  • Article: Condensing heat transfer characteristics of hydrocarbon refrigerants in 9.52 and 12.7 mm smooth tube
    [show abstract] [hide abstract]
    ABSTRACT: Experimental results for heat transfer characteristic and pressure gradients of hydrocarbon (HC) refrigerants and R-22 during condensing inside horizontal double pipe heat exchangers are presented. The test sections which have one tube diameter of 12.70mm with 0.86mm wall thickness, another tube diameter of 9.52mm with 0.76mm wall thickness are used for this investigation. The local condensing heat transfer coefficients of HC refrigerants were higher than that of R-22. The average condensing heat transfer coefficient increased with the increase of the mass flux. It showed the higher values in HC refrigerants than R-22. Comparing the heat transfer coefficient of experimental results with that of other correlations, the presented results had a good agreement with most of the Cavallini’s correlations.
    Heat and Mass Transfer 04/2012; 42(2):144-149. · 0.90 Impact Factor