ABSTRACT Recently, the focus of lightning protection measures for distribution lines has moved from a nearby lightning stroke to a direct lightning stroke. Studies of direct lightning stroke countermeasures are generally carried out by digital simulations using the EMTP (Electro-Magnetic Transients Program). Thus, components of a distribution line must be modeled appropriately in the EMTP for accurate simulations.The authors have previously clarified the surge response of a distribution line by pulse tests using a reduced-scale distribution line model. In this paper, first, the results of the pulse tests are simulated in the EMTP using a conventional model which represents a distribution pole by a single lossless distributed-parameter line model, and comparisons with the test results show that transient overvoltages generated at the insulators cannot accurately be reproduced by the conventional model. This indicates that a special treatment is required to represent the transient response of a distribution pole and wires. Then, this paper proposes new EMTP models of the pole and wires which can reproduce the transient overvoltages at the insulators. The parameter values of the proposed models can be determined based on a pulse test result. © 2010 Wiley Periodicals, Inc. Electr Eng Jpn, 173(1): 11–23, 2010; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.21001

0 0
 · 
0 Bookmarks
 · 
75 Views

Keywords

accurate simulations.The authors
 
conventional model
 
direct lightning stroke
 
direct lightning stroke countermeasures
 
distribution lines
 
distribution pole
 
Electro-Magnetic Transients Program
 
lightning protection measures
 
lightning stroke
 
new EMTP models
 
proposed models
 
Published online
 
pulse test result
 
reduced-scale distribution line model
 
single lossless distributed-parameter line model
 
test results
 
transient overvoltages
 
Wiley InterScience
 
www.interscience.wiley.com). DOI 10
 
© 2010 Wiley Periodicals