asthma attacks. West Virginia Med J, 73:144-8.
Schleibinger, H., Rüden, H., 1999. Air filters from HVAC systems as possible source of volatile
organic compounds (VOC)-laboratory and field assays. Atmos Environment 33, 4571–4577.
Schmidt, F., Sager, U. and Däuber, E. 2002. Dynamic adsorption behavior of cabin air filters.
Filtration and Separation, September.
Schwartz, R.H., McMullen, A.H., Pichichero, ME., et al. 1973. Night-time air filtration and
moderate asthma. J Allergy Clin Immunol 71(Part 2):148. Abstract 240.
Seppänen O, Fisk WJ. 2002. Association of ventilation system type with SBS symptoms in
office workers. Indoor Air 12(2):98-112.
Seppänen, O. A., and W. J. Fisk. 2004. Summary of human responses to ventilation. Indoor Air
14, no. s7: 102-18.
Seppänen, O., W. J. Fisk, and Q. H. Lei. 2006. Ventilation and performance in office work.
Indoor Air 16, no. 1: 28-36.
Shapiro GG, Wighton TG, Chinn T, Zuckerman J, Eliassen AH, Picciano JF, et al. 1999. House
dust mite avoidance for children with asthma in homes of low-income families. Journal of
Allergy and Clinical Immunology 103:1069-1074.
Shapiro, M., Laufer, G. and Gutfinger, C. 1986. Electrostatically Enhanced Granular Bed Filters.
Aerosol Science and Technology 5, no. 1: 39-54.
Shapiro, M., Laufer, G. and Gutfinger, C. 1986. Experimental study on electrostatically
enhanced granular filters. Aerosol Science and Technology 5, no. 4: 435-45.
Shaughnessy RJ and Oatman L, 1992. The use of ozone generators for control of indoor air
contaminants in an occupied environment. Indoor Air Quality ’91. American Society of Heating
Refrigerating and Air-conditioning Engineers, Inc. Atlanta GA pp. 318-324.
66
Shaughnessy, R.J., Levetin, E., Sublette, K. L., 1993. Effectiveness of portable indoor air
cleaners in particulate and gaseous contaminant removal. In: Indoor Air ’93: Proceedings of the
6th International Conference on Indoor Air Quality and Climate, Helsinki, Finland. July 4-8,
1993. Vol 6: 381-384.
Shaughnessy, R.J., Levetin, E., Blocker, J., Sublette, K. L., 1994. Effectiveness of portable
indoor air cleaners: Sensory testing results. Indoor Air 4, 179-188.
Shaughnessy, R. and Sextro, R. 2005. What is considered an “effective” air cleaning device?
Proceedings, 10th International Conference on Indoor Air Quality and Climate, Beijing, China,
Sept. 4-9, 2005. 2970-2975.
Shaughnessy, R.J., Sextro, R.G., 2006. What is an effective portable air cleaning device? A
review. Journal of Occupational and Environmental Hygiene 3, 169–181.
Sheikh A, Hurwitz B, Shehata Y. House dust mite avoidance measures for perennial allergic
rhinitis. Cochrane database of systematic reviews (Online) 2007;(1).
Siegel, J. 2002. Particle deposition on HVAC heat exchangers. Ph.D. Dissertation, University of
California, Berkeley.
Siegel, J.A., Waring, M.S., Yu, X., and Corsi, R.L., 2006. Indoor air quality implications of
portable ion generators. Proceedings of the A&WMA Specialty Conference on Indoor
Environmental Quality – Problems, Research, and Solutions, Research Triangle Park, North
Carolina (July 2006) 1:1-12.
SINTEF 1995. Lifetime tests of air filters in real applications. SINTEF STF A95027,
Trondheim Norway.
Skulberg, K. R., K. Skyberg, K. Kruse, W. Eduard, F. Levy, J. Kongerud, and P. Djupesland.
2005. The effects of intervention with local electrostatic air cleaners on airborne dust and the
health of office employees. Indoor Air 15, no. 3: 152-59.
Skyberg, K., K. R. Skulberg, W. Eduard, E. Skaret, F. Levy, and H. Kjuus. 2003. Symptoms
prevalence among office employees and associations to building characteristics. Indoor Air 13,
no. 3: 246-52.
Skyberg, K., Skulberg, K.R., Kruse, K. , Madso, L., Levy, F., Kongerud, J., Djupesland, P.
(2000) Subjective symptoms and nasal congestion after installation of electrostatic air cleaners in
the office environment—a double blind intervention study. Proceedings of Healthy Buildings
2000 2:55-57. SIY Indoor Air Information Oy, Helskinki, Finland.
Small, W.S. 1961. American Academy of Allergy Report of the Air Processing Committtee for
1960. J Allergy 32:458.
67
Spiegelman J and Friedman, H. 1968. The effects of central air filtration and conditioning on
pollen and microbial contamination. J Allergy 42:193.
Spiegelman, J Blumstein BI Friedman H. 1961. Effects of an air purifying apparatus on ragweed
pollen, mould and bacterial counts. Ann Allergy 19:613.
Squillace SP. 1999. Indoor allergen avoidance: What really works? Journal of Respiratory
Diseases 20(1):13-6.
Sutton DJ, Cloud HA, McNall, PE Jr, Nodolf, K.M., McIver, S.H. 1964. Performance and
application of electronic air cleaners in occupied spaces. ASHRAE J 6:55-88, 1964.
Swanson, MC., Agarwal, M.K., Reed, C.E. 1985. An immunochemical approach to indoor
aeroallergen quantitation with a new volumetric air sampler: studies with mite, roach, cat,
mouse, and guinea pig antigens. J Allergy Clin Immunol 76: 724-729.
Takaro TK, Krieger JW, Song L. Effect of environmental interventions to reduce exposure to
asthma triggers in homes of low-income children in Seattle. J Expo Anal Environ Epidemiol
2004;14(Suppl 1):S133-S143.
Takatori K, Saito A, Yasueda H, and Akiyama K. 2001. The effect of house design and
environment on fungal movement in homes of bronchial asthma patients. Micropathologia 142:
41-49.
Tan ZC, Zhang YH. A review of effects and control methods of particulate matter in animal
indoor environments. Journal of the Air and Waste Management Association 2004 Jul;54(7):845-
54.
Tanthapanichakoon, W., Maneeintr, K., Charinpanitkul, T., and Kanaoka, C. 2003. Estimation
of collection efficiency enhancement factor for an electret fiber with dust load. J Aerosol Sci 34:
1505-1522.
Thatcher, T. L., and D. W. Layton. 1995. Deposition, resuspension, and penetration of particles
within a residence. Atmos Env 29: 1487-97.
Thiam DG, Tim CF, Hoon LS, Lei Z, Bee Wah L. 1999. An evaluation of mattress encasings and
high efficiency particulate filters on asthma control in the tropics. Asian Pac J Allergy Immunol
17(3):169-74.
Tovey E, Marks G. Methods and effectiveness of environmental control. Journal of Allergy and
Clinical Immunology(179-191):-1911.
Tovey, E.R., Chapman, M.D., Wells, C.W., and Platts-Mills,T.A.E. 1981. The distribution of
dust mite allergen in the houses of patients with asthma. American Review of Respiratory
Disease 124: 630-635.
68
Tronville, P. and Rivers, R.D. 2005. International standards: filters for buildings and gas
turbines. Filtration & Separation, September 2005, 39-43.
Tung, T.C.W., Niu, J., Burnett, J., Hung, K., 2005. Determination of ozone emission from a
domestic air cleaner and decay parameters using environmental chamber tests. Indoor Built
Environment 14, 29-37.
Tuomi, T., Engstrom, B., Niemela, R., Svinhufvud, J., 2000. Emission of ozone and organic
volatiles from a selection of laser printers and photocopiers. Applied Occupational and
Environmental Hygiene 15, 629-634.
Turk, B. H., Powell, G., Casey, M., Fisher, E., Ligman, B., Marquez, A., Harrison, J., Hopper,
R., Brennan, T., and Shaughnessy, R. (1998). Impact of ventilation modifications on indoor air
quality characteristics at an elementary school. Proceedings of Healthy Buildings r IAQ’97,
1:155 160, IAQ ’97, Washington, DC.
UL Standard for Safety 867. Electrostatic Air Cleaners.
http://www.ul.com/appliances/household/standards.html , Accessed March 10, 2008.
U.S. Environmental Protection Agency. 1989. Radon reduction methods. A homeowner's guide
(Third edition). Washington, DC: Office of Research and Development, U.S. Environmental
Protection Agency.
U.S. Environmental Protection Agency 1990. Residential air cleaning devices-a summary of
available information. Office of Air and Radiation. EPA-400-I-90-002, February 1990.
U.S. Environmental Protection Agency. 1995. Ozone generators in indoor air settings. U.S. EPA
Report, EPA-600/R-95-154 (NTIS PB96-100201), October 1995.
Van der Heide S, Kauffman HF, Dubois AEJ, De Monchy JGR. 1997. Allergen reduction
measures in houses of allergic asthmatic patients: Effects of air-cleaners and allergen-
impermeable mattress covers. European Respiratory Journal 10(6):1217-23.
Van der Heide S, van Aalderen WM, Kauffman HF, Dubois AE, de Monchy JG. 1999. Clinical
effects of air cleaners in homes of asthmatic children sensitized to pet allergens. J Allergy Clin
Immunol 104:447–451.
Van der Heide S, de Moncy JG. 2000. Health effects of air cleaners on asthmatic children
sensitized and exposed to pets. Proceedings of Healthy Buildings 2000, Vol. 1 287.
Van Leeuwen, W.S. 1924. Bronchial asthma in relation to climate. Proc Roy Soc Med 17:19.
Van Leeuwen, W.S. 1925. Allergic Diseases, Philadelphia, J.B. Lippincott Co.
69
Van Osdell, Douglas W., Benjamin Y. H. Liu, Kenneth L. Rubow, and David Y. H. Pui. 1990.
Experimental Study of Submicrometer and Ultrafine Particle Penetration and Pressure Drop for
High Efficiency Filters. Aerosol Science and Technology 12, no. 4: 911-25.
Van Strien RT, Gehring U, Belanger K, Triche E, Gent J, Bracken MB, et al. 2004. The
influence of air conditioning, humidity, temperature and other household characteristics on mite
allergen concentrations in the northeastern United States. Allergy 59(6):645-52.
Verrall B, Muir DC, Wilson WM, Milner R, Johnston M, Dolovich J. Laminar flow air cleaner
bed attachment: a controlled trial. Ann Allergy 1988 Aug;61(2):117-22.
Villaveces JW, Rosengren, H., and Evan J. 1977. Use of laminar flow portable filter in
asthmatic children. Ann Allergy 1977 38:400.
Virant FS. Methods and effectiveness of environmental control. American Journal of Rhinology
1999;13(4):331-2.
Walata, S. A., T. Takahashi, and Chi Tien. 1986. Effect of particle deposition on granular aerosol
filtration: a comparative study of methods in evaluating and interpreting experimental data.
Aerosol Science and Technology 5, no. 1: 23-37.
Wallace, L.A., 2000. Real-time monitoring of particles, PAH, and CO in an occupied townhouse.
Applied Occupational Environmental Hygiene 15(1): 39-47.
Wallace L, Howard Reed C. 2002. Continuous monitoring of ultrafine, fine, and coarse particles
in a residence for 18 months in 1999-2000. J Air Waste Manag Assoc 52(7):828-44.
Wallace LA, Emmerich SJ, Howard-Reed C. 2004. Effect of central fans and in-duct filters on
deposition rates of ultrafine and fine particles in an occupied townhouse. Atmospheric
Environment 38(3):405-13.
Walsh, D. C., and J. I. T. Stenhouse. 1998. Parameters affecting the loading behavior and
degradation of electrically active filter materials. Aerosol Science and Technology 29, no. 5: 419-
32.
Wang, H.C. and G. Kasper, 1991. "Filtration efficiency of nanometer-size aerosol particles". J.
Aerosol Sci. 22, 31–41.
Wang, Min, and Gail Brion. 2007. Effects of RH on glass microfiber filtration efficiency for
airborne bacteria and bacteriophage over time. Aerosol Science and Technology 41, no. 8: 775-
85.
Warburton CJ, Niven RM, Pickering CA, Fletcher AM, Hepworth J, Francis HC. Domiciliary air
filtration units, symptoms and lung function in atopic asthmatics. Resp Med 1994; 88:771-6.
70
Ward, M., Siegel, J.A., and Corsi, R.L., 2005. The effectiveness of stand alone air cleaners for
shelter-in-place. Indoor Air 15: 127-134.
Wargocki, Pawel, David P. Wyon, Jan Sundell, Geo Clausen, and P. Ole Fanger. 2000. The
effects of outdoor air supply rate in an office on perceived air quality, Sick Building Syndrome
(SBS) symptoms and productivity. Indoor Air 10, no. 4: 222-36.
Wargocki P, Sundell J, Bischof W, Brundrett G, Fanger PO, Gyntelberg F, et al. 2002a.
Ventilation and health in non-industrial indoor environments: report from a European
multidisciplinary scientific consensus meeting (EUROVEN). Indoor Air 12(2):113-28.
Wargocki, P., Wyon, D.P., Nielsen, J.B., and Fanger, P.O. 2002b. Call-centre occupant response
to new and used filters at two outdoor air supply rates. Proceedings, 9th International Conference
on Indoor Air Quality and Climate, Monterey, CA June 30-July 5, 2002. III:449-454.
Wargocki, Pawel, David P. Wyon, and P. Ole Fanger. 2004. The performance and subjective
responses of call-center operators with new and used supply air filters at two outdoor air supply
rates. Indoor Air 14, no. s8: 7-16.
Wargocki P. and Wyon, D.P. 2007. The effects of outdoor air supply rate and supply air filter
condition in classrooms on the performance of schoolwork by children (RP-1257). HVAC&R
Research 13: 165-192.
Waring, M., Siegel, J., and Corsi, R. 2007. Ultrafine particle removal and generation due to
portable air cleaners. ISEA Annual Conference, Research Triangle Park, NC 2007. Abstract
205, Abstract Book.
Waring, M.S., Siegel, J.A., and Corsi, R.L. 2008. Ultrafine particle removal and generation by
portable air cleaners, Atmospheric Environment (2008). On-line preprint accessed March 10,
2008.
Warner JA, Frederick JM, Bryant TN, Weich C, Raw GJ, Hunter C, et al. 2000. Mechanical
ventilation and high-efficiency vacuum cleaning: a combined strategy of mite and mite allergen
reduction in the control of mite-sensitive asthma. J Allergy Clin Immunol 105:75–82.
Warner, JA, Marchant JL, and Warner JO. 1993. Double blind trial of ionizers in children with
asthma sensitive to the house dust mite. Thorax 48:330.
Wasiolek, P., Montassier, N., Hopke, P.K. and Abrams, R. 1993. Analysis of the performance
of a radon mitigation system based on charcoal beds. Environ Tech 14: 401-412
Wathes, C. M., H. E. Johnson, and G. A. Carpenter. 1991. Air hygiene in a pullet house: effects
of air filtration on aerial pollutants measured in vivo and in vitro. Brit Poultry Sci 32: 31-46.
71
Weschler C J., Shields H C. 1988. The influence of HVAC operation on the concentrations of
indoor airborne particles. Proceedings ASHRAE Conference, IAQ 88, Engineering Solutions to
Indoor Air Problems, 11-13 April 1988, Atlanta, Georgia, 166-181. ISBN 0-910110-53-0
Weschler, C.J., Shields, H.C. 1991. The impact of ventilation and indoor air quality on electronic
equipment. ASHRAE Trans. vol.97, Part 1, paper number NY-91-4-1, 455-463, 6 figs, 1 tab,
refs.
Weschler, Charles J. 1991. Predictions of Benefits and Costs Derived from Improving Indoor Air
Quality in Telephone Switching Offices. Indoor Air 1, no. 1: 65-78.
Weschler CJ, Shields HC, Shah BM. 1996. Understanding and reducing the indoor concentration
of submicron particles at a commercial building in Southern California. Journal of the Air and
Waste Management Association 1996;46(4):291-9.
Westerdahl, D., Fruin, S., 2007. In-Cabin ultrafine PM and filtration effectiveness. ISEA
Annual Conference, Research Triangle Park, NC 2007. Abstract 397, Abstract Book.
When to use a HEPA filter for atopic childhood asthma. Journal of Respiratory Diseases
1996;17(10).
Whitby, K.T., Anderson, G.R., and Rubow, K.L. 1983. Dynamic model for evaluating room-
sized air cleaners. ASHRAE Trans 89-2A:172-182.
White, K., Smith, S., and Dingle, P. 2002. HEPA air filtration: an effective method of reducing
household PM exposure. Proceedings, 9th International Conference on Indoor Air Quality and
Climate, Monterey, CA June 30-July 5, 2002. I:891-895.
Wickman M, Emenius G, Egmar AC, Axelsson G, Pershagen G. 1994. Reduced mite allergen
levels in dwellings with mechanical exhaust and supply ventilation. Clin Exp Allergy 24(2):109-
14.
Wood RA, Laheri AN, Eggleston PA. 1993. The aerodynamic characteristics of cat allergen.
Clin Exp Allergy 23(9):733-9.
Wood, R.A., Flanagan, E., VanNatta, M., Chen, P.H. and Eggleston, P.A. (1997) The effect of a
HEPA room air cleaner on cat-induced asthma and rhinitis, J. Allergy Clin. Immunol., 99, 1584–
1584.
Wood RA, Johnson EF, Van Natta ML, Pei HC, Eggleston PA. 1998. A placebo-controlled trial
of a HEPA air cleaner in the treatment of cat allergy. American Journal of Respiratory and
Critical Care Medicine 158(1):115-20.
Wood RA. 2002. Air filtration devices in the control of indoor allergens. Current allergy and
asthma reports 5:397-400.
72
Wu F and Takaro TK 2007 Childhood asthma and environmental interventions, Environ Health
Persp 115:971-75.
Wu, P.-C., Y.-Y. Li, C.-M. Chiang, C.-Y. Huang, C.-C. Lee, F.-C. Li, and H.-J. Su. 2005.
Changing microbial concentrations are associated with ventilation performance in Taiwan's air-
conditioned office buildings. Indoor Air 15, no. 1: 19-26.
Wyon, D.P. 1992. Sick buildings and the experimental approach. Environmental Technology, 13,
313–322.
Wyon, D. P. 2004. The effects of indoor air quality on performance and productivity. Indoor Air
14, no. s7: 92-101.
Xu, J., Zhang, Jh., You, S. 2005. The assessment and function research of plasma air cleaner.
Indoor Air 2005: Proceedings, 10th Int Conf on IAQ and Climate, 2920-2924.
Yanagi, U. and Ikeda, K. 2005. In situ tests about removal performance of airborne microbe
particles by an air filter. Indoor Air 2005: Proceedings, 10th International Conference on Indoor
Air Quality and Climate, Beijing, China, Sept. 4-9, 2005. 3000-3004.
Yang, S. H., and Lee, G. W. M. (2005). Filtration characteristics of a fibrous filter pretreated
with anionic surfactants for monodisperse solid aerosols, J. Aerosol Sci. 36(4):419–437.
Yang, S.H., Lee, G.W.M., Luo, C.H., Wu, C.C., Yu, K.P. and Lou, C.L. 2005. Using the
electrets filter to remove the submicron aerosols. Proceedings, 10th International Conference on
Indoor Air Quality and Climate, Beijing, China, Sept. 4-9, 2005. 2986-2990.
Yu, X., 2005. Critical review and experimental study of portable ion generators as indoor air
cleaning devices. MS Thesis, University of Texas at Austin, Department of Civil, Architectural,
and Environmental Engineering.
Zeng, Q., Kaczmarczyk, J., Melikov, A. and Fanger, P.O. (2002) Perceived air quality and
thermal sensation with a personalized ventilation system, Proceedings of Roomvent,
Copenhagen, Denmark, pp. 1–64.
Zhao, P., Siegel, J.A., and Corsi, R.L. 2005. Experimental characterization of portable ion
generators. Proceedings, 10th International Conference on Indoor Air Quality and Climate,
Beijing, China, Sept. 4-9, 2005. 2957-2961. Notethis reference reflects an error by the
conference publishers—correct reference is Mullen et al., 2005 (q.v.)
Zuraimi MS, Tham KW, Chew FT, Ooi PL. The effect of ventilation strategies of child care
centers on indoor air quality and respiratory health of children in Singapore. Indoor Air 2007
17:317-327.
Zuraimi MS. 2007. Estimates of associated outdoor particulate matter health risk and costs
reductions from alternative building, ventilation and filtration scenarios. Sci Total Env 377: 1-11.
73
Zwemer RJ and Karibo, J. 1973. Use of laminar control device as adjunct to standard
environmental control measures in symptomatic asthmatic children Ann Allergy 1973 31:284.
... After the API employment in general indoor air, the reduction of larger PMs was more obvious than the reduction of the smaller ones, which is in conjugation with a former study of the Department of Energy, USA (DOE, 2005). The obtained trend can be attributed to the fact that larger particles (more inertia) are found in higher concentration in general indoor air (as a result of mechanical (human) activities as walking, sweeping and vacuuming) as compared to smaller ones that travel in airstream direction to get through cross-hatching of fiber and are intercepted by fiber (Wallace, 2008). Shiue et al. (2011) had reported a similar reduction percentage in the mass concentration of PM 0.5 and PM 0.25 , whereas reduction percentage in the mass concentration of PM 2.5 resembles with results in studies by Scheepers et al. (2015), Cheng et al. (2016), and Park et al. (2017). ...
... The efficacy of AP I in presence of candles and incense smoke was found as: small-sized PMs reduced more as compared to large-sized PM. This can be attributed to the fact that small-sized particles travel farther and faster due to less inertia and are more likely to be hit and trapped by fiber on the filter (Wallace, 2008). The reduction percentage in the mass concentration of PM 10 associated with incense and candle smoke after the deployment of AP I was 29.14. ...
Article
Full-text available
The present study deals with an evaluation of the air purifier’s effectiveness in reducing the concentration of different sized particulate matter (PM) and ions in the real-world indoor environment. Two types of air purifiers (API and APII) mainly equipped with High-Efficiency Particulate Air (HEPA) filters that differed in other specifications were employed in general indoor air and the presence of an external source (candles and incense). The Gravimetric sampling of PM was carried out by SKC Cascade Impactor and further samples were analyzed for determining ions’ concentration while real-time monitoring of different sized PM was done through Grimm Aerosol Spectrometer (1.109). The result showed that API reduced PM levels of different sizes ranged from 12-52% and 29-53% in general indoor air and presence of external source respectively. Concerning the APII, a higher decrease percent in PM level was explored in presence of an external source (52-68%) as compared to scenarios of general indoor air (37-64%). The concentrations of the ions were noticed to be decreased in all three size fractions but surprisingly some ions’ (not specific) concentrations increased on the operation of both types of air purifiers. Overall, the study recommends the use of air purifiers with mechanical filters (HEPA) instead of those which release ions for air purification.
... A report to Health Canada by Wallace (2008) highlighted the importance of the clean air delivery rate (CADR), which is calculated by multiplying the efficiency by the air flow rate through the filter, as this determines how much clean air is being supplied. The report concludes that air cleaners can reduce particulate levels in homes, but that attention should be paid to the CADR and the efficiency of the filter. ...
... Liu et al., 2020). Mechanical filtration utilises fibrous filters that capture suspended particles but the performance can be influenced by material of the filter media, air flow and pollutant types (Luengas et al., 2015;Wallace, 2008). Furthermore, the filters can become clogged over time, and so require regular cleaning (for ESP) or changing of fibrous filters to reduce to risk of pollutants being re-emitted, also there is limited evidence of their success in tackling some gaseous pollutants (Fisk, 2013;Siegel, 2014). ...
Article
A systematic literature review was carried out to examine the impact of portable air purifiers (PAPs) on indoor air quality (PM 2.5) and health, focussing on adults and children in indoor environments (homes, schools and offices). Analysed studies all showed reductions in PM 2.5 of between 22.6 and 92.0% with the use of PAPs when compared to the control. Associations with health impacts found included those on blood pressure, respiratory parameters and pregnancy outcomes. Changes in clinical biochemical markers were also identified. However, evidence for such associations was limited and inconsistent. Health benefits from a reduction in PM 2.5 would be expected as the cumulative body of scientific evidence from various cohort studies shows positive impacts of long-term reduction in PM 2.5 concentrations. The current evidence demonstrates that using a PAP results in short-term reductions in PM 2.5 in the indoor environment, which has the potential to offer health benefits. Crown
... In order to determine the capability of an air cleaner for removing pollutants, researchers have introduced three measures: efficiency, CADR, and effectiveness. The efficiency is the fraction of particles that is removed in a single pass through the system and it is presented in percent [66]. Another measure is the CADR, which takes into account the airflow rate through the air cleaner and the particle removal efficiency and is presented in cubic meters per hour (m 3 /h) [67]. ...
Article
Full-text available
Many people spend most of their time in an indoor environment. A positive relationship exists between indoor environmental quality and the health, wellbeing, and productivity of occupants in buildings. The indoor environment is affected by pollutants, such as gases and particles. Pollutants can be removed from the indoor environment in various ways. Air-cleaning devices are commonly marketed as benefiting the removal of air pollutants and, consequently, improving indoor air quality. Depending on the type of cleaning technology, air cleaners may generate undesired and toxic byproducts. Different air filtration technologies, such as electrostatic precipitators (ESPs) have been introduced to the market. The ESP has been used in buildings because it can remove particles while only causing low pressure drops. Moreover, ESPs can be either in-duct or standalone units. This review aims to provide an overview of ESP use, methods for testing this product, the performance of existing ESPs concerning removing pollutants and their byproducts, and the existing market for ESPs.
Article
Portable air cleaners are commonly used to reduce indoor air particles in China, but few studies have evaluated the treatment efficiency under real living conditions. We aimed to evaluate the efficiency of a portable air cleaner in common residences under normal living conditions. A single-blind cross-over field study was conducted in 20 urban residences in Chongqing, China. In each residence, one portable air cleaner was operated without a high-efficiency particulate air (HEPA) filter (sham filtration) for the first 48 h and with a HEPA filter (true filtration) for the next 48 h in the living room. Concentrations of PM1.0, PM2.5, respirable suspended particulate matter (RESP), PM10, and total suspended particulate matter (TSP) were measured simultaneously in indoor and ambient outdoor air. Compared to sham filtration, the average concentrations of indoor air particles were significantly lower when true filtration was used according to paired-sample t-tests (all p-values <0.05). However, indoor concentrations of PM2.5 in 16 (80%) residences were still higher than the World Health Organization's (WHO) air quality guideline during true filtration. The removal efficiencies of the portable air cleaners with HEPA filters for these particles were about 40%. The removal efficiencies for PM1.0, PM2.5, and RESP had significant associations with the room volume, but not with the residence district, season, age of the building, floor level of the apartment, or ambient weather. Our results indicate that a portable air cleaner is effective in improving household air quality, but is not enough to ensure the air quality meeting WHO guideline in all real-world residences in polluted areas.
Article
How HVAC system's performance is affected by the addition of a whole house air cleaner, specifically consumer thermal comfort and system safety has been explored. Whole house air cleaner are effective in cleaning indoor air because it removes particles in the air down to submicron sizes. It offers high filtration efficiency and long air cleaner life. A properly sized air cleaner will provide improved indoor air quality without affecting consumer thermal comfort and safe operation of HVAC equipment. Air cleaner must be selected that is rated at or above the design airflow rate of the HVAC system. If the system is not optimally designed, use the air cleaner with the highest airflow rating. A successful installation of a whole house air cleaner depends on the total external static of the system including ductwork, system blower pressure drop versus airflow rate during the heating/cooling mode, type of blower motor, and air cleaner pressure drop for the system airflow rate.
Article
Air filter products have evolved a great deal in the past few years. Early filtration products were designed to protect the mechanical equipment that conditioned the indoor space. Today the emphasis of filter performance is not only on the mechanical equipment, but also on the inhabitants and the "product" in the conditioned space. This "product" can be people in an office building, patients in a health care setting, semiconductor chips in a manufacturing facility, or artwork in a museum.
Article
Sensitisation to cat allergen is a major risk factor for asthma. Sensitised asthmatics often refuse to part with their cats. It is therefore essential to develop techniques for lowering exposure with a cat in the home. This study investigated the effect of a high efficiency particulate air (HEPA) cleaner (Philips HR 4320) on the levels of airborne Fel d 1 in homes with cats. Air sampling was carried out in seven homes of cat owners. Sampling was performed in two rooms (cat present and without a cat) over a two day period (first day without HEPA cleaner-control; second day with HEPA cleaner running continuously-active). Three one hourly samples were collected over a 9-hour period (baseline, 4-5 hours, 8-9 hours) using a high volume dust sampler (Rotheroe-Mitchell: air flow rate 60 l/min), and the air sample was collected onto a 37 mm Whatman GFA micro-glass fibre filter. Fel d 1 was measured using a two-site monoclonal antibody-based ELISA. The data were analysed using a 2-factor ANOVA with repeated measures. Baseline airborne Fel d 1 levels were 4.8 fold greater when the sampling was performed with a cat in the room than when the cat was elsewhere in the house (GM 9.6 ng/m3, 95% CI 3.59-25.61 vs 1.99 ng/m3, 95% CI 0.38-4.38; p<0.01). The table shows Fel d 1 levels (ng/m3; GM and 95% CI) in the active and control groups. Active Control Baseline 5.04 (1.95-13.03) 3.79 (1.32-10.88) 4-5 hours 0.95 (0.21-4.20) 2.45 (0.38-6.65) 8-9 hours 0.88 (0.21-3.75) 1.56 (0.59-4.17) There was a good correlation between the baseline values and those obtained during the hours 4 and 8 on the control days (hour 1 vs hour 4: r= 0.98, p<0.001; hour 1 vs hour 8: r=0.91, p<0.001). Although a significant reduction in airborne Fel d 1 was observed over the 8 hour period on both active and control days, the fall was significantly greater on the active (HEPA cleaner was on) compared to the control days (p=0.008). In conclusion, HEPA cleaner reduces the airborne levels of cat allergen and may be used as part of an overall avoidance regime for cat sensitised patients who refuse to part with their cat.
Article
This is an excellent review article looking at the role that environmental exposures can play at inducing disease and is specifically divided into three sections: (1) the relationship of allergen exposure to allergic disease outcomes; (2) allergen avoidance in the prevention and management of allergic diseases; and (3) allergen avoidance methods. The authors begin by pointing out that chronic asthma is largely associated with exposure to allergens that occur indoors, in temperate and humid regions, this is largely associated with allergy to house dust mites, whereas in arid climates the strongest risk factor is allergy to the fungus Alternaria. Other factors in selected communities include allergy to cockroach and to furred pets. The authors point out that different allergens are carried by a range of particles of different sizes and shapes that can effect their behavior when disturbed when airborne and inhaled. For example, after dust disturbance, dust mite antigen is mainly associated with large particles, and after fifteen minutes, 10 to 20% remain airborne - typically those associated with smaller particles. Within hours, less than 0.1% may remain airborne; in contrast after disturbance, greater than 20% of cat and dog allergens associated with particles less than 5 μm in size can remain airborne for days. While there is no safe minimum level of exposure in all susceptible individuals, it is clear that there is a relationship between the risk for sensitization and level of exposure. In a study by Wahn, et al (JACI 1997; 99:763-769), such a relationship between the incidence of sensitization to mite and cat allergens versus exposure was clearly demonstrated. When both parents were atopic, there was less than a 1% prevalence of house dustmite allergy developing in the first three years of life if the ambient level of exposure was approximately 0.1 μg of house dust allergen per gram of dust; this increased to a 6% prevalence with allergen levels over 10 μg per gram. Similar observations were noted for cat allergen levels in risk for sensitization. Next, the authors review the effect of allergen avoidance in the prevention and active management of allergy. The Isle of Wight study involved a total of 120 infants with a strong family history of allergic disease. Intervention in half of the children included intensive food and house dust mite allergen avoidance regimens. The study verified that house dust mite intervention in carpets and furnishings significantly reduced allergen levels at 9 months. The rates of sensitization in the intervention and control groups were 1.7 and 9.7% at two years of age, and 5.2 and 24.2% at four years of age - both statistically significant. Another study of nearly 500 infants in Vancouver and Winnipeg also included house dust mite avoidance intervention. At one year follow-up the house dust mite allergen levels were substantially reduced in beds but not floors and there were significantly less rhinitis symptoms (17.2 versus 26.7%) and a strong tendency for less asthma-like symptoms (13.6 versus 18.5%) in the intervention group compared with controlled subjects. The authors continue by looking at the effect of active intervention with environmental control techniques as a way to reduce asthma disease severity, with a review of four randomized placebo-controlled trials, which did show a statistically significant difference between active and control arms of the study over a sustained period of follow-up of at least six months or more. These include studies by Walshaw, et al, in the UK (Q J Med 1986; 58:199-215), Ehnert, et al in Berlin (JACI 1992; 90:135-138), Carswell, et al, in Bristol (Clin Exp Allergy 1996: 26:386-396), and Vander Heide et al, in the Netherlands (Eur Resp J 1997; 10:1217-1223). This review article concludes with a practical synopsis of allergen avoidance methods, including those that, based on literature data, are felt to be definitely useful versus those that are probably useful or objective unlikely to be useful. With regard to dust mite avoidance, encasing pillows and mattresses and laundering bedding in temperatures above 130°F are definitely useful. Other interventions such as replacement of fitted carpets with smooth flooring and cleaning of hard surfaces are possibly useful. Finally, although there may be some role for dry or wet vacuuming and the use of air filtration or air conditioning techniques, it is not felt that acaricides are likely to be useful. The authors are pessimistic when it comes to pet allergen control, noting that even when cats are removed from rooms and the aeroallergen levels drop by up to 70%, the levels in reservoirs throughout the home may decline slowly only after a period of months or years. Accordingly, it is suggested that if pets cannot be relocated the next best option is to keep them out of bedrooms and isolated to rooms with hard surfaces from which the allergen can be removed and to use regular washing for rugs on which the pets lie. The authors conclude by pointing out the extensive amount of research that still needs to be done to answer important clinical questions. For example, what interventions should be applied to high-risk groups in terms of primary prevention and what is the best way to identify such patients? Another group of studies needs to address the effectiveness of various allergen control methods. A third group of studies should develop methods by which patients can easily measure their level of exposure in the home. This could well be an area where compliance with suggested environmental control measures could be greatly enhanced rather than expecting a patient to believe that the time and financial efforts we recommend are truly likely to be beneficial.
Article
A mass-balance model, as well as data on particle-size distributions, filter efficiencies, and particle-deposition rates were used to estimate reductions in indoor concentrations of different particle types attainable with the use of filters in HVAC supply-air streams. In addition, the energy and total costs of various filtration options were estimated. The resultant data were analyzed in detail.
Article
A building's air filtration system can serve as a significant defense component during an airborne chemical and/or biological attack from an external release. To assist building owners and designers in risk analysis and management decisions, this article provides a general introduction to biological and chemical,agents considered most likely to be used in a terrorist attack. HVAC system safeguards are discussed, followed by a description of air filters suitable for use in the chemical and biological arena. An internal release directly to the indoor environment poses additional challenges and solutions that are beyond the scope of this article.
Article
Some of the significant adverse impacts of used filters on indoor air quality of buildings and potential solutions are discussed. The presence of used filters in building results in occupants suffering from Sick Building Syndrome (SBS) symptoms. Used filters have an adverse impact on indoor air quality spreading different kinds of diseases among building occupants, including asthma and other allergic diseases. These filters are unable to prevent particulate and gaseous pollutants from entering the buildings through the ventilation system. The airflow through through these filters need to started earlier to control pollutants before buildings are occupied and improve indoor air quality. The development of low-polluting filtration techniques with higher efficiencies and lower pressure drops is another solution to prevent adverse impact of used filters in buildings.