Publications (1)0 Total impact
-
Conference Proceeding: A method of tracking voltage flicker envelope real-time
[show abstract] [hide abstract]
ABSTRACT: Fast and accurate tracking of voltage flicker envelope is significant to the performance of flicker meter, flicker source location and the mitigation of voltage flicker. Using the energy of a signal and its shifted signals to track the envelope of voltage flicker is presented in this paper. It is assumed that the signal is shifted, once by a lead angle equal to beta, and at another time by a lag angle equal to beta, which generates two new signals u<sup>+</sup>(t) and u<sup>-</sup>(t). According to the energy differences, the relationship between the flicker amplitude and u(t), u<sup>+</sup>(t), u<sup>-</sup>(t) can be obtained, so the voltage flicker envelope is successfully tracked. How to obtain the shifted signals u<sup>+</sup>(t), u<sup>-</sup>(t) is analyzed in the paper. The frequency error e<sub>f</sub>(%), amplitude error e<sub>m</sub>(%) and waveform standard deviation sigma(%) are used as the weighing index of the accuracy of tracking flicker envelope. The theoretical analyzing and RTDS simulation test verify that the suggested method is accurate, fast and anti-noise.Power & Energy Society General Meeting, 2009. PES '09. IEEE; 08/2009
Institutions
-
2009
-
North China Electric Power University
- Key Laboratory of Power Systems Protection & Dynamic Security Monitoring & Control
Beijing, Beijing Shi, China
-