D. Hui,
Z.K. Wang,
J.Y. Zhang,
D. Zhang,
S.T. Dai,
C.H. Zhao,
Z.Q. Zhu,
H.D. Li,
Z.F. Zhang,
Y. Guan, [......],
L.Z. Lin,
L.F. Li,
L.H. Gong,
X.D. Xu,
J.Z. Lu,
Z. Fang,
H.X. Zhang, J.P. Zeng,
G.P. Li,
S.Z. Zhou
[show abstract]
[hide abstract]
ABSTRACT: Superconducting Fault Current Limiter (SFCL) is an attractive appliance for modern electrical power system. A 10.5kV/1.5 kA three-phase HTS fault current limiter was developed by IEE, CAS. This improved rectifier-type SFCL with HTS coil of 6.25 mH is going on a demonstrated long-term reliable operation in a real 10.5 kV substation located in Hunan, China. In a three-phase-to-ground short circuit test of grid, the prospective fault current of 3.5 kA was limited to 635 A at the pre-setup short-circuit point successfully
IEEE Transactions on Appiled Superconductivity 07/2006; · 1.04 Impact Factor